Maytag PPG2GI Technical Literature

TECHNICAL SPECIFICATIONS
Model PPG2GI
M1200 Product Line
Single Packaged Gas/Electric Units 20 SEER, 81% AFUE — 2 - 5 Ton Units
Multi-Stage Cool / Two-Stage Heat
The iQ Drive gas/electric packaged system features modulating compressor technology and variable speed indoor and outdoor fan motors. This system is controlled from a two stage cooling and heating thermostat. The system has the capability of adding up to 18% of additional cooling above the rated capacity. The system has de-humidification capabilities from a capable thermostat or a duct mounted humidistat. These packaged gas/electrics are ultra­high efficient self-contained heating and cooling units that can be installed on the roof or on a slab. The convertible unit design makes installations simple in all applications. Units are ETL and ETLc listed.
Features and Benefits
• Interface control board: Two digit LED provides system operation, status and diagnostic troubleshooting information. Utilizes a NORDYNE-patented capacity control algorithm to select the optimum system capacity level. Internal controls monitor system operation to protect the inverter drive and compressor.
• Cooling operation temperature range: 50 °F to 125 °F.
• Five Minute Restart Time Delay: keeps the unit from restarting, eliminating
the highest cause for compressor failure.
• EXV control: Precise refrigerant superheat control provided by an electronic expansion valve.
• Suction Accumulator: Protection from liquid flood back and future compressor failures.
• Compressor and Component Access: Designed to make servicing easier for the contractor, hinge access panel is provided to all controls and the compressor.
• High Efficiency with low Sound Levels: 20 SEER with sound ratings from 63 to 74 db depending upon operating conditions. Engineered to significantly reduce unwanted noise with compressor sound blanket, variable speed condenser motor and swept-wing fan blade and discharge muffler.
• High Pressure Switch: Protects against abnormally high system pressures. Auto-reset feature prevents nuisance service visits.
• Low Pressure Switch: Protects against loss of system refrigerant charge.
• Liquid Line Filter Drier: Factory installed.
• Micro-Channel Condenser Coils: All aluminum coils that provide high
corrosion resistance and increased heat transfer.
• Anteater Copper Tube (Luvata Uniguard) / Aluminum Fin Indoor Coils:
Indoor coils are designed to optimize heat transfer, and increase durability and reliability.
• Wire Guard Coated with Earth Friendly Epoxy and Plastic Mesh Hail Guard: A guard that will never rust and protects the units coil from being
damaged.
• Designed using galvanized steel: with a polyester urethane coat finish. The 950 hour salt spray finish resists corrosion 50% better than comparable units.
• Heavy-Gauge Full Perimeter Base Rails: Facilitates forklift handling and curb mounting.
• Convertible Air Delivery: Horizontal or downflow to accommodate rooftop or horizontal applications.
• Corrosion-Resistant Drain Pan: Quickly drains away evaporator condensate.
• One Piece Top for Great Fit and Finish, Total Seal: Well designed, quality
construction. Drip edge on top panels whisks away rainwater. Embossed bottom pan keeps blower component compartment dry.
• SmartStart® Control Board: Provides extended life to igniters using hot surface ignition technology. Programmed to learn the heat-up characteristics of the igniter, then adapt the ignition time to the characteristics of the furnace so the igniter is energized appropriately.
• Hot Surface igniter: Innovative application of an appliance type igniter with a 20 year history of reliability.
•EnergyEfcientVariableSpeedECMBlower: Advanced motor
technology provides 16 field selectable cooling and 8 for heating. Extra quiet and smooth blower on and off cycles, automatically adjusts to different static loads.
2
IDENTIFICATION CODE
P PG 2 G I E 24 K 080 X
X = NOx
P = Premier
PG = Packaged 1 = Series
G = Gas
I = 20 SEER
Electrical Code
K = 208/230-60-1
Cooling Capacity
(00) Btu
E = EXV (Electronic) Expansion Value
Heating Capacity
(000) Btu
SPECIFICATIONS
Single Phase
MODEL E24K080X E36K100X E48K120X E60K120X
Heating Input High/Low (Btuh) 80,000 / 52,000 100,000 / 65,000 120,000 / 78,000 120,000 / 78,000 Heating Output High/Low (Btuh) 64,800 / 42,120 81,000 / 52,650 97,200 / 63,180 97,200 / 63,180 Nominal Capacity-Cooling
(Btuh) 24,000 35,200 45,500 54,500 Heating Efficency-AFUE (%) 81 81 81 81 Cooling Efficiency -- SEER 20 20 20 20
Cooling Efficiency -- EER (BTU/WATT) 13 13 12.5 12
Electrical Rating - 60 Hz, Single Phase
Operating Voltage Range 187 - 253 187 - 253 187 - 253 187 - 253 Minimum Circuit Ampacity 20.9 26.7 32.8 40.8 Max. Overcurrent Protection 30 40 50 60
Compressor Data, Rotary, Brushless DC
Volts 208 / 230 208 / 230 208 / 230 208 / 230 Rated Load Amps 11.6 16.2 17.6 24.0 Lock Rotor Amps NA NA NA NA
Indoor Blower, Variable Speed, Brushless DC
Wheel Diameter 11 x 8 11 x 8 11 x 10 11 x 10 Motor HP 1/2 1/2 1 1 Motor Amps 3.8 3.8 7.0 7.0
Outdoor Fan, Variable Speed, Brushless DC
Motor HP 1/3 1/3 1/2 1/2 Motor Amps 2.6 2.6 3.8 3.8 Fan Diameter 24” 24” 24” 24”
Refrigerant Charge (oz) 96 96 136 150 Sound Rating 63-72 65-74 66-74 66-73
3
Loading...
+ 5 hidden pages