Failure to follow safety warnings exactly could result in serious injury, death or property
damage.
–
–
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this
or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
–
Installation and service must be performed by a qualified installer, service agency, or
the gas supplier.
•
Do not try to light any appliance.
•
Do not touch any electrical switch; do not use any phone in your building.
•
Clear the room, building, or area of all occupants.
•
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
•
If you cannot reach your gas supplier, call the fire department.
It is recommended that the owner post, in a prominent location, instructions for the customer’s use in the event the customer
smells gas. This information should be obtained from your gas supplier.
Post the following warning in a prominent location.
FOR YOUR SAFETY
Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or any other appliance.
2
In the State of Massachusetts, the following installation instructions apply:
■ Installations and repairs must be performed by a qualified or licensed contractor, plumber, or gas fitter qualified or licensed by
the State of Massachusetts.
■ Acceptable Shut-off Devices: Gas Cocks and Ball Valves installed for use shall be listed.
■ A flexible gas connector, when used, must not exceed 4 feet (121.9 cm).
IMPORTANT: The gas installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1.
The dryer must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National
Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, Part 1, CSA C22.1.
Important Information __________
IMPORTANT: A means of restraint must be used to prevent
straining of the gas supply when the dryer is moved.
An external means of power removal (disconnect device)
must be provided by the installer.
The dryer must be used only for drying water washed
fabrics.
The dryer must never be operated with any of the back
guards or service panels removed.
The wiring diagram for the dryer is located behind the front
control panel.
“Caution: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper
operation.”
List of Acronyms _______________
HVAC Heating, Ventilating, and Air-Conditioning
in WC Inches of Water Column
UL Underwriters Laboratory
NPT National Pipe Thread
MAXIMUM CAPACITY (DRY WEIGHT) PER POCKET30 lb13.60 kg
TUMBLER DIAMETER271/4"69.21 cm
TUMBLER DEPTH30"76.20 cm
TUMBLER VOLUME PER POCKET10.1 cu ft286 L
TUMBLER / DRIVE MOTOR PER POCKET1/2 hp0.37 kW
DOOR OPENING (DIAMETER)211/2"54.61 cm
DOOR SILL HEIGHT TOP POCKET / BOTTOM POCKET527/8" /
DRYERS PER 20' / 40' CONTAINER11 / 22
DRYERS PER 48' / 53' TRUCK30 / 33
VOLTAGE AVAILABLE120V 1ø 2W 60 Hz
APPROXIMATE NET WEIGHT675 lb306 kg
APPROXIMATE SHIPPING WEIGHT710 lb322 kg
AIRFLOW PER POCKET400 cfm11.3 cmm
HEAT INPUT PER POCKET72000 Btu/hr18143 kcal/hr
GAS
EXHAUST CONNECTION (DIAMETER)8"20.3 cm
INLET PIPE CONNECTION PER POCKET1/2" F.N.P.T.
Shaded areas are stated in metric equivalents
NOTE: The manufacturer reserves the right to make changes in specications at any time without notice or obligation.
1
/4"134.3 cm / 36.2 cm
14
INCOMING ELECTRIC
CONNECTIONS
53 3/8"
[135.5 cm]
52 1/4"
80 3/4"
[205.2 cm]
[132.6 cm]
3 1/8"[7.8 cm]
5"
[12.8 cm]
3 1/2"
[8.9 cm]
29 3/4"
[75.4 cm]
5"
[12.6 cm]
12 1/4"
[31.2 cm]
8"
[20.3 cm]
EXHAUST CONNECTION
MAIN DOOR OPEN
4 7/8"
[12.3 cm]
GAS INLET CONNECTION
1/2" F.N.P.T
78 1/4"
[198.8 cm]
51 7/8"
[131.8 cm]
13 1/4"
[33.7 cm]
DRYER REAR
42 5/8"
[108.3 cm]
4"
[10.2 cm]
4
Installation Instructions _________
Location Requirements _________
WARNING
Excessive Weight Hazard
Use two or more people and mechanical equipment to
lift, move and install dryer.
Failure to do so can result in back or other injury.
Installation should be performed by qualied professional in
accordance with local, state, and country codes. In the absence
of these codes, the installation must conform to applicable
American National Standards: ANSI Z223.1- LATEST EDITION
(National Fuel Gas Code) or ANSI/NFPA NO. 70-LATEST
EDITION (National Electrical Code) or in Canada, the installation
must conform to applicable Canadian Standards: CAN/CGAB149.1-M91 (Natural Gas) or CAN/CGA-B149.2-M91
(Propane Gas) or LATEST EDITION (for General Installation and
Gas Plumbing) or Canadian Electrical Codes Parts 1 & 2 CSA
C22.1-1990 or LATEST EDITION (for Electrical Connections).
Tools Required
ʍ Utility Knife to remove packagingʍ 9/16" Box wrench or 9/16" socket to remove pallet boltsʍ #2 Phillips screwdriver to open box coverʍ Pipe wrench for gas connectionsʍ 7/8" open end wrench or adjustable wrench to install
coin box lock
Leveling feet adjustment
®†
ʍ TORX
adjustment ends
ʍ 1/4" socket or 1/4" open end wrench to make the
adjustment
Moving to Final Location
Move the dryer near the point of installation.
1.
Use a carton knife to cut the plastic lm.
2.
Remove all plastic wrap and corrugated cardboard.
3.
Dispose of/recycle all packaging material.
4.
Leveling Dryer
The dryer is equipped with 4 leveling legs, 1 at each corner of
the base. For optimum performance the dryer should be level
front-to-back and side-to-side.
T20 TORX® T25 to open front and rear to get foot
WARNING
Explosion Hazard
Keep flammable materials and vapors, such as
gasoline, away from dryer.
Failure to do so can result in death, explosion, or fire.
IMPORTANT: The dryer must be installed on noncombustible
oor only.
The dryer is for use in noncombustible locations.
Before installing the dryer, be sure the location conforms to
local codes and ordinances. In the absence of such codes or
ordinances the location must conform with the National Fuel
Gas Code ANSI.Z223.1 LATEST EDITION, or in Canada, the
installation must conform to applicable Canadian Standards:
CAN/CGA-B149.1-M91 (Natural Gas) or CAN/CGA-B149.2-M91
(Propane Gas) or LATEST EDITION (for General Installation and
Gas Plumbing).
The operation of this dryer may affect the operation of other
types of gas dryers, which take their air for safe combustion from
the same room. If in doubt, consult the dryer manufacturer(s).
The dryer must be installed on a sound level oor capable of
supporting its weight. Carpeting must be removed from the oor
area that the dryer is to rest on.
The dryer must not be installed or stored in an area where it will
be exposed to water and/or weather.
Provisions for adequate air supply must be provided as noted in
this manual (refer to Fresh Air Supply Requirements section).
Clearance provisions must be made from combustible
construction as noted in this manual (refer to Dryer Enclosure
Requirements section).
Provisions must be made for adequate clearances for servicing
and for operation as noted in this manual (refer to Dryer
Enclosure Requirements section).
The dryer must be installed with a proper exhaust duct
connection to the outside as noted in this manual (refer to
Exhaust Requirements section).
The dryer must be located in an area where correct exhaust
venting can be achieved as noted in this manual (refer to Exhaust
Requirements section).
IMPORTANT: The dryer should be located where a minimum
amount of exhaust ducting will be necessary.
The dryer must be installed with adequate clearance for air
openings into the combustion chamber.
IMPORTANT: The dryer must be installed in a location/
environment, which the ambient temperature remains between
40°F (4.44°C) and 130°F (54.44°C).
†®Torx and T20 are registered trademarks of Acument Intellectual Properties, LLC.
5
Dryer Enclosure Requirements ___
Bulkheads and partitions should be made of
noncombustible material.
A
B
MAKE-UP AIR OPENINGS
A=12"(30.48 cm)
B=24"(60.96 cm)
A
B
D
F
E
The requirement to allow the dryer door to open completely
A.
is 29" (74 cm).
A minimum overhead clearance of 12" (30.48 cm) is
B.
required.
Dryer should be positioned a minimum of 12" (30.48 cm)
C.
away from the nearest obstruction. 24" (60.96 cm) is
recommended for ease of installation, maintenance, and
service.
1/16" (1.5875 cm) minimum is required.
D.
Flooring should be level or below dryer cabinet for ease of
E.
removing panels during maintenance.
Dryers may be positioned sidewall to sidewall, however a
F.
1/16" (1.5875 cm) minimum allowance must be made for
the opening and closing of the control door, along with the
removal of panels during maintenance.
4" (10.16 cm) maximum.
G.
G
A
B
C
Fresh Air Supply Requirements __
When the dryer is operating, it draws in room air, heats it,
passes this air through the tumbler, and exhausts it out of
the building. Therefore, the room air must be continually
replenished from the outdoors. If the make-up air is inadequate,
drying time and drying efciency will be adversely affected.
Ignition problems and sail switch “uttering” problems may
result, as well as premature motor failure from overheating.
The dryer must be installed with provisions for adequate
combustion and make-up air supply.
EXAMPLE: For a bank of four dryers, 2 unrestricted openings
measuring 12" by 24" (30.48 cm by 60.96 cm) are acceptable.
To compensate for the use of registers or louvers used over the
openings, this area must be increased by approximately 33%.
Make-up air openings should not be located in an area directly
near where exhaust vents exit the building.
Allowances must be made for remote or constricting
passageways or where dryers are located at high
altitudes or predominantly low pressure areas.
IMPORTANT: Make-up air must be free of dry cleaning solvent
fumes. Make-up air that is contaminated by dry cleaning solvent
fumes will result in irreparable damage to the motors and other
dryer components.
NOTE: Component failure due to dry cleaning solvent fumes will
void the warranty.
Exhaust Requirements __________
Exhaust ductwork should be designed and installed by a
qualied professional. Improperly sized ductwork will create
excessive back pressure, which results in slow drying,
increased use of energy, and shutdown of the burner by the
airow (sail) switch, burner hi-limits, or lint chamber hi-limit
protector thermostat. The dryer must be installed with a proper
exhaust duct connection to the outside.
Air supply (make-up air) must be given careful consideration
to ensure proper performance of each dryer. Fresh air
ventilation openings shall not be blocked and/or sealed. As
a general rule, an unrestricted air entrance from the outdoors
of 1.0 ft2 (0.093 m2) is required for each dryer. (Based on 1 inch2
[6.5 cm2] per 1,000 Btu [252 kcal].)
It is not necessary to have a separate make-up air opening for
each dryer. Common make-up air openings are acceptable.
However, they must be set up in such a manner that the
make-up air is distributed equally to all the dryers.
6
As per the National Fuel Gas Code, “Exhaust ducts for type
2 clothes dryers shall be constructed of sheet metal or other
noncombustible material. Such ducts shall be equivalent in
strength and corrosion resistance to ducts made of galvanized
sheet steel not less than 26 gauge (0.0195" [0.50 mm]) thick.”
The ductwork should be laid out in such a way that the
ductwork travels as directly as possible to the outdoors with
as few turns as possible. Single or independent dryer venting
is recommended. It is suggested that the use of 90° turns be
avoided; use 30° and/or 45° bends instead. The radius of the
elbows should preferably be 1-1/2 times the diameter of the
duct. All ductwork should be smooth inside with no projections
from sheet metal screws or other obstructions, which will collect
lint. When adding ducts, overlap the duct being connected.
All ductwork joints must be taped to prevent moisture and lint
from escaping into the building. Inspection doors should be
installed at strategic points in the exhaust ductwork for periodic
inspection and cleaning of lint from the ductwork.
IMPORTANT: Exhaust back pressure measured by a
manometer/magnehelic in the exhaust duct must be no less
than 0 and must not exceed 0.3 in WC (0.75 mb).
NOTE: It is recommended that exhaust or booster fans not be
used in the exhaust ductwork system except where necessary
to maintain exhaust back pressure (in the exhaust duct) between
zero and 0.3" water column. Where employed, booster fans
must not activate the dryer airow proving switch (sail switch)
when the dryer is not in operation.
NOTE: When the exhaust ductwork passes through a wall,
ceiling, or roof made of combustible materials, the opening must
be 2" (5.08 cm) larger than the duct (all the way around). The
duct must be centered within this opening.
The ductwork for this dryer must be suitable for the appliance
category in accordance with national installation regulations of
the country of destination.
If the length of the duct run or quantity of elbows used exceeds
the above noted specications, the cross-sectional area of the
ductwork may need to be increased.
IMPORTANT: For extended ductwork runs, the cross section
area of the ductwork can only be increased to an extent. When
the ductwork approaches the maximum limits noted in this
manual, a professional HVAC rm should be consulted for
proper venting information.
Single Dryer Venting (10" Duct)
IMPORTANT: A minimum exhaust duct size of 10" (25.4 cm)
must be used for extended runs.
For a 10" (25.4 cm) run where a maximum of two elbows are
used (refer to the illustration below), the ductwork from the dryer
outlet must not exceed 45' (13.7 m).
This calculation of 45' (13.7 m) compensates or allows for the
use of a maximum of two elbows. Refer to the illustration below.
SINGLE DRYER VENTING (10" DUCT)
2 x D CLEARANCE
8"(20.3 cm)
DRYER
CONNECTION
10"(25.4 cm) RND DUCT
NOTE A
ROOF
45 FT
MAX
(13.7 m)
INSPECTION
DOOR
CONNECTION
8"(20.3 cm)
DRYER
45 FT MAX
(13.7 m)
INSPECTION
DOOR
NOTE A
10"(25.4 cm)
DUCT
2 x D CLEARANCE
Outside Ductwork Protection
To protect the outside end of the horizontal ductwork from the
weather, a 90° elbow bent downward should be installed where
the exhaust exits the building. If the ductwork travels vertically
up through the roof, it should be protected from the weather by
using a 180° turn to point the opening downward. In either case,
allow at least twice the diameter of the duct between the duct
opening and the nearest obstruction (refer to the diagram).
IMPORTANT: Do not use screens, louvers, or caps on the
outside opening of the exhaust ductwork.
Single Dryer Venting (8" Duct)
IMPORTANT: A minimum exhaust duct size of 8" (20.3 cm)
must be used.
For an 8" (20.3 cm) run where a maximum of two elbows are
used (refer to the illustration below), the ductwork from the dryer
outlet must not exceed 10' (3.0 m).
This calculation of 10' (3.0 m) compensates or allows for the use
of a maximum of two elbows. Refer to the illustration below.
SINGLE DRYER VENTING
2 x D CLEARANCE
8" (20.32 cm) RND DUCT
NOTE A
ROOF
10 FEET
MAXIMUM
(3.05 m)
INSPECTION
DOOR
10 FEET MAXIMUM (3.05 m)
INSPECTION
DOOR
NOTE A
8" (20.32 cm)
RND DUCT
2 x D CLEARANCE
VERTICALHORIZONTAL
NOTE A OPENING MUST BE 2"(5.08 cm) LARGER THAN THE DUCT (ALL THE
WAY AROUND). THE DUCT MUST BE CENTERED WITHIN THIS OPENING
If the length of the duct run or quantity of elbows used exceeds
the above noted specications, the cross-sectional area of the
ductwork may need to be increased.
IMPORTANT: For extended ductwork runs, the cross section
area of the ductwork can only be increased to an extent. When
the ductwork approaches the maximum limits noted in this
manual, a professional HVAC rm should be consulted for
proper venting information.
Multiple Dryer (Common) Venting
If it is not feasible to provide separate exhaust ducts for each
dryer, ducts from individual dryers may be channeled into a
“common main duct.” The individual ducts should enter the
bottom or side of the main duct at an angle not more than 45° in
the direction of airow. The main duct should be tapered, with
the diameter increasing before each individual 10" (25.4 cm)
duct (when dryer common exhaust is used) is added.
IMPORTANT: No more than four dryers or eight tumblers total
should be connected to one main common duct.
The main duct may be any shape provided that the minimum
cross-sectional area is maintained. The illustration below shows
the minimum cross-sectional area for multiple dryer venting.
These gures must be increased if the main duct run from the
last dryer to where it exhausts to the outdoors is unusually long
(over 30' [9.1 m]) or has numerous elbows (more than one) in it.
VERTICALHORIZONTAL
NOTE A OPENING MUST BE 2"(5.08 cm) LARGER THAN THE DUCT (ALL THE
WAY AROUND). THE DUCT MUST BE CENTERED WITHIN THIS OPENING
7
MULTIPLE DRYER VENTING WITH 10"(25.4 cm) DIAMETER EXHAUST
NOTE A
HORIZONTAL
2 x D CLEARANCE
FORMULAS TO CALCULATE DUCTING CROSS SECTIONAL AREA
CROSS SECTIONAL AREA OF A ROUND DUCT= 0.785(19.939 mm)
CROSS SECTIONAL AREA OF A RECTANGULAR DUCT= W x H
NOTE A: OPENING MUST BE 2"(5.08 cm) LARGER THAN THE DUCT (ALL THE
WAY AROUND). THE DUCT MUST BE CENTERED WITHIN THIS OPENING.
CONNECTIONS AT COMMON DUCT
NO OF DRYERS4321
MINIMUM CROSS (SQ IN)
SECTION AREA (SQ CM)
MINIMUM ROUND (IN)
DUCT DIAMETER (CM)
30' MAXIMUM
D
x D WHERE D= DIAMETER OF THE DUCT
TO INDIVIDUAL
WALL
TUMBLER EXHAUST MUST ENTER MAIN
EXHAUST DUCT AT 45 ANGLE
IMPORTANT: NO MORE THAN 4 DRYERS (8 TUMBLERS)
CAN BE CONNECTED TO ONE COMMON DUCT (VENT).
WHERE W= WIDTH AND H= HEIGHT
210164 120 80
1354 1058 774 516
16141210
40353025
9.1 m
DRYERS
NOTE A
INSPECTION DOORS
29.625"(75.25 cm) MINIMUM
DISTANCE BETWEEN
VERTICAL
2 x D CLEARANCE
ROOF
DUCTS
D
H
W
Electrical Information ___________
Electrical Requirements
All electrical connections must be made by a properly licensed
electrician. This is to ensure that the electrical installation is
adequate and conforms to local, state, and national regulations
or codes of the country of destination. In the absence of such
codes, all electrical connections, materials, and workmanship
must conform to the applicable requirements of the National
Electrical Code ANSI/NFPA NO. 70-LATEST EDITION or in
Canada, the Canadian Electrical Codes Parts 1 & 2 CSA C22.11990 or LATEST EDITION.
IMPORTANT: Failure to comply with these codes or ordinances,
and/or the requirements stipulated in this manual can result in
personal injury or component failure.
NOTE: Component failure due to improper installation will void
the warranty.
Each pocket should be connected to an independently protected
branch circuit. The dryer must be connected with copper wire
only. Do not use aluminum wire. The copper conductor wire/
cable must be of proper ampacity and insulation in accordance
with electric codes for making all service connections.
NOTE: The use of aluminum wire will void the warranty.
An individual ground circuit must be provided to each pocket, do
not daisy chain.
Component failure due to improper voltage application will void
the warranty.
The manufacturer reserves the right to make changes in
specications at any time without notice or obligation.
IMPORTANT: A separate protected circuit must be provided to
each pocket.
It is necessary to have a power disconnect for each pocket.
These disconnects must be located within 30' (9 m) of the
dryer and also be identied as being one of two power sources
supplying a dryer.
The dryer must be connected to the electric supply shown on
the data label.
Electrical Service Specications
ELECTRICAL SERVICE SPECIFICATIONS (PER POCKET)
NOTES:
When fuses are used they must be dual
A.
element, time delay, current limiting, class RK1
or RK5 ONLY. Calculate/determine correct fuse
value, by applying either local and/or National
Electrical Codes to listed appliance amp draw
data.
Circuit breakers are thermal-magnetic
B.
(industrial) motor curve type ONLY. For others,
calculate/verify correct breaker size according
to appliance amp draw rating and type of
breaker used.
SERVICE
VOLTAGE
PHASEWIRE
SERVICE
APPROX.
AMP
DRAW
CIRCUIT
BREAKER
MINIMUM
WIRE GAUGE
60 Hz
1201ø28.71514
Grounding
A ground (earth) connection must be provided and installed in
accordance with local, state, and national regulations or codes
of the country of destination. In the absence of these codes,
grounding must conform to applicable requirements of the
National Electrical Code ANSI/NFPA NO. 70-LATEST EDITION,
or in Canada, the installation must conform to applicable Canada
Standards: Canadian Electrical Codes Parts 1 & 2 CSA C22.11990 or LATEST EDITION. The ground connection may be to a
proven earth ground at the location service panel.
8
Electrical Connections
A wiring diagram is located behind the control panel with
connection data.
If local codes permit, power to the dryer can be made by the
use of a exible UL listed power cord/pigtail (wire size must
conform to rating of dryer), or the dryer can be hard wired
directly to the service breaker panel. In both cases, a strain relief
must be installed where the wiring enters the dryer.
Fire Hazard
Use appropriate gauge of copper wire (See chart in
"Electrical Requirements" section).
Use a UL listed strain relief.
Disconnect power before making electrical connections.
Electrically ground appliance per installation
instructions.
Securely tighten all connections.
Failure to do so can result in death, fire, or electrical
shock.
K
C
A
L
B
L
A
C
K
E
T
I
H
W
B
W
H
I
T
E
B
L
A
C
K
B
L
A
C
K
E
T
I
H
W
E
T
I
H
W
D
N
U
O
R
G
D
N
U
O
R
G
D
N
U
O
R
G
Single-Phase Electrical Connection Leads
Black
+
Positive or L1
White
+
Neutral or L2
Green
+
Ground
Input connection wiring must be sized properly to handle the
dryer’s current draw. This information is printed on the dryer’s
data label.
Gas Information ________________
WARNING
Single-Phase (1ø) Wiring Connections / Hookup
The electrical input connections are made into the rear service
box located at the top of the dryer. To gain access, the service
box cover must be removed. (Refer to the specication drawing
in “Specications” section of manual.)
120 Volt Application with Neutral
Remove 3 screws holding down electrical box plate at the top
of the machine.
Remove 2 knockouts provided just in front of electrical box and
insert 3/4" UL listed strain relief into the holes.
Insert the wiring from the two 120 V 15 A circuits (one for top
tumbler and one for bottom tumbler) into the strain reliefs.
Determine the top pocket electrical connections by checking
wire label, which will be marked “top”.
Connect wiring from 120 V 15 A circuit to top pocket wiring as
described in the following illustration (black to black, white to
white and green to chassis ground wire).
Connect wiring from 120 V 15 A circuit to remaining wires
(bottom pocket) as described in the following illustration (black
to black, white to white and green to chassis ground wire).
Tighten strain relief screws assuring to leave a 1/2" of slack in
box.
Replace electrical box plate by inserting 3 screws previously
removed.
Explosion Hazard
Use a new approved gas supply line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to propane, have a qualified person make
sure gas pressure does not exceed 13" (330 mm) water
column.
Examples of a qualified person include:
licensed heating personnel,
authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
Type of Gas
This dryer is equipped for use with natural gas. It is design
certied by CSA International for Propane and butane gases
with appropriate conversion (Propane kit 887299). No attempt
shall be made to convert the dryer from the gas specied
on the serial/rating plate for use with a different gas without
consulting the serving gas supplier. Conversion must be done
by a qualied service technician.
It is your responsibility to have all plumbing connections,
materials, and workmanship conform to local and state
regulations or codes of the country of destination. In the
absence of such codes, all plumbing connections, materials,
and workmanship must conform to the applicable local
requirements. In the USA this is the National Fuel Gas Code
ANSI Z223.1-LATEST EDITION, or in Canada, the Canadian
Installation Codes CAN/CGA-B149.1-M91 (Natural Gas) or
CAN/CGAB149.2-M91 (Propane Gas) or LATEST EDITION.
9
It is important that gas pressure regulators meet applicable
pressure requirements, and that gas meters be rated for the
total amount of all the dryer Btu being supplied.
For ease of service, the individual gas supply line of each dryer
must have its own manual shutoff valve.
The dryer must be isolated from the gas supply piping system
by closing its individual manual shutoff valve during any
pressure test of the gas supply system at test pressures equal to
or less than 1/2 psig (3.5 kPa).
The dryer and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing
of that system at test pressures in excess of 1/2 psig (3.5 kPa).
Failure to isolate or disconnect the dryer from supply as noted
can cause irreparable damage to the gas valve, voiding the
warranty.
NOTE: Undersized gas piping will result in ignition problems,
slow drying, and increased use of energy.
The input ratings shown on the data label are for elevations up
to 2,000' (610 m), unless elevation requirements of over 2,000'
(610 m) were specied at the time the dryer order was placed
with the factory. The adjustment or conversion of dryers in the
eld for elevations over 2,000' (610 m) is made by changing
each burner orice. If this conversion is necessary, contact the
distributor who sold the dryer or contact the manufacturer.
IMPORTANT: If connection to this dryer is made with a
exible hose, it must be suitable for the appliance category in
accordance with national installation regulations of the country
of destination, and if in doubt the installer must contact the
supplier. The manufacturer of this dryer does not recommend
the use of exible gas supply line/hose.
Pipe joint compounds that resist the action of natural, propane,
and butane gases must be used.
In the U.S.A: An individual manual shutoff valve must be
installed within 6' (1.8 m) of the dryer in accordance with the
National Fuel Gas Code, ANSI Z223.1.
In Canada: An individual manual shutoff valve must be installed
in accordance with the B149.1, Natural Gas and propane
Installation Code. It is recommended that an individual manual
shutoff valve be installed within 6' (1.8 m) of the dryer.
Gas Connections
Inlet connection .....1/2" M.N.P.T. (1 per pocket)
Inlet supply size ....1/2" Pipe (minimum) (1 per pocket)
Combined top and bottom require a 3/4" supply (minimum)
Piping / Connections
The dryer is provided with two 1/2" N.P.T. inlet pipe connection
at the rear of the dryer. It is recommended that a gas shutoff
valve be provided to the gas supply line of each pocket for ease
in servicing.
The size of the main gas supply line (header) will vary depending
on the distance this line travels from the gas meter. Specic
information regarding supply line size should be determined by
the gas supplier.
NOTE: Undersized gas supply piping can create a low or
inconsistent pressure, which will result in erratic operation of the
burner ignition system.
Natural Gas Specications**
Nominal
Heating
Value
Btu/ft
1,0006.0-12.0144,000 42.2204.08923.5
*Consult factory for elevations over 2,000' (609.6 m) for correct burner orice
size(s).
** Btu rating for both tumblers.
Supply
Pressure
3
in WCBtu
Gross Heat
Input
kWDMSmmin WC
/hr
Orice
Size*
Orice
(Injector)
Quantity
Pressure
Burner
10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.