INSTALLER: LEAVE THESE INSTRUCTIONS WITH THE APPLIANCE
INSTALLATION MANUAL
Electric 30-inch Wide
Free-standing Double Oven Range
PLEASE KEEP THIS MANUAL FOR FUTURE REFERENCE
THE MANUAL IS INTENDED TO ASSIST IN THE INITIAL INSTALLATION AND ADJUSTMENTS OF THE RANGE.
ENGLISH ' PP. 1-8
ESPANOL ' p_g. 9-16
FRANCAIS ' p. 17-24
Only qualified personnel should
install or service this range.
Read "Safety Instructions" in Use &
Care book before using range.
Improper installation, adjustment,
alteration, service, maintenance or
use of range can result in serious
injury or property damage.
CLEARANCE DIMENSIONS
For complete information in regard to installation of
freestanding range, see figures 1 and 2 on pages 2 and 3.
For SAFETY CONSIDERATIONS do not install a range in
any combustible cabinetry which is not in accord with the
installation clearances shown in figure 1.
CAUTION: This range has been designed in
accordance with the requirements of various safety
agencies and complies with the maximum allowable
wood cabinet temperatures of 194°F. If this range
is installed with cabinets that have a lower working
temperature than 194°F, discoloration, delamination
or melting may occur.
I Your range may not be equipped with some of the features referred to in this
I manual. J
8101 P361-80
(07-2000-00)
INSTALLATION DRAWINGS (Pages 2 & 3)
"A" = 30 inches (76.2 cm) minimum clearance between
the top of the cooking surface and the bottom of an
unprotected wood or metal cabinet, or "A" = 24 inches
(61 cm) minimum when bottom of wood or metal cabinet
is protected by not less than 1/4-inch (6.4 mm) thick
flame-retardant millboard covered with not less than No.
28 MSG sheet steel, 0.015-inch (0.381 mm) thick
stainless steel, 0.024-inch (0.610 mm) thick aluminum, or
0.020-inch (0.508 mm) thick copper.
To eliminate the risk of burns or fire by reaching over
heated surface units, cabinet storage space located
above the surface units should be avoided. If cabinet
storage is to be provided, the risk can be reduced by
installing a range hood that projects horizontally a
minimum of 5 inches (13 cm) beyond the bottom of the
cabinets.
FIGURE 1
NOTE: Figure may not be representative of actual unit.
FIGURE 1
1, 2, 3 - COMBUSTIBLE BUILDING WALLS.
4 - COMBUSTIBLE WALL CABINET.
A free-standing range may be installed adjacent to (0"
from) combustible walls 1, 2 & 3.
NOTE: FOR INSTALLATION IN CANADA, A FREE
STANDING RANGE IS NOT TO BE INSTALLED
CLOSER THAN 12MM FROM ANY ADJACENT
SURFACE.
-2-
- 4-WIRE
GeminiDoubleOvenRange
Dimensions
J
A
B
Inches
25
24
Centimeters
63.5
61
_lDir
COUNTERTOP/ NORMAL
• HEIGHT _ .... COUNTER
OPENING
DEPTH
]
C2
D
E2
F
G
H
!
J
K3
L4
30
36
20
6
7
5 3/4
46 3/4
29 7/8
26 5/16 to 27 1/4
35 7/8
76.2
91.4
50.8
15.2
17.8
14.6
118.7
75.9
66.8 to 69.2
91.1
FIGURE 2
Notes:
1. Provide for either a 3-wire or 4-wire 1201208, 1201240 volt outlet per applicable cord in shaded area shown. Refer
to installation instructions for proper positioning of outlet.
2. For Canadian models, cutout width is 31" (78.7 cm) and dimension E is 20 1/2" (52.1 cm).
3. Excluding handle. Dimension given is from wall to front of oven door, and will vary based on electric outlet
receptacle installation.
4. May vary slightly depending upon leveling leg adjustment.
Important: Because of continuing product improvements, Maytag reserves the right to change specifications
without notice• Dimensional specifications are provided for planning purposes only. For complete details see
installation instructions that accompany each product before selecting cabinetry, making cutouts or beginning
installation•
-3-
MOBILE HOMES
LOCATING THE RANGE
The installation of a range designed for mobile home
installation must conform with the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part
3280 (formerly the Federal Standard for Mobile Home
Construction and Safety, Title 24 HUD, Part 280) or,
when such standard is not applicable, the Standard for
Place range in a well lit area. Do not set range over holes
in the floor or other locations where it may be subject to
strong drafts. Any opening in the wall behind the range
and in the floor under the range should be sealed. Make
sure the flow of cooling/ventilation air is not obstructed
below the range.
Manufactured Home Installations 1982 (Manufactured
Home Sites, Communities and Set-Ups), ANSI
A225.1-1atest edition, or with local codes.
NOTE: A range should NOT be installed over kitchen
carpeting.
ANTI-TIP DEVICE INSTALLATION INSTRUCTIONS
WARNING: A risk of range tip-over exists if the appliance
is not installed in accordance with the provided installation
instructions. The proper use of this device minimizes the
risk of TIP-OVER. tn using this device the consumer must
still observe the safety precautions as stated in the USE
and CARE MANUAL and avoid using the oven doors as a
step stool.
Installation instructions are provided for wood and cement
in either floor or wall. Any other type of construction may
require special installation techniques as deemed
necessary to provide adequate fastening of the ANTI-TIP
bracket to the floor or wall. The bracket may be installed
to engage the LEFT or RIGHT rear leveling foot.
NOTE: The bracket provided is designed for use with
flush mount and non-flush mount outlet receptacles.
Install the bracket with the orientation hole in the longer
leg against the wall or floor as shown in figures 3 and 4.
STEP 1 - Locatinq The Anti-tip Bracket (See Fiqure 3)
Installations With Flush Mount Wall Outlet
A. Determine where either the right or left "EDGE" of the
range will be located and mark the floor or wall.
a.
Place the BRACKET 15/16" (24mm) from the marked
"EDGE" toward center of opening and against the
back wall as shown in figure 3, with orientation hole
against wall.
C. Use the bracket as a template and mark the required
holes, as shown in figure 3, for the type of
construction you will be using.
D. Free-standing range may be secured to either floor or
wall. See Step 2 on page 5 for bracket installation
options.
FLUSH MOUNT WALL OUTLET _ _/._/"_1
RECEPTACLE _ !i
(SEE FIGURE 2 FOR LOCATION SEE "_._111
FIGURES 7 & 8 FOR ROTATION OF _ I
OUTLET RECEPTACLE) II
-ORIENTATION
HOLE
FOR
WALL
[24- mini
FROM EDGE
OF RANGE
MARKED
OF RANGE
HOLES FOR
FLOOR
_LEVELINGFoOT
II
ATTACH ANTI-TIP BRACKET
WITH LONG SCREWS
BRACKET
P
1 1/2" MIN.
[3.8 crn]
FIGURE 3
-4-
Locatinq The Anti-Tip Bracket (See Fiqure 4)
Installations With Alternate Outlet Receptacle (Non-Flush Mount)
If the outlet receptacle must be mounted as shown in figure
B. Place the bracket 15/16" (24 mm) from the marked
4, the range will not push back against the wall.
Therefore, the long leg of anti-tip bracket will have to be on
the floor to properly engage the leveling foot.
C. Use the bracket as a template and mark the required
A. Determine where either the right or left "EDGE" of the
range will be located and mark the floor or wall.
NON-FLUSH MOUNT
OUTLET RECEPTACLE
(SEE FIGURE 2 FOR LOCATION
SEE FIGURES 7 & 8 FOR --_ .t..
ROTATION OF OUTLET "_
_ /*
HOLE FOR
WALL I I I
I/
-ATTACH ANTI-TIP BRACKET
WITH LONG SCREWS
HOLE
ION
BRACKET
"EDGE" toward the center of opening and against the
back wall as shown in figure 4, with orientation hole
against floor.
holes as shown in figure 4 for the type of construction
you will be using.
./
I-TIP
[24- mini
FR Olvl EDGE
OF RANGE
MARKED EDGE
OF RANGE
HOLES FOF_
FLOOR
STEP 2 - Anti-Tip Bracket Installation Options
A. Wood Construction:
1. Floor: Locate the center of the two holes identified in
figures 3 and 4 as applicable, as "HOLES FOR
FLOOR." Drill a 1/8" (3 mm) pilot hole in the center
of each hole (a nail orawl may be used ifa drill is not
available). Secure the ANTI-TtP bracket to the floor
with the two screws provided. Proceed to STEP 3.
. Wall: Locate the center of the two holes identified in
figures 3 and 4 as applicable, as "HOLES FOR
WALL." Drill an angled 1/8" (3 mm) pilot hole in the
center of each hole as shown in figure 5. (A nail or
awl may be used ifa drill is not available). Secure the
ANTI-TIP bracket to the wall with the two screws
provided as shown in figure 5. Proceed to STEP 3.
__ _--LEVELING
"_ _FOOT
FIGURE 4
figures 3 and 4 as applicable, as "HOLES FOR
FLOOR". Secure the ANTI-TIP bracket to the floor.
Proceed to STEP 3.
NOTE: USE A MINIMUM OF (2)
SCRL_!S MUST -
ENTER WOOD
OR METAL.
WALL
SCREWS TO INSTALL ANTI-TbP BRACKET
(SEE FbGURES 3 AND 4 FOR PROPER
ORbENTATION) TO THE WALL OR FLOOR.
-ANTI-TIP
BRACKET
-SCREW BRACKET
SLIDE IN
TO SECURE
B. Cement or Concrete Construction:
1. Suitable screws for concrete construction can be
obtained at the hardware store. Drill the required
size hole for the hardware obtained into the
concrete at the center of the holes identified in
ARTJ 9215-104
FIGURE 5
-5-
STEP 3 - Range Installation
A. A free-standing range may be installed by one person.
B. Align the range to its designated location and slide it
back into position. Note: A minimum clearance of 1/4"
(6 mm) is required between the range and the leveling
foot that will engage the ANTI-TIP bracket, see figure
5.
CAUTION: Damage to the range may occur if range
is moved or lifted by grasping the main top or
backguard.
C. All freestanding ranges with a glass top have a non
lift-up top. Coil tops are lift-up.
D. For SAFETY CONSIDERATIONS as well as optimum
performance adjust the range so that it is level. This
may be checked by placing a spirit level or a large
pan of water on the cooktop or the oven rack. tf an
adjustment is required pull the range forward, tip the
range and rotate the leveling feet as required.
E. To check the range for proper installation of the
anti-tip bracket: Use a flashlight and look underneath
the bottom of the range to see that one of the rear
leveling feet is engaged in the bracket slot.
F. Proceed with the remainder of the installation
instructions provided with the range.
CONNECTING THE RANGE
ELECTRIC SUPPLY
The range must be installed in accordance with Local and
National Electric Code (NEC) ANSt/NFPA No. 70-latest
edition. See rating plate for total connected KW rating.
ELECTRIC SUPPLY (Canada)
The range must be installed in accordance with Local and
Canadian Electric Code CSA STD.C22.1 latest edition.
See rating plate for total connected KW rating.
the back of the range. The range is then connected to this
outlet through an approved range connector (pigtail)
fastened securely to the terminal block with proper strain
relief at the range and a three or four pronged plug at the
opposite end.
RANGE CONNECTIONS
Some models are shipped direct from the factory with
service cords (pigtails) attached. There are no range
connections necessary on these models. Just plug into
the range outlet. On models not provided with a service
cord, connection to the power supply is necessary.
REMEMBER - mobile homes and many LOCAL CODES
DO NOT PERMIT GROUNDING THROUGH NEUTRAL.
Hence, 4-wire service MUST be provided for such
installations. 3-wire service may be used when permitted
by local code. Use COPPER WIRE ONLY. tf a flexible
power cord is required, it is recommended a cord no
longer than 4 ft. be used. Make connections as explained
below and with reference to the appropriate illustration
(see figures 7 and 8). After installation, insure tightness of
all electrical connections and replace all covers.
Remove terminal block access cover from range back.
(See figure 6).
RANGE CONNECTIONS (Canada)
This model was shipped direct from the factory with
service cord (pigtail) attached. There are no range
connections necessary. Just plug into the range outlet.
See figure 2 on page 3 for outlet location.
NOTE: Cord replacement - ONLY a power supply cord
rated at 240 volts minimum, 40 amperes or 50 amperes
power supply cord that is marked for use with nominal
1 3/8" (34.93 mm) diameter connection opening, with
closed loop terminals and marked for use with ranges
shall be used.
OUTSIDE WIRING
Your local utility company will tell you whether the present
electric service to your home is adequate. It may be
necessary to increase the size of the wiring to the house
and service switch to take care of the electrical load
demanded by the range. The kilowatt rating for the range
is specified on the rating plate located on flip-up plate at
the rear of upper left hand corner of backguard.
HOUSE WIRING
Most local Building Regulations and Codes require that all
electrical wiring be done by licensed electricians. All
wiring should conform to Local and National Electrical
Codes. This range requires a single phase three wire
120/240 or a 120/208 volt, 60 Hz, AC circuit. Wiring codes
require a separate circuit be run from the main entrance
panel to the range and that it be equipped with separate
disconnect switch and fuses, either in the main entrance
panel or in a separate switch and fuse box. In some
communities, a solid or flexible continuous armored
conduit must be used from main entrance panel to the
terminal box on the rear of the range. Others will permit
the termination of the range circuit at a polarized three or
four wire plug-in outlet placed at a convenient point near
-6-
CONDUIT
PLATE
FIGURE 6
ACCESS
COVER
TERMINAL
CONNECTION
BLOCK
3-WIRE SERVICE CORD OR CONDUIT INSTALLATION
1. Insure that the copper ground strap IS CONNECTED
between the middle post of the main terminal
connection block and the range chassis.
2. The middle wire of the service cord or ground lead of
3-wire conduit MUST connect to the neutral (middle)
post of the main terminal block. The other two wires of
3. A appropriate strain relief for service cord or conduit
the service cord or conduit connect to the outside
posts of the main terminal connection block. Polarity is
unimportant.
must be attached to the conduit plate.
WHITE
GROUND
(CONNECTED AT
FACTORY)
RELIEF
)UTLET RECEPTACLE
MOUNTED FLUSH TO
FLOOR
MAIN TERMINAL
CONNECTION BLOCK
MIDDLE WIRE OF
SERVICE CORD
OR GROUND LEAD
OF CONDUIT
CONDUIT
PLATE
STAMPED REMOVE BRACKET. FLIP
CORD & RE-AT[ACH WITH HOLE
OUTLET RECEPTACLE TO BE
ROTATED AS SHOWN IF NOT_
"LUSH TO WALL
STAMPED
CONDUIT
FOR USE WITH CONDUIT.
MARKED "CONDUIT"
DOWN.
FLOOR
FIGURE 7
ACCEPTABLE 3-WIRE PLUG INSTALLATION
-7-
4-WIRE SERVICE CORD OR CONDUIT INSTALLATION
(MOBILE HOMES OR AS REQUIRED BY CODES)
1. The copper ground strap connected between the
neutral (middle) post of the main terminal block and the
chassis MUST be cut off as shown in figure 8. Save the
green ground screw to attach the ground from the 4
wire cord. Only a 4 wire cord or conduit should be
used.
2. The ground wire from the service cord or conduit must
connect to the range chassis using the green ground
screw.
THIS PORTION OF_
GROUNDING STRAP \
MUST BE REMOVED.
WHIT
CHASS IS
GROUND
STRAIN-
RELIEF USE WtTH CONDUIT,
MAIN TERMINAL
CONNECTION BLOCK
SERVICE CORD
OR CONDUIT
CORD DOWN,
3. The white wire of the service cord or conduit must
4. An appropriate strain relief for service cord or conduit
E WiRE
connect to the neutral (middle) post of the main
terminal block. The other two wires of the service cord
or conduit connect to the red and black posts of the
main terminal block, respectively.
must be attached to the conduit plate.
\
\
CHASSIS
C4ROUND
REMOVE BRACKET. FLIP
& RE-ATTACH WITH HOLE
MARKED "CONDUIT"
/E OUTLET RECEPTACLE TO eE-_ _ \ /
\ROTATED AS SHOWN IF NOT\ j/_"_c_),,.>"_'_
/\;LUSH TO WALL _ _[
OUTLET RECEPTACLE : I " I t" /
' LTERNATE/ _ I
MOUNTEDFLUSHTO I NSTALLAT ION 1 I /
FLOOR
FIGURE 8
ACCEPTABLE 4-WIRE PLUG INSTALLATION
CONVERSION FROM 3-WIRE TO 4-WIRE SERVICE
(Free-standing Model With 3-Wire Service Cord Attached)
Disconnect range from power. Remove the access cover
on back of range and remove the 3-wire service cord from
the main terminal block. Follow instructions as outlined in
figure 8 to connect the 4-wire service cord.
NOTE: Cord replacement - ONLY a power supply cord
rated at 240 volts minimum, 40 amperes or 50 amperes
power supply cord that is marked for use with nominal
1 3/8" (34.93 mm) diameter connection opening, with
closed loop terminals and marked for use with ranges
shall be used.
-8-