Maytag MED8000AW, MED3000BW, MED4200BG, MED4200BW, MED6000AG Dimension Guide

...
Maytag MED8000AW, MED3000BW, MED4200BG, MED4200BW, MED6000AG Dimension Guide

Electric Dryer

PRODUCT MODEL NUMBERS

MED3000B, MED4000B, MED4200B, MED6000A, MED7000A, MED8000A

Front view:

Side view:

27" (686 mm)

381/8"

(968 mm)

3/4"*

(18 mm)

Back view:

Recommended Installation Spacing:

61/2"

(165 mm)

 

 

 

 

 

3"

 

 

Power supply

18" min.

 

(76 mm)

48 in.2 min.

 

Cord/cable

(457 mm)

 

 

 

 

 

 

(310 cm2)

 

 

297/8"*

 

 

 

 

 

Water inlet

(759 mm)

 

 

 

 

 

(Steam models only)

 

 

 

 

 

 

 

31/2"*

 

 

 

 

 

Vent

(89 mm)

 

 

 

 

 

 

 

 

 

 

24 in.2 min.

 

 

5"

 

 

3"

(155 cm2)

 

 

(127 mm)

 

 

 

 

 

 

 

(76 mm)

 

 

 

 

 

 

 

3/4"*

 

61/8"*

 

 

 

 

 

(156 mm)

 

 

 

 

(18 mm)

 

 

 

 

 

143/8"

1"

 

1"

 

 

 

 

 

 

 

(365 mm)

(25 mm)

 

 

 

(25 mm)

 

 

 

 

 

 

 

 

NOTE: Most installations require a minimum of 5" (127 mm)

* Approx. measurement.

clearance behind dryer for exhaust vent with elbow. See

 

“Venting Requirements”.

 

Installation spacing for recessed area or closet installation

The dimensions shown below are the recommended spacing for this dryer.

■■ Additional spacing should be considered for ease of installation and servicing.

■■ Additional clearances might be required for wall, door, floor moldings, and dryer venting.

■■ Additional spacing of 1" (25 mm) on all sides of the dryer is recommended to reduce noise transfer.

■■ For closet installation, with a door, minimum ventilation openings in the top and bottom of the door are required. Louvered doors

W10558997

with equivalent ventilation openings are acceptable. Companion appliance spacing should also be considered.

01/2013

ELECTRICAL REQUIREMENTS

To supply the required 3 or 4 wire, single phase, 120/240 volt, 60 Hz., AC only electrical supply (or 3 or 4 wire, 120/208 volt electrical supply, if specified on the serial/rating plate) on a separate 30-amp circuit, fused on both sides of the line. A time-delay fuse or circuit breaker is recommended. Connect to an individual branch circuit.

VENTING REQUIREMENTS

Exhaust venting: Exhaust your dryer to the outside. 4" (102 mm) diameter vent is required. Rigid or flexible metal exhaust vent must be used. Do not use plastic or metal foil vet. Exhaust hood must be at least 12" (305 mm) from the ground or any object that may be in the path of the exhaust.

Exhaust hoods:

The Vent System Chart provides venting requirements that will

Recommended Styles:

help achieve best drying performance.

 

 

 

 

Louvered Hood

Box Hood

Acceptable Style:

Angled Hood

Determine vent path:

■■ Select route that will provide straightest and most direct path outdoors.

■■ Plan installation to use fewest number of elbows and turns.

■■ When using elbows or making turns, allow as much room as possible.

■■ Bend vent gradually to avoid kinking. ■■ Use as few 90° turns as possible.

Determine vent length and elbows needed for best drying performance:

■■ Use following Vent System Chart to determine type of vent material and hood combinations acceptable to use.

NOTE: Do not use vent runs longer than those specified in Vent System Chart. Exhaust systems longer than those specified will:

■■ Shorten life of dryer.

■■ Reduce performance, resulting in longer drying times and increased energy usage.

Whirlpool Vent System Chart

 

Number of

Type

Box/louvered

Angled

 

 

90° elbows

of vent

hoods

hoods

 

 

 

 

 

 

 

 

0

Rigid metal

64 ft. (20 m)

58 ft. (17.7 m)

 

 

 

 

 

 

 

 

1

Rigid metal

54 ft. (16.5 m)

48 ft. (14.6 m)

 

 

 

 

 

 

 

 

2

Rigid metal

44 ft. (13.4 m)

38 ft. (11.6 m)

 

 

 

 

 

 

 

 

3

Rigid metal

35 ft. (10.7 m)

29 ft. (8.8 m)

 

 

 

 

 

 

 

 

4

Rigid metal

27 ft. (8.2 m)

21 ft. (6.4 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Bottom exhaust installations have a 90º turn inside the dryer. To determine maximum exhaust length, add one 90º turn to the chart.

Because Whirlpool Corporation policy includes a continuous commitment to improve our products, we reserve the right to change materials and specifications without notice.

Dimensions are for planning purposes only. For complete details, see Installation Instructions packed with product. Specifications subject to change without notice.