SC20C Series
Signal Conditioner with
Discharge Air Temperature Limiter
For direct or indirect fired gas applications, the track mounted
SC20C Series performs multiple functions. The control will
convert a controller's DC output signal of 4 to 20 milliamps or 0 to
10 volts to a 0 to 20 volt DC signal used to drive the Maxitrol
Selectra
temperature regardless of the controller supplied input. Three
discharge temperature ranges are available and are selectable
using a 3-pin header. The temperature is set within the selected
range using the onboard potentiometer. Temperature is
measured using a TS194/TS194Q with MT Series mixing tube.
5 psi (350 mbar) inlet pressure, 30,000 CFH (850 m
maximum, and pipe sizes from 3/8" to 4". (For additional valve
information see Bulletin MT2035, or consult your Maxitrol sales
representative.)
®
valve.
It will also limit the heater's maximum selected discharge air
Modulator and modulator-regulator valves are available up to
3
/h)
Three Position DIP Switch
4-20 mA
all positions on
ON
0-10 V
23
1
all positions off
SC20_MS_EN_08.2006
Dimensions: 7.5" L x 3.38" W x 2.09" H
SIGNAL CONDITIONER:
Ambient Limits...............-40o to 150oF (-40o to 66oC)
SIGNAL CONDITIONER POWER REQUIREMENTS:
24V AC transformer, 20 VA capacity (50/60 Hz).
(No grounded secondary.)
LIMITS DISCHARGE AIR TEMPERATURE:
Three Temperature Ranges: Jumper Pins
o
80
to 130oF (27o to 54.5oC) None
110o to 160oF (43o to 65.5oC) 2 & 3
150o to 200oF (65.5o to 93oC) 1 & 2
CONNECTIONS:
1/4" Spade
Wiring Diagram
B
1
T
24 VAC
POWER
1 2 3 4 5 (-) 6 (+)
24VAC
20VA
VALV E
OUTPUT
M OR MR
Valve
SENSOR
T2 T1
J1
1
3
TS194(Q)
23555 Telegraph Rd., P.O. Box 2230
© 2006 Maxitrol Company, All Rights Reserved.
Maxitrol Company
Southfield, MI 48037-2230 U.S.A.
248.356.1400 • Fax 248.356.0829
SIGNAL IN
Controller
(Note Polarity)
INPUT
Unit
TO AVOID INTERNAL DAMAGE TO THE SC20C SERIES
SIGNAL CONDITIONERS FOLLOW THESE GUIDELINES:
Transformer secondary must not be grounded in any
1.
portion of the circuit external to the SC20C Series signal
conditioners. If existing transformer is grounded, a
separate isolated transformer must be used.
Multiple SC20C Series signal conditioners controlled
2.
by a signal source with common outputs (terminals 5 &
6) require separate transformers for each SC20C
Series signal conditioner.
Multiple SC20C Series signal conditioners powered by
3.
a single transformer require isolated signal inputs
(terminals 5 & 6) to each SC20C Series signal
conditioner.
www.maxitrol.com