Maxitrol SC11S Installation Manual

SC11S and SC25S Signal Conditioners
INSTALLATION INSTRUCTIONS
Terminals
24 VAC
Terminals 1 & 2
Modulating
Gas Valve
Terminals 3 & 4
Input Signal
Terminals 5 & 6
Note Polarity
_
+
DESCRIPTION
SC11S and SC25S:
The SC11S and SC25S analog signal conditioners convert a 0-10 VDC or 4-20 mA control signal to an output level capable of driving one or more Selectra modulating gas valves. A 3-position DIP switch configures the SC11S or SC25S for a 0-10VDC or 4-20mA input signal.
A timer circuit initially xes the modulator output to 0 VDC
SC25S Only:
The SC25S also monitors and limits minimum and
maximum discharge air temperatures. The SC25S
senses the discharge air temperature using a TS194 (Q)
limit, the SC25S will override the control signal and reduce DC voltage (high limit) or increase DC voltage (low limit) in order to maintain discharge air temperatures between the set limits. When measured discharge air temperature is between the limit settings, the DC output is a function of the control signal (4-20 mA, 0-10 VDC) only.
Control Input
Start Voltage
Setting
Min DA Limit Settings
Max DA
Limit Range Settings
TS194Q Sensor
Max DA Adjustment
Start Time Adjustment
Actual Size: 7.5" L x 3.38" W x 2" H
SPECIFICATIONS:
Power Voltage: 24 VAC, 50/60 Hz
Control Input: 4-20 mA or 0-10 VDC
(Note Polarity) (user selectable DIP switch)
Output: 0-20 VDC, 1.8A max load
Start Time: 5 to 30 seconds nominal
(user adjustable dial)
Connections: ¼" Quick Connect Tab
Mounting: Snap Track w/Screws
READ PRIOR TO INSTALLATION:
To Avoid Internal Damage to Signal Conditioners Follow These Guidelines.
1. Transformer secondary must not be grounded
in any portion of the circuit external to the signal
conditioner. A separate, independent transformer is recommended.
2. Multiple signal conditioners controlled by a signal source with common outputs (terminals 5 & 6) require separate transformers for each signal conditioner.
3. Multiple signal conditioners powered by a single transformer require independent signal inputs
(terminals 5 & 6) to each signal conditioner.
© 2008 Maxitrol Company, All Rights Reserved.
1
SC11S and SC25S Signal Conditioners
INSTALLATION INSTRUCTIONS
JUMPER SETTINGS
SC25S Only:
J1 J1 J1
J2 J2 J2
Max DA Limit Range Settings: 80ºF - 130ºF nominal
110ºF - 160ºF nominal 150ºF - 200ºF nominal
150ºF - 200ºF
110ºF - 160ºF
80ºF - 130ºF
Min DA Limit Settings: 40ºF, 50ºF, or 60ºF
60ºF
50ºF
SC11S and SC25S:
J3 J3 J3
Maxitrol Company 23555 Telegraph Rd., P.O. Box 2230 Southeld, MI 48037-2230 U.S.A.
SC11S_25S_MS_EN_04.2008
40ºF
0 Voltage Start
20 VDC Start
Disabled
Start Voltage Selection: 20 VDC (xed), 0 VDC
2
© 2008 Maxitrol Company,
www.maxitrol.com
All Rights Reserved.