SC10C-B6S1 Signal
Conditioner
for direct or indirect fired
SC10C_MS_EN_06.2006
Replaced MS2036-07/05
gas applications
The track mounted SC10 can convert a controller's
DC output signal of either 4 to 20 milliamps or 0 to 10
volts, to a 0 to 20 volt DC signal. Toggling between
4-20 mA or 0-10 V is achieved with an on-board three
position DIP (dual in-line package) switch: 4-20 mA all positions on, 0-10 V - all positions off.
Selectra® electronic gas flame modulation is a
superior alternative to methods such as motor driven
butterfly valves. When computer or other process
controls are specified instead of standard Maxitrol
companion electronic controls, the signal conditioner
provides compatibility with Maxitrol modulator /
modulator-regulator valves.
Signal conditioners and M/MR valves can be
configured for direct or indirect fired applications. They
may be field installed on existing equipment or
specified for new equipment installation.
The SC10C-B6S1 can replace the SC10-A6S2 or
SC10-V6S2.
Wiring Diagram
DIMENSIONS: 4.75" W x 3.38" H x 2.09" D
Modulator and modulator-regulator valves are
available up to 5 psi (350 mbar) inlet pressure, 30,000
CFH (850 m
4". (For additional valve information see Bulletin
MT2035, or consult your Maxitrol sales representative)
SC10 output to valve: a milliamp/voltage input
corresponds to a voltage output.
SIGNAL CONDITIONER:
Ambient Limits...............-40o to 150oF (-40o to 66oC)
SIGNAL CONDITIONER POWER REQUIREMENTS:
24V AC transformer, 20 VA capacity (50/60 Hz).
(No grounded secondary.)
TO AVOID INTERNAL DAMAGE TO THE SC10
3
/h) maximum, and pipe sizes from 3/8" to
IMPORTANT
READ PRIOR TO INSTALLATION
SIGNAL CONDITIONER FOLLOW THESE
GUIDELINES:
Three Position DIP Switch
4-20 mA
all positions on
© 2006 Maxitrol Company, All Rights Reserved
ON
0-10 V
23
1
all positions off
1. Transformer secondary must not be grounded in any
portion of the circuit external to the SC10 signal conditioner.
If existing transformer is grounded, a separate isolated
transformer must be used.
2. Multiple SC10 signal conditioners controlled by a
signal source with common outputs (terminals 5 & 6)
require separate transformers for each SC10 signal
conditioner (0-10 V input only).
3. Multiple SC10 signal conditioners powered by a
single transformer require isolated signal inputs (terminals
5 & 6) to each SC10 signal conditioner.