Maxitrol MP2+ Installation Manual

Multiple Program Process Temperature Controller
Installation Guide
www.maxitrol.com
© 2006 Maxitrol Company, All Rights Reserved

Please read these instructions fully prior to attempting to in­stall, operate, and/or maintain the MP2+ system. Failure to do so may result in improper operation and/or component dam­age.
Installation shall conform with local codes, or in the absence of local codes, in accordance with the National Fuel Gas Code ANSI Z223.1/NFPA54 or CSA B149.1 as is applicable, and op­erated in accordance with the manufacturer’s instructions. These instructions do not supersede OEM’s installation or op­erating instructions. Installation, inspection, and replacement must be performed by a qualified installer or gas supplier.
This control must be electrically wired in accordance with lo­cal codes, or in the absence of local codes, with the Nation­al Electrical code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1 as applicable.
Warnings
2
Inappropriate and/or improper installation, adjustment, al­teration, service or maintenance can cause property dam­age, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
Disconnect power before installation to prevent electrical shock or equipment damage.
FOR YOUR SAFETY If you smell gas: 1 Open windows.
Do not touch electrical switches. Extinguish any open flame. Immediately call your gas supplier.
FOR YOUR SAFETY The use and storage of gasoline or other flammable va­pors and liquids in open containers in the vicinity of this control or other appliance is hazardous.
2 3 4
© 2006 Maxitrol Company, All Rights Reserved
Warnings ............................................................................................................. 2
General Statement ...............................................................................................3
Contents ..............................................................................................................3
Technical Data .................................................................................................... 4
Components ........................................................................................................4
Dimensions .........................................................................................................5
Wiring Diagrams ................................................................................................. 6
Installation ...........................................................................................................8
MP2+ Process Control System ............................................................... 8
MP2+ Process Control System w/
TM02 Multifunctional Timer Control .....................................................9
Glossary ............................................................................................................10
Contents
3
The MP2+ system is intended for multiple low temperature process ap­plications, for example paint spray booths or other curing processes. It is ideal for multiple temperature critical and time sensitive process applica­tions requiring temperatures from 60°F to 240°F.
General Statement
Please refer to the MP2+ User’s / Programming
Guide for programming instructions.
© 2006 Maxitrol Company, All Rights Reserved
NOTE: The technical data listed in this manual does not include normal op­erating deviations that occur in the actual manufacturing process. The listed specifications may not meet the individual unit’s actual specifications. Slight deviations in an individual unit’s performance may be encountered due to possible changes in the controlled con­ditions in which the unit is tested and calibrated. Check ratings given in OEM instructions to assure the MP2+ is suitable for the application.
Technical Data
NOTE: Please read safety warning instructions fully for Maxitrol Modulator Valves [MI2040] prior to attempting to install, operate, and/or main­tain the MP2+ system.
Components
AM02+ Amplifier TDM02 Remote Selector Display Interface TM02 Auxiliary Multifunctional Timer Control (optional)
Standard 6 Position 4 Conductor Telephone Cable, 3 feet Ethernet Patch Cord, 3 feet
    
Power Requirements
TDM02
AM02+
TM02
Ambient Temperature Limits
Connections
Valves
Sensor
Independent 24 VAC, 40 VA capacity transformer
Operating: -40°F(-40°C) to 158°F(70°C) Non-operating: -40°F(-40°C) to 185°F(85°C)
Operating, Non-operating: -40°F(-40°C) to 185°F(85°C)
AM02+ to TDM02 = Standard 6 Position 4 Conductor Telephone Cable AM02+ to TM02 = Ethernet Patch Cord
1,000 ohm RTD TS194Q use with mixing tube
M411, M511, M611, MR212
4
© 2006 Maxitrol Company, All Rights Reserved