
www.maxitrol.com
A1093 AMPLIFIER
TD92 TEMPERATURE DIAL
TS194Q SENSOR WITH MIXING TUBE
MODULATINING GAS VALVE
s
e
iS
r
e
11/04 MS2099
3
MODULATION
FOR USE WITH 2-STAGE BURNER SYSTEMS

asily turn a 2-stage indirect fired furnace into
a modulating furnace with Maxitrol’s
Series 3 electronic gas modulation system.
E
mance, a comfortable work environment, and precise control of discharge air temperature are just a few of the
advantages the Series 3 system has over a conventional
system.
Maxitrol Company originally designed the Series 3 system
for use with duct furnaces - additional applications include indirect makeup air heaters and commercial furnaces.
Heaters using atmospheric indirect fired gas burners are
typically used in both large and small industrial and commercial buildings. Any of these heaters with a 2-stage gas
valve and a 2-speed combustion blower is a candidate for
a Series 3 upgrade.
You’ll be glad you did. Improved perfor-
Such furnaces typically have a turn down that is 50% of
the high fire input. Converting to Maxitrol’s Series 3 system can reduce the turn down to 25%, or lower, of the
high fire input. By controlling the switch point of a relay
connected to the gas valve and inducer we are able to create
two separate modulation ranges.
A higher turn down allows you to accurately control the
discharge air temperature and significantly reduces the cycling of the heater, resulting in a consistent room temperature. This is especially true when you’re using multiple units with a large duct system (see example).
We also eliminate problems associated with lighting the
burner at the lowest gas input by providing an adjustable
timer and adjustable VDC output to the modulating valve
on start-up.
Many of the benefits of upgrading to the Series 3 modulation system are a direct result of the system’s ability to
obtain a higher turn down on atmospheric indirect-fired
applications.
SYSTEM REQUIREMENTS
Two-stage gas combination control. Low stage (flow) set approx. 50% of High stage (flow).
Two-speed combustion blower (inducer).
PRODUCT SPECIFICATIONS
Power Requirements
Ambient Limits
A1093 Dimensions
TD92 Dimensions
Valves
Sensor
Discharge Air Temperature Range
Combustion Blower and
Gas Valve Relay
The Series 3 system is used with Maxitrol’s industry leading Selectra modulator and modulator-regulator (M/MR)
valves. These unique electronic valves provide quick reaction times & offer continuous burner pressure adjustment.
24 VAC, 50/60 Hz Class II transformer
-40°F (-40°C) to 158°F (70°C)
7.5” x 3.4” x 1.9”
4.0” x 4.0” x 2.8”
M420, M520, M620 Series (one required)
TS194Q with mixing tube
TD92-0509: 50°F (10°C) to 90°F (32.2°C)
(Other temperature control ranges configured upon request.)
Normally Open 20 AMP maximum at 25°C
es
i
r
3
Se
Burner Light Off Adjustment
TYPICAL MANIFOLD PRESSURES
Position
High stage 2
Low stage 2
High stage 1
Low stage 1
Adjustable timer (0-30 sec) & adjustable VDC (5-15 VDC)
output to the modulating gas valve on startup.*
* Starts when power is supplied to amplifier.
Inlet
Pressure
(in. w.c.)
7”
7”
7”
7”
Outlet
Combination
Control
(in. w.c.)
3.6”
3.6”
1.0”
1.0”
Outlet
Modulator
(in. w.c.)
3.5”
0.7”
1.0”
0.2”
% of
Max
Input
100
45
55
25
www.maxitrol.com

T
WO
-S
TAGE
M
ODULATING INDIRECT
Combination Control 2-Stage
(High Fire, Low Fire)
F
URNACE
M420
M520
M620
EXAMPLE
TYPICAL APPLICATION REQUIRING 16:1 TURNDOWN
Multiple Units
Large single duct system
4 duct furnaces each with a rated input of 400,000 BTUH
4 units total 1.6M BTUH
One unit is modulated by Series 3 resulting in a 4:1 Turn Down - 100,000 BTUH to 400,000 BTUH
The other units are staged ON/OFF using customer supplied staging control
Total turn down: 16:1
FOR USE WITH ENERGY/BUILDING MANAGEMENT SYSTEMS
SUPPLIED WITH SERIES 3
The Series 3 discharge air temperature can be set using a current
loop output from an energy/building management system.
No modification to the A1093 is required. However, the following must be observed:
The input current range should be limited from 5.0mA to 13.0mA.
This range corresponds to a set point temperature range of 50°F to
130°F (i.e. 0.1mA/°F). (The input current range for the A1093 is
not a standard 4-20mA interface.)
TYPICALLY S UPPLIED WITH FURNACE
(See Typical Wiring Diagram)
A1093 Amplifier
TD92 Temperature Dial
TS194Q with mixing tube
Modulating Gas Valve
2-stage Combination Gas Valve
2-speed Inducer
2 SPDT Relays
1 SPST Relay
Powers A1093 with separate transformer when 24 VAC is supplied
to combination gas valve.
1 N.O. SPST Timer Relay (optional)
Gives time for inducer to reach High speed position.
24 VAC 20 VA Transformer (separate, recommended)

A1093 WITH EXTERNAL CURRENT LOOP
CURRENT LOOP INPUT
5.0 mA = 50°F
13.0 mA = 130°F
Rin = 100 ohms
(nominal)
es
i
er
S
3
Note:
Connect externally powered current loop to TB1, terminals 10 and 11 as
shown. No external connection is required to “LOOP” (TB1, terminal 9)
or (TB1, terminal 12). Connections to TB2 are not shown.
TYPICAL WIRING DIAGRAM
@ 2004, Maxitrol Company,
All Rights Reserved.
www.maxitrol.com P.O. Box 2230 Southfield, MI 48037-2230 U.S.A. tel 248.356.1400 fax 248.356.0829