Maxitrol A1093 User Manual

www.maxitrol.com
A1093 AMPLIFIER TD92 TEMPERATURE DIAL TS194Q SENSOR WITH MIXING TUBE MODULATINING GAS VALVE
s e
iS
r e
11/04 MS2099
3
MODULATION
FOR USE WITH 2-STAGE BURNER SYSTEMS
asily turn a 2-stage indirect fired furnace into a modulating furnace with Maxitrol’s Series 3 electronic gas modulation system.
E
mance, a comfortable work environment, and precise con­trol of discharge air temperature are just a few of the advantages the Series 3 system has over a conventional system.
Maxitrol Company originally designed the Series 3 system for use with duct furnaces - additional applications in­clude indirect makeup air heaters and commercial furnaces. Heaters using atmospheric indirect fired gas burners are typically used in both large and small industrial and com­mercial buildings. Any of these heaters with a 2-stage gas valve and a 2-speed combustion blower is a candidate for a Series 3 upgrade.
You’ll be glad you did. Improved perfor-
Such furnaces typically have a turn down that is 50% of the high fire input. Converting to Maxitrol’s Series 3 sys­tem can reduce the turn down to 25%, or lower, of the high fire input. By controlling the switch point of a relay connected to the gas valve and inducer we are able to create two separate modulation ranges.
A higher turn down allows you to accurately control the discharge air temperature and significantly reduces the cy­cling of the heater, resulting in a consistent room tem­perature. This is especially true when you’re using mul­tiple units with a large duct system (see example).
We also eliminate problems associated with lighting the burner at the lowest gas input by providing an adjustable timer and adjustable VDC output to the modulating valve on start-up.
Many of the benefits of upgrading to the Series 3 modu­lation system are a direct result of the system’s ability to obtain a higher turn down on atmospheric indirect-fired applications.
SYSTEM REQUIREMENTS
Two-stage gas combination control. Low stage (flow) set approx. 50% of High stage (flow).
Two-speed combustion blower (inducer).
PRODUCT SPECIFICATIONS
Power Requirements
Ambient Limits
A1093 Dimensions
TD92 Dimensions
Valves
Sensor
Discharge Air Temperature Range
Combustion Blower and
Gas Valve Relay
The Series 3 system is used with Maxitrol’s industry lead­ing Selectra modulator and modulator-regulator (M/MR) valves. These unique electronic valves provide quick reac­tion times & offer continuous burner pressure adjustment.
24 VAC, 50/60 Hz Class II transformer
-40°F (-40°C) to 158°F (70°C)
7.5” x 3.4” x 1.9”
4.0” x 4.0” x 2.8”
M420, M520, M620 Series (one required)
TS194Q with mixing tube
TD92-0509: 50°F (10°C) to 90°F (32.2°C) (Other temperature control ranges configured upon request.)
Normally Open 20 AMP maximum at 25°C
es i
r
3
Se
Burner Light Off Adjustment
TYPICAL MANIFOLD PRESSURES
Position
High stage 2 Low stage 2 High stage 1 Low stage 1
Adjustable timer (0-30 sec) & adjustable VDC (5-15 VDC) output to the modulating gas valve on startup.*
* Starts when power is supplied to amplifier.
Inlet
Pressure
(in. w.c.)
7” 7” 7” 7”
Outlet
Combination
Control
(in. w.c.)
3.6”
3.6”
1.0”
1.0”
Outlet
Modulator
(in. w.c.)
3.5”
0.7”
1.0”
0.2”
% of Max
Input
100
45 55 25
www.maxitrol.com
T
WO
-S
TAGE
M
ODULATING INDIRECT
Combination Control 2-Stage
(High Fire, Low Fire)
F
URNACE
M420 M520 M620
EXAMPLE
TYPICAL APPLICATION REQUIRING 16:1 TURNDOWN
Multiple Units
Large single duct system
4 duct furnaces each with a rated input of 400,000 BTUH
4 units total 1.6M BTUH
One unit is modulated by Series 3 resulting in a 4:1 Turn Down - 100,000 BTUH to 400,000 BTUH
The other units are staged ON/OFF using customer supplied staging control
Total turn down: 16:1
FOR USE WITH ENERGY/BUILDING MANAGEMENT SYSTEMS
SUPPLIED WITH SERIES 3
The Series 3 discharge air temperature can be set using a current loop output from an energy/building management system. No modification to the A1093 is required. However, the follow­ing must be observed:
The input current range should be limited from 5.0mA to 13.0mA. This range corresponds to a set point temperature range of 50°F to 130°F (i.e. 0.1mA/°F). (The input current range for the A1093 is not a standard 4-20mA interface.)
TYPICALLY S UPPLIED WITH FURNACE
(See Typical Wiring Diagram)
A1093 AmplifierTD92 Temperature DialTS194Q with mixing tubeModulating Gas Valve
2-stage Combination Gas Valve2-speed Inducer2 SPDT Relays1 SPST Relay
Powers A1093 with separate transformer when 24 VAC is supplied to combination gas valve.
1 N.O. SPST Timer Relay (optional)
Gives time for inducer to reach High speed position.
24 VAC 20 VA Transformer (separate, recommended)
A1093 WITH EXTERNAL CURRENT LOOP
CURRENT LOOP INPUT
5.0 mA = 50°F
13.0 mA = 130°F Rin = 100 ohms (nominal)
es i
er S
3
Note: Connect externally powered current loop to TB1, terminals 10 and 11 as shown. No external connection is required to “LOOP” (TB1, terminal 9) or (TB1, terminal 12). Connections to TB2 are not shown.
TYPICAL WIRING DIAGRAM
@ 2004, Maxitrol Company, All Rights Reserved.
www.maxitrol.com P.O. Box 2230 Southfield, MI 48037-2230 U.S.A. tel 248.356.1400 fax 248.356.0829
Loading...