Line Pressure Regulators and Over-Pressure Protection Devices
For piping systems up to 5 psi
SYSTEM COMPONENTS
Maximum Inlet Pressure:
CSA Certied ............................................. 5 psi (345 mbar)
Emergency Exposure Limits:
(inlet side only) ............................................. 65 psi (4.5 bar)
Outlet Pressure Range:
Certied spring .......................................... 7 - 11 inches w.c.
Maximum Individual Load:
Largest single appliance served (regulator with OPD)
325-3L47 (3/8”, 1/2”) (w/OPD 47 attached) ... 125,000 Btu/hr
325-3L48 (1/2”) (w/OPD 48 attached) ............ 200,000 Btu/hr
325-5AL48 (1/2”) (w/OPD 48 attached) ......... 235,000 Btu/hr
325-5AL48 (3/4”) (w/OPD 48 attached) ......... 320,000 Btu/hr
325-5AL600 (3/4”) (w/OPD 600 attached) ...... 425,000 Btu/hr
325-5AL600 (1”) (w/OPD 600 attached) ......... 465,000 Btu/hr
CSA Design Certied Z21.80 / CAN 6.22
Attention: Line pressure regulators with separate
overpressure protection devices shall be factory
preassembled, and supplied to the eld as a unit.
Capacity:
Total load of all appliances combined (regulator with OPD)
325-3L47 (3/8”, 1/2”) (w/OPD 47 attached) ....125,000 Btu/hr
325-3L48 (1/2”) (w/OPD 48 attached) ........... 200,000 Btu/hr
325-5AL48 (1/2”) (w/OPD 48 attached) ......... 235,000 Btu/hr
325-5AL48 (3/4”) (w/OPD 48 attached) ......... 320,000 Btu/hr
325-5AL600 (3/4”) (w/OPD 600 attached) ...... 425,000 Btu/hr
325-5AL600 (1”) (w/OPD 600 attached) ......... 465,000 Btu/hr
Venting:
OPD 47 ................... integral vent limiting orice w/dust cap
OPD 48 (optional 12A09 vent limiter) .................... 1/8” NPT
OPD 600 (optional 12A09 vent limiter) .................... 1/8” NPT
Gases: Intended for application in natural gas piping
systems up to 5 psi.
Ambient Temperature Limits: -40° to 205°F (0° to 96°C)
Note: All Maxitrol gas appliance regulators must be installed
and operated in accordance with Maxitrol’s ‘Safety Warning’
bulletin.
The 325 Series is suitable for
limited horizontal mounting
(less than or equal to 90°
from upright). But when using
the vent limiting device, the
regulator must be mounted in
a horizontal upright position.
Upright
Install the regulator properly
with gas owing as indicated
by the arrow on the casting (also see the Safety
Warning Instructions bulletin).
NOTE: Vent limiters are designed for use indoors
and in spaces where limiting the amount of gas
escapement due to diaphragm failure is critical. Vent
limiters should not be used outdoors if they are
exposed to the environment. 13A15 vent protector
is available for outdoor use when vent protection is
required.
© 2008 Maxitrol Company, All Rights Reserved
1
FEATURES
• CSA certied for up to 5-psi inlet pressure
• Over-pressure protection device (OPD) to limit
downstream pressure in case of regulator failure
• Maxitrol OPD approved and tested with the
regulator
• Self-aligning valve with lever action for dead end
regulator lockup
• Optional vent limiter eliminates the need to run
vent piping to an outside area
BENEFITS
• Meets ANSI standard Z21.80 for line pressure
regulators — for use on piping systems such as
CSST or semi-rigid copper tubing up to 5-psi
• OPD provides required downstream over pressure protection for supply pressures in
excess of 2-psi
• Pounds to inches regulator provides precise
control from pilot ows to full regulator capacity
• Meets many utility specications
THE NEW LINE PRESSURE REGULATOR
STANDARD - ANSI Z21.80
Although Maxitrol’s 325 Series are certied (ANSI Z21.18)
as appliance regulators (see bulletin 325LVR_MS_EN),
in the past they have often been used as line pressure
regulators. Until very recently, there was no standard for
line pressure regulators.
Z21.80 is the new ANSI standard for line pressure regulators,
intended for application in natural gas piping systems. As of
May 1, 2002, CSA requires that all line pressure regulators
above 2-psi must leave the factory pre-assembled and leak
tested. At supply pressures in excess of 2-psi, the new line
regulator standard requires a means (an over-pressure
protection device / OPD) — approved and tested with
the regulator — to limit the downstream pressure to 2-psi
maximum, in the event of regulator failure. Line pressure
regulators with separate overpressure protection
devices shall be factory preassembled, and supplied to
the eld as a unit. Maxitrol-built OPDs provide the required
downstream over-pressure protection.
As optional accessories, the regulators and OPDs offer an
automatic vent limiting device. The 12A09 or 12A39 vent
limiters eliminate the need to run vent piping to an outside
area - in the event of a diaphragm rupture, gas escapement
is limited to within the ANSI standards level. The 325 Series
are suitable for limited horizontal mounting (less than or
equal to 90° from upright) - but when using a vent limiting
device, the regulator must be mounted in a horizontal upright
position for best performance. Install the regulator properly
with gas owing as indicated by the arrow on the casting.
To deliver positive dead-end lock up, the 325 Series feature
a high leverage valve linkage assembly. Lockup pressure
can vary with the speed of the solenoid valve and its
location. The regulators are capable of precise regulating
control from full ow down to pilot ows.
The self-aligning valve is made of nitrile rubber. Housings
are durable aluminum die castings and all internal parts
are carefully selected and corrosion resistant. The
diaphragms are of high quality supported synthetic rubber
compounds.
The regulator with OPD is certied for inlet pressures up to
5-psi, and can withstand emergency exposure inlet pressure
up to 65-psi. The regulator alone provides no downstream
over-pressure protection in the event of failure.
Other 325 Series regulators will continue to be available
as CSA certied appliance regulators, as well as noncertied models for up to 10-psi inlet pressure (see bulletin
325LVR_MS_EN).
NOTE: Immediately after installation and prior to
operating any appliance: It is important to check the
preassembled pipe connection between the regulator
and OPD for leakage. Even though the Maxitrol 5 psi line
regulator with OPD is shipped as an assembly, installation
of the assembly can result in turning (tightening or
loosening) of the preassembled connection. If gas leakage
is detected, follow the same procedures to stop the leak as
you would use with any eld pipe connection, and repeat
step number 5 according to the ‘Safety Warning’ bulletin.
© 2008 Maxitrol Company, All Rights Reserved
2