Maxitrol 12A09 User Manual

325 Series Line Pressure Regulators with Over-Pressure Protection Devices
For Piping Systems up to 5 PSI
TABLE OF CONTENTS
Description .................................................................................. 1
Specications ........................................................................... 1, 2
Capacities ................................................................................... 2
Pressure Drop ............................................................................ 3
Spring Range Selection .............................................................. 3
Dimensions ................................................................................. 4
Sizing Instructions ...................................................................... 4
DESCRIPTION
325-3L47
325-3L48
325 Series pounds to inches regulators are for use on residential, commercial, and industrial applications.
The 325 Series with OPDs features a high leverage valve linkage assembly to deliver positive dead-end lock-up. The regulators are capable of precise regulating control from full ow down to pilot ow.
B Models: Imblue Technology™ increases corrosion resistance and provides extra protection against the elements for regulators used in outdoor applications.
NOTE: (B) in model number designates Imblue Technology™.
NOTICE
To comply with the ANSI standard Z21.80/CSA 6.22 for Line Pressure Regulators, installations exceeding 2 psi nominal require a tested and approved overpressure protection device (OPD) for use with the regulator.
Line pressure regulators with separate overpressure protection devices shall be factory preassembled and supplied to the eld as a unit.
Immediately after installation and prior to operating any appliance it is important to check the preassembled pipe connection between the regulator and the OPD for leakage. Even though the Maxitrol 5 psi line regulator w/OPD is shipped as an assembly, installation of the assembly can result in turning (tightening or loosening) of the preassembled connection. If gas leakage is detected, follow the same procedures to stop the leak as you would use with any eld pipe connection, and repeat step 3 according to Maxitrol Safety Warning Instructions, LPROPD_MI_EN.FR.
SPECIFICATIONS
Gases
Suitable for natural, manufactured, mixed gases, liqueed petroleum gases, and LP gas-air mixtures.
Approvals
CSA: ANSI Z21.80/CAN 6.22
Minimum Inlet Pressure
CSA Certied...............................................................1 psi (7 kPa)
325-5AL48
325-7AL210D
Figure 1: 325 Series Line Pressure Regulators with OPDs
325-5AL600
Maximum Inlet Pressure
Model CSA Certied
325-3(B)L47 325-3(B)L48 325-5A(B)L48 325-5A(B)L600
Natural/LP
5 psi (34.5 kPa)
325-7A(B)L210D
Model CSA Certied
325-3(B)L47 325-3(B)L48 325-5A(B)L48 325-5A(B)L600
NAT: 5 psi (34.5 kPa)
LP: 2 psi (13.8 kPa)
325-7A(B)L210D
Outlet Pressure Range
Certied Spring ............................................................ 7 - 11” w.c.
Emergency Exposure Limits
All Models (Inlet Side Only) ................................ 65 psi (450 kPa)
Maximum Individual Load/Capacity
325-3(B)L47 (3/8”, 1/2”) (w/OPD 47 attached).....125,000 Btu/hr
325-3(B)L48 (1/2”) (w/OPD 48 attached)............. 200,000 Btu/hr
325-5A(B)L48 (1/2”) (w/OPD 48 attached).............235,000 Btu/hr
325-5A(B)L48 (3/4”) (w/OPD 48 attached).............320,000 Btu/hr
325-5A(B)L600 (3/4”) (w/OPD 600 attached)........425,000 Btu/hr
325-5A(B)L600 (1”) (w/OPD 48 attached).............465,000 Btu/hr
325-7A(B)L210D (1 1/2”, 1 1/4”) (w/OPD 210D attached) ...........
.............................................................................1,250,000 Btu/hr
Ambient Temperature Limits
All Models ..................................... -40ºF to 205ºF (-40ºC to 96ºC)
© 2011 Maxitrol Company, All Rights Reserved.
1
325 Series Line Pressure Regulators with OPDs
Mounting Position
The 325 Series is suitable for multi-poise mounting, but when used with a vent limiting device, the regulator must be mounted in a horizontal upright position (see Figure 2). Install the regulator properly with gas owing as indicated by the arrow on the casting. (See Maxitrol Safety Warning Instructions, LPROPD_ MI_EN.FR.)
®
Vent Limiting Devices
12A09 (1/8” NPT)
®
Vent Protectors
12A39 (3/8” NPT)
UPRIGHT
Figure 2: 325 Regulator in Upright Postion
12A49 (1/2” NPT)
®
Vent Limiting Devices for Indoor Applications:
325-3(B)L......................................................................12A09
325-5A(B)L..................................................................12A39
325-7A(B)L..................................................................12A49
OPD 48................................................................................12A09
OPD 600..............................................................................12A09
OPD 210D...........................................................................12A39
NOTICE
Maxitrol vent limiting devices eliminate the need to run vent piping to the outside. Vent limiting devices are designed for use indoors and in spaces where limiting the amount of gas escapement due to diaphragm failure is critical. Vent limiting
devices should not be used outdoors if they are exposed to the environment. Vent protectors are available for all
outdoor applications to ensure proper vent protection.
®
Vent Protectors for Outdoor Applications:
325-3(B)L......................................................................13A15
325-5A(B)L......................................................................13A15-5
325-7A(B)L.........................................................................13A25
OPD 48................................................................................13A15
OPD 600..............................................................................13A15
OPD 210D........................................................................13A15-5
13A15 (1/8” NPT)
Figure 3: Vent Accessories
13A25 (1/2” NPT)13A15-5 (3/8” NPT)
CAPACITIES - 0.64 sp gr gas expressed in CFH (m
Model Number
(pipe size)
325-3(B)L47 (3/8”, 1/2”)
325-3(B)L48 (1/2”)
325-5A(B)L48 (1/2”)
325-5A(B)L48 (3/4”)
325-5A(B)L600 (3/4”)
Outlet Pressure
Set Point
8.0” w.c. 110 110 110
11.0” w.c. 103 113 113
8.0” w.c. 184 184 184
11.0” w.c. 181 181 181
8.0” w.c. 229 229 229
11.0” w.c 213 220 220
8.0” w.c. 263 263 263
11.0” w.c. 237 254 254
8.0” w.c. 396 396 396
11.0” w.c. 326 355 355
3
/h)
Operating Inlet Pressure
3 psi (6.9 kPa) 4 psi (10.3 kPa) 5 psi (13.8 kPa)
325-5A(B)L600 (1”)
325-7A(B)L210D
(1 1/2”, 1 1/4”)
© 2011 Maxitrol Company, All Rights Reserved.
8.0” w.c. 413 441 441
11.0” w.c. 355 377 407
8.0” w.c. 1123 1123 1189
11.0” w.c. 1081 1107 1107
2
325 Series Line Pressure Regulators with OPDs
PRESSURE DROP - 0.64 sp gr gas expressed in CFH (m
Model Number
7.0” w.c. (1.7 kPa) 1/2 psi (3.4 kPa) 3/4 psi (5.2 kPa) 1 psi (6.9 kPa)
3
/h) (for system pressure drop calculations)
Pressure Drop
325-3(B)L47 (3/8”) 140 198 246 283
325-3(B)L48 (1/2”) 145 204 250 289
325-5A(B)L48 (1/2”) 304 441 552 632
325-5A(B)L48 (3/4”) 315 448 568 652
325-5A(B)L600 (3/4”) 347 488 620 732
325-5A(B)L600 (1”) 362 513 644 750
325-7A(B)L210D (1 1/4”, 1 1/2”) 804 1096 1362 1624
NOTE: All Maxitrol line pressure regulators with OPDs must be installed and operated in accordance with Maxitrol’s Safety Warning
Instructions.
3
Flow Rate (m
100
@ 0.64 SG gas)
403020103 06865421
80
100 200
20
10
Pressure Drop (in. w.c.)
1
Figure 4: Pressure Drop Chart
Flow Rate (cfh @ 0.64 SG gas)
10 9 8
7
6
5
4
3
2
Pressure Drop (kPa)
1
.9 .8
00001000100101
SPRING RANGE SELECTION
Outlet Pressure Range (all models):
Certied Spring .................................................. 7 - 11” w.c.
© 2011 Maxitrol Company, All Rights Reserved.
3
325 Series Line Pressure Regulators with OPDs
DIMENSIONS - Expressed in inches (mm)
Model Number Pipe Size* Swing Radius
A B C
Dimensions
325-3(B)L47 3/8”, 1/2” 3 (76) 3 1/2 (90) 8 (203) 4 (100)
325-3(B)L48 1/2” 3 (76) 3 1/2 (90) 8 1/2 (216) 4 (100)
325-5A(B)L48 1/2”, 3/4” 4 13/32 (112) 5 1/3 (135) 10 (254) 5 1/2 (140)
325-5A(B)L600 3/4”, 1” 4 13/32 (112) 5 1/2 (140) 11 (279) 5 1/2 (140)
325-7A(B)L210D 1 1/4”, 1 1/2” 6 3/4 (171) 7 (178) 15 3/8 (391) 9 (229)
* Standard models NPT threads
NOTE: Dimensions are to be used only as an aid in designing clearance for the regulator. Actual production dimensions may vary
somewhat from those shown.
C
A
A
B
325-3(B)L47
C
C
A
B
325-3(B)L48
C
C
B
325-5A(B)L47
A
B
325-5A(B)L600
SIZING INSTRUCTIONS
TO SELECT A REGULATOR WITH OPD OF SUFFICIENT FLOW
- ONE MUST KNOW:
1. Available inlet pressure (maximum static/minimum operating).
2. Desired outlet pressure.
3. Required maximum capacity (total load, all appliances combined) and maximum individual load.
4. Pipe size.
Example: To select a 325 series line regulator with OPD of sufcient capacity to handle ow...
KNOWN:
A. Required: 1/2” NPT line regulator with OPD, outlet pressure of
7” w.c., with static pressure of 5 psi, and a minimum operating inlet pressure of 1 psi, Natural Gas.
A
B
325-7A(B)210D
B. Combined BTU rating of all appliances to be served by the
regulator: 145,000 Btu/hr.
C. Largest single appliance’s BTU rating: 90,000 Btu/hr
SOLUTION:
A. In the Capacities Table (page 2), locate 325-3L47 (1/2”) = 125
CFH, 325-3L48 (1/2”) = 200 CFH, 325-5AL48 (1/2”) = 235 CFH.
B. The total BTU load requirement cannot exceed the equivalent
CFH result from step A. The combined 145,000 Btu/hr requirement exceeds the 325-3L47 (1/2”) capacity, but is less than that of the 325-3L48 (1/2”), and 325-5AL48 (1/2”).
C. The 90,000 Btu/hr single largest appliance rating is below the
325-3L48 maximum individual load capacity of 200,000 Btu/hr.
D. The 325-3L48 is the correct (1/2”) line regulator with OPD for
this application.
Maxitrol Company 23555 Telegraph Rd., P.O. Box 2230 Southeld, MI 48037-2230 U.S.A.
LPROPD_MS_EN_09.2011
www.maxitrol.com
4
© 2011 Maxitrol Company,
All Rights Reserved.
Loading...