Master Bilt BSD User Manual

BSD SERIES
REFRIGERATORS AND FREEZERS
Installation, Operation and
Maintenance Instructions
INSPECTION
When the equipment is received, all items should be carefully checked against the bill of lading to insure all crates and cartons have been received. All units should be inspected for concealed damage by uncrating the units immediately. If any damage is found, it should be reported to the carrier at once, and a claim should be filed with the carrier. This equipment has been inspected and tested at the manufacturing facility and has been crated in accordance with transportation rules and guidelines. Manufacturer is not responsible for freight lo ss or damage.
INSTALLATION
GENERAL
If casters are installed, care should be taken when removing the unit from the crate base. The unit is heavy and can present a hazard if not handled with care. Remove the unit crate and crate base. Discard hardware used to secure the cabinet to the crate base. Ensure that at least two persons are available to install the casters. Lay the cabinet on its back to create access to the cabinet bottom. Attach the casters to the cabinet base suing the factory installed screws as shown below. Remove the ¼ x 20 x ¾ screws (4 per caster) that are factory installed. Position the caster and reinstall. Ensure that the locking casters are installed on the front of the cabinet. After installation is complete, return the cabinet to its upright position. The cabinet should set in the upright position for at least one hour prior to energizing. This is required to allow the refrigeration to settle to its normal state. The cabinet should also be levelled when it is placed in its permanent location.
1 4/07
If the doors are out of alignment on the cabinet, the doors can be adjusted. This can be accomplished by opening the door(s) and loosening the screws that hold both the top and bottom hinges to the cabinet. After adjusting the door so that it is aligned correctly, tighten the screws to securely hold the hinges in place.
ELECTRICAL
Check the proposed outlet to be used to insure that the voltage, phase and current carrying capacity of the circuit from the electrical panel correspond to the requirements of the cabinet. NEVER use an extension cord to wire any unit. On permanently connected units, those not furnished with a plug-in service cord, all inter-wiring between the electrical panel and the unit must be done in accordance with the National Electric Code and all state and local codes. Refer to the serial tag for all pertinent electrical information.
Observe all Warning Labels. Disconnect power supply to eliminate injury from electrical shock or moving parts when servicing equipment.
GENERAL OPERATION
The refrigerators and freezers employ a unit cooler evaporator located outside the cabinet as the heat removing source. Through the refrigeration process, heat is captured in the evaporator, transferred to the condensing unit on top of the cabinet, and expelled to the surrounding outside air. It is extremely important to allow a four (4) inch clearance on the top, rear, and sides of the unit for the refrigeration process to function properly.
These refrigerators and freezers utilize a programmable controller to control the temperature and defrost settings. The controller, which is located on the facade of the unit, is factory set. Please see the default settings sheet and separate instructions that are included on the operation of this controller.
REFRIGERATORS
During the operation of a refrigerator unit, frost will periodically form on the coil surface. Each time the compressor cycles "off", the evaporator fans will continue to run, which will keep the internal temperature uniform and at the same time remove any frost build up on the coil. The water produced will collect in the unit cooler drain pan and travel down the drain tube to the condensate vaporizer.
FREEZERS
After shutting the door on freezer models, a short amount of time must be allowed before the door can be reopened. This is due to the tight seal maintained between the door and the cabinet. Waiting a few moments for the pressure to equalize permits the door to be opened easily.
A positive defrost is required to remove frost from the coil in freezer models. This is accomplished by energizing heaters during the defrost cycle that are positioned on the coil surface. The programmable controller is factory set to allow four defrosts per day.
2 4/07
As the preset defrost time is reached, the controller automatically terminates the refrigeration process by turning off the condensing unit and unit cooler fan motors, and energizes the defrost heaters. As the coil temperature increases, the frost begins to melt producing water which runs down the coil to the unit cooler drain pan and exits through the drain tube to the vaporizer. After all the frost has been removed and the coil temperature reaches approximately 50°F [10ºC], the defrost is terminated through the action of the defrost termination control located on the unit cooler, and the refrigeration process resumes. In order to insure that any excess water remaining on the coil is not sprayed into the cabinet interior, and all heat generated by the defrost is removed, the unit cooler fans
will not operate until the coil temperature reaches approximately 25°F [-4ºC].
GENERAL MAINTENANCE
PERIODIC CLEANING
Beginning with the initial installation, the interior surfaces of the cabinet should be periodically wiped down with a solution of warm water and baking soda. This solution will remove any odors from spillage that has occurred. The exterior of the cabinet should also be cleaned frequently with a commercial grade of glass cleaner.
Monthly cleaning of the condenser will aid the heat transfer characteristics of the refrigeration system and increase its efficiency. To accomplish this, remove the cover panel from the cabinet and use a wire brush to loosen any dirt particles that are attached to the fins. Use a vacuum cleaner to remove the loosened particles. Failure to keep the
condenser coil clean and clear of obstructions could result in temperature loss and damage to the compressor.
All moving parts have been permanently lubricated and will generally require no maintenance.
3 4/07
MAINTENANCE SERVICE AND ANALYSIS GU IDE
REFRIGERATION SYSTEMS - ALL MODELS
MALFUNCTION
POSSIBLE CAUSE SOLUTION
Compressor will not start - 1. Service cord unplugged 1. Plug in service cord no hum 2. Fuse blown or removed 2. Replace fuse
3. Overload tripped 3. Determine reasons and correct
4. Control stuck open 4. Repair or replace
5. Wiring incorrect 5. Check wiring against the diagram Compressor will not start - 1. Improperly wired 1. Check wiring against the diagram
hums but trips on overload 2. Low voltage to unit 2. Determine reason and correct protector 3. Starting capacitor defective 3. Determine reason and replace
4. Relay failing to close 4. Determine reason, correct or replace Compressor starts and runs, 1. Low voltage to unit 1. Determine reason and correct
but short cycles on overload 2. Overload defective 2. Check current, replace overload protector
protector 3. Excessive head pressure 3. Check ventilation or restriction in refrigeration system
4. Compressor hot-return gas hot 4. Check refrigerant charge, fix leak if necessary Compressor operates long 1. Short of refrigerant 1. Fix leak, add charge
or continuously 2. Control contact stuck 2. Repair or replace
3. Evaporator coil iced 3. Determine cause, defrost manually
4. Restriction in refrigeration system 4. Determine location and remove restriction
5. Dirty condenser 5. Clean condenser Compressor runs fine, but 1. Overload protector 1. Check wiring diagram
short cycles 2. Cold control 2. Differential too close - widen
3. Overcharge 3. Reduce charge
4. Air in system 4. Purge and recharge
5. Undercharge 5. Fix leak, add refrigerant Starting capacitor open, 1. Relay contacts stuck 1. Clean contacts or replace relay
shorted or blown 2. Low voltage to unit 2. Determine reason and correct
3. Improper relay 3. Replace Relay defective or burned out 1. Incorrect relay 1. Check and replace
2. Voltage too high or too low 2. Determine reason and correct Refrigerated space too warm 1. Control setting too high 1. Reset control
2. Refrigerant overcharge 2. Purge refrigerant
3. Dirty condenser 3. Clean condenser
4. Evaporator coil iced 4. Determine reason and defrost
5. Not operating 5. Determine reason, replace if necessary Standard temperature system 1. Control setting is too low 1. Reset the control
freezes the product 2. Control points stuck 2. Replace the control Objectionable noise 1. Fan blade hitting fan shroud 1. Reform or cut away small section of shroud
2. Tubing rattle 2. Locate and reform
3. Vibrating fan blade 3. Replace fan blade
4. Condenser fan motor rattles 4. Check motor bracket mounting, tighten
5. General vibration 5. Compressor suspension bolts not loosened on applicable models - loosen them
6. Worn fan motor bearings 6. Replace fan motor Pan Area 1. No cooling 1. Make sure switch is in the "on" position
2. Too cold 2. Adjust temperature control - see instructions under pan area
3. Too warm 3. Adjust temperature control - see instructions under pan area
4 4/07
INSTRUCTIONS FOR REVERSING
THE SWING OF SOLID DOORS
Complete the following steps if re versing the swing of the solid door(s) is desired. These st eps apply to both refrigerators and freezers.
1. With a one, two, or three door model, firs t open the door and locate the sc rews holding the hinges and door in position.
2. Two people are recomm ended to make this change. One per son should hold the door at a 90° angle to the cabinet while the other pers on removes the screws holding the door to the cabinet. T he normal installation at the factory is to have the spring loaded door-closing mechanism located at the bottom of the cabinet.
When removing the sprin g tension bracket from the cabinet bott om, be careful that it does not snap back. This may result in pinched fingers.
3. After the door(s) ar e removed, remove the door lock strike(s) f r om the cabinet by removing the two mounting screws.
4. Find the holes, drilled through the outer skin only, located on the opposite side of the door opening from where the hinges were previously located. Drill through the tapping plate found behind these holes using a 7/32" drill bit.
5. Turn the door over and align it to the c abinet s o it will swing in the desired dir ec tion. The spring loaded door­closing hinge will now be located at the top of the reversed door. Mount the hinges to the cabinet us ing the holes that were drilled out in step 4, along with the previously removed screws. Check the door(s) to be certain that it is mounted squarely and that the gaskets s eal properly around the door opening. The door can be adjusted by moving the top or bottom hinge slightly.
6. The original hinge holes can be filled with silicone, or with 1/4-20x3/4 pan head stainless steel screws if desired.
7. Locate the door lock str ike by visually aligning it to the dead bolt lock in the door while the door is in the closed position. W hile holding the strike in pos ition, mark the top, bottom, and edge of the strike on the cabinet wall or m ullion with a pencil or fine point m arker that will rem ain legible until completion of the tas k. Verify that the strike is positioned properly by assuring that it is aligned to the marks and hold it securely; open and close the door and extend and retract the dead bolt to m ake certain they clear without touching.
The strike cannot be adjusted after it is mounted.
8. Align the strike to the mark s, which were m ade in step 7 and m ark the centers of the holes for the m ounting screws. Using a #20 drill bit, drill the holes you just m arked approximately one-half inch deep. Take care not to puncture the interior side of the ca binet. Note: If a #20 bit is not available, use a 5/32" drill bit.
9. Mount the door lock s trike using the screws that were r emoved from the original position. The sc rews may have to be forced until the thread cutting tip has passed through the entire metal thickness. The original door strike holes can be filled with silicone, or with two 10-24x1/2 stainless steel pan head screws if desired.
9/05 040625
Loading...