Market Forge 3500-D Service Manual

SERVICE & PARTS MANUAL
Models:
Pressureless Steam Cooker
3500 3550
MARKET FORGE CANADA LTD. Mississauga, Ontario, Canada
Form No. S-2196 4/79 Printed in U.S.A.
TABLE OF CONTENTS
1.2 Basic Fu
nctioning
1-1 5.2 Trouble
-
Shooting Guide
5-1
5.4 Electrical Trouble
-
Shooting
2.1 Assembly
2-1 5.4.1 Incoming Power
5-3 2.2 Setting In Place
2-1 5.4.2 Electrical Inspection
5-3
2.4 Installation Check
-
Out 2-1 5.4.4 15-MINUTE Timer
5-5
2.4.1 Initial Control Settings
2-1 5.4.5 60-MINUTE Timer
5-5
2.4.2 Cooker
Check
-
Out 2-1 5.4.6 Door I
nterlock Switch
5-5 2.4.3 Shut-Down Procedure
2-2 5.4.7 Steam Solenoid Valves
5-5
5.4.8 Indicator Lights
5-5
SECTION
3
OPERATION
5.4.9 Cooking Compartment Thermostat
3.2 Operating
Procedures
3-1 5.4.1.0
Buzzer
5-6
3.2.1 Steam Source Operation
3-1 5.4.1.1
Cold Water Condenser Circuit
5-6
3.2.2 Preheating
3-1 5.4.1.2
Wiring
5-6
3.2.3 Cooking
3-1
3.2.4 Shut-Down Procedure
3-1 SECTION
6
MAINTENANCE
3.3 Cleani
ng
3-2 6.1 General
6-1
SECTION
4
PRINCIPLES OF OPERATION
6.2.1 Door Disassembly and Cleaning
6-1
4.2 Plumbing Circuits
4-1 6.2.3 Cooking Compartment Cleaning
6-1
4.2.1 Steam Inlet Line
4-1 6.3 Repair and Replacement
6-2 4.2.2 Steam Exhaust and Drain Lines
4-1 6.3.1 Door Assembly
6-2
4.2.3 Steam Exhaust Condensing System
4-1 6.3.2 Exterior Panel Removal
6-2
4.2.4 Pressure Safety Valve
4-2 6.3.3 Steam and W
ater Solenoid Valve
4.3 Electrical Circuits
4-2
Replacement
6-2
4.3.1 Control Circuit Components
4-3 6.4 Door Adjustment
6-3
6.4.1 Latch Adjustment
6-3
7.2 Ordering Information
7-1
Paragraph Page Paragraph Page
SECTION 1 INTRODUCTION SECTION 5 TROUBLE-SHOOTING
1.1 Description 1-1 5.1 General 5-1
SECTION 2 INSTALLATION
3.1 Operating Controls and Indicators 3-1
Procedures 5-2
Switch 5-6
4.1 General 4-1 6.2.2 Door Latch Lubrication 6-1
6.4.2 Door Tension Adjustment 6-3
SECTION 7 ILLUSTRATED PARTS LIST
7.1 General 7-1
LIST OF ILLUSTRATIONS
Figure
3-2 Pan Support Removal
3-3 6-2 Control Panel Removal
6-2 6-3 Plumbing and Interior View
6-3
SECT ION
4
PRINCIPLES OF OPERATION
6-4 Latch Adjustment
6-3
4-1 Pictorial Diagram
— Steam
&
Water
Circuits
4-2 SE
CTION
7
ILLUSTRATED PARTS LIST
4-2 Pictorial Diagram
— Electrical
7-1 Cabinet Assembly
7-2
Circuits
4-3 7-2 Door Assembly
7-4 7-3 Plumbing Assembly
7-6 SECT ION
5
TROUBLE
-
SHOOTING
7-4 Control Panel
7-8
5-1 Wiring Diagram, Model
3500
5-4 5-2 Schematic Diagram, Model
3500
5-7
3-1
Controls and Indicators
3-3 5-1 General Trouble
-
Shooting Guide
5-1
SECT ION 3 OPERATION
3-1 Controls & Indicators 3-2 6-1 Inner Door Removal 6-1
Page Figure Page
SECTION 6 MAINTENANCE
LIST OF TABLES
Table Page Table SECTION 3 OPERATION SECTION 5 TROUBLE-SHOOTING
5-2 Electrical Fault Isolation Guide 5-3
Page
SECTION 1 INTRODUCTION
This service and parts manual contains general information, installation, operation, principles of operation,
trouble-shooting and maintenance information for the Market Forge 3500 and 3550 Pressureless Steam
Cookers. Also included is a parts list in which each replaceable part is identified and shown in an
accompanying exploded view.
1.1 DESCRIPTION The Model 3500 is a pressureless steam cooker
consisting of two independently controlled compartments enclosed in a single cabinet. The model 3550 includes a single compartment. Each compartment is equipped with a separate two-piece door with inner gasket plate isolated from the exterior surface. Door latches operate by cam action for positive sealing of inner door in one continuous hand motion. Steam and steam condensing circuits are electrically controlled. Operating controls are displayed on a single front -mounted panel, and include separate timers with indicator lights for selection of either 15-minute precision timed cooking or 60-minute long duration cooking.
A separate steam source required for operation of
the Pressureless Cooker is normally purchased with it, in which case the cooker is factory mounted with all steam, drain, cold water and electrical intercon­nections completed. Model 3500/Boiler and 3550/ Boiler configurations with the cookers on 24-inch wide cabinet bases containing electrically powered steam boilers (model suffix E)are on the cover. Other applications include the 3500 or 3550 Cooker on a gas-fired boiler (model suffix G), a steam coil boiler (model suffix SC), or a cabinet containing steam and drain controls for direct connection to a remotely located boiler (model suffix D). The Model 3500 may also be mounted on larger boiler cabinets or be com­bined with other cooking equipment. Model 3550 utilizes the same boiler cabinets, designated by the same suffixes as for the 3500.
1-1 S-2196
1.2 BASIC FUNCTIONING The Model 3500 may be operated with only one
compartment in use, or, both may be used simultaneously (The 3550 has only one compartment). Each compartment is equipped with identical controls allowing selection of either 15­MINUTE TIMER or 60-MINUTE TIMER operation by setting a two-position switch. The cooker becomes operational when the selector switch is set to either timer position, the timer is set at the desired cooking time, and the compartment door is closed. The timer indicator light comes on and the steam solenoid valve opens allowing steam to flow into the compartment through a slotted steam standpipe.
When steam flowing inside the compartment has raised the interior temperature to 212°F, the contacts of a thermostatic switch automatically close, completing the circuit to the timer motor and starting the cooking time period. At the end of the set interval, timer contacts switch to shut off the cooking operation and sound a signal buzzer. The buzzer is silenced by
returning the timer dial to the OFF position.
Steam emitted from the compartment along with liquid cooking drainage is directed through a drain screen inside the compartment into the cooker drain line. A cold water solenoid valve connected into the cooker drain line is automatically actuated by a thermostatic switch in the boiler drain to condense the steam to water prior to discharge into the boiler drain.
PRESSURELESS STEAM COOKER
1.3 SERVICE Required service, both preventive and corrective,
is explained in Section 6. Should repairs be required, a network of authorized agencies is available to assist with prompt service. A current Directory of Authorized Service Agencies may be obtained by contacting:
Product Service Department Market Forge 35 Garvey Street Everett, Massachusetts 02149
Product Service Department Market Forge Canada, Ltd. 1375 Aimco Blvd., Unit 5 Mississauga, Ontario,Canada L4W 1B5 Telephone: (416) 621-9252
The model and serial numbers must be referenced when corresponding with Market Forge. The data plate containing the serial number pertaining to the equipment is located on the lower front trim of the cabinet.
Telephone: (617) 387-4100
S-2196
SECTION 2 INSTALLATION
2-1
S-2196
2.1 ASSEMBLY The Pressureless Cooker is factory mounted on a
cabinet base containing either a steam boiler or direct steam connection controls for the cooker. The assembled unit is shipped bolted to a skid with cabinet feet in a separate container. Steps required for assembly are as follows:
1. Remove the four bolts which fasten the equipment frame to the skid.
2. Install feet in threaded mounting locations of the cabinet frame.
3. Mount the two pan support racks on studs located inside the cooking compartment.
4. Attach panels to lower cabinet. Detailed instructions are enclosed with the panels.
2.2 SETTING IN PLACE If possible a location should be selected under an
exhaust hood which will remove small amounts of water vapor emitted when the cooker doors are opened. Level the unit in final location by turning the adjustable feet. Using the cabinet top as a reference, obtain level adjustment left-to-right and front -to-back.
2.3 MECHANICAL CONNECTIONS
Since the Pressureless Cooker is interconnected at the factory to the steam boiler or direct steam plumbing, no field connections are required to the cooker. All electrical and plumbing connections are routed to the steam boiler cabinet through the 6-inch high space between the floor and the bottom edge of the cabinet frame. Connection locations for the cooker mounted on steam boilers of electric, gas and steam coil utility and direct connected steam are shown in separate Installation Instructions for each.
2.4 INSTALLATION CHECK-OUT
After the Cooker is completely assembled and all mechanical connections made to its steam source (steam boiler or direct steam connection plumbing), both steam source and cooker must be given a thorough check-out before being put into operation. Checkout procedures for the cooker mounted on steam boilers of electric, gas and steam coil utility or direct connected steam are given in separate
Installation Instructions for each. Procedures for the cooker only are included in subsection 2.4.2. If the cooker fails to perform as described, consult Table 5-1 of the Trouble-Shooting Guide for corrective action. If difficulty arises with the boiler, reference the separate service and parts manual for that equipment.
Before making this check-out the operator must be thoroughly familiar with the operating procedures in Section 3, and with the function of each control described in Table 3-1. Reference Figure 3-1 for identification of controls required in the following procedures.
2.4.1 Initial Control Settings
Before beginning the start-up procedures for the cooker, the instruction plate and service manual for the steam boiler must be consulted and all start-up procedures completed to supply 15 PSI steam to the steam inlet line for the cooker.
1. All steam boiler controls are in the operating mode and 15 PSI steam is applied to the cooker inlet plumbing.
2. Cooker timers for both compartments (Figure 3-1;
3, 4) are in the OFF position.
3. Cooker compartments are empty of all information materials, pan supports are mounted in place and doors are open.
2.4.2 Cooker Check-Out The cooker check-out procedures are as follows:
1. Place selector switches (Figure 3-1, 2) in 15 MINUTE TIMER (up) position.
2. Set 15-Minute Timers (3) to about the "4-minute" position. Observe that indicator lights are off and steam does not enter compartments.
3. Close cooker compartment doors being certain latch handles (1) are in the down position and latches are securely engaged. Observe that indicator lights turn on and steam can be heard rushing int o the compartment simultaneously with the door closing.
4. Observe the boiler drain line for passage of steam into the open floor drain. Correct steam condenser operation is evidenced by presence of water flowing from the drain line.
2-2 PRESSURELESS STEAM COOKER
5. Observe cooker operation for several minutes. Operation is correct if timer dials begin to rotate after a short delay period required for preheating. After the delay period plus the "4-minute" initial setting, the timer dials will return to the "0-
Pressureless Cooker except to check that all timer dials (3, 4) are in the OFF position and the compartment doors are open. Consult the steam boiler instruction plate and complete the shut-down
procedures for the boiler. minute" position at which a buzzer sounds. The buzzer is silenced by turning the dial to the OFF position.
6. Open cooking compartment doors and repeat Steps 1 through 5 for the 60 MINUTE TIMER (down) position of selector switch (1).
Before final check-off of the Cooker/Boiler system for use in cooking, boiler start-up and shut-down must be completed two more times
NOTE
to insure cleanliness and proper operation.
2.4.3 Shut-Down Procedure No shut -down procedure is required for the
S-2196
SECTION 3 OPERATION
3.1 OPERATING CONTROLS AND INDICATORS
The controls and indicators required to operate the Pressureless Steam Cooker are listed in Table 3-1, together with a short functional description of each. Figure 3-1 shows the physical location of each control and indicator.
3.2 OPERATING PROCEDURES The 3500 and 3550 are pressureless steam
cookers which defrost frozen foods and cook fresh and defrosted foods. Each cooking compartment permits selection of either short duration (0-15 minutes) timing or long duration (0-60 minutes) cooking periods. Instructions for operation are included in this section. Consult Test Kitchen Bulletin #59 for detailed cooking information.
3.2.1. Steam Source Operation The Pressureless Cooker is supplied mounted
on a cabinet containing either a steam boiler or controls for direct connected steam. Manual controls are accessed by opening the cabinet door. The start -up procedure for the steam source is completed once before each daily operating period of the cooker. (For steam boilers see instruction plate.)
3.2.2 Preheating Before each initial operation of the cooker, and
at any other time when the cooking compartment is cold, a 1-minute preheating period is required. To preheat the cooker put steam source into operation and proceed as follows:
1. Close cooking compartment door and latch securely by pushing down on latch handle (1).
2. Place selector switch (2) for compartment(s) to be used in 15-MINUTE TIMER (up) position.
3. Set 15-Minute Timer Dial (3) to "1-minute" setting.
NOTE
Total elapsed preheating time equals the timer setting plus a short delay period needed to activate a thermostatic switch included in the controls.
4. Turn off buzzer which sounds to indicate cooking is complete by setting the 15-Minute Timer Dial (3) to OFF position.
3.2.3 Cooking Before loading the cooker, be sure compartment
is hot. See 3.2.2 for preheating instructions.
1. Slide pans of food into cooking compartment pan supports.
2. Close cooking compartment door and push down on latch handle (1) to engage.
3. Place Selector Switch (2) in required position:
a. 15-MINUTE TIMER—For short duration timing.
b. 60-MINUTE TIMER— For long cooking
periods.
4. Set appropriate timer to the required cooking time (see Test Kitchen Bulletin #59).
5. Turn off buzzer which sounds to indicate cooking is complete by setting timer dial (3 or
4) to the OFF position.
6. Open door by lifting up on latch handle (1).
7. Unload by sliding pans of food from pan supports, taking care to avoid hitting compartment opening.
3.2.4 Shut-Down Procedure No shut -down procedure is required for the
cooker except to check that both timer dials (3, 4) are in the OFF position, and that both compartment doors are open. When all cooking has been completed for the day the steam source must be shut off. (For steam boilers see instruction plate.)
3-1 S-2196
3-2 PRESSURELESS STEAM COOKER
3.3 CLEANING After each period of daily operation (more
frequently as required to maintain cleanliness) the cooker should be thoroughly cleaned by completing the following steps:
1. Remove left and right side pan supports (Figure 3-2) by lifting up and off mounting studs. Wash with detergent using a brush to clean drain screen.
i-2196
Figure 3-1. Controls & Indicators
Rinse and set aside for reassembly.
2. Wash cooking compartment interior using detergent and water. Rinse and dry thoroughly.
3. Replace pan supports in compartment and Leave door open.
NOTE
Supports with drain screens must be installed on left side of each compartment.
OPERATION
The cooking interval selector switch. Placed in up
Fig. 3-1 Ref. Description Function
TABLE 3-1
CONTROLS AND INDICATORS
(See Figure 3-1)
1 Latch Handle
Selector Switch
2
15-MINUTE TIMER/60- MINUTE TIMER
3 15-Minute Timer
4 60-Minute Timer
5
6
Indicator Light (red) 15-Minute Timer
Indicator Light (red) 60-Minute Timer
Secures cooker door in closed position. Lift to open.
position for 15-minute maximum timed interval; down position for 60-minute maximum timed period.
Controls short interval precision timed cooking from 0 to 15 minutes.
Controls longer duration cooking times from 0 to 60 minutes.
Indicates when lit that cooker is in operation controlled by 15-minute timer.
Indicates when lit that cooker is in operation controlled by 60-minute timer.
7 Buzzer Signals end of cooking Period (not shown).
Figure 3-2. Pan Support Removal
SECTION 4 PRINCIPLES OF OPERATION
4.1 GENERAL
The 3500 Pressureless Steam Cooker consists of two identical cooking compartments, one above the other, in a single cabinet assembly. (Model 3550 has only one compartment.) Each compartment is fitted with independent electrically controlled steam circuits and spring loaded, self-sealing doors with cam-action latches. Compartments can be used separately (or simultaneously for model 3500) for either of two timed intervals— 15-minute maximum timing' or long duration 60-minute maximum timing. The principles of operation in this section include an explanation of steam, steam condensing and electrical circuits and their functioning for the Model 3500. Operation is identical for the single compartment 3550.
4.2 PLUMBING CIRCUITS
The plumbing circuits consist of the piping, steam solenoid valves, steam jet pipe, drain, cold water condenser, and pressure safety relief valve required to provide controlled steam application to the cooking compartments. A simplified diagram of these circuits
for model 3500 is shown in Figure 4-1. NOTE
Figure 4-1 is strictly a pictorial schematic diagram and is not intended to show the actual configuration of the plumbing. All components are shown in correct relationship with each other. However, the diagram does not show their
actual locations or position within the cooker.
As shown in the diagram, steam inlet and exhaust connections are connected at the factory directly into a steam boiler or direct connected steam plumbing enclosed within a base cabinet on which the cooker is mounted. The boiler (or direct connected steam control system) is equipped to supply constant, regulated steam at 14-15 PSI. Steam exhaust, having been reduced to water by the cold water condenser, is directed into the boiler (or direct connected steam
control) drain system.
Steam inlet lines for compartments are equipped with normally closed solenoid valves operated by the electrical control circuits. The inlet valves are opened whenever the compartment control circuit is activated by use of either the 15-minute or 60-minute timers.
4-1 S-2196
4.2.1 Ste am Inlet Line A steam supply line is plumbed from the boiler
output (or direct connected steam control), to a 1/2 inch "T" fitting connected to the input sides of both steam inlet solenoid valves. At all times when a cooking compartment is not in use the valve for the compartment remains closed to prevent steam from entering. During operation the appropriate inlet solenoid valve is opened by activation of the control circuit. Steam is projected onto the surface of pans of food loaded into the compartment by a jet pipe located inside the compartment. Steam continues to flow through the compartment in this manner until the
control circuit closes the solenoid valve.
4.2.2 Steam Exhaust and Drain Lines Steam exhaust and compartment drainage are
removed from the cooking compartments by a separate line from each, connecting with the boiler (or direct connected steam plumbing) drain system. Perforated strainers at the drain line openings inside each compartment allow only steam, condensation and liquid cooking drainage to enter. Prior to discharge into the boiler drain system, steam is converted to water by the cold water condensing systems for each compartment.
4.2.3 Steam Exhaust Condensing System The steam condensing system consists of the
identical, two-position, normally closed cold water solenoid valves (one only in the model 3550) with outlet sides connected into the exhaust plumbing for each cooking compartment. A spray nozzle directs cold water about the inside of the drain lines to increase cold water contact with exhausted steam. Valve inlet sides are connected to the cold water supply line of the steam boiler (or direct connected steam plumbing). The valves function simultaneously (even though only one compartment may be in use) and independently of other cooker controls, in response to a thermostatic switch located at the discharge opening of the boiler drain line. The switch allows the valves to open at all times when the drain temperature exceeds 193°F.
Loading...
+ 23 hidden pages