Contact Thomson Power Systems, to obtain these instruction manuals. A soft-copy of the
most current versions of these manuals are available at www.thomsonps.com.
1.2. GENERAL DESCRIPTION
The TSC 900 controller utilizes multiple 32 bit microprocessor-based design technology, which
provides high accuracy for all voltage sensing and timing functions. Digital Signal Processing
(DSP) technology is utilized for all voltage, frequency and current sensing. The TSC 900 is
factory configured to control all the operational functions and display features of the automatic
transfer switch. All features of the TSC 900 are fully programmable from the front panel color
graphical touchscreen display and are security password protected. The graphical
touchscreen display screen provides a user-friendly operator interface with many display
options available. The microprocessor design provides many integrated standard features,
which were previously only available as add-on optional features.
PM 151 REV 1 15/10/08 Thomson Power Systems
2
2. INSTALLATION
This equipment contains static-sensitive parts. Please observe the following
anti-static precautions at all times when handling this equipment. Failure to
observe these precautions may cause equipment failure and/or damage.
TSC 900 TRANSFER SWITCH CONTROLLER
CAUTION!!!
The following precautions must be observed:
Discharge body static charge before handling the equipment (maintain exposed body contact
with a properly grounded surface while handling the equipment, a grounding wrist strap
can/should also be utilized).
Do not touch any components on the printed circuit board with your hands or any other
conductive equipment.
Do not place the equipment on or near materials such as Styrofoam, plastic and vinyl. Place
the equipment on properly grounded surfaces and only use an anti-static bag for transporting
the equipment.
2.1. GENERAL INFORMATION
NOTE:
Installations should be done in accordance
The following installation guidelines are provided for general information only pertaining to
typical site installations. For specific site installation information, consult Thomson Power
Systems as required. NOTE: Factory installations of THOMSON POWER SYSTEMS
PM 151 REV 1 15/10/08 Thomson Power Systems
with all applicable electrical regulation
codes as required.
TSC 900 TRANSFER SWITCH CONTROLLER
3
supplied transfer switches that have been tested and proven may deviate from these
recommendations.
2.2. NOTES TO INSTALLER
If the transfer switch has programmable/multi-tap system voltage capability (refer to electrical
schematic), confirm the transfer switch has been configured for the system voltage.
WARNING
Failure to confirm and match transfer
switch voltage with the system voltage
could cause serious equipment damage.
If the transfer switch requires reconfiguring, the TSC 900 controller will also require
reprogramming.
CAUTION!!!
Qualified personnel must complete all installation and/or service work performed
only. Failure to do so may cause personal injury or death.
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
4
2.3. AC VOLTAGE SENSING INPUT
The TSC 900 can accept direct AC voltage sensing inputs on the generator, utility and load
from 120-600VAC (nominal). Sources up to 600VAC (phase to phase) and can connected wye
or delta with grounded or ungrounded neutral without the need for additional sensing
transformers. The TSC 900 voltage sensing can support the following types of electrical
systems:
2.4. AC CURRENT SENSING INPUT
The TSC 900 can accept 4 x 0-5Aac current inputs from the secondary windings of current
transformers (CT’s). CT’s are to be connected on the load side of the ATS (Phase A,B,C & N).
Wiring of CT primary and secondary windings must be done in strict accordance with
schematic diagram to ensure the correct phasing on 3 phase systems.
Do not unplug any current transformer inputs while
energized as severe high voltages can develop which may
PM 151 REV 1 15/10/08 Thomson Power Systems
WARNING
cause personal injury or death.
TSC 900 TRANSFER SWITCH CONTROLLER
5
Engine Start Contacts
Qty 2
Isolated Form B contacts (10A, 250VAC Resistive)
Programmable Output Contacts
Qty 8
Isolated Form C contacts (2A, 250VAC Resistive)
Close to Utility Supply
Qty 1
120VAC1, 10A (Resistive) powered output contact
Close to Generator Supply
Qty 1
120VAC1, 10A (Resistive) powered output contact
Trip Utility Supply
Qty 1
120VAC1, 10A (Resistive) powered output contact
Trip Generator Supply
Qty 1
120VAC1, 10A (Resistive) powered output contact
2.5. AC CONTROL POWER INPUT
The TSC 900 requires 120VAC (nominal) control power input voltage. Independent AC control
power is required from both utility and generator supplies via potential transformers. AC
control power is utilized for internal TSC 900 control circuits and external control device loads.
The TSC 900 requires approximately 12VA AC power for internal control circuits. The
maximum external load is limited by output contact ratings (i.e. 10A resistive, 120/250VAC).
Total AC control power requirements for each supply must be determined by adding both
internal and external load requirements.
2.6. AUXILIARY DC CONTROL POWER INPUT
The TSC 900 can be optionally supplied with 24Vdc auxiliary control power input voltage for
applications requiring continuously energized control and display features. The maximum input
power draw is 20Watts. The 24Vdc power must be from a regulated/filtered DC supply with
maximum +-10% voltage range.
2.7. PROGRAMMABLE INPUTS
The TSC 900 provides Qty 16 Programmable Inputs. Each input is activated by external
contact closure to common (i.e. DC Negative ground). Each programmable input can be
independently programmed to different functions. Refer to Programming section for available
features.
2.8. OUTPUTS
The TSC 900 provides the following types of output circuits:
1
NOTE: Output voltage is dependent upon AC control power input voltage.
Interposing relays are required between the TSC 900 outputs and the end device if loads
exceed the output current rating.
2.9. EXTERNAL ATS CONTROL WIRING
As a minimum, all external control wiring to/from the ATS must conform to the local regulatory
authority having jurisdiction on electrical installations. Specific wire sizes listed below are for
typical circuits of distances up to 500ft (150m)1, are as follows:
Utility or Generator Voltage Sensing #14 AWG (2.5mm2)
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
6
Transfer output signals #14 AWG (2.5mm2)
Remote Start Contact for Engine Controls #14 AWG (2.5mm2)
NOTE: For long control wire runs or noisy electrical environments the control wires
should be twisted & shielded with a suitable drain wire. The shielded cable drain wire
must be grounded at one end only. The drain wire grounding location may vary as
micro-processor controllers generally exist at both ends (engine generator set &
transfer switch) and one may be more susceptible depending on the level of induced
noise. The most susceptible controller will require the shield ground point as close as
possible to the controller. Wire runs from 500ft to 1000ft should be twisted and
shielded and increased to #12 AWG where total loop resistance is greater than 5
ohms.
1
For distances exceeding 1000ft. (300m) consult Thomson Power Systems
2.10. REMOTE START CONTACT FIELD WIRING
Field wiring of a remote start contact from a transfer switch to a control panel should conform
to the following guidelines to avoid possible controller malfunction and/or damage.
2.8.1. Remote start contact wires (2 #14 AWG (2.5mm2)) should be run in a separate
conduit (ferromagnetic type) and in all cases separated from any AC wiring.
2.8.2. Avoid wiring near AC power cables to prevent pick-up of induced voltages.
2.8.3. An interposing relay may be required if field-wiring distance is excessively long
(i.e. greater than 1000 feet (300m)) and/or if a remote contact has a resistance
of greater than 5.0 ohms. In extremely noisy environments, the wire run
lengths indicated may not provide reliable operation and can only be corrected
by the use of an interposing relay. The interposing relay is generally installed at
the engine controls and utilizes DC power. It is strongly suggested that the
ground return wire of the interposing relay be used for the interface to the TSC
900 remote start contact, this will ensure integrity of the DC power supply to the
engine generator set controls in the event of a shorted or grounded wire remote
start interface wire.
2.8.4. The remote start contact provided is voltage free (i.e. dry contact). Exposing
the remote start contact to voltage or current levels in excess of its rating will
damage the transfer controller.
2.11. COMMUNICATION CABLE INSTALLATION
Communication cable wiring from the controller’s communication port must be suitably routed
to protect it from sources of electrical interference. Guidelines for protection against possible
electrical interference are as follows:
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
7
Use high quality, shielded cable only with drain wire grounded at the controller end
only.
Route the communication cable at least 3 M (10’) away from sources of electrical
noise such as variable speed motor drives, high voltage power conductors, UPS
systems, transformers, rectifiers etc.
Use separate, dedicated conduit runs for all communication cables. Do not tightly
bundle communication cables together in the conduit. Conduit should be
ferromagnetic type near sources of possible electrical interference. The entire
length of conduit should be grounded to building earth ground.
When communication cables must cross over low or high voltage AC power
conductors, the communication cables must cross at right angles and not in parallel
with the conductors.
For additional information on protection against electrical interference, contact
THOMSON POWER SYSTEMS factory.
2.12. DIELECTRIC TESTING
Do not perform any high voltage dielectric testing on the transfer switch with the TSC 900
controller connected into the circuit, as serious damage will occur to the controller. All AC
control fuses or control/sensing circuit isolation plugs connected to the TSC 900 must be
removed/disconnected if high voltage dielectric testing is performed on the transfer switch.
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
8
USB 2.0 Cable
GHC
SCU
3. DESCRIPTION
The TSC 900 controller consists of two parts; a front door mounted graphical touch screen display
(GHC), and a switch control unit (SCU) which is mounted inside the transfer switch door. The two
parts are interconnected via a USB 2.0 high speed communication cable which includes DC power.
The GHC Display is shown as in FIGURE 7. The GHC is interconnected to the SCU via plug-in
USB cable. The main features of the GHC Display are described as follows with reference to
FIGURE 7.
FIGURE# 7
1. RS232 Communication Port #1: This port is utilized for Modbus RTU Serial communication
2. RS232 Communication Port #2: This port is utilized RS232 Serial communication
3. USB Communication Port #1: This port is utilized for communication from GHC to TSC 900
SCU module.
4. Ethernet Communication Port: This port is utilized for Modbus TCP Ethernet communication
5. USB Communication Port #2: This port is utilized for customer use.
6. USB Communication Port #3: This port is utilized for customer use.
7. SD Memory Card Slot: This is used for program operation and memory storage
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
10
2 1 4 3 5 8 7
9
11
12
13
14
15
16 6 10
17
18
3.2. SWITCH CONTROL UNIT (SCU) HARDWARE
The Switch Control Unit internal PCB is shown in the following diagram:
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
11
12
10
9
7
11
8
6
18
1 2 3
4 5 16
15
14
13
17
The Switch Control Unit (SCU) with case and main I/O connections are detailed in the
following diagram:
11. J10a Engine Start 2 Contact (Single Gen SRC 2)
12. J10b Engine Start 1 Contact (Dual Gen SRC 1)
13. J13 – GHC Aux 5Vdc Power
14. J14- GHC USB Port
15. J15 – RS232 Programming Port
16. J1 – ATS Control
17. SCU Healthy Diagnostic LED
18. Engine Start Outputs On Diagnostic LED
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
12
Mode
Description
ATS Mechanism
Control Outputs
Engine Start Output
AUTO
ATS automatically transfers to generator
(source 2) during a utility (source 1) failure and
automatically returns power to utility once
restored
Outputs automatically
operate ATS
mechanism per
automatic sequence of
operation
Output contact closes to start
engine during a utility (source 1)
failure and opens to stop engine
once utility power has transferred
back on load.
OFF
ATS is Out of Service - will not automatically
operate during a utility power failure
Outputs remain in their
last state to keep ATS
in its current position
Output is disabled - engine will not
start during a utility power failure1
MANUAL
ATS is Out of Service -will not automatically
operate during a utility power failure. ATS can
be operated manually for testing or emergency
operation
Outputs de-energize to
allow ATS to be
operated manually
Output is disabled - engine will not
start during a utility power failure1
.Engine will stop if was previously
running
SERVICE
DISCONNECT
ATS transfers to neutral position to disconnect
power to the load. ATS will not automatically
operate during a utility power failure.
Outputs momentarily
energize to move ATS
mechanism to the
neutral position
Output is disabled - engine will not
start during a utility power
failure1.Engine will stop if was
previously running
ON LOAD
TEST
When ONLOAD TEST mode is initiated, a utility
power failure condition will be simulated which
will cause engine to start and ATS will transfer
to generator supply. When TEST mode is
terminated, ATS will transfer back to utility
supply and engine will stop
Outputs automatically
operate ATS
mechanism per
automatic sequence of
operation
Output contact closes to start
engine during the ONLOAD TEST
mode. Output automatically opens
when test mode is terminated and
ATS is back on utility power
OFF LOAD
TEST
When OFF LOAD TEST mode is initiated,
engine will start and run off load. When OFF
LOAD TEST mode is terminated, engine will
stop
Outputs do not change
state unless utility or
generator supply fails
in Off Load test mode
Output automatically closes to start
engine during the OFF LOAD test
mode. Output automatically opens
when test mode is terminated
TIMED TEST
When a TIMED TEST is initiated, the ATS will
perform test per the selected type (i.e. on load
or off load) and time period. The Generator, will
continue to run for the TIMED TEST duration,
then will automatically stop.
Outputs operate ATS
mechanism per
automatic sequence of
operation if
programmed for ON
LOAD TEST operation.
Output contact closes to start
engine during the TIMED TEST
mode. Output automatically opens
when exercise mode is terminated
EXERCISE
SCHEDULE
When an EXERCISE SCHEDULE occurs, the
ATS will perform exercise test on the preselected calendar date and time. The
Generator will operate on load or off load as
selected, and will continue to run for the
Exercise duration period as selected. If a reoccurring Exercise mode is selected, ATS will
repeat an exercise test based on the calendar
dates and times as selected.
Outputs operate ATS
mechanism per
automatic sequence of
operation if
programmed for ON
LOAD TEST operation.
Output contact closes to start
engine during the EXERCISE test
mode. Output automatically opens
when exercise mode is terminated
3.3. ATS OPERATION MODE DESCRIPTIONS
The TSC 900 has the following main operating modes as described per the table below:
1
The TSC 900 requires continuous control power (i.e. utility/gen power on, or 24Vdc aux power on) to keep the automatic engine
start output disabled. If control power is de-energized, the engine start output will energize in approximately 3 minutes, once its
internal control power reservoir de-energizes. This in turn will cause a repeating engine start/stop event every 3-4 minutes. To
prevent engine start/stop cycling condition upon loss of control power, the local engine control panel should be selected for the OFF
operating mode.
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
13
Operating modes for the ATS are selected either via the TSC 900 GHC Home page screen
(using the “Change Mode” button) as shown on the screen images below or can be selected via
external control switches as optionally connected to the TSC 900 Programmable inputs. Refer to
Section 4 - Operating Instructions for further information.
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
14
3.4. AUTOMATIC SEQUENCE OF OPERATION
3.4.1. OPEN TRANSITION TRANSFER
Note: For specific device settings and ranges, refer to Section 6 - Factory Default
Programming.
Under normal operating conditions, the transfer switch operates automatically during a
failure and restoration of utility power and does not require operator intervention.
When utility supply voltage drops below a preset nominal value on any phase, an
engine start delay circuit will be initiated. Following expiry of the engine start delay
period an engine start signal (contact closure) will be given.
Once the engine starts, the transfer switch controller will monitor the generators
voltage and frequency levels. Once the generator voltage and frequency rises above
preset values, a warm up time delay will be initiated. Once the warm up timer expires,
the transfer to utility supply signal will be removed (i.e. contact opening) and the
transfer to generator supply signal (contact closure) will be given to the transfer switch
mechanism. The load will then transfer from the utility supply (i.e. opening the utility
power switching device) to the generator supply (closing the generator power switching
device) to complete a break-before-make open transition transfer sequence.
The generator will continue to supply the load until the utility supply has returned and
the retransfer sequence is completed as follows: When the utility supply voltage is
restored to above the preset values on all phases, a utility return delay circuit will be
initiated. Following expiry of the utility return timer, the transfer to generator supply
signal will be removed (contact opening), the transfer to utility supply signal (contact
closure) will be given to the transfer switch mechanism. The load will then be
transferred from the generator supply back to the utility supply. During the utility retransfer sequence a neutral position delay circuit can be employed which will cause the
transfer mechanism to pause in the “neutral position (i.e. with both transfer power
switching devices open) for the duration of the neutral delay timer setting, once the
time delay expires, the re-transfer sequence will be completed.
An engine cooldown timer circuit will be initiated once the load has successfully retransferred back onto the utility supply. Following expiry of the cooldown delay period
the engine start signal will be removed (remote start contact opened) to initiate
stopping of the generator set.
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
15
3.4.2. CLOSED TRANSITION TRANSFER
For transfer switches equipped with the closed transition transfer option (i.e. ATS
Model Code Digit #13 “Operation Type” 3 or 4), the TSC 900 is configured to provide
additional logic for this application. When the TSC 900 controller receives an input
signal for Closed Transition Transfer Mode, the TSC 900 is configured to operate as
follows:
Under normal closed transition operating conditions, the transfer switch operates
automatically during a failure and restoration of utility power and does not require
operator intervention.
When utility supply voltage drops below a preset nominal value on any phase, an
engine start delay circuit will be initiated. Following expiry of the engine start delay
period an engine start signal (contact closure) will be given.
Once the engine starts, the transfer switch controller will monitor the generator voltage
and frequency levels. When the generator voltage and frequency rises above preset
values, a warm up time delay will be initiated. When the warm up timer expires the
transfer to utility supply signal will be removed (logic contact(s) opening) and the
transfer to generator supply signal (logic contact(s) closure) will be given to the transfer
switch Power Switching Devices. The load will then transfer from the utility supply (i.e.
opening the utility power switching device) to the generator supply (closing the
generator power switching device) to complete a break-before-make open transition
transfer sequence.
The generator will continue to supply the load until the utility supply has returned and
the retransfer sequence is completed as follows: When the utility supply voltage is
restored to above the preset values on all phases, a utility return delay circuit will be
initiated. Following expiry of the utility return timer, the utility power-switching device
will close when it is in synchronism with the generator supply. If the transfer switch is
supplied with a Fast (Momentary) Closed Transition transfer control option, the
generator power switching device will immediately trip within ~100 milliseconds after
the utility power switching device closes to complete the “make-before-break” retransfer sequence. If the transfer switch is supplied with a “Soft-Load” Closed
Transition transfer control option, the generator power switching device will remain
closed for a longer time period to allow a soft-load power transfer sequence to be
completed via external loading controller. The generator power switching device will
then trip open to complete the “make-before-break” re-transfer sequence.
PM 151 REV 1 15/10/08 Thomson Power Systems
16
An engine cooldown timer circuit will be initiated once the load has successfully retransferred back onto the utility supply. Following expiry of the cooldown delay period,
the engine start signal will be removed (remote start contact opened) to initiate
stopping of the generator set.
TSC 900 TRANSFER SWITCH CONTROLLER
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
17
3.4.3. AUTOMATIC LOAD SHED OPERATION
The TSC 900 can be configured for automatic load shedding operation by use of a
programmable output contact. Under normal utility power conditions, the load shed
control is not activated. When an utility power failure occurs and the ATS transfer’s to
the generator supply, the load shed circuit is automatically initiated for a preprogrammed time delay setting. Once the Load shed initiate timer expires, the Load
shed circuit is reset. Automatic Load shed can also be configured for automatic load
shed based on generator under frequency and/or ATS load kW (over power) set points.
Refer to Section 5.14 for programming instructions. The automatic sequence of
operation is further described as per the following flow chart.
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
18
3.4.4. TEST MODE
3.4.4.1. ON LOAD TEST (OPEN TRANSITION TRANSFER)
When an operator selects an ON LOAD TEST mode, the ATS controller will
initiate a simulated utility power failure condition. The transfer switch will
operate as per a normal utility power fail condition with all normal time delays
enabled. The neutral delay circuit logic will be active during transfer to and
from the generator supply (i.e. when both sources of power are available). The
transfer switch will remain on generator supply while in the Test mode. When
the Test mode is manually canceled, the ATS will re-transfer back to the utility
supply following the utility return delay, then the generator will cooldown before
stopping.
3.4.4.2. ON LOAD TEST (CLOSED TRANSITION TRANSFER)
When a load test is initiated in the closed transition transfer mode, the
generator will start and following its warm up delay, the generator will close its
power-switching device when it is in synchronism with the utility supply. If the
transfer switch is supplied with a “Momentary” Closed Transition transfer control
option, the utility power switching device will immediately trip open within ~100
milliseconds after the generator power switching device closes to complete the
“make-before-break” transfer sequence. If the transfer switch is supplied with a
“Soft-Load” Closed Transition transfer control option, the utility power switching
device will remain closed long enough to allow a soft-load power transfer
sequence to be completed as controlled by an external device. The utility power
switching device will then trip open to complete the “make-before-break”
transfer sequence. The generator will continue to supply the load until the test
mode has been removed and the re-transfer sequence is completed as follows:
The utility power-switching device will close when it is in synchronism with the
generator supply via external logic device. If the transfer switch is supplied with
a “Momentary” Closed Transition transfer control option, the generator power
switching device will immediately trip open within ~100 milliseconds after the
utility power switching device closes to complete the “make-before-break” retransfer sequence. If the transfer switch is supplied with a “Soft-Load” Closed
Transition transfer control option, the generator power switching device will
remain closed long enough to allow a soft-load power transfer sequence to be
completed as controlled by an external device. The generator power switching
device will then trip open to complete the “make-before-break” re-transfer
sequence.
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
19
3.4.5. ABNORMAL SEQUENCE OF OPERATION
3.4.5.1. GENERATOR FAILURE ON LOAD
Should the generator set fail while on load, the transfer switch will automatically
re-transfer the load back to the utility supply if within nominal limits. The utility
return timer will be bypassed in this condition.
NOTE:
This operating condition applies to a normal utility failure as well
as any test condition.
3.4.5.2. TRANSFER SWITCH FAIL ALARM LOGIC
The TSC 900 controller contains logic to detect a transfer mechanism failure.
Should a failure be detected, a forced transfer to the alternate supply will be
initiated if the TSC 900 is programmed for force transfer. Refer to the
programming Section 5 for further information in Force Transfer operation.
3.4.5.3. SERVICE ENTRANCE ATS
For Service Entrance Rated transfer switch applications, the transfer switch
control logic will include signal the transfer switch mechanism to move to the
“Service Disconnected” position when Service Disconnect Operation is
required. In this mode the TSC 900’s transfer control outputs and Transfer Fail
feature is disabled. On return to normal operation, the Utility Power-Switching
Device will be closed to the utility supply if available. Should the utility supply
be out of limits the generator will be issued a start command and the load
transfer to the generator supply once its warm-up time has expired. The ATS
returns to Auto control and will return to the utility supply as previously describe
for the appropriate ATS design type.
PM 151 REV 1 15/10/08 Thomson Power Systems
20
3.5. GHC DISPLAY MAIN MENU PAGE DESCRIPTIONS
The GHC software provides the TSC 900 control and monitoring information which is visible
on the GHC Display or remote PC. All screen page navigation is controlled by a touchscreen
display using a “finger swipe” motion and/or button press actions. The GHC has preprogrammed display pages which are selected manually using the touchscreen display. The
display pages are organized into the following main menu pages in software:
TSC 900 TRANSFER SWITCH CONTROLLER
PM 151 REV 1 15/10/08 Thomson Power Systems
TSC 900 TRANSFER SWITCH CONTROLLER
21
LED
Label
Light Off
Light On
Light Flashing
Engine
Start (RED)
Engine is not commanded to
start/run
Engine is commanded to
start/run
n/a
Exercise
(Yellow)
Exercise Schedule is not
enabled or active
Exercise Schedule is enabled
but not currently active
Exercise is
currently active
Test
(Yellow)
Test is not active
Local Test is active (On Load
or Off Load)
Remote Test is
active
Load Shed
(Yellow)
Load Shed is not active
Load Shed is activated
n/a
Alarm Icon –flashes when a new Alarm has been activated
The Home Page is utilized as a summary control and monitoring screen for the ATS.
This screen provides a mimic bus showing current ATS position, identifies which
sources are energized, voltage levels and overall ATS operating mode. On three
phase systems, all phase to phase voltages will be displayed for each source and load.
The mimic bus will automatically change color as follows:
Utility –dark green = de-energized, light green = energized
Generator - dark green = de-energized, red = energized
Power Switching Device status is depicted as follows:
Utility Closed:Generator Closed:
The following Status LEDs are shown on the Home page:
Test or Timed test modes can be activated from the Home page by press of the
“Change Mode” button which activates a pull down menu. Refer to OPERATING
INSTRUCTION section of this manual for operating procedures.
PM 151 REV 1 15/10/08 Thomson Power Systems
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.