Manitowoc Ice SD0302A, SY0304A, SD0303W, SY0305W, SD0322A Owner’s Manual

...
Manitowoc
Installation, Use & Care Manual
This manual is updated as new information and models are released.
Visit our website for the latest manual. www.manitowocice.com
America’s #1 Selling Ice Machine
S Model
Ice Machines
This manual contains English and French text
Section 1 General Information
Model Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Section 2 Installation Instructions
Location of Ice Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Ice Machine Heat of Rejection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Removing Drain Plug and Leveling the Ice Storage Bin . . . . . . . . . . . . . . . . . . . . 6
Air Baffle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Electrical Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Maximum Breaker Size & Minimum Circuit Amperage Chart . . . . . . . . . . . . . . . . 8
Water Supply and Drain Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Water Supply and Drain Line Sizing/Connections . . . . . . . . . . . . . . . . . . . . . . . . 10
Remote Condenser/Line Set Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Remote Ice Machine Usage with Non-Manitowoc Multi-Circuit Condensers . . . 15
Installation Check List
Additional Checks for Remote Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Before Starting the Ice Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table of Contents
Ice Deflector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Bin Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dispenser Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Fuse/Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Minimum Circuit Ampacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Ground Fault Circuit Interrupter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Minimum Power Cord Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
For United Kingdom Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Water Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Water Inlet Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Drain Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Water-Cooled Condenser Water Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Cooling Tower Applications (Water-Cooled Models) . . . . . . . . . . . . . . . . . . . . . 9
Remote Ice Machines
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Guidelines for Routing Line Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Calculating Remote Condenser Installation Distances . . . . . . . . . . . . . . . . . . . 13
Lengthening or Reducing Line Set Lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Connecting A Line Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Remote Receiver Service Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Head Pressure Control Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Internal Condenser Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Condenser T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Quick Connect Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Non-Manitowoc Multi-Circuit Condenser Sizing Chart . . . . . . . . . . . . . . . . . . . . 16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2 Part Number 000006520 11/11
Section 3 Operation
Section 4 Maintenance
Table of Contents (continued)
Ice Making Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Safety limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Operational Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Ice Thickness Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Cleaning and Sanitizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Cleaning/Sanitizing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Heavily Scaled Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Exterior Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Cleaning / Sanitizing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Sanitizing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Procedure to Clean Heavily Scaled Ice Machines . . . . . . . . . . . . . . . . . . . . . . . . 23
Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Sanitizing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Parts Removal for Cleaning/Sanitizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Exterior Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Door Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Cleaning the Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Removal from Service/Winterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Section 5 Customer Support
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Safety Limit Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Commercial Ice Machine Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Residential Ice Machine Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Part Number 000006520 11/11 3

Model Numbers

!
Warning
!
Warning
!
Warning
!
Warning
Section 1
General Information
This manual covers the following models:
Self-Contained
Air-Cooled
SD0302A SY0304A
SD0322A SY0324A
SR0420A SD0422A SY0424A
SD0452A SY0454A
SR0500A SD0502A SY0504A
SD0602A SY0604A
SR0850A SD0852A SY0854A
SD1002A SY1004A
SD1202A SY1204A
SD1402A SY1404A
SR1600A SD1602A SY1604A
SR1800A SD1802A SY1804A
----
----
----
----
----
NOTE: Model numbers ending in HP indicate High Pressure water regulating valve. Standard pressure = 150 psi (10.34 bar) High pressure = 350 psi (24.13 bar)
Self-Contained
Water-Cooled
SD0303W SY0305W
SD0323W SY0325W
SR0421W SD0423W SY0425W
SD0453W SY0455W
SR0501W SD0503W SY0505W
SD0603W SY0605W
SR0851W SD0853W SY0855W
SD1003W SY1005W
SD1003WM
SD1203W SY1205W
SD1403W SY1405W
SD1403WM
SR1601W SD1603W SY1605W
SR1801W SD1803W SY1805W
SD3303W
SD3303WHP
SY3305W
SY3305WHP
SD3303WM
Remote
----
----
----
----
----
----
----
----
----
SR0590N SD0592N SY0594N
SD0692N SY0694N
SR0890N SD0892N SY0894N
SD1092N SY1094N
---
---
SD1492N SY1494N
SR1690N SD1692N SY1694N
SR1890N SD1892N SY1894N
----
----
----
----
----
Remove all ice machine panels before lifting and installing.

ICE DEFLECTOR

An ice deflector is required when the ice machine is installed on a bin. An ice deflector is not required when the ice machine is installed on a dispenser.
Manitowoc ice machines require a deflector when installed on an ice storage bin.
Prior to using a non-Manitowoc ice storage system with Manitowoc ice machines, contact the manufacturer to assure their ice deflector is compatible with Manitowoc ice machines.
Do not operate equipment that has been misused, abused, neglected, damaged, or altered/modified from that of original manufactured specifications.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision concerning use of the appliance by a person responsible for their safety.
S3000C ice machines are only approved for use on Manitowoc B1100-00/B1400-00 bins.

BIN INSTALLATION

All ice machines installed on a bin require an ice deflector.
Manitowoc bins have a deflector installed and require no modifications when used with a forward facing evaporator.
Ice machines with multiple evaporators require a deflector kit.

DISPENSER INSTALLATION

No adapter is needed for machines that match the size of the dispenser unless required by the dispenser manufacturer.
No deflector is required unless specified by the dispenser manufacturer.
A bin thermostat to control ice level is recommended.
4 Part Number 000006520 11/11
Section 2
!
Caution
Installation Instructions

Location of Ice Machine

The location selected for the ice machine must meet the following criteria. If any of these criteria are not met, select another location.
The location must be free of airborne and other contaminants.
The air temperature must be at least 35°F (1.6°C), but must not exceed 110°F (43.4°C).
Remote air cooled - The air temperature must be at least -20°F (-29°C), but must not exceed 120°F (49°C).
The location must not be near heat-generating equipment or in direct sunlight and must be protected from weather.
The location must not obstruct air flow through or around the ice machine. Refer to the chart below for clearance requirements.

Clearance Requirements

S300
Top/Sides 16" (40.6 cm) 8" (20.3 cm)
Back 5" (12.7 cm) 5" (12.7 cm)
S320/S450/S500/
S600/S850/S1000
Top/Sides 8" (20.3 cm) 8" (20.3 cm)
Back 5" (12.7 cm) 5" (12.7 cm)
S420
Top/Sides 12" (30.5 cm) 8" (20.3 cm)
Back 5" (12.7 cm) 5" (12.7 cm)
S500
230/50/1 Tropical Rating
To p 24" (61 cm)
Sides/Back 12" (30.5 cm)
S1200
To p 8" (20.3 cm) 8" (20.3 cm)
Sides 12" (30.5 cm) 8" (20.3 cm)
S1400/S1600/S1800
Top/Sides 24" (61.0 cm) 8" (20.3 cm)
Back 12" (30.5 cm) 5" (12.7 cm)
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained
Water-Cooled
Water-Cooled
and Remote*
Water-Cooled
and Remote*
Self-Contained Air-Cooled
Water-Cooled
and Remote*
Water-Cooled
and Remote*
S3300** Water-Cooled
Top/Sides 8" (20.3 cm)
Back 24" (61.0 cm)
*There is no minimum clearance required for water-cooled or remote ice machines. This value is recommended for efficient operation and servicing only. **S3300 - 24” on all sides is recommended to allow access without moving the bin/ice machine.
The ice machine must be protected if it will be subjected to temperatures below 32°F (0°C). Failure caused by exposure to freezing temperatures is not covered by the warranty.
Part Number 000006520 11/11 5
Installation Instructions Section 2
!
Caution
AIR
BAFFLE

Ice Machine Heat of Rejection

Series
Ice Machine
S300 5000 6000 S320 3800 6000 S420 5900 6900 S450 5900 6900 S500 6100 6900 S600 9000 13900
S850 13000 16000 S1000 17700 21000 S1200 20700 24500 S1400 23500 27000 S1600 21000 31000 S1800 30000 35000 S3300 45000 51000
B.T.U./Hour Because the heat of rejection varies during the ice making cycle,
the figure shown is an average.
Air Conditioning
Heat of Rejection
Ice machines, like other refrigeration equipment, reject heat through the condenser. It is helpful to know the amount of heat rejected by the ice machine when sizing air conditioning equipment where self-contained air­cooled ice machines are installed.
This information is also necessary when evaluating the benefits of using water-cooled or remote condensers to reduce air conditioning loads. The amount of heat added to an air conditioned environment by an ice machine using a water-cooled or remote condenser is negligible.
Knowing the amount of heat rejected is also important when sizing a cooling tower for a water-cooled condenser. Use the peak figure for sizing the cooling tower.
Peak

Removing Drain Plug and Leveling the Ice Storage Bin

1. Remove threaded plug from drain fitting.
2. Screw the leveling legs onto the bottom of the bin.
3. Screw the foot of each leg in as far as possible.
The legs must be screwed in tightly to prevent them from bending.
4. Move the bin into its final position.
5. Level the bin to assure that the bin door closes and seals properly. Use a level on top of the bin. Turn the base of each foot as necessary to level the bin.
6. Inspect bin gasket prior to ice machine installation. (Manitowoc bins come with a closed cell foam gasket installed along the top surface of the bin.)
7. Remove all panels from ice machine before lifting. and installing on bin. Remove both front panels, top cover, left and right side panels.

Air Baffle

SELF-CONTAINED AIR-COOLED ONLY The air-cooled baffle prevents condenser air from
recirculating. To install:
1. Remove the back panel screws next to the condenser.
2. Align the mounting holes in the air baffle with the screw holes and reinstall the screws.
6
Part Number 000006520 11/11
Section 2 Installation Instructions
!
Warning
!
Warning
Important

Electrical Service

All wiring must conform to local, state and national codes.

VOLTAGE

The maximum allowable voltage variation is ±10% of the rated voltage at ice machine start-up (when the electrical load is highest).
The ice machine must be grounded in accordance with national and local electrical codes.
All electrical work, including wire routing and grounding, must conform to local, state and national electrical codes. The following precautions must be observed:
The ice machine must be grounded.
A separate fuse/circuit breaker must be provided for each ice machine.
A qualified electrician must determine proper wire size dependent upon location, materials used and length of run (minimum circuit ampacity can be used to help select the wire size).
The maximum allowable voltage variation is +/-10 of the rated voltage at ice machine start-up (when the electrical load is highest).
Check all green ground screws in the control box and verify they are tight before starting the ice machine.
Observe correct polarity of incoming line voltage. Incorrect polarity can lead to erratic ice machine operation.

FUSE/CIRCUIT BREAKER

A separate fuse/circuit breaker must be provided for each ice machine. Circuit breakers must be H.A.C.R. rated (does not apply in Canada).

MINIMUM CIRCUIT AMPACITY

The minimum circuit ampacity is used to help select the wire size of the electrical supply. (Minimum circuit ampacity is not the ice machine’s running amp load.)
The wire size (or gauge) is also dependent upon location, materials used, length of run, etc., so it must be determined by a qualified electrician.

ELECTRICAL REQUIREMENTS

Refer to Ice Machine Model/Serial Plate for voltage/ amperage specifications.

GROUND FAULT CIRCUIT INTERRUPTER

Ground Fault Circuit Interrupter (GFCI/GFI) protection is a system that shuts down the electric circuit (opens it) when it senses an unexpected loss of power, presumably to ground. Manitowoc Ice does not recommend the use of a GFCI/GFI circuit protection with our equipment. If code requires the use of a GFCI/GFI then you must follow the local code. The circuit must be dedicated, sized properly and there must be a panel GFCI/GFI breaker. We do not recommend GFCI/GFI outlets as they are known for more intermittent nuisance trips than panel breakers.

MINIMUM POWER CORD SPECIFICATIONS

Maximum
Breaker Size
15 amp 14 gauge 6 feet (1.83 m) 20 amp 12 gauge 6 feet (1.83 m) 30 amp 10 gauge 6 feet (1.83 m) 40 amp 8 gauge 6 feet (1.83 m)
Minimum Wire Size
Maximum Length of
Power Cord
If a power cord is used, the wire size to the receptacle is dependent upon location, materials used, length of run, etc., so it must be determined by a qualified electrician. Local, state or national requirements will supersede our minimum requirements.

FOR UNITED KINGDOM ONLY

As the colors of the wires in the mains lead of the appliance may not correspond with the colored markings identifying the terminals in your plug, proceed as follows:
The wire which is colored green and yellow terminal in the plug which is marked with the letter E or by the earth ground symbol or colored green or green and yellow.
The wire colored blue with the letter N or colored black.
The wire colored brown marked with the letter L or colored red.
must be connected to the terminal which is marked
must be connected to the terminal which is
must be connected to the
Part Number 000006520 11/11 7
Installation Instructions Section 2
Important
Important

Maximum Breaker Size & Minimum Circuit Amperage Chart

Due to continuous improvements, this information is for reference only. Please refer to the ice machine serial number tag to verify electrical data. Serial tag information overrides information listed on this page.
Air-Cooled Water Cooled Remote
Minimum
Breaker
Circuit Amps
Ice Machine
Voltage/
Phase/
Cycle
Maximum
Fuse/Circuit
115/1/60 25 15.6 25 14.8 N/A N/A
S300
230/1/50 15 7.4 15 6.9 N/A N/A 230/1/60 15 6.7 15 6.3 N/A N/A 115/1/60 15 11.3 15 10.5 N/A N/A
S320
208-230/1/60 15 6.0 15 5.6 N/A N/A
230/1/50 15 6.0 15 5.6 N/A N/A 115/1/60 20 14.2 20 13.5 N/A N/A
S420/S450
208-230/1/60 15 6.1 15 5.7 N/A N/A
230/1/50 15 7.1 15 6.8 N/A N/A 115/1/60 20 20.0 20 13.5 25 20.0
S500
208-230/1/60 15 6.1 15 5.7 15 8.3
230/1/50 15 7.1 15 6.8 15 6.7
S600
208-230/1/60 15 8.3 15 7.9 15 8.9
230/1/50 15 6.7 15 6.1 15 7.1
208-230/1/60 20 11.9 20 10.9 20 11.9
S850
208-230/3/60 15 9.2 15 8.2 15 9.2
230/1/50 20 10.8 20 9.4 15 10.4
S1000
S1200
208-230/1/60 208-230/3/60
230/1/50 20 12.7 20 11.3 20 12.3
460/3/60 208-230/1/60 208-230/3/60
230/1/50
30 17.3 30 16.3 25 15.7 15 10.6 15 9.6 15 10.6
N/A N/A 15 4.5 N/A N/A
35 25.0 35 25.0 N/A N/A 20 16.0 20 16.0 N/A N/A 30 20.0 30 20.0 N/A N/A
208-230/1/60 30 18.3 30 16.9 30 17.9
S1400
208-230/3/60 20 13.2 20 11.8 20 12.8
230/1/50 30 15.1 30 13.7 30 14.7 440-480/3/60 N/A N/A 15 6.4 N/A N/A 208-230/1/60 30 19.8 30 18.4 30 19.4
S1600
208-230/3/60 20 13.5 20 12.1 20 13.1
230/1/50 30 16.7 30 15.3 30 16.3 208-230/1/60 40 23.8 40 22.4 40 23.4
S1800
S3300
208-230/3/60
230/1/50 208-230/1/60 208-230/3/60 N/A N/A 30 30 N/A N/A
230/1/50 440-480/3/60
25 15.4 25 14.0 25 15.0 40 21.9 40 20.5 40 21.5
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A 15 9.9 N/A N/A
S3300 Only - Verify the direction of rotation correct is correct on the 3ph scroll compressor. The ice machine will have high suction pressure, low discharge pressure and will be noticeably loud. Reverse any two incoming power leads to reverse rotation.
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit Amps
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit Amps
8
Part Number 000006520 11/11
Section 2 Installation Instructions
!
Caution
Important

Water Supply and Drain Requirements

WATER SUPPLY

Local water conditions may require treatment of the water to inhibit scale formation, filter sediment, and remove chlorine odor and taste.

WATER INLET LINES

Follow these guidelines to install water inlet lines:
If you are installing a Manitowoc Arctic Pure water filter system, refer to the Installation Instructions supplied with the filter system for ice making water inlet connections.
Do not connect the ice machine to a hot water supply. Be sure all hot water restrictors installed for other equipment are working. (Check valves on sink faucets, dishwashers, etc.)
If water pressure exceeds the maximum recommended pressure of 80 psi (552 kPa), obtain a water pressure regulator from your Manitowoc distributor.
Install a water shut-off valve for both the ice making and condenser water lines.
Insulate water inlet lines to prevent condensation.

WATER-COOLED CONDENSER WATER PRESSURE

Water pressure at the condenser cannot exceed 150 psig (10.34 bar) with the standard water-regulating valve. Contact your distributor if your water pressure is greater than 150 psig (10.34 bar). A special order condensing unit is available that allows water pressure up to 350 psig (24.13 bar)

COOLING TOWER APPLICATIONS (WATER-COOLED MODELS)

A water cooling tower installation does not require modification of the ice machine. The water regulator valve for the condenser continues to control the refrigeration discharge pressure.
It is necessary to know the amount of heat rejection, and the pressure drop through the condenser and water valves (inlet and outlet) when using a cooling tower on an ice machine.
Water entering the condenser must not exceed 90°F (32.2°C).
Water flow through the condenser must not exceed 5 gallons (19 liters) per minute.
Allow for a pressure drop of 7 psi (0.5 bar) between the condenser water inlet and the outlet of the ice machine.
Do not apply heat to water valve inlet fitting. This will damage plastic water inlet connection.

DRAIN CONNECTIONS

Follow these guidelines when installing drain lines to prevent drain water from flowing back into the ice machine and storage bin:
Drain lines must have a 1.5 inch drop per 5 feet of run (2.5 cm per meter), and must not create traps.
The floor drain must be large enough to accommodate drainage from all drains.
Run separate bin and ice machine drain lines. Insulate them to prevent condensation.
Vent the bin and ice machine drain to the atmosphere. Do not vent the condenser drain on water-cooled models.
S3300 requires base drain connection (1" FPT).
Water exiting the condenser must not exceed 110°F (43.3°C).
.
The Commonwealth of Massachusetts requires that all water-cooled models must be connected only to a closed loop, cooling tower system.
Part Number 000006520 11/11 9
Installation Instructions Section 2
!
Caution
ELECTRICAL ENTRANCE
18" (46 CM) VENT TUBE
AIR GAP
1/2" (1.3 CM) MIN
DRAIN ID
1/2" DRAIN CONNECTION
PLASTIC FITTING ON OPPOSITE
SIDE DO NOT APPLY HEAT
OPEN, TRAPPED AND
VENTED DRAIN
DO NOT TRAP DRAIN LINE,
LEAVE AIR GAP BETWEEN
DRAIN TUBE AND DRAIN
3/8" FPT ICE MAKING WATER INLET FITTING,
PLASTIC FITTING ON OPPOSITE SIDE DO NOT
APPLY HEAT
1/2" FPT CONDENSER WATER DRAIN
(WATER COOLED UNITS ONLY)
3/8" FPT CONDENSER WATER INLET
(WATER COOLED UNITS ONLY)
1/2" CPVC SOCKET AUXILLARY
BASE DRAIN

Water Supply and Drain Line Sizing/Connections

Plumbing must conform to state and local codes.
Location
Ice Making Water Inlet
Ice Making
Water Drain
Condenser Water Inlet
Condenser
Water Drain
Bin Drain
Large Capacity
Bin Drain
Water
Temperature
35°F (1.6°C) Min.
90°F (32.2°C) Max.
--- ---
90°F (32.2°C) Max.
--- ---
--- --- 3/4" (1.91 cm) Female Pipe Thread
--- --- 1" (2.54 cm) Male Pipe Thread 1" (2.54 cm) min. inside diameter
The exact locations of inlets and drains for the model you are working on may vary.
Water Pressure Ice Machine Fitting
20 psi (1.4 bar) Min.
80 psi (5.52 bar) Max.
Standard
20 psi (1.4 bar) Min.
150 psi (10.34 bar) Max.
High Pressure Option
20 psi (1.4 bar) Min.
350 psi (24.1 bar) Max.
3/8" (.95 cm) Female Pipe Thread
1/2" (1.27 cm) FPT S3300 Only
1/2" (1.27 cm) Female Pipe Thread
1" (2.54 cm) FPT S3300 Only
1" (2.54 cm) FPT Base Drain
S3300 Only
1" Female Pipe Thread S3300 Only
1/2" (1.27 cm) Female Pipe Thread
1" (2.54 cm) FPT S3300 Only
Tubing Size Up to Ice
Machine Fitting
3/8" (.95 cm) min inside diameter
1/2" (1.27 cm) S3300 Only
1/2" (1.27 cm) min inside diameter
1" (2.54 cm) S3300 Only
3/8" Female Pipe Thread
1/2" (1.27 cm) min inside diameter
1" (2.54 cm) S3300 Only
3/4" (1.91 cm) minimum
inside diameter
10
Typical Water Supply Drain Installation
Part Number 000006520 11/11
Section 2 Installation Instructions
Important
Important
!
Warning
!
Caution

Remote Condenser/Line Set Installation

Remote Single
Ice Machine
S500 JC0495
S600/S800/S1000 JC0895
S1400/S1600/
S1800
*Line Set Discharge Line Liquid Line
RT 1/2" (1.27 cm) 5/16" (.79 cm) RL 1/2" (1.27 cm) 3/8" (.95 cm)
Air Temperature Around the Condenser
Minimum Maximum
-20°F (-29°C) 120°F (49°C)
Circuit
Condenser
JC1395
Line Set*
RT-20-R404A RT-35-R404A RT-50-R404A RT-20-R404A RT-35-R404A RT-50-R404A RL-20-R404A RL-35-R404A RL-50-R404A

REMOTE ICE MACHINES REFRIGERANT CHARGE

Each remote ice machine ships from the factory with a refrigerant charge appropriate for installation with line sets of up to 50' (15.25 m). The serial tag on the ice machine indicates the refrigerant charge.
Additional refrigerant may be required for installations using line sets between 50' and 100' (15.25-30.5 m) long. If additional refrigerant is required, refer to the chart below for the correct amount to be added.
EPA CERTIFIED TECHNICIANS
If remote line set length is between 50' and 100' (15.25 and 30.5 m), add additional refrigerant to the nameplate charge. Refer to the table below for the model being worked on.
Tubing length: _________________________________ Refrigerant added to nameplate: ___________________ New total refrigerant charge: ______________________
Manitowoc remote systems are only approved and warranted as a complete new package. Warranty on the refrigeration system will be void if a new ice machine head section is connected to pre-existing (used) tubing or remote condensers.
Ice Machine
S500 6 lb. (96 oz.) 1.5 lb. (24 oz.) 7.5 lb. (120 oz.) S600 6.5 lb. (104 oz) 1.5 lb. (24 oz.) 8 lb. (128 oz.)
S850 8.5 lb. (136 oz.) 2 lb. (32 oz.) 10.5 lb. (168 oz.) S1000 8.5 lb. (136 oz.) 2 lb. (32 oz.) 10.5 lb. (168 oz.) S1400 11 lb. (176 oz.) 2 lb. (32 oz.) 13 lb. (208 oz.) S1600 11.5 lb. (184 oz.) 2 lb. (32 oz.) 13.5 lb. (216 oz.) S1800 12.5 lb. (200 oz.) 1 lb. (16 oz.) 13.5 lb. (216 oz.)
Nameplate Charge
(Charge Shipped in Ice Machine)
Potential Personal Injury Situation
The ice machine contains refrigerant charge. Installation of the line sets must be performed by a properly trained and EPA certified refrigeration technician aware of the dangers of dealing with refrigerant charged equipment.
Never add more than nameplate charge to the refrigeration system for any application.
Refrigerant to be Added for
50'-100' Line Sets
Maximum System Charge
(Never Exceed)
Part Number 000006520 11/11 11
Installation Instructions Section 2
!
Caution

GENERAL

Condensers must be mounted horizontally with the fan motor on top with nothing obstructing it. There must be at least a 16" (41 cm) clearance from the bottom for air intake. The front coupling panel and one other panel (back or side) must also be unobstructed.
Remote condenser installations consist of vertical and horizontal line sets between the ice machine and the condenser. When combined, they must fit within approved specifications. The following guidelines, drawings and calculation methods must be followed to verify a proper remote condenser installation.
The 60 month compressor warranty (including the 36 month labor replacement warranty) will not apply if the remote ice machine is not installed according to specifications.
This warranty also will not apply if the refrigeration system is modified with a condenser, heat reclaim device, or other parts or assemblies not manufactured by Manitowoc Ice unless specifically approved in writing by Manitowoc Ice.

GUIDELINES FOR ROUTING LINE SETS

First, cut a 2.5" (6.35 cm) circular hole in the wall or roof for tubing routing. The line set end with the 90° bend will connect to the ice machine. The straight end will connect to the remote condenser.
Follow these guidelines when routing the refrigerant lines. This will help ensure proper performance and service accessibility.
1. Optional - Make the service loop in the line sets (as shown below). This permits easy access to the ice machine for cleaning and service. Do not use hard rigid copper at this location.
2. Required - Do not form traps in the refrigeration lines (except the service loop). Refrigerant oil must be free to drain toward the ice machine or the condenser. Route excess tubing in a supported downward horizontal spiral (as shown below). Do not coil tubing vertically.
3. Required - Keep outdoor refrigerant line runs as short as possible.
3
2
1
DOWNWARD
HORIZONTAL
SPIRAL
2
1
3
Routing Line Sets
12
Part Number 000006520 11/11
Section 2 Installation Instructions
!
Caution
H
R
Combination of a Rise and a
Horizontal Run
Combination of a Drop and a
Horizontal Run
Combination of a Rise, a Drop
and a Horizontal Run
SV1196 SV1195 SV1194

CALCULATING REMOTE CONDENSER INSTALLATION DISTANCES

Line Set Length
The maximum length is 100' (30.5 m). The ice machine compressor must have the proper oil
return. The receiver is designed to hold a charge sufficient to operate the ice machine in ambient temperatures between -20°F (-29°C) and 120°F (49°C), with line set lengths of up to 100' (30.5 m).
Line Set Rise/Drop
The maximum rise is 35' (10.7 m). The maximum drop is 15' (4.5 m).
If a line set has a rise followed by a drop, another rise cannot be made. Likewise, if a line set has a drop followed by a rise, another drop cannot be made.
Calculated Line Set Distance
The maximum calculated distance is 150' (45.7 m). Line set rises, drops, horizontal runs (or combinations of
these) in excess of the stated maximums will exceed compressor start-up and design limits. This will cause poor oil return to the compressor.
Make the following calculations to make sure the line set layout is within specifications.
1. Insert the measured rise into the formula below. Multiply by 1.7 to get the calculated rise. (Example: A condenser located 10 feet above the ice machine has a calculated rise of 17 feet.)
2. Insert the measured drop into the formula below. Multiply by 6.6 to get the calculated drop. (Example. A condenser located 10 feet below the ice machine has a calculated drop of 66 feet.)
3. Insert the measured horizontal distance into the formula below. No calculation is necessary.
4. Add together the calculated rise, calculated drop, and horizontal distance to get the total calculated distance. If this total exceeds 150' (45.7 m), move the condenser to a new location and perform the calculations again.
Maximum Line Set Distance Formula
Step 1. Measured Rise (35' [10.7 m] Maximum) ______ x 1.7 = _______ Calculated Rise Step 2. Measured Drop (15' [4.5 m] Maximum) ______ x 6.6 = _______ Calculated Drop Step 3. Measured Horizontal Distance (100' [30.5 m] Maximum) _______ Horizontal Distance Step 4. Total Calculated Distance 150' (45.7 m) _______ Total Calculated Distance
H
D
H
R
D
Part Number 000006520 11/11 13
Installation Instructions Section 2
SV1603
REMOVE FRONT, TOP,
AND LEFT SIDE PANEL
FOR ACCESS TO
RECEIVER VALVE
TURN
COUNTERCLOCKWISE
TO OPEN
RECEIVER SERVICE
VALVE CAP (TURN
COUNTERCLOCKWISE
TO REMOVE)

LENGTHENING OR REDUCING LINE SET LENGTHS

In most cases, by routing the line set properly, shortening will not be necessary. When shortening or lengthening is required, do so before connecting the line set to the ice machine or the remote condenser. This prevents the loss of refrigerant in the ice machine or condenser.
The quick connect fittings on the line sets are equipped with Schraeder valves. Use these valves to recover any vapor charge from the line set. When lengthening or shortening lines follow good refrigeration practices, purge with nitrogen and insulate all tubing. Do not change the tube sizes. Evacuate the lines and place about 5 oz (143g) of vapor refrigerant charge in each line.

CONNECTING A LINE SET

1. Remove the dust caps from the line set, condenser and ice machine.
2. Apply refrigeration oil to the threads on the quick disconnect couplers before connecting them to the condenser.
3. Carefully thread the female fitting to the condenser or ice machine by hand.
4. Tighten the couplings with a wrench until they bottom out.

REMOTE RECEIVER SERVICE VALVE

The receiver service valve is closed during shipment. Open the valve prior to starting the ice machine.
1. Remove the top and left side panels.
2. Remove the receiver service valve cap.
3. Backseat (open) the valve.
4. Reinstall the cap and panels.
5. Turn an additional 1/4 turn to ensure proper brass­to-brass seating. Torque to the following specifications:
Liquid Line Discharge Line
10-12 ft lb.
(13.5-16.2 N•m)
35-45 ft lb.
(47.5-61.0 N•m)
6. Check all fittings and valve caps for leaks.
7. Make sure Schraeder cores are seated and Schraeder caps are on and tight.
Backseating the Receiver Service Valve
14
Part Number 000006520 11/11
Section 2 Installation Instructions
Important
!
Caution
!
Caution

Remote Ice Machine Usage with Non-Manitowoc Multi-Circuit Condensers

WARRANTY

The sixty (60) month compressor warranty, including thirty six (36) month labor replacement warranty, shall not apply when the remote ice machine is not installed within the remote specifications. The foregoing warranty shall not apply to any ice machine installed and/or maintained inconsistent with the technical instructions provided by Manitowoc Ice, Inc. Performance may vary from Sales specifications. S-Model ARI certified standard ratings only apply when used with a Manitowoc remote condenser.
If the design of the condenser meets the specifications, Manitowoc’s only to be extended to the Manitowoc manufactured part of the system. Since Manitowoc does not condenser in conjunction with the ice machine, Manitowoc will not endorse, recommend, or approve the condenser, and will not be responsible for its performance or reliability.
Manitowoc warrants only complete new and unused remote packages. Guaranteeing the integrity of a new ice machine under the terms of our warranty prohibits the use of pre-existing (used) tubing or condensers.

HEAD PRESSURE CONTROL VALVE

Any remote condenser connected to a Manitowoc S-Model Ice Machine must have a head pressure control valve (available from Manitowoc Distributors) installed on the condenser package. Manitowoc will not accept substitute “off the shelf” head pressure control valves.
approval is for full warranty coverage
test the

FAN MOTOR

The condenser fan must be on during the complete ice machine freeze cycle (do not cycle on fan cycle control). The ice maker has a condenser fan motor circuit for use with a Manitowoc condenser. It is recommended that this circuit be used to control the condenser fan(s) on the multi-circuit condenser to assure it is on at the proper time. Do not exceed the rated amps for the fan motor
circuit listed on the ice machine’s serial tag. INTERNAL CONDENSER VOLUME
The multi-circuit condenser internal volume must not be less than or exceed that used by Manitowoc (see chart on next page). Do not exceed internal volume and try
to add charge to compensate, as compressor failure will result.
CONDENSER T
T is the difference in temperature between the condensing refrigerant and entering air. The T should be 15 to 20°F (-9.4 to -6.6°C) at the beginning of the freeze cycle (peak load conditions) and drop down to 12 to 17°F (-11.1 to -8.3°C) during the last 75% of the freeze cycle (average load conditions).

REFRIGERANT CHARGE

Remote ice machines have the serial plate refrigerant charge (total system charge) located in the ice maker section. (Remote condensers and line sets are supplied with only a vapor charge.)
Never add more than nameplate charge to ice machine for any application.

QUICK CONNECT FITTINGS

Do not use a fan cycling control to try to maintain discharge pressure. Compressor failure will result.
Part Number 000006520 11/11 15
The ice machine and line sets come with quick connect fittings. It is recommended that matching quick connects (available through Manitowoc Distributors) be installed in the multi-circuit condenser, and that a vapor “holding” charge, 5 oz. (150 ml), of proper refrigerant be added to the condenser prior to connection of the ice machine or line set to the condenser.
Installation Instructions Section 2
SINGLE CIRCUIT REMOTE CONDENSER
ELECTRICAL DISCONNECT
DISCHARGE LINE
LIQUID LINE
ELECTRICAL DISCONNECT
ELECTRICAL SUPPLY
ICE MACHINE
BIN
DISCHARGE REFRIGERANT LINE
LIQUID REFRIGERANT LINE
36.00" (91.44 cm) DROP
TO CIRCUIT BREAKER PANEL

NON-MANITOWOC MULTI-CIRCUIT CONDENSER SIZING CHART

Internal
Ice
Machine
Model
Refrigerant Heat of Rejection
Type Charge
Average
Btu/hr
Btu/hr
Peak
Condenser
Volu me (cu ft )
Design
Pressure
Min Max Discharge Liquid
500 psig
(3447 kpa)
S500 R-404A
6 lbs. 6,100 6,900 0.020 0.035
(34.47 bar)
safe working
pressure S600 R404A 6.5 lbs. 9,000 13,900 0.045 0.060 S850 R-404A 8.5 lbs. 13,000 16,000 0.045 0.060 2,500 psig
S1000 R-404A 8.5 lbs. 17,700 21,000 0.045 0.060 S1400 R-404A 11 lbs. 20,700 24,500 0.085 0.105 S1600 R-404A 11.5 lbs 21,000 31,000
S1800 R-404A 12.5 lbs. 30,000 35,000
0.085 0.105
0.085 0.105
(17237 kpa)
(172.37 bar)
burst
pressure
Quick Connect Stubs-
Male Ends
coupling
P/N
83-6035-3
mounting flange P/N 83-6006-3
coupling
P/N
83-6034-3
mounting flange P/N 83-6005-3
Head
Pressure
Control
Valve
Manitowoc
P/N
83-6809-3
no
substitutes
Typical Single Circuit Remote Condenser Installation
16
Part Number 000006520 11/11
Section 2 Installation Instructions
!
Warning

Installation Check List

Is the Ice Machine level?
Have all of the electrical and water
connections been made?
Has the supply voltage been tested and
checked against the rating on the nameplate?
Is there proper clearance around the ice
machine for air circulation?
Is the ice machine grounded and polarity
correct?
Has the ice machine been installed where
ambient temperatures will remain in the range of 35° - 110°F (1.6° - 43.3°C)?
Has the ice machine been installed where the
incoming water temperature will remain in the range of 35° - 90°F (1.6° - 32.2°C)?
Is there a separate drain for the potable
water, bin and water-cooled condenser?
Are the ice machine and bin drains vented?
S3300 Only - Is the compressor direction of
rotation correct? The ice machine will have high suction pressure, low discharge pressure and will be noticeably loud. Reverse any two incoming power leads to reverse rotation.

Additional Checks for Remote Models

Has the receiver service valve been opened?
Does the remote condenser fan operate
properly after start-up?
Has the remote condenser been located
where ambient temperatures will remain in the range of -20° - 120°F (-29 - 49°C).
Is the line set routed properly?
Are both refrigeration lines to remote
condenser run so they do not lay in water and are properly insulated?

Before Starting the Ice Machine

Are all electrical leads free from contact with
refrigeration lines and moving equipment?
Has the owner/operator been instructed
regarding maintenance and the use of Manitowoc Cleaner and Sanitizer?
Has the owner/operator completed the
warranty registration card?
Has the ice machine and bin been sanitized?
Is the toggle switch set to ice? (The toggle
switch is located directly behind the front panel).
Is the ice thickness control set correctly?
(Refer to Operational Checks to check/set the correct ice bridge thickness).
All Manitowoc ice machines are factory-operated and adjusted before shipment. Normally, new installations do not require any adjustment.
To ensure proper operation, follow the Operational Checks in Section 3 of this manual. Starting the ice machine and completing the Operational Checks are the responsibilities of the owner/operator.
Adjustments and maintenance procedures outlined in this manual are not covered by the warranty.
Potential Personal Injury Situation
Do not operate equipment that has been misused. abused, neglected, damaged, or altered/modified from that of original manufactured specifications.
Part Number 000006520 11/11 17

Ice Making Sequence Of Operation

Section 3
Operation
NOTE: The toggle switch must be in the ice position and the water curtain/ice dampers must be in place on the evaporator before the ice machine will start.

Water Purge Cycle

The ice machine purges any remaining water from the water trough down the drain.

Freeze Cycle

Water flows across the evaporator and the refrigeration system chills the evaporator. Ice builds on the evaporator until water contacts the ice thickness probe.

Harvest Cycle

Any remaining water is purged down the drain as refrigerant gas warms the evaporator. When the evaporator warms, the sheet of cubes slides off the evaporator and into the storage bin. If all cubes fall clear of the water curtain (or ice damper) the ice machine starts another freeze cycle.

Off Cycle

If the water curtain or ice damper are held open by ice cubes the ice machine shuts off. When the water curtain or ice damper closes the ice machine starts a new cycle at the water purge.

Control Board Timers

The control board has the following non-adjustable timers:
The ice machine is locked into the freeze cycle for 6 minutes before a harvest cycle can be initiated. Freeze lock is bypassed after moving the toggle switch from OFF to ICE position for the first cycle only.
The maximum freeze time is 60 minutes at which time the control board automatically initiates a harvest sequence.
The maximum harvest time is 3.5 minutes for single evaporators and 7 minutes for multiple evaporator model. The control board automatically initiates a freeze sequence when these times are exceeded.

SAFETY LIMITS

Safety limits are stored and indicated by the control board after three cycles. The number of cycles required to stop the ice machine varies for each safety limit.
Safety Limit 1 all models - If the freeze time reaches 60 minutes, the control board automatically initiates a harvest cycle. If 6 consecutive 60-minute freeze cycles occur, the ice machine stops.
Safety Limit 2 single evaporator models - If the harvest time reaches 3.5 minutes, the control board automatically returns the ice machine to the freeze cycle. If 500 consecutive 3.5 minute harvest cycles occur, the ice machine stops.
Safety Limit 2 multiple evaporator models - If the harvest time reaches 7 minutes, the control board automatically returns the ice machine to the freeze cycle. If 500 consecutive 7 minute harvest cycles occur, the ice machine stops.
Safety Limit 3 multiple evaporator models - If the low refrigerant pressure control opens, the ice machine shuts off and starts a 5 minute delay period. If 3 consecutive low pressure events occur, the ice machine stops and flashes the harvest light.
Use the following procedures to determine if the control board contains a safety limit indication.
1. Move the toggle switch to OFF.
2. Move the toggle switch back to ICE. Watch the safety limit lights/harvest light on the control board. If a safety limit has been recorded, the corresponding light will blink once, twice or three times to indicate which safety limit stopped the ice machine.
18 Part Number 000006520 11/11
Section 3 Operation
Important
ADJUSTING SCREW
1/8" (3 mm)
ICE BRIDGE THICKNESS

Operational Checks

GENERAL

Manitowoc ice machines are factory-operated and adjusted before shipment. Normally, new installations do not require any adjustment.
To ensure proper operation, always follow the Operational Checks:
when starting the ice machine for the first time
after a prolonged out of service period
after cleaning and sanitizing NOTE: Routine adjustments and maintenance
procedures are not covered by the warranty.
Scroll refrigeration compressors must be operated for a minimum break in period of 24 hours before full ice production will be reached.

ICE THICKNESS CHECK

After a harvest cycle, inspect the ice cubes in the ice storage bin. The ice thickness probe is factory-set to maintain the ice bridge thickness at 1/8" (3 mm).
NOTE: Make sure the water curtain is in place when performing this check. It prevents water from splashing out of the water trough.
1. Inspect the bridge connecting the cubes. It should be about 1/8" (3 mm) thick.
2. If adjustment is necessary, turn the ice thickness probe adjustment screw clockwise to increase bridge thickness, counterclockwise to decrease bridge thickness. Set at 1/4" (6 mm) gap between ice machine and evaporator as starting point, then adjust to achieve a 1/8" (3 mm) bridge thickness.
NOTE: Turning the adjustment 1/3 of a turn will change the ice thickness about 1/16" (1.5 mm).
Part Number 000006520 11/11 19
Ice Thickness Check
3. Make sure the ice thickness probe wire and the bracket do not restrict movement of the probe.
Section 4
!
Caution
!
Caution
!
Warning
Maintenance

Cleaning and Sanitizing

GENERAL

You are responsible for maintaining the ice machine in accordance with the instructions in this manual. Maintenance procedures are not covered by the warranty.
Clean and sanitize the ice machine every six months for efficient operation. If the ice machine requires more frequent cleaning and sanitizing, consult a qualified service company to test the water quality and recommend appropriate water treatment. An extremely dirty ice machine must be taken apart for cleaning and sanitizing.
Manitowoc Ice Machine Cleaner and Sanitizer are the only products approved for use in Manitowoc ice machines.
Use only Manitowoc approved Ice Machine Cleaner and Sanitizer for this application (Manitowoc Cleaner part number 94-0546-3 and Manitowoc Sanitizer part number 94-0565-3). It is a violation of Federal law to use these solutions in a manner inconsistent with their labeling. Read and understand all labels printed on bottles before use.
Do not mix Cleaner and Sanitizer solutions together. It is a violation of Federal law to use these solutions in a manner inconsistent with their labeling.

CLEANING/SANITIZING PROCEDURE

This procedure must be performed a minimum of once every six months.
The ice machine and bin must be disassembled cleaned and sanitized.
All ice produced during the cleaning and sanitizing procedures must be discarded.
Removes mineral deposits from areas or surfaces that are in direct contact with water.

HEAVILY SCALED CLEANING PROCEDURE

Perform this procedure if you have some or all of these symptoms.
Ice machine stops on Safety Shutdown.
Your water has a high concentration of minerals.
The ice machine has not been on a regular maintenance schedule.

EXTERIOR CLEANING

Clean the area around the ice machine as often as necessary to maintain cleanliness and efficient operation. Use cleaners designed for use with stainless steel products.
Sponge any dust and dirt off the outside of the ice machine with mild soap and water. Wipe dry with a clean, soft cloth.
Heavy stains should be removed with stainless steel wool. Never use plain steel wool or abrasive pads. They will scratch the panels.
Wear rubber gloves and safety goggles (and/or face shield) when handling Ice Machine Cleaner or Sanitizer.
20 Part Number 000006520 11/11