Manitowoc Ice K00364 User Manual

RED
LEAD
LEAD
JUMPER
K00364 Electronic Bin Thermostat
Installation Instructions
This kit reduces overfill and cond ensation issues and can be used on any Manit owoc ice machine installed on an ice dispenser. Order kit number K00336 for the following models IB0620, IB0820, IB1020, QF0400 and QF2300.

Control Settings

Ice Cube Machines: The machines use the factory control settings.
The controller has a one-minute time delay anytime power is interrupted and restored.

Positioning the Touchpad Jumpers

P5 Jumper

The P5 jumper position determines if the touchpad is locked or unlocked. The control is factory locked; to unlock, move the jumper from one pin to two pins.
SENSOR
BLACK SENSOR
MATCH WIRING TO ICE MACHINE VOLTAGE
LOCATIONS
BIN SWITCH OR
TOGGLE SWITCH

P4 Jumper

The P4 jumper labeled Jump 1 is used to set the control for heating or cooling mode. Jump 2 is used to establish set point at either cut-in or cut-out.
Cubers Flake/Nugget/Chiplet
Setting Control Set point Value
To view and adjust set point, foll ow these steps:
A. Press MENU until the display flashes SP. B. Press MENU ag ain to display the existing set
point value.
C. Press up or down (arrows) to change the set
point value.
D. Press MENU again to save the new value. The
display returns to the sensed temperature.
E. If no setup entry is made for 30 seconds, the
control reverts to the normal temperature display.

IMPORTANT:

If MENU is not pressed after changing the set point value, the control reverts to the previously programmed set point value.
Manitowoc Ice, Inc.
2110 South 26th Street, P.O. Box 1720, Manitowoc, WI 54221-1720 USA 8016563 Telephone 920-682-0161, Fax - Sales: 920-683-7589, Service/Parts: 920-683-7585, Other: 920-683-7879 Sheet 1 of 4 Web Site - www.manitowocice.com Rev. 03/14/06
Fault Code
Definition
Solution

Differential, Anti-Short Cycle Delay, Temperature Offset, or Sensor Failure Operation

To set or verify the Differential, Anti-Short Cycle Delay, Temperature Offset or Sensor Failure Op eration use the following method:
Factory preset temperature control code settings, as follows:
A. Press and hold MENU until the display
changes to flashing SP.
B. Press up and down (arrows) repeatedly until
the desired function is displayed.
C. Press MENU to display the function’s current
value.
D. Press up and down (arrows) until the desired
value is displayed.
E. Press MENU to save the new value. The
display returns to the sensor temperatur e.
F. If no setup entry is made for 30 seconds, the
control reverts to the temperature display.
Any saved control settings are non-v olatile and remain in the control’s memory during power interruptions.
Check Procedure
WARNING
Line voltage is present inside control. Contact with line voltage can cause serious injury or death.
If the control system does not function properly, verify that the control is wired and set up properly. If the problem persists, use the following procedures to determine the cause of the problem

IMPORTANT:

Follow these troubleshooting procedures in the order presented. Do not skip any of the steps in the procedures.
1. Check for proper voltage to the control. A. Remove the cover by loosening the four cover
screws.
B. Use an AC voltmeter to check the voltage
between the common and 120V or 240V terminals.
C. The voltage must be between 102 and 132
volts for 120V applications; 177 and 264 volts for 208/230V applications.
D. If the voltage reading is not within the required
range, check the power source and input power wires for problems.
2. Fault Codes If the LCD displays an alarm or fault code (SF or EE):
SF flashing
alternately with
OP
SF flashing
alternately with
SH
EE
Open temperature
sensor or sensor wiring
Shorted temperature
sensor or sensor wiring
Program failure
See Step 3. Cycle
power to reset control.
See Step 3. Cycle
power to reset control
Reset the control by pressing MENU. If
problem persists,
replace the control.
3. Check for proper operation.

IMPORTANT:

Perform Steps 1 and 2 before performing these steps:
A. Disconnect the load from the output relay
terminals.
B. Reconnect the sensor leads and supply power
to the control.
C. Replace t he cover. D. Check the control settings for proper values. E. Press and hold MENU until SP appears. F. Press u p and down (arrows) to change the set
point temperature above and below the sensor temperature until the relay energizes and de­energizes.
G. If the output relay does not perform as
indicated, replace the control.
H. If proper operation of the control is verified,
reconnect the load.
Loading...
+ 5 hidden pages