IMPORTANT: Installation of natural
gas should be completed by a
qualified installer, service agency
or gas supplier.
WARNING: If the information in
this manual is not followed exactly, a fire or explosion may
result causing property damage,
personal injury or loss of life.
Vermont Castings GPF
Gas Patio Fire
Models: GPFMN, GPFMP
FOR YOUR SAFETY:
• Installation and service must be
performed by a qualified installer, service agency or the gas
supplier.
• Do not store or use gasoline or
other flammable vapors and
liquids in the vicinity of this or
any other appliance.
Model GPF is a decorative gas log set for outdoor use
only . This appliance must not be used for cooking.
IMPORTANT:Read all instructions and warnings
carefully before starting installation. Failure to follow
these instructions may result in a possible fire hazard
and will void the warranty.
WARNING: Improper installation, adjustment,
alteration, service or maintenance can cause injury or
property damage. Read the installation, operating and
maintenance instructions thoroughly before installing or
servicing this equipment.
WARNING: This appliance shall be used only outdoors
in a well-ventilated space and shall NOT be used inside
a building, garage or any other enclosed area.
WARNING: This log set must NOT be installed in an
unvented appliance.
WARNING: This unit is not for use with solid fuel.
NOTE: All new LP cylinders (and in many cases used
cylinders) may contain water, air or other contaminants,
and it is essential that these be removed before filling
the cylinder and placing into service. Water vapor
present in the gas vapor may cause the regulator to
“freeze up” and cause an interruption to the gas flow.
This interruption will cause the unit to shut down. To
prevent this form occurring it is essential that a
qualified individual ALWAYS purge a new tank
thoroughly before placing it into service. It is
recommended that cylinders that have not been used
for extended periods of time also be purged before use.
The installation must conform with Local Codes or, in
the absence of local codes, with the National Fuel Gas
Code ANSI Z223.1 or CSA-B149.1 Installation Code.
The appliance and its individual shut off valve must be
disconnected from the gas supply piping system during
any pressure testing or the system at test pressures in
excess of 1/2 psig (3.5kPa).
This appliance must be isolated from the gas supply
piping system by closing its individual manual shut off
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than 1/
2 psig (3.5kPa).
The following clearances to combustible construction
must be maintained: Bottom - 0 inches (0mm), Sides
(all around) - 16 inches (406mm) and Top - (7 feet
(2.1m).
Always keep the appliance area clear and free from
combustible materials, gasoline and other flammable
vapors and liquids.
Vermont Castings GPF
Do not locate appliance where it can get excessively
wet. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the unit and to replace any part of
the control system and any gas control which has been
under water.
•Children and adults should be alerted to the hazards
of high surface temperatures and should stay away to
avoid burns or clothing ignition.
•Young children should be carefully supervised when
they are in the area of the appliance.
•Never leave unit unattended during operation.
•Clothing or other flammable materials should not be
hung from the appliance, or placed on or near the
appliance.
•Any guard or other protective device removed for
servicing the appliance must be replaced prior to
operating the appliance.
•Installation and repair should be done by a qualified
service person. The appliance should be inspected
before use and at least annually by a qualified service
person. More frequent cleaning may be required as
necessary. It is imperative the control compartment,
burners and circulating air passageways of the
appliance be kept clean.
•Inspect the fuel supply connection (including the hose
for LP models) before each use of the appliance.
•If it is evident there is excessive abrasion or wear, or
the hose is cut, it must be replaced prior to the
appliance being put into operation.
•The pressure regulator and hose assembly supplied
with LP models must be used. Replacement pressure
regulators and hose assemblies must be those
specified in this manual.
•The LP gas supply cylinder used with LP models must
be constructed and marked in accordance with the
specifications for LP gas cylinders of the U.S.
Department of Transportation (DOT).
•Cylinders must be stored outdoors in a well-ventilated
area out of reach of children. Disconnected cylinders
must have threaded valve plugs tightly installed and
must not be stored in a building, garage or any other
enclose area.
•Storage of this appliance indoors is permissible only
it has been disconnected from its fuel supply (natural
gas line or LP gas cylinder).
•The LP gas cylinder supply system must be arranged
for vapor withdrawal.
•The LP gas cylinder used must include a collar to
protect the cylinder valve.
•When an LP model is not in use, the LP gas must be
turned off at the supply cylinder.
3
Vermont Castings GPF
Assembly and Installation
The logs and burner assembly are shipped together.
1. Remove the gas log set and burner assembly and
check for damage. DO NOT install damaged
components. The logs are fragile - handle with care.
2. Place the burner assembly on a flat, stable surface
in an outdoor location such as a patio or a deck.
This location must be adjacent to the gas supply line
(natural gas) or LP gas supply cylinder. NOTE:
Minimum clearances to combustibles must be
maintained.
Remember, you must have easy access to the gas
valve control knob AFTER the appliance is installed
and connected to the gas supply.
The ON/OFF Gas Valve is used to turn the burner
on and off.
Natural Gas Models
Connect the incoming gas supply line to the on/off gas
valve of the appliance. (Fig. 3) Make certain ALL gas
connections are tight. Test for leaks. Use a 50/50
solution of liquid soap and water to test for leaks at gas
fittings and joints. Apply water/soap solution with a
brush only -
do not over apply. NEVER test with an
open flame.
LP Gas Models
1. Place cylinder base (provided with unit) on a level
surface.
2. Be sure to place cylinder in ring on base.
3. Make sure tank valve is in its full off position. (Turn
clockwise to stop)
4. Check tank valve features to ensure it has proper
external mating threads. (Tank valve Marked: USE
WITH TYPE 1)
5. Inspect hose shipped with the unit for damage.
Never attempt to use damaged or plugged
equipment. See your local LP Gas Dealer for
repairs.
6. After inspecting the LP hose shipped with the unit,
connect the end with the female fitting on the hose
to the male fitting on the on/off gas valve at the end
of the flex tube and make sure it is tight.
7. When connecting regulator assembly to the tank
valve, hand tighten nut clockwise to a positive stop.
DO NOT use a wrench to tighten. Use of a wrench
may damage quick closing coupling nut and result in
a hazardous condition. (Fig. 3)
8. Locate the hose out of pathways where people may
trip over it or in areas where the hose may be
subject to accidental damage.
9. Open tank valve fully (counterclockwise). Turn the
on/off valve at the unit slowly to the on position and
use a 50/50 solution of liquid soap and water to test
for leaks at gas fitting and joints. Apply water/soap
solution with a brush only - do not over apply.
NEVER test with an open flame. If a leak is found,
turn tank valve off and do not use the appliance until
repairs can be made by a local LP Gas Dealer. DONOT attempt to make repairs yourself.
10. Never attempt to use this appliance or any
components that have been damaged or exposed to
an accidental fire.
Fig. 3 Gas line connection.
4
Natural Gas Supply Line
Burner
Assembly
Propane
Regulator Hose
Cylinder Base
Burner Assembly
Valve
Valve
FP1130
Vermont Castings GPF
Enclosures for LP Gas Supply Systems
If you build an enclosure for an LP gas cylinder, follow
these recommended specifications. You must also
follow local codes.
Enclosures for LP gas supply cylinders shall be
ventilated by openings at the level of the cylinder valve
and at floor level. The effectiveness of the opening(s)
for purposes of ventilation shall be determined with the
LP gas supply cylinder(s) in place. This shall be
accomplished by one of the following:
1. One side of the enclosure shall be completely open;
or
2. For an enclosure having four sides, a top and
bottom:
a. At least two ventilation openings at cylinder valve
level shall be provided in the side wall, equally sized,
spaced at 180 degrees (3.14 rad), and unobstructed.
Each opening shall have a total free area of not less
than 1/2 square inch per pound (3.2 sq. cm/kg) of
stored fuel capacity and not less than a total free
area of 10 square inches (64.5sq. cm).
b. Ventilation opening(s) shall be provided at floor level
and shall have a total free area of not less than 1/2
inch per pound (3.2 sq. cm/kg) of stored fuel
capacity and not less than a total free area of 10
square inches (64.5 sq. cm). If ventilation openings
at floor level are in a side wall, there shall be at least
two openings. The bottom of the openings shall be
at floor level and the upper edge no more than 5
inches (127mm) above the floor. The openings shall
be equally sized, spaced at 180 degrees (3.14 rad)
and unobstructed.
c. Every opening shall have minimum dimensions so
as to permit the entrance of a 1/8 inch (3.2mm)
diameter rod.
3. Cylinder valves shall be readily accessible for hand
operation. A door on the enclosure to gain access to
the cylinder valves is acceptable, provided it is
nonlocking and can be opened without the use of
tools.
4. There shall be a minimum clearance of 2 inches
(50.8 mm) between the lower surface of the floor of
the LP gas supply cylinder enclosure and the
ground.
5. The design of the enclosure shall be such that (1)
the LP gas supply cylinder(s) can be connected,
disconnected and the connections inspected and
tested outside the cylinder enclosure; and (2) those
connections which could be disturbed when
installing the cylinder(s) in the enclosure can be leak
tested inside the enclosure.
6. Be certain to mount or set the LP gas cylinder on a
flat stable surface and restrain it to prevent it from
tipping.
Purge the gas supply line of any trapped air prior to the
first firing of the unit.
WARNING: During the initial purging and
subsequent lightings, NEVER allow gas valve to
remain in the “Open” position without first placing
a burning match on the top of the burner.
Place the logs on the burner assembly. Refer to log
placement instructions.
Test fire the unit after referring to the SAFETY
INFORMATION and Lighting Instructions found on page
9.
CAUTION: Do not leave the burner on with the
cover on.
NOTE: Carbon (soot) may build up on the surface of
the logs with heavy use. This is more likely to occur
when using LP gas. The soot should be cleaned off the
surface of the logs periodically to prevent excessive
build up. To clean the logs, be sure the fire is out, the
gas supply is turned off and the logs are cool to the
touch. The soot can then be brushed off with a dry
bristle brush or cloth. Take care while cleaning the logs
as they can become damaged if mishandled. Care
should be taken to dispose of the soot and cleaning
materials properly. Keep away from clothing and
outdoor furniture.
5
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.