Convertible Direct Vent
Fireplaces: 360DVS2
360DVS3
360DVSL
360DVSR
INSTALLER/CONSUMER
SAFETY INFORMATION
PLEASE READ THIS MANUAL
BEFORE INSTALLING AND USING
APPLIANCE
IMPORTANT: Read all instructions
and warnings carefully before
starting installation. Failure to follow
these instructions may result in a
possible fire hazard, and will void the
warranty.
WARNING:
manual is not followed exactly, a fire or
explosion may result, causing property
damage, personal injury, or loss of life.
If the information in this
FOR YOUR SAFETY:
• Installation and service must be per
formed by a qualified installer, service
agency, or
the gas supplier.
• Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
If you smell gas:
1. Open windows
2. Do not touch electrical switches.
3. Do not try to light any appliance.
4. Extinguish any open flame.
5. Do not use any telephone in your
building.
6. Immediately call your gas supplier
from a neighbor’s phone.
7. Follow your gas supplier’s
instructions.
8. If you cannot reach your gas supplier,
call the fire department.
-
Homeowner’s Installation
and Operating Manual
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
10006326 4/08 Rev. 5
Page 2
360 DVS Series Direct Vent Fireplaces
Table of Contents
Thank you, and Congratulations on your purchase of a CFM Corporation Fireplace.
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE.
IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these
instructions fully may result in a possible fire hazard and will void the warranty.
Installation and Operating Instructions ........................................................................................................3
Important Curing/Burning Instructions ................................................................................................
Replacement Parts .......................................................................................................................................36
Optional Accessories
Fan Kits .............................................................................................................................................
This gas appliance should be installed by a qualified installer,
preferably NFI or WETT (Canada) certified, in accordance
with local building codes and current CSA-B149.1 Installation
Codes for Gas Burning Appliances and Equipment. If the unit
is being installed in a mobile home, the installation should comply
with the current CAN/CSA Z 240.4 code. For U.S.A. Installations,
follow local codes and/or the current National Fuel Gas Code,
ANSI Z223.1/NFPA 54.
FOR SAFE INSTALLATION AND OPERATION PLEASE
NOTE THE FOLLOWING:
1. This fireplace gives off high temperatures and should be located
out of high traffic areas and away from furniture and draperies.
2. Children and adults should be alerted to the hazards of high
surface temperatures of this fireplace and should stay away
to avoid burns or ignition of clothing.
3. CAUTION: Due to high glass surface temperature, chil-
dren should be carefully supervised when in the same
room as fireplace.
11. When the fireplace is installed directly on carpeting, vinyl
tile, or any combustible material other than wood, it must be
installed on a metal or wood panel extending the full width
and depth of the fireplace.
12. This fireplace requires adequate ventilation and combustion
air to operate properly.
13. This fireplace must not be connected to a chimney flue serving a
separate solid fuel-burning fireplace.
14. When the fireplace is not in use, it is recommended the gas
valve be left in the “OFF” position.
WARNING: Check with your electronics manufacturer
before installing a television or other electronic device above this fireplace.
360DVS2/ 360DVS3/ 360DVSL/ 360DVSR
CERTIFIED TO
ANSI Z21.88-2005 / CSA 2.33-2005
Vented Gas Fireplace Heaters
This appliance may be installed in an aftermarket, permanently located, manufactured home, or mobile home
where not prohibited by local codes.
This appliance is only for use with type of gas
indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is
used.
4. Under no circumstances should this fireplace be modified.
Parts removed for servicing should be replaced prior to
operating this fireplace again.
5. Installation and any repairs to this fireplace must be per
formed by a qualified installer, service agency or gas sup
plier. A professional service person should be contacted to
inspect this fireplace annually. Make it a practice to have
all of your gas fireplaces checked annually. More frequent
cleaning may be required due to excess lint and dust from
carpeting, bedding material, etc.
6. Control compartments, burners and air passages in this fireplace should be kept clean and free of dust and lint. Make
sure the gas valve and pilot light are turned off before you
attempt to clean this fireplace.
7. The venting system (chimney) of this fireplace should be
checked at least once a year, and if needed, your venting
system should be cleaned.
8. Keep the area around your fireplace clear of combustible
materials, gasoline and other flammable vapor and liquids.
This fireplace should not be used as a drying rack for cloth
ing, nor should Christmas stockings or decorations be hung
on or around the fireplace.
9. Under no circumstances should any solid fuels (wood, coal,
paper or cardboard, etc.) be used in this fireplace.
10. The flow of combustion and ventilation air must not be obstructed in any way.
10006326
-
-
IMPORTANT:
PLEASE REVIEW THE FOLLOWING CAREFULLY
Remove any plastic from trim parts before turning the
fireplace ON.
It is normal for fireplaces fabricated of steel to give off
some expansion and/or contraction noises during the
start up or cool down cycle. Similar noises are found with
your furnace heat exchanger or car engine.
It is not unusual for your gas fireplace to give off some
odor the first time it is burned. This is due to the curing of
the paint and any undetected oil from the manufacturing
process.
Please ensure that your room is well ventilated - open
all windows.
It is recommended that you burn your fireplace for at least
ten (10) hours the first time you use it. If the optional fan
kit has been installed, place the fan switch in the “OFF”
position during this time.
-
Proposition 65 Warning: Fuels used in gas, woodburning or oil fired appliances, and the products of
combustion of such fuels, contain chemicals known to
the State of California to cause cancer, birth defects
and other reproductive harm.
California Health & Safety Code Sec. 25249.6
3
Page 4
360 DVS Series Direct Vent Fireplaces
Requirements for the Commonwealth of
Massachusetts
All gas fitting and installation of this heater shall only be
done by a licensed gas fitter or licensed plumber.
For all side wall horizontally vented gas fueled
equipment installed in every dwelling, building or
structure used in whole or in part for residential
purposes, including those owned or operated by the
Commonwealth and where the side wall exhaust
vent termination is less than seven (7) feet above
finished grade in the area of the venting, including
but not limited to decks and porches, the following
requirements shall be satisfied:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber
or gas fitter shall observe that a hard wired carbon
monoxide detector with an alarm is installed on each
additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled
equipment. It shall be the responsibility of the property
owner to secure the services of qualified licensed
professionals for the installation of hard wired carbon
monoxide detectors.
In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with
alarm and battery back-up may be installed on the next
adjacent floor level.
In the event that the requirements of this subdivision
can not be met at the time of completion of installation,
the owner shall have a period of thirty (30) days
to comply with the above requirements; provided,
however, that during said thirty (30) day period, a
battery operated carbon monoxide detector with an
alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in
accordance with the above provisions shall comply with
NFPA 720 and ANSI/UL 2034 listed and IAS certified.
Signage
A metal or plastic identification plate shall be
permanently mounted to the exterior of the building at
a minimum height of eight (8) feet above grade directly
in line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2)
inch in size, “GAS VENT DIRECTLY BELOW, KEEP
CLEAR OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall
horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the
inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of
248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the most
current edition of NFPA 54 as adopted by the Board;
and
• Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure
used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side
wall horizontally vented gas equipment provides a
venting system design or venting system components
with the equipment, the instructions provided by the
manufacturer for installation of the equipment and the
venting system shall include:
• Detailed instructions for the installation of the venting
system design or the venting system components;
and
• A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side
wall horizontally vented gas fueled equipment does
not provide the parts for venting the flue gases, but
identifies “special venting systems”, the following
requirements shall be satisfied by the manufacturer:
• The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
• The “special venting systems” shall be Product
Approved by the Board, and the instructions for
that system shall include a parts list and detailed
installation instructions.
A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists
for venting instructions, and/or all venting design
instructions shall remain with the appliance or
equipment at the completion of the installation.
4
10006326
Page 5
J
J
K
K
H
D
A
E
B
I
E
A
F
C
H
Electrical
Access
Gas Line
Access
Electrical
Access
Gas Line
Access
K
J
J
K
J
J
G
J
J
K
K
H
D
A
E
B
E
A
F
CK
H
G
I
Electrical
Access
Gas Line
Access
Electrical
Access
Gas Line
Access
J
J
K
J
J
Rear Vent Configuration
Top Vent Configuration
360DVS Series Direct Vent Fireplaces
Fireplace Dimensions - 360DVS2
Fig. 1a Fireplace specifications—360DVS2
Appliance Dimensions
Ref. Rear Vent Configuration Top Vent ConfigurationA 38¹⁄₈” (968 mm) 38¹⁄₈” (968 mm)
B 43
¹⁄₄” (1099 mm) 43¹⁄₄” (1099 mm) C 24” (610 mm) 24” (610 mm)
D 24” (610 mm) 24” (610 mm)
E 37
F 35⁷⁄₈” (911 mm) 35⁷⁄₈” (911 mm)
G 30¹⁄₂” (775 mm) 7” (178 mm)
H 12” (305 mm) 12” (305 mm)
I 3
Ref. Rear Vent Configuration Top Vent ConfigurationA 38
B 40
C 24” (610 mm) 24” (610 mm)
D 24” (610 mm) 24” (610 mm)
E 37
F 35
G 30
H 12” (305 mm) 12” (305 mm)
I 3
J 2
K 1
Ref. Rear Vent Configuration Top Vent ConfigurationModel 360DVS3 360DVSL/R 360DVS3 360DVSL/RROD (See Note 1) (See Note 2) (See Note 1) ( See Note 2)
ROH 38
to 3¹⁄₈” (79 mm) allowance for flue collar
ROW 40
NOTE 1: 24” (610 mm) minus two times (2x) finishing material thickness to be even with face of unit.
NOTE 2: 24³⁄₄” (629 mm) minus one time (1x) finishing material thickness to be even with face of unit.
8
⁵⁄₈” (981 mm) Not to be framed until unit is set in place, due
⁵⁄₈” (1032 mm) minus one time (1x) finishing material thickness to be even with face of unit.
CFM124
10006326
Page 9
A B C D E
V
W
X
Y
Z
O
N
M
L
K
J
F
G
H
I
Fig. 3 Locating your gas fireplace
X
X
X
Y
Y
Y
Z
A
A
B
A Wall Location (Fig. 3)
Y (Minimum distance between a glass panel and a
Z (Minimum distance between edge of a glass panel
B Island Location (Fig. 3)
X (Maximum length of horizontal venting) = 20’ (6.1m)
Top of unit to ceiling ................................. 36” (914 mm)
Front of unit to combustibles ................... 36” (914 mm)
Appliance
Top .........................................0” (0 mm) to standoff
Side and bottom .................................... 1” (25 mm)
Top ........................................................ 2” (51 mm)
The height at which a combustible mantel is fitted
above the fireplace is dependent on the depth of the
mantel. This also applies to the distance between the
mantel leg (if so fitted) and the fireplace. For correct
mounting height and width, refer to Fig. 4a and 4b and
the Mantel Chart below.
The fitting of a bay window trim kit does not affect the
distances and reference points referred to in the diagram and chart.
Noncombustible mantels and legs may be installed at
any height and width around the appliance.
When using paint or lacquer to finish the mantel, such
paint or lacquer must be heat resistant to prevent discoloration.
10006326
Locating Your Fireplace
LU584-2
parallel wall) = 3’ (914mm)
and an adjacent wall) = 3” (76mm)
Refer to the venting section in this manual for specific dimensions.
Clearance to Combustibles
1” (25 mm)
Mantels
360DVS Series Direct Vent Fireplaces
Fireplace
Louvre Assembly
Top
Top of Combustion
Chamber
Bottom of Door Trim
Mantel Chart
Mantel Shelf Mantel from Top
Ref. or Breast Plate Ref. of Comb. Chamber
V 10” (254 mm) A 19” (483 mm)
W 8” (203 mm) B 17” (432 mm)
X 6” (152 mm) C 15” (381 mm)
Y 4” (102 mm) D 13” (330 mm)
Z 2” (51 mm) E 11” (297 mm)
Fig. 4a Combustible mantel minimum installation.
Top View
Mantel Leg
CFM197
Front View
Side of Combustion
Chamber
Mantel Mantel Leg From Side
Ref. Leg Depth Ref. of Comb. Opening
F 10” (254 mm) K 11¹⁄₂” (292 mm)
G 8” (203 mm) L 9¹⁄₂” (241 mm)
H 6” (152 mm) M 7
I 4” (102 mm) N 5
J 2” (51 mm) O 3¹⁄₂” (89 mm)
Fig. 4b Combustible mantel leg minimum installation.
¹⁄₂” (191 mm)
¹⁄₂” (140 mm)
CFM146
Mantel
Leg
CFM170
9
Page 10
360 DVS Series Direct Vent Fireplaces
Hearth
A hearth is not mandatory; however, for aesthetic
purposes, we recommend installing a noncombustible
hearth that projects out 12” (305mm) or more from the
front of the fireplace.
Cold climate installation recommendation:
When installing this unit against a noninsulated exterior wall or chase, it is mandatory
the outer walls be insulated to conform to
applicable insulation codes.
Framing & Finishing
1. Choose the unit location.
2. Place the unit into position and secure it to the floor
with 1¹⁄₂” (38mm) screws or nails. Holes to secure
the unit to the floor are located behind the access
door grille on the left and right sides of the unit.
3. Frame in the fireplace with a header across the top.
It is important to allow for the finished wall face when
setting the depth of the frame.
4. Drywall (sheetrock) or wood material may be placed
with a zero clearance to the top edges of the appliance when finishing walls above sides of the appliance with glass windows. NOTE: Attach wall finish-
ing to constructed frame, not the appliance.
5. On 360DVSL and 360DVSR, drywall, wood, or wood
molding may be placed with zero clearance to the
rear wall of the unit, along the vertical edge formed
by the standoffs, to intersection of the rear wall, to
the side wall having the small glass window. NOTE:
Attach wall finishing to constructed frame, not
the appliance.
Final Finishing
Noncombustible materials such as brick or tile may be
extended over the edges of the face of the appliance.
DO NOT cover any vent or grille panels.
If a Trim Kit is going to be installed on the fireplace, the
brick or tile will have to be installed flush with the edges
of the appliance.
When purging the gas lines, the window
frame assembly must be removed.
The gas pipeline can be brought in through the vent
end of the fireplace as well as the bottom. Knockouts
(to allow gas pipe installation and testing any gas connection) are provided on the bottom behind the valve.
It is most convenient to bring the gas line in from the
vent end of the valve, as this allows fan installation or
removal without disconnecting the gas line.
The gas line connection can be made with properly
tinned 3/8” copper tubing, 3/8” rigid pipe, or an approved flex connector. Since some municipalities have
additional local codes, it is always best to consult your
local authority and the CSA-B149.1 installation codes.
For USA installations, consult the current National Fuel
Gas Code, ANSI Z223.1/NFPA 54.
Always check for gas leaks with a mild
soap and water solution. Do not use an
open flame for leak testing.
The gas control is equipped with a captured-screw type
pressure test point, therefore it is not necessary to provide a 1/8” test point upstream of the control.
10
10006326
Page 11
360DVS Series Direct Vent Fireplaces
TP
TH
TP
TH
1/2” Gas Supply
1/2” NPT X 1/2” Flare Shut-Off Valve
3/8” Flex Line
(From Valve)
FP297a
Fig. 5 Gas shutoff valve and flex connector.
When using copper or flex connector, use only approved fittings. Always provide a union when using
black iron pipe so that the gas line can be easily disconnected for burner or fan servicing. Refer to the gas
specification for pressure details and ratings.
Isolate or disconnect this or any other gas appliance control from the gas line when pressure testing.
DO NOT subject the fireplace valve to test
pressures exceeding 1/2 psi.
EB-1 Electrical Junction Box Connection
The fireplace, when installed, must be
electrically connected and grounded in accordance with local codes; in the absence
of local codes, use the current CSA C22.1
Canadian Electrical Code.
For USA installations, follow the local
codes and National Electrical Code ANSI/
NFPA No. 70.
It is strongly suggested the wiring of the
EB-1 Electrical Junction Box be carried out
by a licensed electrician.
Ensure power to the supply line has been
disconnected before commencing with this
procedure.
The EB-1 electrical junction box has been supplied
standard on this model to allow for easy connection of
the optional fan kits. (Fig. 6)
To connect the EB-1 box to the house electrical supply
follow the steps below.
1. Remove the front cover of the EB-1 box.
2. Remove the plug socket assembly from the EB-1
box.
3. Feed the supply line in from the out through the elec
trical knockout.
4. Connect the ground wire of the supply line to the
green screw of the socket assembly.
5. Connect the white wire of the power line to the
chrome screw of the socket assembly.
6. Connect the black wire of the power supply line to
the brass screw (polarized) of the socket assembly.
10006326
7. Refit the socket assembly back into the electrical
box and replace the cover plate.
8. The EB-1 electrical junction box is now ready to sup
ply power to the FK12 or FK24 fan kit, if used.
EB-1 Electrical box Depending on the specific model,
this box may be installed on
FP1428
Fig. 6 EB-1 attachment.
either side of the appliance.
Remote ON/OFF Switch Installation
Do not wire the remote ON/OFF wall switch
for this gas appliance into a 120V power
supply.
1. Thread the wiring through the holes on the end
panels of the appliance. Take care not to cut the wire
or insulation on metal edges. Route the wire to a
conveniently located receptacle box.
2. Attach the wire to the ON/OFF switch and install the
switch into the receptacle box.
3. Connect the other ends of the wire to the gas control
valve, as shown in Figure 7.
Remote ON/OFF Switch
-
Fig. 7 Remote switch wiring diagram for R models.
Alternate Switch Location
The remote switch can be installed on the front or the
side of the access door. Simply mount the switch to the
bracket provided and screw the bracket to either side
of the frame, lining up the screws with the prepunched
holes. (Fig. 8)
-
Electrical
Inlet Hole
Gas Inlet
Hole
Gas
Control
Valve
FP1429
11
Page 12
360 DVS Series Direct Vent Fireplaces
FP1430
Fig. 8 Alternate switch location.
Optional Top Vent Application
This appliance is shipped as a rear vent unit. If the
installation layout requires the unit to be a top vent configuration, the appliance can be converted by following
the steps below.
When removing and refitting the plates and
adapter, be sure the associated gasket is
undamaged and refitted as required.
1. Remove the ten (10) screws securing the outer collar adapter to the fireplace body. (Fig. 9)
2. Set the collar aside, complete with the gasket.
NOTE: Do not damage the gasket, as the adapter
and gasket must be refitted.
3. Remove the insulation material (exposed in Step
2) from the top of the unit. (Fig. 10) This material
can be discarded; however, if the unit is converted
back to rear-vent, a new piece of insulation material
approved by CFM Corporation must be used for this
purpose.
NOTE: When converting appliance to top vent,
ensure the insulation material referred to in step 3 is
completely removed.
4. Remove the 4 screws securing the flue cover plate
to the top of the intake box and remove the cover
and gasket. (Fig. 11)
5. Remove 4 screws securing the flue pipe to back of
the intake box and remove pipe and gasket. (Fig. 11)
6. Secure the plate and gasket removed in step 4 over
the flue opening in the back of the intake box. En
sure the gasket is in place and undamaged.
7. Install the flue pipe and gasket removed in step 5
over the flue opening in the top of the intake box.
8. Refit the outer collar adapter and gasket to the unit
with the round collar on the top. Secure the adapter
with the 10 screws removed in step 1.
-
Remove These Screws
Remove
These
Screws
Outer Collar Adapter
FP1431
Fig. 9 Remove screws from outer collar adapter.
Insulation Pad
(Must be removed)
Flue
Pipe
FP1432
Fig. 10 Remove flue cover and pipe.
Flue Cover
Plate
Flue
Pipe
12
FP1433
Fig. 11 Flue pipe removal.
10006326
Page 13
Electronic Gas Control Valve
PILOT
HONEYWELL IGNITION MODULE
ORANGE
BLUE
BLACK
WHITE
NOVA SIT 822 VALV
E
HI
LO
POWER CORD
W/FEMALE SPADE
120 VAC RTN
WHITE
GREEN
BLACK
120 VAC HOT
BLACK
YELLOW
24 VAC RET
40VA TRANSFORMER
24 VAC HOT
BLACK
WHITE
WALL SWITCH
WHITE
OFF
1 2 3 5 6 8 9
MV MV/VP PV GRD 24V SENSE SPARK
24V
ORANGE
RED
GREEN
BLACK
This appliance may be fitted with a Honeywell ignition
module.
Installation of the remote ON/OFF starter switch on
electronic ignition units (Fig. 12):
1. Thread the wiring through the holes on the side
panels of the appliance. Take care not to cut the wire
or insulation on metal edges. Route the wire to a
conveniently located receptacle box.
2. Attach the wire to the ON/OFF switch and install the
switch into the receptacle box.
3. Connect the white wire from the wall switch to the
black wire from the transformer, using an approved
wire nut. Connect the black wire from the wall switch
to the black wire running from the #6 position of the
ignition module, also using an approved wire nut.
360DVS Series Direct Vent Fireplaces
General Venting
Your fireplace is approved to be vented either through
the side wall, or vertically through the roof.
• Only CFM Corporation venting components, specifi-
• Venting terminals shall not be recessed into a wall or
• Horizontal venting must be installed on a level plane
There must not be any obstruction such as bushes,
cally approved and labeled for this fireplace, may be
used.
siding.
without an inclining or declining slope.
FP1225
Fig. 12 Honeywell ignition module.
garden shed, fencing, deck or utility building within 24”
(610mm) from the front of the termination hood.
Do not locate the termination hood where excessive
snow or ice buildup may occur. Be sure to check the
vent termination area after snow falls; clear it to prevent
accidental blockage of the venting system. When using
a snow blower, make sure snow is not directed toward
the vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observing minimum clearances as shown on the following
page.
10006326
13
Page 14
360 DVS Series Direct Vent Fireplaces
V
V
V
V
V
V
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I
Operable
Operable
Fixed
Closed
V
B
INSIDE
CORNER DETAIL
V
A
G
N
N
CFM145a
General Venting Information - Termination Location
Canadian Installations1 US Installations
2
A = Clearance above grade, veranda, porch, 12” (30cm) 12” (30cm)
deck, or balcony
B = Clearance to window or door that may be 6” (15cm) for appliances 6” (15cm) for appliances
opened < 10,000Btuh (3kW), 12” (30cm) < 10,000 Btuh (3kW), 9”
for appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for
appliances > 50,000 Btuh (15kW)
C = Clearance to permanently closed window 12” (305mm) recommended to 12” (305mm) recommended to
prevent window condensation prevent window condensation
D = Vertical clearance to ventilated soffit located
above the terminal within a horizontal 18” (458mm) 18” (458mm)
distance of 2’ (610mm) from the center
line of the terminal
E = Clearance to unventilated soffit 12” (305mm) 12” (305mm)
F = Clearance to outside corner see next page see next page
G = Clearance to inside corner (see next page) see next page see next page
H = Clearance to each inside of center line 3’ (91cm) within a height of 15’ (5m) 3’ (91cm) within a height of 15’
extended above meter/regulator assembly above the meter/regulator assembly (5m) above the meter/regulator
assy
I = Clearance to service regulator vent outlet 3’ (91cm) 3’ (91cm)
J = Clearance to nonmechanical air supply inlet 6” (15cm) for appliances < 10,000 6” (15cm) for appliances
to building or the combustion air inlet to any Btuh (3kW), 12” (30cm) for < 10,000 Btuh (3kW), 9”
other appliances appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for
appliances > 50,000 Btuh (15kW)
K = Clearance to a mechanical air supply inlet 6’ (1.83m) 3’ (91cm) above if within 10
feet (3m) horizontally
L = Clearance above paved sidewalk or paved 7’ (2.13m)† 7’ (2.13m)†
driveway located on public property
M = Clearance under veranda, porch, deck or 12” (30cm)‡ 12” (30cm)‡
balcony
N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof
surface, and any other obstruction within a horizontal distance of 18” (450mm).
1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes
† A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor:
NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent Fireplaces are certified as part of the appliance, with clearances tested and
approved by the listing agency.
3. CFM Corporation assumes no responsibility for the improper performance of the appliance when the venting system does not
meet these requirements.
Fig. 13 Vent termination clearances.
14
10006326
Page 15
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
G =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
F =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
G
Balcony with no side wall
M =
Combustible &
Noncombustible
12" (305 mm)
M
Balcony with perpendicular side wall
M = 24" (610 mm)
P = 20” (508 mm)
M
F
Alcove Applications*
C
D
C
E
V
V
Combustible &
Noncombustible
V
V
V
E = Min. 6” (152 mm) for
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O = 8’ (2.4 m) Min.
O
P
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
Fig. 14 Termination clearances.
Canadian Installations:
General Information Assembling Vent Pipes
Venting system must be installed in accordance with the
current CSA-B149.1 installation code.
USA Installations:
The venting system must conform with local codes and/
or current National Fuel Gas Code ANSI Z223.1/NFPA
54.
Only venting components manufactured by CFM Corpo
-
ration can be used in Direct Vent systems.
Twist Lock Pipes
When using twist-lock pipe, it is not necessary to use
sealant on the joints. The only areas of the venting
system that need to be sealed with high-temperature
silicone sealant are the sliding joints of telescopic vent
sections used in the system.
10006326
360DVS Series Direct Vent Fireplaces
No.
of Caps D
1 3’ (914 mm) 2 x D
2 6’ (1.8 m) 1 x D
3 9’ (2.7 m) 2/3 x D
4 12’ (3.7 m) 1/2 x D
D
= # of Termination caps x 3
Min.
C
= (2 / # termination caps) x D
Max.
To join the twist lock pipes together, align the beads
of the male end with the grooves of the female end.
While bringing the pipes together, twist the pipe until the
flange on the female end contacts the external flange
on the male end. It is recommended that you secure the
joints with three (3) sheet metal screws; however, this is
not mandatory with twist lock pipe.
NOTE: For ease of assembly, use a lubricant (Vaseline
or similar substance) on male end of twist lock pipe
prior to assembly.
Male End
Screw Holes
Fig. 15 Twist lock pipe joints.
C
Min.
Max.
Actual
Actual
Actual
Actual
Actual
Female End
584-15
TWL100
15
Page 16
360 DVS Series Direct Vent Fireplaces
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
eg: A
eg: B
How to Use the Vent Graph
The vent chart should be read in conjunction with the
following vent installation instructions to determine the
relationship of the vertical and horizontal dimensions of
the vent system.
1. Determine the height of the center of the horizontal
vent pipe exiting through the outer wall. Using this
dimension on the Sidewall Vent Graph bellow, locate
the point intersecting with slanted graph line.
2. From the point of this intersection, draw a vertical
line to the bottom of the graph.
3. Select the indicated dimension, and position the
fireplace in accordance with same.
Example A:
If vertical dimension from floor of the fireplace is 11’
(3.4 m), horizontal run to the face of outer wall must
not exceed 14’ (4.3 m).
Example B:
If vertical dimension from floor of the unit is
7’ (2.14 m), horizontal run to the face of outer wall
must not exceed 8¹⁄₂’ (2.6 m).
Rear Wall Application
When installed as a rear vent unit this appliance may be
vented directly to a termination located on the rear wall
behind the appliance.
• Specific rear vent starter kits must be used in these
applications (see ‘venting components’). The appli-
ance has been approved for installation flat against a
rear wall. (Fig. 17)
• Maximum horizontal distance between the rear of
the appliance and the outside face of the rear wall is
20” (508 mm). (Fig. 17)
• Minimum clearances between any combustible ma-
terial and the vent pipe sections are:
Top ..............................................2” (51 mm)
Sidewall vent graph showing the relationship between vertical and
horizontal dimensions for a Direct Vent flue system.
Fig. 16 Sidewall vent graph.
16
Vertical dimension from floor of the unit
to center of the horizontal vent pipe
Fig. 17 Rear vent application.
Rear Wall Installation
Step 1
Locate and cut vent opening in the rear wall.
Combustible walls: Cut a rectangular hole measuring
10³⁄₈” H x 9³⁄₈” W (265 x 240 mm) through the exterior
wall and frame. Frame in the opening per Figure 18.
Noncombustible walls: Cut a round hole measuring
7¹⁄₂” (190 mm) diameter through the exterior wall and
frame. (Fig. 18)
STEP 2
For combustible walls: Measure wall thickness and cut
zero clearance sleeve parts to proper length.
DV Graph
Max. length is 12” (305 mm). Assemble sleeve
to its maximum opening of 10³⁄₈” x 9³⁄₈” (265 x
240 mm), and attach to firestop with #8 sheetmetal
screws (supplied). Install firestop assembly. (Fig. 19)
NOTE: Zero clearance sleeve is required only for combustible walls.
FP1434
10006326
Page 17
360DVS Series Direct Vent Fireplaces
Vent Opening for Combustible Wall
9³⁄₈”
(240mm)
10³⁄₈”
(265mm)
Framing Detail
Vent Opening for Noncombustible Wall
7¹⁄₂”
(190mm)
VO584-100
Fig. 18 Locate vent opening on rear wall.
Maximum
Length
12” (305mm)
#8 Screws (2)
#8 Screws (2)
Zero Clearance
Sleeve
Zero Clearance
CFM135a
Fig. 19 Adjustable zero clearance sleeve.
Sleeve
Firestop
Side View
STEP 3
Measure the horizontal length requirement for the venting including a 2” (51 mm) overlap, i.e. from the elbow
to the outside wall face plus 2” (51 mm), or the distance
required if installing a second 90˚ elbow. (Fig. 20)
STEP 4
Install the 4” (102 mm) vent to the appliance collar
and secure with three (3) sheetmetal screws. Install
the 7” (178 mm) vent pipe to the appliance collar and
secure with three (3) sheetmetal screws. It is not necessary to seal this connection.
It is critical there be no downward slope
away from the appliance when connecting
the vent or elbow.
STEP 5
Guide vent through the vent hole as you place the appli
ance in its installed position. Guide the 4”
(102 mm) and 7” (178 mm) collars of the vent termination into the outer ends of the venting.
Do not force the termination. If the vent pipes do not
align with the termination, remove and realign the venting at the appliance flue collars.
Attach the termination to the wall as outlined in the
instruction sheet supplied with the termination.
Vertical Sidewall Application
It is very important the venting system maintain its balance between the combustion air intake and the flue
gas exhaust, certain limitations concerning vent configurations must be strictly adhered to.
• The vent graph (Fig. 16), showing relationship be-
tween vertical and horizontal side wall venting, will
help determine allowable dimensions.
• Minimum clearance between vent pipes and com-
bustible materials is 1” (25 mm) on top, bottom, and
sides, unless otherwise noted.
• When the vent termination exits through foundations
less than 20” (508 mm) below siding outcrop, the
vent pipe must flush up with the siding.
• It is best to locate the fireplace in such a way that
minimizes the number of offsets and horizontal vent
length. The horizontal vent run refers to the total
length of vent pipe from the flue collar of the fireplace to the face of the outer wall.
NOTE: When installing the appliance as a rear vent
unit, the 90˚ transition elbow attached directly to the
rear of the unit is not included in the following criteria
and calculations. Unless it is specifically mentioned,
this elbow should be ignored when calculating venting
layouts.
FP1435
Fig. 20 Maximum three (3) 90° elbows per installation.
-
10006326
17
Page 18
360 DVS Series Direct Vent Fireplaces
A
B
90
o
1
2
3
4
1
2
3
4
Horizontal plane means no vertical rise exists on this
portion of the vent assembly.
• The maximum number of 90˚ elbows per side wall
installation is three (3).
• If a 90˚ elbow is fitted directly on top of the fireplace
flange, the maximum horizontal vent run before the
termination or a vertical rise is 36” (914mm).
• The maximum number of 45° elbows permitted per
side wall installation is two (2). These elbows can be
installed in either the vertical or horizontal run.
• For each 45° elbow installed in the horizontal run,
the length of the horizontal run MUST be reduced by
18” (45 cm). This does not apply if 45° elbows are
installed on the vertical part of the vent system.
• The maximum number of elbow degrees in a system
Max. 20”
(508mm)
Fig. 21 Maximum horizontal run w/no rise.
Max. 36”
(914mm)
FP1436
is 270°. Example shown in Figure 23:
Elbow 1 = 90°
• If a 90° elbow is used in the horizontal vent run
(level height maintained), the maximum horizontal
vent length is reduced by 36” (914 mm). (Fig. 21)
This does not apply if the 90° elbows are used to
increase or redirect a vertical rise.
Example: According to the vent graph (Fig. 16),
the maximum horizontal vent length in a system
with a 7¹⁄₂” (191mm) vertical rise is 20 ft. (6.1m), but
if a 90° is required in the horizontal vent, it must be
reduced to 17 ft. (5.2m).
NOTE: The sum of Dim. A and Dim. B must not be
greater than 17 ft. (5.2m). (Fig. 22)
Fig. 23 Maximum elbow usage.
Vertical Side Wall Installation
STEP 1
Locate and cut vent opening in the side wall. It may be
necessary to first position the fireplace and measure to
obtain the hole location. Depending on whether the wall
is combustible or noncombustible, cut the opening to
size per Figure 24.
Combustible walls: Cut a rectangular hole measuring
9³⁄₈” H x 9³⁄₈” W (240 x 240mm) through the exterior wall
and frame. Frame in the opening per Figure 24.
A + B = 17’
(5.2m) Max.
Noncombustible walls: Cut a round hole measuring
7¹⁄₂” (190 mm) diameter through the exterior wall and
frame. (Fig. 24)
7’6” (2.3m)
STEP 2
For combustible walls: Measure wall thickness and
cut zero clearance sleeve parts to proper length. Max.
length is 12” (305mm). Assemble the sleeve and attach
it to the firestop with #8 sheet metal screws (supplied).
Install the firestop assembly. (Fig. 25)
Fig. 22 Horizontal run reduction.
FP1437
Zero clearance sleeve is required only for
combustible walls.
18
FP1438
10006326
Page 19
360DVS Series Direct Vent Fireplaces
X
X
X
X
Vent Opening for Combustible Wall
9³⁄₈”
(240mm)
9³⁄₈”
(240mm)
Vent Opening for Noncombustible Wall
7¹⁄₂”
(190mm)
Fig. 24 Locate vent opening on rear wall.
Framing Detail
VO584-100
Maximum
Length
12” (305mm)
#8 Screws (2)
STEP 4
Apply a bead of silicone to the inner and outer flue
collars of the fireplace and using appropriate length of
pipe section(s) attach to fireplace with three (3) screws.
Follow with the installation of the inner and outer elbow,
again secure joints as described in “Connecting Vent
Pipes” section.
STEP 5
Measure the horizontal length requirement including a
2” (51 mm) overlap, i.e. from the elbow to the outside
wall face plus 2” (51 mm) (or the distance required if
installing a second 90° elbow. (Fig. 27)
Always install horizontal venting on a level
plane.
#8 Screws (2)
Zero Clearance
Sleeve
CFM135a
Fig. 25 Adjustable zero clearance sleeve.
Zero Clearance
Sleeve
STEP 3
Place fireplace into position. (Fig. 26) Measure the vertical height (X) required from the base of the flue collars
to the center of the wall opening.
Fig. 26 Vertical height requirement.
Firestop
Side View
FP1439
FP1441
Fig. 27 Horizontal length requirement.
STEP 6
Use appropriate length of pipe section—telescopic or
fixed—and install. The 20” (508 mm) section of pipe
which goes through the wall is packaged with the
7DVSK starter kit, and can be cut to suit if necessary.
Seal vent pipe and firestop gaps with high temperature
sealant to restrict cold air being drawn in around the
fireplace.
STEP 7
Apply high temperature sealant to 4” (102 mm) and
7” (178 mm) collars, or to the termination 1” (25 mm)
away from the crimped end. Guide 4” and 7” collars of
vent terminations into respective vent pipes. Double
check vent pipes to see that they overlap the collars by
10006326
19
Page 20
360 DVS Series Direct Vent Fireplaces
2” (51 mm). Secure termination to the wall with screws
provided, and caulk around the wall plate to weatherproof.
One alternative to screwing the termination directly to
the wallis the use of expanding plugs or an approved
exterior construction adhesive.
Or, you may attach the termination with screws through
the inner body into the 4” (102 mm) vent pipe; however,
for this method, you must extend the 4” (102mm) pipe
approximately 6” (153 mm) beyond the outer face of the
wall.
Support the horizontal pipes with metal
pipe straps every 36” (914mm).
Below Grade Installation
When it is not possible to meet required vent terminal
clearances of 12” (305 mm) above grade level, we recommend using a starter kit. It allows installation depth
down to 7” (178 mm) below grade level. Measure 7”
(178 mm) from the center of the horizontal vent pipe as
it penetrates through the wall.
NOTE: Ensure sidewall venting clearances are observed. If venting system is installed below ground,
we recommend a window well with adequate and
proper drainage.
If installing a snorkel, a minimum 24” (610 mm)
vertical rise is necessary. The maximum horizontal
run with 24” (610 mm) vertical pipe is 36” (914mm).
The measurement is taken from the collar of the
fireplace (or transition elbow) to the face of exterior
wall. See sidewall vent graph, Page 15, for extended
horizontal runs if the vertical exceeds 24” (610 mm).
1. Establish vent hole through the wall. (Fig. 24)
2. Remove soil to depth of about 16” (406 mm) below
base of snorkel. Install window well (not supplied).
Refill hole with 12” (305 mm) of coarse gravel, leaving a clearance of about 4” (102 mm) below snorkel.
(Fig. 28)
3. Install vent system.
4. Ensure a watertight seal is made around the vent
pipe coming through the wall.
5. Apply high-temperature sealant caulking (supplied)
around 4 in. and 7 in. snorkel collars.
6. Slide snorkel into vent pipes and secure to wall.
7. Level the soil so as to maintain a 4” (102 mm) clear
ance below snorkel. (Fig. 29)
-
Zero Clearance
Sleeve (if required)
Firestop
7” Pipe
24” (610mm)
Minimum
FP1442
Fig. 28 Below grade installation.
Screws
•A minimum of 24” (610mm)
•The 22” (559mm) vertical rise
Foundation Wall
vertical pipe must be installed
when using the 7TDVSNORK
Kit.
(center to center) of the snorkel
may be included for calculation
of maximum horizontal run.
7TDVSNORK
(Snorkel)
Min. 4” (102mm)
Clearance
(Ground)
Window Well
Gravel
Drain
Do not backfill around the snorkel. A clearance of at least 4” (102mm) must be maintained between the snorkel and the soil.
If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fasten brackets to wall first, then secure to snorkel with self
drilling #8 x 1/2 sheetmetal screws. It will be necessary
to extend vent pipes out as far as protruding wall face.
(Fig. 29)
• Vertical installations up to 40’ (12 m) in height. Up
to a 10’ (3 m) horizontal vent run can be installed
within the vent system using a maximum of two 90°
elbows. (Fig. 30)
Max. Height 40’
(12.2m)
Min. Height 8’
(2.4m)
Max. Height
40’ (12.2m)
Min. Height
8’ (2.4m)
Max. 10’ (3m)
Support Straps
Every 36”
(914mm)
Max. 10’ (3m)
1 + 2 + 3 + 4 = 270°
FP1444
Fig. 31 Maximum elbow usage.
FP1443
Fig. 30 Support straps for horizontal runs.
• Up to two 45° elbows may be used within the hori-
Fig. 32 Maximum termination to roof clearance.
FP1185
zontal run. For each 45° elbow used on the horizontal level the maximum horizontal length must be
reduced by 18” (457 mm).
Example: Maximum horizontal length:
Zero elbows = 10’ (3 m)
1 x 45° elbows = 8¹⁄₂’ (2.6 m)
2 x 45° elbows = 7’ (2.1 m)
• A minimum of an 8 ft. (2.43 m) vertical rise.
• Two (2) sets of 45° elbow offsets may be used within
the vertical sections. From zero to max 8 ft. (2.43 m)
vent pipe can be used between elbows. (Fig. 30)
• 7DVCS supports offsets. (Fig. 33) This application
will require you first determine the roof pitch and use
the appropriate starter kit. See Venting Components
List, Page 22.
• The maximum angular variation allowed in the sys-
tem is 270˚. (Fig. 31)
• The minimum height of the vent above the highest
point of penetration through the roof is 2’ (610mm).
(Fig. 32)
10006326
21
Page 22
360 DVS Series Direct Vent Fireplaces
11"
(279 mm)
11"
(279 mm)
Vertical Through-the-Roof Installation
1. Locate your fireplace.
2. Plumb to center of the (4”) flue collar from ceiling
above and mark position.
3. Cut an opening equal to 9
4. Proceed to plumb for additional openings through
the roof. In all cases, the opening must provide a
minimum of 1” (25 mm) clearance to the vent pipe,
i.e., the hole must be at least 9³⁄₈” x 9³⁄₈” (240 x
240mm).
5. Place fireplace into position.
6. Place firestop(s) #7DVFS or Attic Insulation Shield
#7DVAIS into position and secure. (Fig. 35)
7. Install roof support (Fig. 33) and roof flashing making
sure upper flange is below the shingles. (Fig. 34)
8. Install appropriate pipe sections until the venting is
above the flashing. (Fig. 34)
9. Install storm collar and seal around the pipe.
10. Add additional vent lengths for proper height.
(Fig. 32)
11. Apply high temperature sealant to 4” and 7” collars
of vertical vent termination and install.
³⁄₈” x 9³⁄₈” (240 x 240mm).
If there is a room above ceiling level, a
firestop spacer must be installed on both
the bottom and the top sides of the ceiling
joists. (Fig. 35) If an attic is above ceiling
level, a 7DVAIS (Attic Insulation Shield)
must be installed.
NOTE: The enlarged ends of the vent sections are to
always face downward.
Attic Insulation
Shield
Joist
Ceiling Installation
Upper Floor
Typical Roof Sup-
port Application
Fig. 33 Chimney support.
Typical Ceiling Sup
port Application
Sheet Metal Screws (#5)
(3 per joint)
Sealant
Storm Collar
-
CFM110
Joist
Firestop
Spacer
Nails (4)
CFM100
Fig. 35 Firestop and attic insulation shield.
Fig. 34 Roof flashing.
22
TWL101a
10006326
Page 23
Twist Lock Venting Components
7TDVRVT Through-the-Wall Rear Vent Termination
Starter Kit Model 7TDVSK - Sidewall
Starter Kit Model 7TDVSKV - Vertical Venting
for 7TDVSKV-A: order 1/12 to 6/12 roof pitch for 7TDVSKV-B: order 7/12 to 12/12 roof pitch
for 7TDVSKV-F: order flat roof
Starter Kit Model 7TDVSKS - Snorkel Kit
Snorkel Termination - 7TDVSNORK
for Below Grade Installation
45˚ Elbow
7TDVT45 for Rear Vent to Vertical Vent
or Vertical/Horizontal Offsets
90˚ Transition Elbow
7TDVRT90 for Rear Vent to Vertical Vent
90° Elbow
7TDV90 Vertical/Horizontal Offset
360DVS Series Direct Vent Fireplaces
Telescopic Vent Sections:
7TDVP1218 - 12” to 18” adjustable length
7TDVP3564 - 35” to 64” adjustable length
Pipe Sections for vertical or horizontal venting:
Model 7TDVP8” 4 per box
Model 7TDVP12” 4 per box
Model 7TDVP24” 4 per box
Model 7TDVP36”
Model 7TDVP48”
Firestop Spacer
Model 7DVFS
Attic Insulation Shield
Model 7DVAIS
10006326
Vertical/ Horizontal Combination Offset Support
Model 7DVCS
23
Page 24
360 DVS Series Direct Vent Fireplaces
1.
2.
�
Operating Instructions
Glass Information
Only glass approved by CFM Corporation
should be used on this fireplace.
• The use of any non-approved replacement glass will
void all product warranties.
• Care must be taken to avoid breakage of the glass.
• Do not operate appliance with glass front
removed, cracked or broken.
• Replacement glass (complete with gasket) is
available through your Majestic Fireplaces
dealer and should only be installed by a licensed
qualified service person.
7. To reinstall the window frame assembly reverse
this procedure.
Front Window Frame Assembly
1. Remove the top and bottom louvre assembly.
2. Remove the lower window trim (held in place with
magnets).
3. Remove both lower retaining screws. Access to
these screws is gained through the holes along the
lower edge of the frame behind the trim. (Fig. 38)
4. Tilt lower edge of frame out slightly and lift window
frame assembly up and away from the fireplace.
5. To reinstall the window frame assembly reverse
the process.
Lower Clamps
Louvre Removal
• The top side and top end
louvres are removed by simply
lifting the louvre assembly and
pulling the assembly away
from the fireplace. (Fig. 36)
• The lower side louvres are
hinged along there lower
edge and are folded down for
access to components in the
base cavity of the fireplace.
• The lower end louvre assembly
on the 360DVS3/ SL/ SR units
is removed in the same manner as the top louvre assemblies.
FP1227
Window Frame Assembly Removal
Side Window Frame Assemblies
1. Shut off the gas supply.
2. Allow the fireplace to cool if it has been in operation.
3. Remove the top louvre assembly.
4. Lower the bottom louvre assembly.
5. Release the two clamps along lower edge of the
frame by pulling down on clamp handles. (Fig. 37)
6. Tilt lower edge of frame out slightly and lift window
frame assembly up and away from the fireplace.
24
Figure 36
Glass Panel
Louvre
Window
Frame
Assembly
Push
Clamp
Handle
Fig. 37 Window frame assembly removal.
Location of Lower
Retaining Screws
Fig. 38 Retaining screw.
Window
Frame
Assembly
Pull Clamp
Hook
FP1228
FP1445
10006326
Page 25
360DVS Series Direct Vent Fireplaces
Glass Cleaning
It is necessary to periodically clean glass. During startup, condensation, which is normal, forms on the inside
of the glass. This condensation causes lint, dust and
other airborne particles to cling to glass surface.
Also initial paint curing may deposit a slight film on the
glass. It is therefore recommended glass be cleaned
two or three times with a non-ammonia based household cleaner and warm water. The use of fireplace glass
cleaner is recommended within the first few weeks of
operation.
After the initial cleaning process the glass should be
cleaned two or three times during each operating season depending on the environment in the house.
Clean the glass after the first two weeks of
operation.
Do not clean the glass when hot.
Do not use an abrasive cleaner.
Do not strike or slam the glass.
Ceramic Refractory Installation
The vertical refractory panels are installed in the unit
prior to shipment. For assembly procedures, refer to
Figure 39.
1. Unpack the ceramic refractory panels from the car
ton.
Handle the refractory material carefully, the
panels are fragile.
2. Place the two end floor refractory panels on the base
of the fireplace.
3. Place both side panels along the side of the base.
NOTE: 360DVS2 is the only 360DV unit that is fitted
with two (2) end vertical panels, as shown in Figure
39. 360DVSL and 360DVSR units are each fitted
with one end vertical panel and two side vertical
panel. The 360DVS3 has only one end vertical
panel.
Vertical Panels in
Place When Shipped
Floor Panels Placed
FP1446
Fig. 39 Ceramic panel installation.
During Installation
-
Log Installation
Refer to Figures 40 and 41 for log location and alignment.
Because of the log stack design, these instructions can
be followed from either side of the fireplace. To follow
these instructions, identify the logs by the number cast
into the underside.
For correct operation of the fireplace, the logs must be
correctly placed in the sequence described below:
1. Unpack the logs from the shipping carton. The logs
are fragile; handle them carefully.
Handle and dispose of plastic bags in
which logs were shipped in a safe manner.
As with all plastics, they are not toys and
should be kept away from infants.
2. Remove both sides of the window frame assembly
(where applicable).
3. Place the
hole located on the underside of the log is to be
placed over the center of the grate. The inner end
of the log ensures that the bottom hole is located on
the pin of the support.
4. Place the
square hole located on the underside of the log is to
place over the corner leg of the grate. The inner end
of the log ensures the bottom holes are located on
the pin of the support.
5. Place the
square hole fits over the corner leg of the grate.
The inner end of this log maintains a recess on the
underside, which locates over the knob on the top of
the log front left (B121) to secure the inner end in
place.
6. Place the
the log rests on the grate. The notch at the back of
the log locates over the knob on the top of the log rear (B120). The bottom of the log rests on top of
the log front left (B121).
7. Place the
a step on the outer end, which rests against the
prong of the grate. The alternate end rests on the
side floor refractory panel.
8. Place the
hole on the underside, which rests over the knob on
the top of the log rear (B120). The bottom of the log
rests against the side floor refractory panel, and the
side rests against the last prong of the grate.
9. Place the
hole on the underside, which rests over the knob on
the top of the log front right (B122). The alternate
end rests against the side floor refractory panel and
positions between the two (2) prongs of the grate.
log rear (B120) on the grate. The square
log front left (B121) on the grate. The
log front right (B122). Once more, the
log rear left (B123). The bottom back of
log bottom left (B124). The log maintains
log rear right (B125). The log maintains a
log center (B126). The log maintains a
10006326
25
Page 26
360 DVS Series Direct Vent Fireplaces
B120
B121
B122
B123
B124
B126
B125
B120
B121
B122
B123
B126
B125
LO
HI
Turn
counterclockwise
to decrease
flame height
Turn clockwise
to increase
flame height
Fig. 40 360DVS log placement.
Side of Fireplace
LG320
Side of Fireplace
Venting Side
Fig. 41 360DVS log placement.
Lava Rock and Ember Material Placement
Your log set contains Ember Material and two types of
Lava Rocks. Set these materials in place after the logs
have been installed.
Ember Material (Pt. #51915)
Remove ember material from the bag and separate it
into small pieces, then scatter it over burner tiles in a
random fashion. Do not pack down ember material;
leave it in a ‘fluffy’ state.
Lava Rock (Pt. #10001454)
Remove lav rock material from packaging and spread
it over ceramic floor panels outside log stack. Do not
place this lava rock material on burner tiles.
Venting Side
LG321
Flame & Temperature Adjustment
RN/ RP Models
For units equipped with ‘HI/LO’ valves the flame adjustment is accomplished by rotating the ‘HI/LO’ adjustment
knob located near the center of the gas control valve.
(Fig. 42 and Fig. 43)
Fig. 42 Flame adjustment knob for Honeywell valve.
26
10006326
Page 27
L
O
H
I
Turn
counterclockwise
to increase
flame height
Turn clockwise
to decrease
flame height
Fig. 43 Flame adjustment knob for SIT valve.
Flame Characteristics
It is important to periodically perform a visual check
of the pilot and burner flames. Compare them to the
pictorials illustrated below. (Figs. 45 & 46) If the flame
patterns appear abnormal, contact a qualified service
provider for service and adjustment.
360DVS Series Direct Vent Fireplaces
3/8” - 1/2”
(10 - 13mm)
F584-703
Fig. 45 Correct pilot flame appearance.
10006326
Fig. 46 Correct log flame appearance.
LG322
LG323
27
Page 28
360 DVS Series Direct Vent Fireplaces
PILOT
ON
OFF
ON
P
I
L
O
T
O
F
F
O
F
F
5
4
3
2
1
O
F
F
P
i
l
o
t
3/8" - 1/2"
Lighting and Operating Instructions
FOR YOUR SAFETY, READ BEFORE LIGHTING.
WARNING: If you do not follow these instructions exactly, a fire or explosion
may result, causing property damage, personal injury or loss of life.
A. This heater has a pilot light, which must be lit
manually. When lighting the pilot follow these
instructions exactly:
B. BEFORE LIGHTING, smell all around the
heater area for gas. Be sure to smell next to the
floor because some gas is heavier than air and
will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any fireplace.
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
Lighting Instructions
1. STOP! Read the safety information above.
2. Turn off all electrical power to the fireplace.
3. For MN/MP/TN/TP appliances ONLY, go on to
Step 4. For RN/RP appliances turn the On/Off
switch to “OFF” position or set thermostat to
lowest level.
4. Open control access panel.
5. Push in gas control knob slightly and turn
clockwise to “OFF”.
• If you cannot reach your gas supplier, call
the Fire Department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not
push in or turn by hand, do not try to repair it, call a
qualified service technician. Applying force or any
attempted repair may result in a fire or explosion.
D. Do not use this fireplace if any part has been under
water. Immediately call a qualified service techni
cian to inspect the heater and to replace any part of
the control system and any gas control which has
been under water.
10. Push the control knob all the way in and hold.
Immediately light the pilot by repeatedly depressing the piezo spark igniter until a flame appears.
Continue to hold the control knob in for about one
(1) minute after the pilot is lit. Release knob and it
will pop back up. Pilot should remain lit. If it goes
out, repeat steps 5 through 8.
-
Euro SITSIT NOVAHoneywell
6. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you
smell gas, STOP! Follow “B” in the safety infor
mation above. If you do not smell gas, go to the
next step.
7. Remove glass door before lighting pilot. (See
Glass Frame Removal section).
8. Visibly locate pilot by the main burner.
9. Turn knob on gas control counterclockwise
to “PILOT”.
To Turn OFF Gas to Heater
1. Turn the On/Off switch to Off position or set the
thermostat to lowest setting.
2. Turn off all electric power to the fireplace if service
is to be performed.
28
• If knob does not pop up when released, stop
and immediately call your service technician or
gas supplier.
-
• If after several tries, the pilot will not stay lit,
turn the gas control knob to “OFF” and call
your service technician or gas supplier.
11. Replace glass door.
12. Turn gas control knob to “ON” position.
13. For RN/RP appliances turn the On/Off switch to
“ON” position or set thermostat to desired setting.
14. Turn on all electrical power to the fireplace.
3. Open control access panel.
4. Push in gas control knob slightly and turn
clockwise to “OFF”. Do not force.
5. Close control access panel.
10006326
Page 29
360DVS Series Direct Vent Fireplaces
HI
LO
Lighting and Operating Instructions
For Fireplaces equipped with SIT822 Gas Valve (EN or EP)
Warning: If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury and loss of life.
For your safety, read the following warnings
before lighting the appliance:
A. This fireplace is equipped with an ignition device
which automatically lights the pilot.
DO NOT try to
light the pilot by hand.
B. BEFORE OPERATING
, smell all around the
appliance area for gas. Be sure to smell next to
the floor because some gas is heavier than the air
and will settle on the floor.
What to do if you smell gas
• Do not try to light any appliance
• Do not operate any electrical switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas suppliers
instructions.
Lighting Instructions
1.
STOP! Read the safety information above before
continuing.
2. Turn off all electrical power to the appliance.
3. This appliance is equipped with an ignition device
which automatically lights the pilot. DO NOT try to
light the pilot by hand.
4. Access the gas control by lowering the lower
access door (louvre assembly).
• If you cannot contact your gas supplier call
the Fire Department
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not
push in or turn by hand do not try to repair it, call
a qualified service technician. Force or attempting
repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and replace
any part of the control system and any gas control
that has been under water.
5. Turn the remote switch, if used, OFF. Turn the
wireless remote, if used, OFF.
6. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you smell
gas STOP. Follow instructions B in the safety
warnings above. If you do not smell gas go onto the
next step.
7. Close the access door.
8. Turn ON all electrical power to the appliance.
9. Turn remote switch or wireless remote to ON.
10. If the appliance will not operate, follow the
instructions “Turning Off the Gas to the Appliance”
(below), and call your service technician or gas
supplier.
Turning Off the Gas to the Appliance
1. Turn the remote switch to the “OFF” position.
2. Turn OFF all electrical power to the fireplace if
service is required.
3. Open the lower access panel.
4. Turn the shutoff valve on the flexible gas line to the
“OFF” position.
10006326
1/2” Gas Supply
NOTE: Shutoff valve
is shown in “ON” position
1/2” NPT x 1/2” Flare
Shut-Off Valve
3/8” Flex Line
(from valve)
29
Page 30
360 DVS Series Direct Vent Fireplaces
Troubleshooting the Gas Control System
NOTE: Before troubleshooting the gas control system, be sure external gas shut off is in the “On” position.
WARNING: REMOVE GLASS FRONT BEFORE DOING ANY GAS CONTROL SERVICE WORK.
SIT NOVA 820 MILLIVOLT VALVE
1. Spark ignitor will not light A. Defective or misaligned Using a match, light pilot. If pilot lights, turn off electrode at pilot. pilot and push the red button again. If pilot will not
light, check the gap at electrode and pilot; it should
be 1/8” to have a strong spark.
B. Defective ignitor (Push Button) Push piezo Ignitor Button. Check for spark at electrode and pilot. If no spark to pilot, and electode
wire is properly connected, replace ignitor.
2. Pilot will not stay lit after A. Defective pilot generator Check pilot flame. Must impinge on thermocouple/
carefully following lighting (thermocouple), remote wall thermopile. NOTE: This pilot burner assembly
instructions. switch. utilizes both a thermocouple and a thermopile.
The thermocouple operates the main valve opera tion (ON/ OFF). Clean and/or adjust pilot for maxi-
mum flame impingement on thermopile and thermo couple.
B. Defective automatic valve Turn valve knob to “Pilot.” Maintain flow to pilot;
millivolt meter should read greater than 10 mV. If
the reading is okay and the pilot does not stay on,
replace the gas valve. NOTE: An interrupter block
(not supplied) must be used to conduct this test.
3. Pilot burning, no gas to A. Wall switch or wires defective Check wall switch and wires for proper connections
main burner Jumper wires across terminals at wall switch; if
burner comes on, repalce defective wall switch. If
okay, jumper wires across wall switch wires at valve;
if burner comes on, wires are faulty or connections
are bad.
B. Thermopile may not be 1. Be sure wire connections from thermopile at
generating sufficient gas valve terminals are tight and thermopile is
millivoltage. fully inserted into pilot bracket.
2. One of the wall switch wires may be grounded.
Remove wall switch wires from valve terminals if
pilot now stays lit, trace wall switch wiring for
ground. May be grounded to fireplace or gas
supply.
3. Check thermopile with millivolt meter. Take reading at thermopile terminals of gas valve—
should read 250-300 millivolts (minimum 150)
while holding valve knob depressed in pilot position and wall switch “OFF.” Replace faulty
thermopile if reading is below specified minimum.
C. Plugged burner orifice. Check burner orifices for debris and remove.
D. Defective automatic valve Turn valve knob to “ON,” place wall switch to “ON” —
operator. millivolt meter should read greater than 100 mV. If
the reading is okay and the burner does not come
on, replace the gas valve.
4. Frequent pilot outage A. Pilot flame may be too low Clean and/or adjust pilot flame for maximum flame
problem. or blowing (high) causing the impingement on thermopile and thermocouple.
pilot safety to drop out.
B. Possible blockage of the vent Check the vent terminal for blockage (recycling the
terminal. flue gases)
SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION
30
10006326
Page 31
360DVS Series Direct Vent Fireplaces
NOTE: Remove glass before servicing.
START
TURN GAS SUPPLY OFF
.
TURN ON/OFF SWITCH
TO CALL FOR HEAT.
POWER TO MODULE?
(24V NORMAL)
SPARK ACROSS
IGNITOR SENSOR GAP?
YES
YES
YES
TURN GAS ON.
PILOT BURNER LIGHTS?
SPARK STOPS WHEN
PILOT IS LIT?
MAIN BURNER LIGHTS?
SYSTEM RUNS UNTIL
ON/OFF SWITCH IS IN
"OFF" POSITION?
TROUBLESHOOTING
ENDS.
YES
YES
YES
NO
NO
NO
NO
NO
NO
CHECK: LINE VOLTAGE (120VAC).
LOW VOLTAGE TRANSFORMER
(19.5 MINIMUM VAC).
ON/OFF SWITCH.
WIRING CONNECTIONS.
UNPLUG IGNITION LEAD
AND CHECK SPARK
AT MODULE
(24VAC NORMAL).
SPARK OK?
REPLACE MODULE.
CHECK IGNITION CABLE GROUND WIRING, CERAMIC INSULATOR,
AND GAP. CORRECT AS NECESSARY.
CHECK BOOT OF IGNITION CABLE FOR SIGNS OF MELTING OR
BUCKLING. TAKE PROTECTIVE ACTION TO SHIELD CABLE AND
BOOT FROM EXCESSIVE TEMPERATURES.
CHECK THAT ALL MANUAL GAS VALVES ARE OPEN, SUPPLY TUBING
AND PRESSURES ARE GOOD, AND PILOT BURNER ORIFICE IS NOT
BLOCKED.
CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND PILOT
OPERATOR ON GAS CONTROL.
CHECK FOR 24VAC ACROSS PV-MVPV TERMINALS ON MODULE. IF
VOLTAGE IS OKAY, REPLACE GAS CONTROL IF NOT, REPLACE MODULE.
NOTE: IF S8600B GOES INTO LOCKOUT, RESET SYSTEM.
CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE.
CLEAN FLAME ROD.
CHECK ELECTRICAL CONNECTIONS BETWEEN FLAME ROD & MODULE.
CHECK FOR CRACKED CERAMIC FLAME ROD INSULATOR.
CHECK THAT PILOT FLAME COVERS FLAME ROD AND IS STEADY BLUE.
ADJUST PILOT FLAME.
IF PROBLEM PERSISTS, REPLACE MODULE.
CHECK FOR 24VAC ACROSS MV-MVPV TERMINALS. IF NO VOLTAGE,
REPLACE MODULE.
CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND GAS
CONTROL. IF OKAY, REPLACE GAS CONTROL OR GAS CONTROL
OPERATOR.
NOTE: IF S8600B GOES INTO LOCKOUT, RESET SYSTEM.
CHECK FOR CONTINUITY OF IGNITION CABLE AND GROUND WIRE.
NOTE: IF GROUND IS POOR OR ERRATIC, SHUTDOWN MAY OCCUR
OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL AT THE TIME
OF CHECKOUT.
CHECK THAT THE PILOT FLAME COVERS FLAME ROD AND IS STEADY
AND BLUE.
IF CHECKS ARE OKAY, REPLACE MODULE.
NO
YES
Troubleshooting the Gas Control System
SIT 822 Valve with a Honeywell Electronic Igniter
10006326
31
Page 32
360 DVS Series Direct Vent Fireplaces
Troubleshooting – Honeywell VS8421
STARTCHECK
Gas Supply On
YES
Pilot Lights With Piezo
Ignitor
YES
PILOT STAYS LIT
NO
NO
NO
• Supply Line Hooked Up
• Shutoff Valve Open
• Lockout Has Engaged. Wait 60
Seconds And Try Again.
• For Spark At Electrode While
Depressing Piezo
1/8" Gap To Pilot Hood Needed.
• All Wiring Connections
• Replace Piezo Ignitor
• For Air In The Lines
• Thermopile Needs A Min.
325mv. Adjust Pilot Flame
Height.
• All Wiring Connections
• Replace Thermopile
• Thermocouple Needs A Min. Of
14mv
32
YES
PILOT LIGHTS MAIN
BURNER
YES
SYSTEM OK
NO
• Valve Is Turned On
• Wall Switch Is Not Turned On.
Watch For Grounded Wires!
• Thermopile Needs A Min. 325mv.
• Plugged Burner Orifice
• Defective Valve. Turn To Pilot,
Meter Should Read Greater Than
100mv. If Not, Replace.
10006326
Page 33
360DVS Series Direct Vent Fireplaces
A
B
C
O
F
F
P
I
L
O
T
O
N
Fuel Conversion Instructions
To convert this appliance from gas type to another, follow these instructions. Before proceeding, turn control
knob to “OFF” and turn gas supply OFF. Turn OFF any
electricity that may be going to the appliance.
CAUTION: Logs may be HOT! Allow to cool before
proceeding.
This conversion procedure must be carried
out by an authorized service provider.
1. Disconnect power to unit and shut off the gas supply.
3. Carefully remove the logs and lava rock material.
4. Remove the screws holding the burner housing as
sembly in place.
5. Remove the burner housing assembly. On some
models you may need to loosen the pilot bracket
retaining screw/nut, and tilt the pilot and bracket
assembly to gain sufficient clearance to remove the
burner housing assembly.
6. Remove front and rear orifice and replace with
orifice supplied in the conversion kit.
NOTE: On 360DV/S2/S3/SL/SR, both burner orifices
are the same size.
7. Remove the screws holding the air shutter to the
burner tubes. (Fig. 47) Note the alignment of the air
shutter on the tubes. Remove the air caps and replace them with the new air shutters supplied in the
conversion kit.
-
PSE PilotUsing a suitable wrench on hexagonal body, un
screw the pilot hood assembly from the pilot. Do not
twist the hood itself. Remove the orifice and replace
it with the new orifice supplied in the kit. Refit the pilot hood assembly. Do not overtighten the pilot hood.
The hood must return to its original alignment. Take
care not to damage the thermocouple, thermopile or
igniter.
9. SIT 820 NOVA Gas Control Valve (Fig. 48)a) Using a Torx T20 or slotted screwdriver, remove
and save three (3) pressure regulator mounting
screws (A), pressure regulator tower (B), and diaphragm (C).
b) Ensure the rubber gasket (D) is properly posi
tioned and install the new HI/LO pressure regulator
to the valve using the new screws (E) supplied with
the kit. Tighten the screws securely. (Reference
torque: 25 in.lb.)
c) Install the enclosed identification label (F) to the
valve body where it can be easily seen.
Air Shutter Retaining Screws
Air Shutters
Fig. 47 Air shutter adjustment.
8. SIT Top Convertible Pilot Gently lift off pilot hood from the pilot.
NOTE: Do not
remove the spring clip holding the hood in place. Using a correctly-sized Allen key, unscrew the exposed
orifice. Insert the new orifice supplied in the kit; do
not overtighten the orifice. Replace the pilot hood
ensuring the index tab aligns with the notch on the
hood.
The Honeywell valve fitted to this unit is suitable for use
with LP or Natural Gas. It is converted to the required
gas application by installing a color-coded conversion
screw.
a) Using a suitable small screwdriver, lift out the cen-
tral regulator cap from the “HI/LO” knob on the valve.
b) Unscrew the exposed conversion screw.
c) Insert the new color coded conversion screw. Do
not overtighten the screw; it must be finger- tight.
d) Refit the regulator cap.
e) Mount conversion label supplied with the conver
-
sion screw to the valve in a visible position.
Regulator Cap
Conversion
Screw
Pressure Regulator Housing
HV120
Fig. 50 Honeywell conversion screw replacement.
10. Reassemble fireplace in the reverse order, except
for the window frame assembly. Leave this off until
after unit has been checked for leaks and the gas
supply has been bled.
11. After bleeding the gas line and checking for leaks
with a soap solution, replace the window frame assembly.
12. Fire up the unit. Check for flame impingement on
the logs, adjusting them as necessary.
13. Check manifold and supply pressures against the
appliance specifications.
The procedure for converting from one gas
to another is the same regardless of the
initial gas used. The only variations are
in orifice sizes and component part numbers. Your authorized service provider will
ensure correct parts are used.
34
10006326
Page 35
Maintenance
360DVS Series Direct Vent Fireplaces
Burner and Burner Compartment
It is important to keep the burner and the burner compartment clean. At least once per year remove the logs
and lava rock/ember material. Vacuum and wipe out the
burner compartment. Remove and refit the logs per the
instructions in this manual.
Always handle the logs with care as they
are fragile and may also be hot if the fireplace has been in use.
FK24/FK12 Fan Assembly
The fan unit requires periodic cleaning. At least once
per month in the operating season, open the lower louvre panels and wipe or vacuum the area around the fan
to remove any build up of dust or lint.
Brass Trim
Clean the brass trim pieces using a soft cloth lightly
dampened with lemon oil. Do not use water or household cleaners on any brass components.
Cleaning the
Standing Pilot Control S
The burner and control system consists of:
• burner tube • gas orifice
• pilot assembly • thermopile
• millivolt gas valve
Most of these components may require only an occasional checkup and cleaning and some may require adjustment. If repair is necessary, it should be performed
by a qualified technician.
5. Vacuum burner compartment especially around
orifice primary air openings.
6. Visually inspect pilot. Brush or blow away any dust
or lint accumulation.
7. Reinstall logs.
8. Ignite pilot; refer to Lighting Instructions.
9. Reinstall window frame assembly.
ystem
To obtain proper operation, it is imperative that the pilot
and burner’s flame characteristics are steady, not lifting
or floating.
Typically, the top 3/8 – 1/2” (10 – 13 mm) of the thermo
pile should be engulfed in the pilot flame. (Page 26, Fig.
46)
To adjust pilot burner (to be done by a qualified service
technician):
1. Remove pilot adjustment cap.
2. Adjust pilot screw to provide properly sized flame.
3. Replace pilot adjustment cap.
The primary air shutter is set at factory and should be
adjusted, if necessary, only by a qualified service technician.
Cleaning Electronic Ignition System
The Electronic Ignition burner/control system consists
of:
• main burner
• gas orifice
• pilot burner
• 24VAC valve with transformer
The process for taking care of Electronic Ignition units is
identical to that for taking care of Standing Pilot models.
-
10006326
35
Page 36
360 DVS Series Direct Vent Fireplaces
L
O
H
I
PILOT
ADJ
PILOT
ON
OFF
4a/b
5a/b
6
11
9
11
8
10
7
12
18
24
27
17
2
29
28
22
23
26
21
20
25
19
13
14
3a/b
15a/b
16a/b
31a/b
32
35
33
HI
LO
34a/b
25
36
37
30
1
1a
1b
1c
1d
1e
1f
1g
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time,
without notice.
3a. Burner Housing Assembly, Nat. 10006148 10006148 10006148 10006148
3b. Burner Housing Assembly, Prop. 10006299 10006299 10006299 10006299
* Ceramic Burner Tile 10002165 10002165 10002165 10002165
* Orifice/s, Main burner (Nat.) Refer to the rating plate for specific orifice information
* Orifice/s, Main Burner (Prop.) Refer to the rating plate for specific orifice information
4a. Pilot assembly PSE (Nat.) 10001741 10001741 10001741 10001741
4b. Pilot assembly PSE (Prop.) 10001742 10001742 10001742 10001742
5a. Pilot assembly SIT Top Conv. (Nat.) 10002264 10002264 10002264 10002264
5b. Pilot assembly SIT Top Conv. (Prop.) 10002265 10002265 10002265 10002265
25. Trim Window Top/Bottom w/Magnets PB 57483 57483 57483 57483
26. Trim Window Top/Bottom w/Magnets PB n/a 10006197 10006197 10006197
*Window Frame Assembly, side 10002483 10002483 10002483 10002483
*Window Frame Assembly, end N/A 10002484 10002484 10002484
*Window Glass (complete with gasket), side 10002533 10002533 10002533 10002533
*Window Glass (complete with gasket), end N/A 10002534 10002534 10002534
*Gasket Kit (glass replacement, 1x11’ length) 57317 57317 57317 57317
27. Window Frame Clamp 54174 54174 54174 54174
28. Refractory Lining (vertical end walls) 10006254 10006254 10006254 10006254
29. Refractory Lining (vertical side wall) N/A N/A 10006285 10006285
30. CR Bottom Kit w/out Rear 10006257 10006257 10006257 10006257
*Air Inlet Cover Plate Assembly 10006174 10006174 10006174 10006174
*Air Inlet Cover Plate Gasket 10006171 10006171 10006174 10006171
*Flue Pipe Plate Assembly 10002554 10002554 10002554 10002554
*FluePipe Plate Gasket 10002237 10002237 10002237 1000223
*Flue Cover Plate 10002298 10002298 10002298 10002298
*Flue Cover Plate Gasket 10002233 10002233 10002233 10002233
*Relief Plate (with gasket) 10002429 10002429 10002429 10002429
*Deflector, Cabinet Top Short N/A 10002260 10002260 10002260
*Corner Post (left) N/A 10006190 10006190 10006190
*Corner Post (right) N/A 10006191 10006191 10006191
*Corner Post Mounting Bracket N/A 10006195 10006195 10006195
*Deflector Cabinet Top Long 54364 54364 54364 54364
31a. Pilot Assembly SIT Top Convertible EN 10002387 10002387 10002387 10002387
31b. Pilot Assembly SIT Top Convertible EP 10002388 10002388 10002388 10002388
32. Ignitor Electrode SIT EN/EP 52465 52465 52465 52465
33. Cable Ignitor SIT EN/EP 10000696 10000696 10000696 10000696
34a. SIT822 Gas Control Valve EN 57884 57884 57884 57884
34b. SIT822 Gas Control Valve EP 57883 57883 57883 57883
This auxiliary fan system increases the efficiency of the
circulation of the heated air.
The FK24 fan kit allows variable speed control of the
circulation fan and also incorporates a heat sensor in
the circuit.
Specifications
115 Volt / 60Hz / 56 Watts
Maintenance
The fan itself does not require regular maintenance,
however periodic cleaning of the fan and the surrounding area is required.
Check the area under the control door (lower louvre assembly) and in front of the fan and wipe or vacuum this
area at least once a month during the operating season.
Installation
The fan assembly and other components are supplied
fully wired, eliminating the need for a licensed electrician to carry out the installation.
If hard wiring the fan in using Method B (following) we
strongly recommend the use of a licensed electrician.
1. Open the lower louvre assembly. Maneuver the fan
and bracket assembly around the gas valve and
lines to locate the unit onto the screw studs on the
back of the fireplace.
2. Install the thermal sensor under the bottom of the
firebox, locating it over the two (2) 10 mm studs, and
secure it with nuts.
3. Locate the fan speed control unit. This can be fit
ted behind the lower louvre assembly as in Figure
51, or located remotely in a conveniently located
wall mounted electrical box. Remote location of the
speed control will require suitable extension of the
component wiring.
4. The power supply may be connected in two ways:
Method ARoute the 6’ lead fitted to the unit to a conveniently
located wall socket.
Method BThe EB-I receptacle box (Pt. # ZA1200) may be
hard-wired into the house supply. The fan lead is
then plugged into the EB-I box.
-
FK12
This auxiliary fan system increases the efficiency of the
circulation of the heating air.
The FK12 Fan Assembly is a fixed speed fan system
and does not allow for variable speed control. It does
not use the speed control unit or the heat sensor included with the FK24 Kit.
Specifications
115 Volts / 60 Hz / 56 Watts.
Maintenance
The fan itself does not require regular maintenance;
however, periodic cleaning of the fan and the surrounding area is required.
Check the area under the control door (lower louvre
assembly), and in front of the fan. Wipe or vacuum this
area at least once a month during the operating season.
Installation
The fan assembly is supplied fully wired eliminating the
need for a licensed electrician to carry out the installation.
1. Open the lower Louvre assembly. Maneuver the fan
and bracket assembly around the gas valve and
lines to locate the unit against the back wall of the
appliance, resting on the base.
2. With the protective cover removed from the self-ad
hesive ‘Velcro’ strips apply mild pressure to the fan &
bracket unit to secure the strips to the metal panels.
No further securing is required.
3. Power to the fan can be supplied by plugging the
supplied lead into a conveniently-located wall socket
by using a hard-wired EB-I receptacle box.
FK24 Fan
Electrical
Inlet Hole
Fan Speed
Control Box
Gas
Inlet
Hole
Heat
Sensor
10006326
FP1448
Fig. 51 Fan installation.
Electrical Box (EB-1)
39
Page 40
360 DVS Series Direct Vent Fireplaces
C
B
A
Black
White
Ground
Trim - bottom
Trim - top
Trim Window Top/Bottom
S
c
r
e
w
s
S
c
r
e
w
s
Screws
Screws
Top trim piece
Top deflector plate
Trim-left
Trim-right
Wiring Instructions
The fireplace, when installed, must be elec
trically connected and grounded in accordance with local codes, or in the absence
of local codes, with the current CSA C22.1
Canadian Electric Code. For USA installations, follow local codes and the National
Electrical Code
ANSI/ NFPA No. 70.
Any electrical rewiring of this fan must be
done by a licensed electrician.
Should this fan require servicing or repair,
the power supply must be disconnected. For
rewiring of any replacement parts, refer to
Figure 51.
Method A (Not using EB-1; Fig. 52)
1. Connect the ground wire to the power supply line to
ground stud located on the base of the firebox.
2. Connect the black wire of the supply line to either
terminal of the speed control unit.
3. The second terminal of the speed control unit is
attached to either terminal of the thermal sensor.
4. The second terminal of the thermal sensor is con
-
nected to either terminal of the fan motor.
5. The second fan motor terminal is connected to the
white wire of the supply line.
Decorative Trim Frame Kit
-
The DV360TKMP Medium Trim Kit in polished brass is
available for the 360DVS2 model only.
Each kit contains 4 polished brass trim pieces and the
necessary attaching screws to frame one side window of
the unit.
Installation (Refer to Fig. 53)
1. Remove the top louvre assembly.
2. Lower the bottom louvre assembly to expose the lou
vre hinges. Unscrew the retaining screws and remove
the louvre assembly from the hinges.
3. Remove the retaining screws that secure the top
deflector plate (above the top louvre opening), and
remove the plate.
-
A: Speed Control
B: Temperature Sensor
C: Fan
Fig. 52 Method ‘A’ fan wiring diagram.
CFM105
Method B
For instruction on wiring the EB-1 Electrical Junction Box,
see section EB-1 Electrical Junction Box Connection on
Page 10.
Remote Controls
Optional remote control units are available to control different functions of the appliance.
Model Function(s) Controlled
RC1 ON/OFF
RC2 ON/OFF & Temperature
IMTFK Wall-mounted thermostat control
40
FP1449
Fig. 53 Decorative trim frame installation.
4. Using the screws provided, attach the lower trim piece
to the predrilled holes in the lower edge of the bottom
louvre opening.
5. Using the screws provided, attach the two side trim
pieces to the predrilled holes in the vertical side frames.
6. Use the top deflector plate and the screws removed in
step 3 to clamp the top trim piece in place. With the trim
piece in place along the top edge, refit and secure the
top deflector plate.
7. Reattach the lower louvre panel to the hinges and replace the top louvre assembly.
All protective plastic wrap must be removed
from the trim pieces before the appliance is
put into service. If plastic wrap is not removed, a health or fire hazard may develop.
10006326
Page 41
360DVS Series Direct Vent Fireplaces
10006326
41
Page 42
360 DVS Series Direct Vent Fireplaces
42
10006326
Page 43
360DVS Series Direct Vent Fireplaces
LIMITED LIFETIME WARRANTY
PRODUCT COVERED BY THIS WARRANTY
All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic brand gas fireplaces equipped with
an Insta-Flame Ceramic Burner, or standard steel tube burner.
BASIC WARRANTY
CFM Corporation (hereinafter referred to collectively as the Company)
warrants that your new Vermont Castings or Majestic Gas Fireplace/
Stove is free from manufacturing and material defects for a period of
one year from the date of purchase, subject to the following conditions
and limitations.
EXTENDED LIFETIME WARRANTY
The heat exchanger, where applicable, and combustion chamber
of every Vermont Castings or Majestic gas product is warranted for
life against through wall perforation. All appliances equipped with an
Insta-Flame Ceramic Burner have limited lifetime coverage on the
ceramic burner plaque. Warrantees are made to the original owner
subject to proof of purchase and the conditions and limitations listed
on this Warranty Document
COMPONENT WARRANTY
CAST IRON: All external and internal cast iron parts are warranted for a
period of three years.
Note: On porcelain enamel finished external parts and accessories The
Company offers no Warranty on chipping of enamel surfaces. Inspect
all product prior to accepting it for any damage to the enamel.
The salt air environment of coastal areas or a high humidity environment
can be corrosive to the porcelain enamel finish. These conditions can
cause rusting of the cast iron beneath the porcelain enamel finish,
which will cause the finish to flake off.
Dye lot variations with replacement parts and/or accessories can occur
and are not covered by warranty.
GLASS DOORS: Glass doors are covered for a period of one year.
Glass doors are not warranted for breakage due to misuse or accident.
Glass doors are not covered for discoloration or burned in stains due to
environmental issues, or improper cleaning and maintenance.
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be
cleaned with Lemon oil only.
mix and masonry cleaners may corrode the brass finish. The Company
will not be responsible for, nor will it warrant any brass parts which are
damaged by external chemicals or down draft conditions.
GAS VALVES: Gas valves are covered for a period of one year
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and
mechanical components of the burner assembly are covered for one year.
All steel tube burners are warranted for one year.
ACCESSORIES: Unless otherwise noted all components and CFM
Corporation company supplied accessories are covered for a period of
one year.
CONDITIONS AND LIMITATIONS
• This new Vermont Castings or Majestic product must be installed by
a competent, authorized, service contractor. A licensed technician, as
prescribed by the local jurisdiction must perform any installation/service
work. It must be installed and operated at all times in accordance with
the Installation and Operating instructions furnished with the product.
Any alteration, willful abuse, accident, or misuse of the product shall
nullify this warranty.
• This warranty is non-transferable, and is made to the original owner,
provided that the purchase was made through an authorized supplier
of the Company.
• The customer must pay for any Authorized Dealer in-home travel fees
or service charges for in-home repair work. It is the dealers option
whether the repair work will be done in the customer’s home or in the
dealer’s shop.
• If upon inspection, the damage is found to be the fault of the manufacturer,
repairs will be authorized at no charge to the customer parts and/or
labor.
Brass cleaners cannot be used. Mortar
10006326
• Any part and/or component replaced under the provisions of this
warranty is covered for six months or the remainder of the original
warranty, whichever is longest.
• This warranty is limited to the repair of or replacement of part(s) found
to be defective in material or workmanship, provided that such part(s)
have been subjected to normal conditions of use and service, after
said defect is confirmed by the Company’s inspection.
• The company may, at its discretion, fully discharge all obligations
with respect to this warranty by refunding the wholesale price of the
defective part(s)
• Any installation, labor, construction, transportation, or other related
costs/expenses arising from defective part(s), repair, replacement,
or otherwise of same, will not be covered by this warranty, nor shall
the Company assume responsibility for same. Further, the Company
will not be responsible for any incidental, indirect, or consequential
damages except as provided by law.
• SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR
LIMITATIONS OF INCIDENTAL AND CONSEQUENTIAL DAMAGES
OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY
LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR
CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC
RIGHTS AND YOU MAY HAVE OTHER RIGHTS WHICH VARY FROM
STATE TO STATE.
• All other warranties-expressed or implied- with respect to the product,
its components and accessories, or any obligations/liabilities on the
part of the Company are hereby expressly excluded.
• The Company neither assumes, nor authorizes any third party to
assume on its behalf, any other liabilities with respect to the sale of
this Vermont Castings or Majestic product
• The warranties as outlined within this document do not apply to
chimney components or other non CFM Corporation accessories used
in conjunction with the installation of this product..
• Damage to the unit while in transit is not covered by this warranty but
is subject to claim against the common carrier. Contact the dealer
from whom you purchased your fireplace/stove (do not operate the
appliance as this might negate the ability to process the claim with
the carrier).
• The Company will not be responsible for:
a) Down drafts or spillage caused by environmental conditions such
as near-by trees, buildings, roof tops, hills, or mountains.
b) Inadequate ventilation or negative air pressure caused by
mechanical systems such as furnaces, fans, clothes dryers, etc.
• This warranty is void if:
a) The fireplace has been operated in atmospheres contaminated
by chlorine, fluorine, or other damaging chemicals.
b) The fireplace has been subjected to prolonged periods of dampness
or condensation
c) Any damages to the fireplace, combustion chamber, heat exchanger
or other components due to water, or weather damage, which is the
result of but not limited to, improper chimney/venting installation.
d) Any alteration, willful abuse, accident, or misuse of the product
has occurred.
IF WARRANTY SERVICE IS NEEDED…
1) Contact your supplier. Make sure you have your warranty,
your sales receipt, and the model/serial number of your CFM
Corporation product.
2) D O N OT ATTE MPT TO D O ANY SERVIC E WOR K
YOURSELF.
43
Page 44
Efficiency Ratings
Model EnerGuide Ratings Steady State (%) D.O.E. Fireplace Efficiency (%) Fan-OFF Fan-ON (AFUE%)