Lynx LOH60, LOH48, LOH36 User Manual

INSTALLATION INSTRUCTIONS
HOOD MODELS – LOH36, LOH48 & LOH60
IMPORTANT SAFETY INSTRUCTIONS
PLEASE READ ENTIRE INSTRUCTION BEFORE PROCEEDING.
IMPORTANT: Save these Instructions for the Local Electrical Inspector's use.
INSTALLER: Please leave these Installation Instructions with this unit for owner.
OWNER: Please retain these Instructions for future reference
WARNING - TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS, HOODS SHOULD BE INSTALLED WITH VENTILATORS APPROVED FOR USE WITH THE HOOD. SEE TABLE – 1 ON THIS PAGE FOR APPROVED VENTILATORS.
WARNING - TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Installation work and Electrical Wiring
Must Be Done By Qualified Person(s) In Accordance With All Applicable Codes & Standards. Including Fire-Rated Construction. “WARNING” To Reduce The Risk Of Fire, Use Only Metal Duct Work.
B. Sufficient air is needed for proper
combustion and exhausting of gases
CAUTION - TO REDUCE THE RISK OF FIRE AND TO PROPERLY EXHAUST AIR, BE SURE TO DUCT AIR OUTSIDE FOR DUCTED FANS – DO NOT VENT EXHAUST AIR INTO SPACE WITHIN WALLS OR CEILING OR INTO ATTICS, CRAWL SPACES OR GARAGES.
Read this instruction completely before starting installation. Planning the complete installation before starting any work is
highly recommended. This includes all aspects of the installation including hood location, ducting, electrical requirements, and adequacy of mounting surfaces.
TABLE - 1 Model LOHI = Internal ventilator
Model LOHE = Remote ventilator
DUCTING: Use a minimum 10" round duct for LOHI and LOHE installations. See Page – 3. A standard starting transition
(33895) is included with the Hood.
SAFTY WARNING:
Turn off power circuit at the service entrance and lockout panel before wiring the range hood.
through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufactures guideline and safety standard such as those published by the National Fire Protection Association (NFPA) and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
C. When cutting or drilling into wall or
ceiling, do not damage electrical wiring and other hidden utilities.
This hood series has been designed to be used with the ventilators shown in Table – 1. Before cutting into cabinets, it is necessary to confirm that the correct ventilator is being used. Your dealer should have reviewed your needs prior to your purchase. Be sure you have the correct ventilation system. CAUTION: To Reduce The Risk Of Fire And Electrical Shock, Install This Rangehood Only With Blowers Manufactured By Lynx Professional Grills.
D. Ducted fans must always be vented to the
outdoors.
E. Before Servicing or Cleaning Unit,
Switch Power off At Service Panel And Lock Service Disconnecting Means to Prevent Power From Being Switched On Accidentally. When The Service Disconnecting Means Cannot be Locked, securely Fasten A Prominent Warning Device, Such As A Tag, To The Service Panel
NOTE: Unit must be vented
to the outside of the building.
Page 1 of 8 P/N 11857.00 Rev A
BEFORE STARTING INSTALLATION, YOU MUST IDENTIFY THE VENTILATOR MODEL BEING USED AND IF A TOP OR REAR EXHAUST IS TO BE USED.
Prepare cabinet and/or wall for mounting either top (Fig - 1) or rear (Fig 6 & 7) exhaust. Use furring strips to level cabinet mounting surface with any cabinet trims.
For knock out removal see Fig- B
Ventilator Model
Knock out
Remove
Transition
#
#
See Fig
LOHI Top Exhaust 1 33895 1,2,3 LOHE Top Exhaust 1 33895 1,2,3 LOHI Rear Exhaust 2 33895 4,5,6,7
LOHE Rear Exhaust 2 33895 5,6,7
LOHE ventilator will require revision of some wiring in the hood receptacle box - See LOHE instructions.
NOTE: LOHE requires a dedicated 20 AMP Power
Supply. All other ventilators require a dedicated 15 AMP Power Supply
CAUTION: The hood is of sufficient weight that two installers are recommended to prevent injury or damage to the hood in handling.
Turn the power on at the service entrance and check the operation of the controls.
NOTE: be sure that all dampers are operating properly and are free to open.
Break the metal webs by placing a screwdriver at one corner of the plate and hitting screwdriver sharply with a hammer. After breaking a second web the plate can be flexed to break other webs. Wear eye protection when using tools.
RECEPTACLE BOX COVER
Knock Outs
Cover
Caution: When knock outs are removed the edges will be sharp! Sharp Edges should be Filed or Covered with
Hood Top
Metal Tape.
Attach and secure the transition to the hood with #6x3/8 sheet metal screws and tape all joints prior to installing the hood. Attach hood to cabinet using #10 wood screws. Holes are located in the back panel and top panel of the hood for mounting. Use a minimum of four #10x3/4 wood screws to
Hood Wiring Access
Mounting Screw
mount the hood. Longer screws are required if wall board or other nonstructural surfaces are used between the hood and
main mounting surface which should be a minimum of 3/4”
thick. When using rear holes for additional mounting use appropriate anchors if not engaging the wood structure. HINT: If you find vibration noise is present because of
Remove Appropriate Knock Outs and Connect Wiring According to Hood and Blower Installation Instructions. CAUTION: Always Install Receptacle Box Cover.
Fig – A
cabinet structure use additional screws, in holes available, to make the mounting more ridged. Connect 120 volt, 60 Hz power through the conduit hole in
1
top of hood, connecting to pigtail in hood junction box, white to white, black to black and connect green ground wire to the power supply ground wire per local codes. See Fig – A.
2
NOTE: Recommended height over BBQ Grills = 36
inches.
Hood is recommended for use over domestic gas or electric appliances. Not recommended for use over solid fuel fired appliances.
Fig - B
After installing the hood, install the internal blower (Top Exhaust See Fig 2; Rear Exhaust See Fig - 4) unit by positioning the blower onto bracket-A, notched blower bracket will center blower. Rotate into position against hood and secure Bracket – B to Hood with #8 sheet metal screws. If the remote ventilator is used see related instructions. The
Page 2 of 8 P/N 11857.00 Rev A
FIG-1
4"
HOOD MODELS LOHI
TOP EXHAUST
Bottom View Of Cabinet -
Internal Or Remote Blowers
C
5" "A"
L
7-1/8"
7-1/8"
10-1/4"
Hood Width
36" 48" 60"
12"
Dim "A"
10-3/8 14-3/8
20-3/8
FIG-2
Remove Knock Out # 1
Sheet Metal Screws. Tape All Joint & Seams
Air Flow
LOHI
Rotate
Into
Position
& Secure
With 2 Screws
Secure Transition To Hood Using #6 X 3/8"
FIG - 4
Remove Knock Out # 2
LOHI
Rotate
Into
Position
& Secure
With 2 Screws
FIG - 5
Use # 33895 Transition To 10" Duct Or Wall Cap
Route To Outside W/Wall Cap - LOHC
Secure Transition To Hood Using #6 x 3/8" Sheet Metal Screws. Tape All Joints And Seams.
Wiring Access
3/4"
Add Furring Strips To Provide An Even
Bottom Surface For The Hood Mounting
Use # 33895 Transition
To 10" Duct
12"
3"
All Hoods
The 10" Discharge With Transition Will Be On The Center Line Of Hood Width And On Center Line of 12" Dimension.
HOOD MODELS LOHI
REAR EXHAUST
FIG - 6
Bottom View Of Cabinet
Internal Or Remote Blowers
A
5"
B
FIG - 7
10-1/2"
A
Center Of Round Duct Using
Transition
4"
Wiring Access
Add Furring Strips To Provide An Even
Bottom Surface For The Hood Mounting
Rear Exhaust
1-3/4"
Width Of Hood
Back Wall
Vertical Discharge
10" Duct to
Discharge W/Roof Cap
Transition # 33895
30"
C
L Top Of Hood
"A"
3/4"
14-1/2"
7-1/4"
C
L Of Hood
18"
Hood Width
36" 48" 60"
12"
Back Wall
Top Of Hood
7-1/8"
A
18"
Cut Hole In Drywall To Accept Transition # 33895
FIG - 3
Dim "A"
10-3/8 14-3/8 20-3/8
Page 3 of 8 P/N 11857.00 Rev A
Outside Patio or Lanai Installation
Construction methods and installation shall comply with all local building codes. Internal ducting shall be sealed using outdoor rated metal duct tape.
The LYNX hood with stainless steel canopy is approved for installation in an outside patio or lanai area if the area is covered with a protective roof over the hood (wall style hoods are to be also mounted to a solid protective rear wall) and installed with a GFCI protected branch circuit. Roof or Wall Caps are to be sealed to prevent moisture migration to structure interior; use an outdoor rated sealant suitable for adhesion to the installation materials. See Fig-8 for rear exhaust installation and Fig-9 for top exhaust installation.
Wall Cap
A A
B Rear
Exhaust
A = 42" Minimum B = 30" Minimum
Front View
Fig - 8
See Fig – 10 for structure with elevated roof/ceiling.
The Roof shall cover the top of the hood and extend a minimum of 42” from each side of the hood and 30”
minimum from the outer most edges of the hood front. Since, outdoor areas are subject to strong cross drafts it is recommended that the hood extend at least 3 – inches, and
preferably 6 – inches, over either side of the cooking area to maximize the cooking discharge capture area. Cross drafts will affect the efficiency of the ventilation system and cooking discharge can escape capture by the hood/ventilation system. Be sure to plan for adequate ventilator (blower) capacity to minimize cross drafts influencing the removal of cooking discharges.
Side View
Page 4 of 8 P/N 11857.00 Rev A
The installation instruction that accompanies the hood shall be followed to ensure all safety Instructions and guidelines are adhered to. NOTE: Hood is recommended for use over domestic gas or electric appliances. Not recommended for use over solid fuel fired appliances. See Fig-10 for soffit construction
12"
Roof Cap
Soffit
B
A
A
Top
Exhaust
B = 30" MinimumA = 42" Minimum
Front View
Side View
Fig - 9
See Fig – 10 for structure with elevated roof/ceiling.
For installations with elevated Roof/Ceiling use a Soffit, or optional stainless steel extension
Constructed Soffit
MIN
4"
Soffit
B
Top
Exhaust
12"
Hood Widths
B = 30" Minimum
Side View
Soffit Top, Sides & Front Shall Be Enclosed. Fasten To Top Of Hood
Stainless Canopy Extension
Canopy
Extension
Fasten Wall Board Panel To Underside
Of Top Flange
Fasten To Top
Of Hood
Fig - 10
Soffit shall be constructed of materials suitable for outdoor installation and be sealed to prevent moisture migration to structure interior.
Page 5 of 8 P/N 11857.00 Rev A
Loading...
+ 10 hidden pages