- 45 Day Transit Temperature Indicator with display
Description
The LogTag® TICT is a single-trip, low cost electronic temperature indicator for monitoring
temperature and time statistics during the transportation and storage of chilled or frozen products.
The product is made from durable polycarbonate plastic and features an LCD display and a
START/STOP button.
The LogTag TICT can monitor and record statistics against four factory pre-set temperature limits for
up to 45 days, showing OK if environmental conditions remain within. If, however, temperatures
exceed two high temperature alarm limits or go below two low temperature alarm limits, the LCD
shows a REJECT alert, indicating the goods require further checking.
An interface cradle is available so trip statistics can be downloaded and saved for analysis in the
freely available companion software LogTag Analyzer, including trip duration, minimum and maximum
temperatures and exposure to levels outside the alarm limits.
Alerts
After the start delay time has elapsed, the TICT provides a visual alert on the display indicating
OK () or Reject () throughout transport and storage.
Once the indicator has stopped at the completion of the trip, detailed information regarding
temperature and time exposure during transportation and storage is made available via download in
LogTag Analyzer.
The four alarm limits are factory pre-set. Custom configurations can be ordered, allowing clients to
select different alarm limit values, sampling intervals and alert event options such as instant or
delayed reject alerts.
Stored Statistics
Comprehensive statistics are collected and stored on a daily basis and can be downloaded using
LogTag Analyzer.
Run time for the trip (days, hours, minutes). Each day represents a period of 24 hours from
0:00:00 to 23:59:59. Day 1 begins when the start delay has elapsed and the Indicator starts
monitoring. A new day starts when the internal clock advances from 23:59:59 to 0:00:00.
Maximum temperature reached for each day the indicator was running
Minimum temperature reached for each day the indicator was running
The first alarm trigger time and duration for each of the four alarms on each day the indicator
was running. Trigger time is the number of hours and minutes into the current day the alarm
was triggered
OK indicator (). No alarms events have been generated,
load has not been subjected to temperatures outside
specified limits.
Reject alert indicator (). Alarm event has been generated,
as temperatures have been outside specified temperature
limits; load needs to be checked.
Alarm Event Types
HT1
(High Temperature 1)
HT2
(High Temperature 2)
LT1
(Low Temperature 1)
LT2
(Low Temperature 2)
Each of the alarm event types are factory pre-set.
If an alarm event is enabled and the temperatures monitored
generate an alarm, the alert will change from OK to
Reject and the alarm type will be displayed.
Battery Condition
(Battery tested hourly when
running and stopped)
Displayed when the battery test reports OK.
Displayed when the battery test reports low
Operation
READY
When READY is shown, the TICT is ready to be started for a
single trip.
RUN
The Indicator is running and temperature readings are taken.
The display shows the alert indicators (OK or Reject )
and the statistical information is updated every sampling
interval and stored every 24 hours.
STOP
The indicator has been stopped; stored statistics can now be
downloaded.
Start Delay
DELAY
Shown during the Start Delay.
Battery
condition
OK or Low
Alarm
Event
Types
Operating
State
Alert Indicator
OK or Reject
®
Display Overview
- 45 Day Transit Temperature Indicator with display
The TICT Indicator is shipped in a state of low energy
consumption (hibernation) to maximise battery life.
Pressing the START/STOP button will wake the Indicator
and display the battery condition as either OK or Low for 30
seconds. If the button is not pressed again during that time, the
display will turn off and the Indicator will re-enter hibernation.
An Indicator with a low battery cannot be started.
To start the Indicator, press and hold the START/STOP button
for 6 seconds
.
RUN will flash.
When RUN is permanently lit, release the button within
2 seconds.
The indicator now starts the delay countdown, while the display
shows the text DELAY. This delay allows the indicator to
acclimatise to the temperature of the load, so it does not trigger
an alarm too early. This is the reason the indicator should be
placed into the load to be monitored as soon as possible after it
has been started.
If the selected factory pre-set profile does not have a start delay
enabled, the Indicator will start taking temperatures immediately.
As soon as the start delay time has elapsed, the indicator starts
taking temperatures according to the sample interval defined in
the factory pre-set profile.
As long as the temperature readings stay within the limits
defined by the four pre-set alarm events, the OK Alert () is
displayed.
READY
RUN
®
Operation
1. Starting the Indicator
- 45 Day Transit Temperature Indicator with display
If an alarm event is generated, the Reject Alert () is displayed.
Depending on the factory pre-set profile, up to four different
alarm event types are enabled.
HT1 or HT2 alarm events are generated when recorded
temperatures exceed an upper limit for a specified number of
readings. (LT1 and LT2 are the corresponding alarm events for
recorded temperatures below lower limits).
Alarm events can be generated for example by a single
temperature above (below) the limit, or by a number of
sequential or accumulated readings above (below) the
temperature limit. The alarm event types are independent of
each other and are defined in the factory pre-set profile.
To stop the Indicator, press and hold the START/STOP button
for 5 seconds
.
STOP will flash.
When STOP no longer flashes, release the button within
2 seconds.
STOP remains permanently lit and the indicator no longer
processes new temperature values or statistics.
If you release the STOP button before the STOP text becomes
permanently lit, or you do not release the STOP button inside 2
seconds after the STOP text is permanently lit, the unit will not
stop, and the state returns to RUN.
The OK or Reject Alert and any generated alarm events at
the time the indicator was stopped will continue to be available
on the LCD for up to 6 months after the indicator has been
stopped. The display will turn off once stopped, but you can turn
it back on by briefly pressing the START/STOP button.
HT1
LT2
STOP
RUN
®
- 45 Day Transit Temperature Indicator with display
3. Stopping the Indicator
The indicator will automatically stop after the number of days defined in the factory pre-set profile,
typically after 45 days.
If you want to preserve the alert display at the conclusion of a trip shorter than 45 days, you must
manually stop the indicator as soon as it is removed from the load. You must take care doing so, as
the indicator cannot be restarted once stopped.
Please note that downloading the summary statistics with LogTag Analyzer will also stop the
indicator, and no additional readings will be taken or processed.
(Stops the Real Time Clock, increases length of period in
which the unit can be downloaded)
off
on or off
Allow stopping with STOP button
on
on or off
HT1
(High
Temperature
Limit 1)
Monitor this alarm
enabled
enabled or disabled
Temperature limit value
10°C
-25°C to 60°C (-13°F to 140°F)
Alarm activation
instant
instant, accumulated or
consecutive**
Activation delay time
***
N/A
1 minute to 45 days
HT2
(High
Temperature
Limit 2)
Monitor this alarm
enabled
enabled or disabled
Temperature limit value
8°C
-25°C to 60°C (-13°F to 140°F)
Alarm activation
accumulated
instant, accumulated or
consecutive**
Activation delay time
***
12 hours
1 minute to 45 days
LT1
(Low
Temperature
Limit 1)
Monitor this alarm
enabled
enabled or disabled
Temperature limit value
2°C
-25°C to 60°C (-13°F to 140°F)
Alarm activation
accumulated
instant, accumulated or
consecutive**
Activation delay time
***
12 hours
1 minute to 45 days
LT2
(Low
Temperature
Limit 2)
Monitor this alarm
enabled
enabled or disabled
Temperature limit value
0°C
-25°C to 60°C (-13°F to 140°F)
Alarm activation
instant
instant, accumulated or
consecutive**
Activation delay time
***
N/A
1 minute to 45 days
®
- 45 Day Transit Temperature Indicator with display
TICT Factory Pre-sets
LogTag® TICT indicators cannot be client configured, but instead are purchased with one of a number
of different factory configuration profiles pre-installed. If a default configuration does not suit,
customers can compile their own profile by specifying the parameters in the table below when
ordering. Please note that minimum order quantities apply for TICT units with profiles not stocked by
LogTag®.
The default configuration profile is called “Profile 0001”; each custom configuration is assigned a
different profile number which can be used for ordering.
* Preferred intervals are 1, 2, 3, 4, 5, 6, 10, 12 and 15 minutes
** Instant = one temperature reading is above/below limit; consecutive = temperature readings are above/below limit for the time defined in the
activation delay time without interruption (single event); accumulative = temperature readings above/below limit for a total of time defined in
the Activation delay time, but may not necessarily be sequential.
*** Delay times for alarm activations must be in multiples of the sampling interval.
0.1°C or better in range of -20°C to +60°C (temperature shown after download)
Accuracy
±0.5°C (±1.5°F) or better for -10°C to +25°C (+14°F to +77°F).
±1.0°C (±2.0°F) or better for range of -25°C to -10°C (-13°F to +14°F).
±1.0°C (±2.0°F) or better for range of +25°C to +60°C (+77°F to +140°F).
Capacity
Minimum & maximum temperature for each of the 45 days.
1st activation of each alarm for each day including trigger time and duration of
each event.
Please note the TICT does not store each individual temperature reading taken.
Memory type
Non volatile.
Sampling Interval
Factory pre-set between 1 and 59 minutes; 5 minute interval for profile 0001
Recordings
45 day statistics, min/max temperature/time and alarm trigger time/duration for
each day.
Start delay
Factory pre-set between 1 and 255 minutes; 60 minute delay for profile 0001
Sensor
Precision electronic thermistor
Sensor Reaction time
T90 less than 7 minutes by method detailed in EN12830:1999
Vibration
Withstands vibration specification as detailed in EN12830:1999
Shock
Withstands shock specification as detailed in EN12830:1999
Withstand 5 drops 1m to smooth concrete floor without loss of function or
calibration.
Environmental
IEC 60529: IP64
Resistance to Electrical Storms
Designed to resist the effects of intense electrical storms.
Power source
Internal 3V Lithium Li-Mg – non replaceable
Battery life
Minimum storage life of 18 months before ‘start’.
Monitoring period: 45 days.
Minimum accessibility (display) period of 6 months after ‘stop’
Size
71.5mm(W) x 33.0mm(H) x 8.6mm(T)
Weight
23g.
Case Material
Polycarbonate
Warranty
One year replaceable warranty against defects in materials and workmanship
from the date of purchase. Excludes misuse or abuse of the product or as a
result of unauthorized alteration or repairs.
Calibration
Certificate of Traceability and Calibration to ISO/IEC17025 available on request.
EMC compliance
EC EMC directives (EN 61000-6-1:2005 & EN 61000-6-3:2006)
Including electrostatic discharge as prescribed in EN 61000-4-2.
Complies with FCC Part 15 Subparts A and B.
Alarm events
Four factory pre-set alarm events, two over temperature and two under
temperature.
Each alarm event can be instant reject or accumulative reject. It can also be
disabled.
Alert indication
OK = Temperature has remained within the alarm limits.
Reject = Alarm event has been generated
Display is static allowing photocopying.
®
Product Specifications
- 45 Day Transit Temperature Indicator with display