Lochinvar SPS0250 Installation Manual

SL-PS-I-O Rev B
Solar Pump Station
Installation and Operation
Manual
SPS0250, SPS0500 & SPS1000
WARNING:
Save this manual for future reference.
This manual must only be used by a qualified heating installer/ service technician. Read all instructions, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
Contents
HAZARD DEFINITIONS .................................................... 2
1. GENERAL INFORMATION
Included components ..................................................... 3-4
2. INSTALLING THE SOLAR STATION
Installing the solar station on a wall ................................... 5
Installing the relief valve ..................................................... 5
Installation, wall bracket for expansion tank ...................... 5
Installation, connection lines to tank and collector ............ 5
Piping .......................................................................... 5
Clamp ring screw connections ................................... 5
3. TECHNOLOGY, INSTALLATION AND COMMISSIONING
Clamp ring screw connections .......................................... 6
Operation, multi-function ball valve and check valve .......... 6
4. COMMISSIONING THE SOLAR SYSTEM
General .............................................................................. 7
Flat seal screw connections .............................................. 7
Filling, flushing and bleeding ............................................. 7
5. PRESSURE LOSS AND RESIDUAL
DELIVERY HEIGHT ..................................................... 8
6. VFS FLOW SENSOR .................................................. 9
7. TECHNICAL DATA FOR SOLAR STATION ........ 10-11
8. COMPONENT BREAKDOWN
SPS0250 ......................................................................... 12
SPS0500 ...........................................................................12
SPS1000 ...........................................................................13
9. SERVICE
Air separator .................................................................... 14
Flat seal screw connections ............................................ 14
Clamp ring screw connections ........................................ 14
Disassembling the solar station ........................................14
Draining the system .......................................................... 14
10. FAULTS, CAUSES AND RECTIFICATIONS
Pump doesn’t run when power is switched on .................15
Motor blocked ....................................................................15
Pump noise .......................................................................15
Revision Notes ................................................. Back Cover
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
CAUTION
CAUTION
NOTICE
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
2
1 General Information
SL-PS Installation & Operation Manual
WARNING
WARNING
WARNING
WARNING
Before starting work, the Installer must read, understand and note these installation and operating instructions.
The solar pump station may only be installed and maintained by trained professionals. Trainees may only work on the product under the supervision of an experienced person.
All instructions in this Installation & Operation manual should be observed when using the solar station. No other form of use is intended.The manufacturer is not liable for any damage resulting from misuse of the solar station. For safety reasons, modifications or changes are not permitted.
The solar station must be installed as far away from the collectors as possible. Extremely high temperatures may occur in the pipes near the collectors. If installing in attic space, ensure that the instruments do not overheat.
The pressure / temperature operating parameters must be within the prescribed limits. Excess operating temperatures should be avoided for continuous operation.
The provisions stated in DIN EN 12976-1 should be observed when installing solar systems.
The expansion tank should be regularly checked according to DIN 4807.
Solar systems should be grounded to protect against lightning.
The system’s electrical connection for sensors and voltage supply should only be established by a
trained professional. The relevant specifications (VDE 0100, VDE 0185, VDE 0190 etc.) should be observed as well as special local (construction) requirements. (Grey cable = tank, black cable = collector)
WARNING
WARNING
WARNING
WARNING
The solar pump station’s componentry varies depending on type and equipment.
The diagrams used are examples.
Subject to technical changes and further developments.
A properly sized expansion tank must be used to avoid damage to the solar thermal system.
Thermal expansion tanks should be sized to account for 1.5 times the solar system circuit volume.
The expansion tank may be hot, ensure that scalding does not occur.
Failure to heed these instructions, especially the safety instructions, can result in the destruction of and defects on the expansion tank, endanger persons, and impair the operation.
3
1 General Information
SL-PS Installation & Operation Manual
Included Components
Solar Station:
Grundfos solar circulation pump
VFS sensor (flow sensor)
145 psi relief valve, with pressure gauge
Multi-function instruments (Flow Check, Thermometer,
Fill Valve)
EPP two-part bracket with mounting kit
Installation kit:
Wall and tank bracket with mounting kit
Solar Control unit:
LCD Plus solar control unit with integrated energy balance function.
2 collector and 2 tank sensors Pt 1000
Technical documentation:
Figure 1-2 SPS1000
Operation and installation instructions (with appendix) for pump and solar control unit.
Figure 1-1 SPS0250/ SPS0500
4
2 Installing the solar station
SL-PS Installation & Operation Manual
Installing the solar station on a wall
Remove front insulation shell.
The solar pump station forms a single unit with the wall
bracket and rear insulation shell. Secure both components as a complete unit at the intended location, working the front and using anchors and screws suitable for the wall construction type.
Installing the relief valve
The solar station is equipped with a solar safety relief valve which meets the relevant requirements.
Fit the enclosed relief valve to the outlet of the return instruments above the pump using the 3/4" union nuts. A gasket is enclosed with the solar station for use when installing the relief valve.
The enclosed discharge connection bracket should be fitted to the safety valve so that there is no risk of scalding should liquid escape. Follow local codes for drainage piping.
The following information should be noted:
The safety valve must be easily accessible.
Installation, wall bracket for expansion tank: (Lochinvar/TiSUN accessories)
Fit the wall bracket for the expansion tank (if equipped) to the right of the solar station.
Ensure that the corrugated stainless steel hose is long enough for the connection between the pump station and the expansion tank, not forgetting the expansion coupling.
Installation, connection lines to tank and collector
A) Piping
Connect the lines between the solar pump station and tank.
Connect supply and return lines to the collectors.
B) Clamp ring screw connections
Refer to Section 3: Technology, installation and commissioning,
on page 6.
No valves should be placed between relief valve and pump station. The relief valve should be piped to a suitable drain as close as possible to the pump station with no reducing couplings or other restrictions. The piping must be sloping away from the pump station at all times.
Dirt traps or other constrictions are not permitted between the collectors (field) and safety valve.
5