Lochinvar SPS0250 User Manual

Page 1
Solar Pump Station and Differential Control
3 Models - Covering up to 1000sq.ft. of Collector Area
Complete System Control
Variable Speed Pump
Built-in Differential Control w/ Pump Control
2 Year Limited Warranty
Page 2
®
Commercial Solar Pumping Stations
The Lochinvar/TiSUN Commercial Solar Pump Station, complete with Differential Solar Control is an all in one solar pumping package. Standard features include a differential control with eight different system capabilities, variable speed pump, air separator, flush and fill valves, safety group, and EPP two piece insulation. Lochinvar can provide the right pump station to meet almost any solar pumping need.
Available in three sizes, capable of providing flow through up to 1000 square feet of collector area, the Commercial Solar Pump Station can provide adequate flow through many different size collector arrays.
How it works...
The Lochinvar/TiSUN Commercial Solar Pump Station with Solar Differential Control constantly monitors the collector temperature and the tank temperature. As the tank temperature cools below setpoint and the difference between the two temperatures reaches a field adjustable setpoint, the differential control will start the circulation pump. If the variable speed pump feature is utilized the solar differential control will adjust the speed of the pump to achieve the highest temperature difference between the collector and the tank.
This large temperature difference will harvest the solar heat in the most efficient manner possible. If the constant flow feature is used the pump will operate at a steady speed. The pump will continue to operate until the tank reaches its desired temperature or there is no longer sufficient difference between the collector and the tank temperature to heat the tank.
Outstanding Features
SD Card
Graphical LED Interface with Backlight
Data Logging with SD Card
Two Collector Sensors
Two Tank Sensors
Electronic Flow Sensor
BTU Metering
8 System Functionality
- One or Two Collector Fields
- One or Two Tanks
- Two Pumps, One Diverter Valve
3 Outputs, 2 For Pump Speed Regulation
(PWM Signal)
Impulse Flow Sensor Input
SD Software
Supply/Return Multi-Function Valve with Thermometer and Check Valve
EPP, Two Part Insulation Shell
EPP Heat Insulation
145 PSI Relief Valve
Pressure Gauge
Fill and Flush Valve with Shut-off
Variable Speed Circulation Pump
Fill and Flush Valve with Shut-off
VFS Flow Sensor
Page 3
Selectable System Configurations
The differential control has eight preset system types that can be selected to match control logic to system type. For example if you had one collector array and one tank the control scheme would match System 1. There is a preset system program for different system types.
System 1
T1
System 3
T1
System 5
T1
System 2
Basic system with 1 tank, 1 pump, 1 collector array,
T1
and 2 sensors.
Extra functionality can be added with 1 or 2 sensors for booster
T2
pump, thermostat, cooling, differential control or
T2
anti-stagnation.
System with 2 tanks, 1 pump, 1 diverter valve, 1 collector array, and 3 sensors.
Extra functionality can be added with 1 sensor for thermostat, cooling or anti-stagnation.
T4
System 4
System with 2 tanks, 2 pumps, 1 collector array, and 3 sensors.
Extra functionality can be added with 1 sensor for thermostat, cooling or anti-stagnation.
T2
T4
T1
T4
System with 1 tank, 1 pump, 1 diverter valve, 2 collector arrays, and 3 sensors.
Extra functionality can be added with 1 sensor for thermostat, cooling or anti-stagnation.
T2
System 6
T4
System with 1 tank, 2 pumps, and 2 collector arrays, and 3 sensors.
Extra functionality can be added with 1 sensor for thermostat, cooling or anti-stagnation.
T2
T1
System with 1 pump, 1 tank, 1 collector array, 1 diverter valve, and 4 sensors.
T3
T2
Extra functionality can be added
T4
with 1 sensor for thermostat, cooling or anti-stagnation.
System 7
T1
System with 1 tank, 2 pumps, 1 collector array, 1 external heat exchanger, and 2 sensors.
Add extra functionality with 1 sensor for thermostat, cooling, anti-stagnation or differential
T2
control.
System 8
T1
System with 1 tank, 2 pumps, 1 collector array, 1 external heat exchanger, and 3 sensors.
Extra functionality can be added with 1 sensor for thermostat, cooling or anti-stagnation.
T4
T2
Extra Programmable Functions
In addition to the eight preset system types, the Lochinvar/TiSUN Solar Pump Station with Differential Control has four extra functions that can be added to many of the system types to expand the system’s functionality. Extra functions include a thermostat output for enabling an external heat source, a cooling function for keeping the tank at a usable temperature during times of high solar radiation, an anti-stagnation function to keep the collector at a usable temperature during times of low or no hot water demand, and a differential control function that can be used to prioritize the heat distributed to additional heat loads.
Cooling
T1
T3
P1
P3
T2
Cooling function for keeps the tank at a usable temperature during times of high solar radiation
Differential Control
T1
P1
T3
T2
T4
P3
Differential control function that can be used to prioritize the heat distributed to additional heat loads.
Thermostat
T1
P1
Anti-Stagnation
T1
P3
P1
Thermostat output enables an external heat source.
T3
P3
T2
Anti-stagnation function to keep the collector at a usable temperature during times of low or no hot water demand.
T2
Page 4
Solar Pump Station Dimensions
5"
14"
4-1/2"
1" WATER CONNECTIONS
1/2" WATER CONNECTIONS
7-1/4"
12"
1-12"
9-3/4"
1-3/4"
Models SPS0250 & SPS0500
14"
5"
Models SPS1000
1/2" WATER CONNECTIONS
4-1/2"
3/4" WATER CONNECTIONS
12-1/4"
1-1/2"
7-1/2"
9-3/4"
1-3/4"
4-1/2"
SPS-01
Max. Collector Connection Pump Model Area Served Size Model
SPS0250 250 ft2 3/4” UPS 28/88U
2
SPS0500 500 ft SPS1000 1000 ft
3/4” UPS 25/99U
2
1” UP 25/120U
2 year limited warranty
V
N
I
H
C
O
L
L
E
B
A
N
O
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com
FG-10M-9/10–Printed in U.S.A.
O
C
R
P
R
O
A
R
A
T
I
O
N
E
E
S
S
E
N
N
N
,
E
T
Loading...