Lochinvar Space Saver Booster, SSB-s-01 Installation Manual

Electric booster water heaters are available for operation on standard power systems. Check the nameplate for the proper power supply.
All internal electrical connections have been made at the factory. See Circuit Breaker and Fuse Sizing Chart for supply wire size, fuse, breaker and conduit recommendations.
AL CONNECTIONS
1. Locate the heater terminal or fuse block(s) in the control box. The control box is under the front hinged jacket cover.
3. A grounding lug is provided near the supply terminals. An equipment grounding conductor must be properly connected to it.
4. Replace and secure cover(s).
For the most effective operation install the booster heater as close as possible to the dishwasher.
TEMPERATURE AND PRESSURE RELIEFVALVE
For protection against excessive pressures and temperatures in the booster heater, install temperature and pressure protective equipment required by local codes. The manufacturer supplies valves constructed with brass working parts and heat resistant silicone seat discs for all booster heater models.
Temperature/pressure protective equipment should not be less than a combination temperature/pressure relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of the production of this equipment and meets the requirements for Relief Valves and Automatic Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22-latest edition. The temperature/pressure relief valve must be marked with a minimum set pressure not to exceed the marked hydrostatic test pressure of the booster heater.
Valves supplied by manufacturer are designed for high temperature commercial operation. Do not substitute OEM valves with valves designed for domestic water heaters.
WARNING !!
To assure proper operation and avoid a possible unsafe condition, the booster heater must be installed in a horizontal position with the base parallel to the floor and the inlet connection at the lowest point.
WARNING !!
Employ recirculation if distance between booster and dishwasher exceeds NSF specifications.
NOTE:
PLUMBING INSTALLATION
INSTRUCTIONS
Do not turn on power to booster heater until the tank has been filled with water and all air has been vented through the dishwater rinse nozzle. The heating elements will burn out in seconds if operated when they are not immersed in water, unless the heater is equipped with a low-water cutoff (LWCO).
CAUTION !!
ELECTRICAL CONNECTIONS
The main power circuit must be disconnected prior to performing any maintenance on the booster heater to avoid possible personal injury or damage to the heater.
WARNING !!
For proper electrical installation conforming to local electrical codes, consult a licensed electrical contractor.
WARNING !!
ELECTRICAL INSTALLATION
INSTRUCTIONS
1
INSTALLATION AND SERVICE MANUAL
SSB-i&s--01
SPACE SAVER BOOSTER
PRESSURE REDUCING VALVE
Proper operation of the dishwater rinse nozzles requires available water pressure at the nozzle be between 15 and 25 psi when nozzle is operated. 20 psi is recommended.
If water pressure available to the booster heater inlet is over 20 psi, a pressure reducing valve should be mounted in the hot water supply line to the booster heater.
The pressure reducing valve supplied by the manufacturer has a built-in high pressure by-pass which prevents excessive pressure build­up as the booster heats up.
TEMPERATURE/PRESSURE GAUGES
Manufacturer recommends a temperature/pressure gauge be installed in both the inlet and outlet lines to the booster heater. These gauges provide an instant visual check of the water temperature and pressure entering the booster heater and leaving the heater. The visual check is helpful in eliminating unnecessary service calls.
WARNING:
INLET
Connect the booster heater water inlet to a hot water supply line from the regular water heater. Water temperature from the regular water heater should be 100°F or 140°F (52°C or 60°C) and should not exceed 160°F (71°C). Minimum temperature differential between inlet and outlet temperatures should never be less than 20°F (11°C). Provide the inlet line with a shut-off valve, a full open gate or ball type valve, together with a pressure reducing valve. Set pressure reducing valve at 20 psi (1.4 kg/cm2) flow pressure.
A 3/4 in. union fitting and a drain valve are needed for easy servicing.
Be sure water flows through the pressure reducing valve in the proper direction. Check directional arrow. Valve will reduce pressure only during flow conditions.
NOTE:
Do not connect the heater directly to a boiler or furnace coil or any other uncontrolled temperature source. Such hook-up could cause the thermostat to lose control and the unit could overheat.
WARNING !!
To avoid development of a leak, do not back up or loosen any pipe fittings.
CAUTION !!
PLUMBING CONNECTIONS
The valves are set to relieve at 150 psi orwhen water temperature reaches 210°F (99°C). Read tag on valve for additional information.
CAUTION !!
For Installing Temperature and Pressure Relief Valves in accordance with American National Std. Z21-22 latest edition. Combination temperature and pressure relief valves with extension thermostats must be installed so that the temperature-sensing element is immersed in the water within the top 6" (152 mm) of the tank. They must be installed eitherin the hot outlet service line or directly in a tank tapping. Combination temperature and pressure relief valves that do not have extension elements must be mounted directly in a tank tapping located within the top 6" (152 mm) of the tank, and shall be adequately insulated and located so as to assure isolation from flue gas heat or other ambient conditions that are not indicative of stored water temperature. To avoid water damage or scalding due to valve operation, drain pipe must be connected to valve outlet and run to a safe place of disposal. Drain pipe must be as short as possible and be the same size as the valve discharge connection throughout its entire length. Drain line must pitch downward from the valve and terminate at least 6" (152 mm) above the floor drain where any discharge will be clearly visible. The drain line shall terminate plain, not threaded, with a material serviceable for temperatures up to 250ºF(121ºC) orgreater. Excessive length, over 15' (4.57m), or use of more than two elbows can cause a restriction and reduce the discharge capacity of the valve. No shut-off valve shall be installed between the relief valve and tank, orin the drain line. Valve lever must be tripped periodically to insure that waterways are clear. This device is designated for emergency safety relief and shall not be used as an operating control. Do not use an antisiphon or check valve on the incoming water line.
CAUTION !!
2
OUTLET
Using a 3/4 in. union and piping connect the booster heater water outlet to the dishwasher sanitizing rinse pipe connection.
Install a temperature/pressure gauge in outlet line. Water temperature at outlet should be 180°F (82°C).
The temperature sensing element
must be in water stream.
Manufacturer recommends a shock absorber be installed in the outlet line as close as possible to the dishwasher The shock absorber softens the water hammer caused by automatic dishwasher valves.
INSTALLATION CHECK
1. Close drain pipe valve and fill booster heater with water.
2. Check all pipe connections for installation leaks.
3. Check relief valve dischar ge opening to be certain it is not blocked.
4. Vent air from tank before operating.
WATER REACHES 180ºF (82ºC), BUT DOES NOT MAINTAIN 180ºF THROUGH THE ENTIRE DISHWASHINGOPERATION.
CAUSE A
Low incoming temperature, particularly during peak operational periods, is the most common cause of this condition. If incoming temperature is correct at the start of the dishwashing operation, check again at the end. It is possible for the supply of 140ºF (60ºC) water to be exhausted during the washing cycle.
SOLUTION
- If incoming temperature is 140ºF (60ºC) at the start of the washing cycle, but falls below at the end, the primary water heater is not delivering sufficient 140ºF (60ºC) water and the condition is correctable with installation of a commercial primary water heater model of the correct size. Contact your representative to assure proper sizing of the primary heater.
CAUSE B
If incoming water temperature is correct and it holds through the dishwashing operation, another possible reason for this condition is that the water pressure may be too high. Water pressure to the dishwasher must be approximately 20 psi for proper operation of the booster and dishwasher rinse cycle.
SOLUTION -
If pressure exceeds 20 psi with the dishwasher rinse valve open, install a pressure reducing valve with built in bypass check.
CAUSE C
The booster may be undersized.
SOLUTION -
Check the dishwasher model with the sizing
guide to be sure the correct booster has been installed.
CAUSE D
The booster may have been ordered with improper voltage.
SOLUTION
-
Consult specifications plate on the booster. Voltage and amperage are clearly marked. Check this infor­mation against the service to which it is connected. If heater was incorrectly specified consult factory for instructions.
CAUSE E
A low voltage condition may exist. Low voltage is a common cause on large model heaters.
SOLUTION
- Verify wire size and circuit for the application.
THE BOOSTER HEA TER DOES NOTHEATATALLOR ONL Y DELIVERS 130-150ºF (54ºC - 66ºC) WATER.
CAUSE A
Sometimes upon completion of an installation, the booster operation is checked by energizing the heater before the tank is completely filled with water. When elements of the immersion type are not completely covered by water at the time the heater is turned ON, the high temperature in the tank may damage the element(s) unless the unit has been equipped with a low water cut-off.
SOLUTION
- Damaged elements must be replaced.
CAUSE B
Fuses may be blown or circuit breaker tripped.
SOLUTION
- Inspect the fuses or circuit breaker and refer to data sheet for the booster model installed. If undersized fuses or circuit breakers were installed, replace with size recommended in the data sheet. See Section “Booster repeatedly blows fuses or trips circuit breakers.”
Thermostats should also be inspected. Elements damaged by overheating in “dry” environment can easily damage thermostats.
NOTE:
BOOSTER HEATER SERVICE
PROCEDURES
Leave tank filled with water during electrical hookup to prevent possible element burnout.
CAUTION !!
INSTALLATION CHECK
Be certain the connection is made to the final rinse and not to the wash tank.
NOTE:
Do not run a cold water line to the heater.
NOTE:
3
CAUSE C
Thermostats may not be functioning correctly or may be improperly set.
SOLUTION
- Inspect thermostats for proper operation and correct settings. If setting is below the maximum, reset to 190ºF(88ºC) If defective and not functioning, replace.
CAUSE D
Contactors are not performing.
SOLUTION
- Inspect contactors for proper operation by visual observation. Assuming no fuses are blown and power is coming to the booster, inspect the coil and replace if defective.
CAUSE E
ECO (high temperature limit switch) may be defective.
SOLUTION
- Check for proper operation and replace if
defective.
CAUSE F
The fuse is blown.
SOLUTION
- Replace fuse. If fuse continues to blow, either a contactor coil is defective, or the booster control transformer is defective. If booster has more than one contactor, disconnect wires so only one contactor at a time is energized. The defective one can then be isolated and replaced.
On all boosters with low water cut-off, the following trouble shooting procedures apply.
CAUSE G
Relay does not pull in after booster is filled with water and air bled out.
SOLUTION
1. Check for voltage at line terminals 1 and 2 using volt-meter or test light. If there is no voltage, refer to CAUSE F.
2. Open circuit between ground and the probe. Check for broken wire or poor contact at connections. To test, run temporary wires from probe terminal #3. If relay pulls in, the wire is broken and should be replaced.
3. Check or open relay coils. With line voltage applied at 1 and 2, connect a jumper wire between 6 and 7. Relay should pull in when the jumper is connected and fall out when the jumper is removed. Failure to do so indicates one of the coils is open and the relay should be replaced.
4. Fouled probe. If solution 2 discloses no broken wire or poor connection and relay still does not pull in, probe tip may be insulated by lime buildup. If relay operates when a jumper wire is connected between terminals 3 and ground, the probe is fouled. Remove probe and clean the electrode.
TEMPERATURE REACHES ONLY 170-175ºF (77ºC - 79ºC). THIS CONDITION AS DIFFERENTIATED FROM CONDITION II INDICATES THE BOOSTER HEATER IS FUNCTIONING, BUT MAY NOT BE REACHING PROPER TEMPERATURE (180ºF, 82ºC).
CAUSE A
Booster should be close to the dishwasher, (5 feet or less). If the booster is more than 5 feet away, the heat loss through the pipes is the most likely reason the dishwasher thermometer reads only 170ºF
(77ºC). Make certain the thermostats are set to their maximum calibration. They are pre-set at the factory to 190ºF (88ºC) to compensate for heat loss but they may have been turned down to 180ºF (82ºC) by someone overlooking heat loss through the pipes.
SOLUTION
- The booster should be moved to within 5 feet of the dishwasher if possible, and the pipes should be insulated.
CAUSE B
Thermostats may not be functioning correctly.
SOLUTION
- If maximum reading is below 180ºF, (82ºC) first turn the pointers all the way up on all thermostats. If the reading is still below 180ºF (82ºC), minor adjustments can be made on the thermostats. If recalibration does not help, the thermostat is defective and should be replaced.
BOOSTER HEA TER REPEATEDLYBLOWS FUSES OR TRIPS CIRCUIT BREAKERS.
CAUSE A
Fuses are undersized-too small to carry the load.
SOLUTION
- Check “Fuse and Disconnect Switch Sizes” table for recommended sizes. Replace undersized fuses with correct one.
CAUSE B
Short circuit in internal heater wiring.
SOLUTION
- By visual inspection check for: loose connections, grounded heating elements, frayed insulation and foreign matter touching wiring terminals.
WHEN THE DISHWASHER AND THE BOOSTER HAVE BEEN IDLE FOR SEVERAL HOURS, RELIEF VALVE OPENS OR ECO TRIPS.
CAUSE A
A cause of overheating and resulting relief is excessive primary water temperature. Primary water temperature should not exceed 160ºF (71ºC).
SOLUTION
- Check to be sure primary water heater is functioning properly. Primary water heater thermostats may be set too high, causing nuisance tripping. Adjust primary heater thermostats to 140-150ºF (60ºC - 66ºC).
Fuses or circuit breakers should not be loaded to more than 80% of their rating.
NOTE:
To help determine this cause, check rinse temperature in the dishwasher. Since the dishwasher temperature gauge could become defective, it is preferable to rely on a temperature sensitive tape or a thermometer rather than the gauge for checking this cause.
NOTE:
4
Loading...
+ 8 hidden pages