Lochinvar RPV-S Service Manual

INSTALLATION & SERVICE MANUAL
RPV-I&S
POWERED VENT GAS WATER HEATER
WARNING
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
FOR YOUR SAFETY Do not store or use gasoline or other flammable, combustible, or corrosive vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any telephone in your building.
• Immediately call your gas supplier from a neighbor’s telephone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
For your family’s comfort, safety and convenience we recommend water heaters to be installed and serviced by a plumbing professional.
TABLE OF CONTENTS
GENERAL INFORMATION............................................................1
Locating The Water Heater ................................................2
Minimum Clearances ..........................................................3
Venting ..............................................................................3
Specifications for
48 Gal, 65,000 BTU input (189.3 L, 19.1 kW/Hr) 65 Gal, 65,000 BTU input (246.1 L, 19.1 kW/Hr)
75 Gal, 76,000 BTU input (283.9 L, 22.3 kW/Hr) .............4
Specifications for
40 Gal, 40,000 BTU input (151.4 L, 11.7 kW/Hr)
48 Gal, 40,000 BTU input (189.3 L, 11.7 kW/Hr) .............5
Combustion Air Supply..............................................................7
Water Connections ....................................................................8
Gas Connections........................................................................9
Electrical Connections................................................................9
Wiring Diagram for
48 Gal, 65,000 BTU input (189.3 L, 19.1 kW/Hr)
65 Gal, 65,000 BTU input (246.1 L, 19.1 kW/Hr)
75 Gal, 76,000 BTU input (283.9 L, 22.3 kW/Hr) .............10
Wiring Diagram for
40 Gal, 40,000 BTU input (151.4 L, 11.7 kW/Hr)
48 Gal, 40,000 BTU input (189.3 L, 11.7 kW/Hr) .............11
GENERAL OPERATION................................................................9
Lighting and Shutdown Instructions.....................................12
Thermostat Adjustment .........................................................12
Burner Flame Check................................................................12
MAINTENANCE ...........................................................................13
INSTALLATION INSTRUCTIONS FOR POTABLE WATER AND
SPACE HEATING .........................................................................14
VENT PIPE PREPARATION AND JOINING ....................................14
GENERAL INFORMATION
This gas-fired water heater’s design is certified by CSA International under the
American National Standard Z21.10.1 - (as indicated on the rating plate) and CSA 4.1-M - (as indicated on the rating plate).
This water heater must be installed in accordance with local codes or, in the absence of local codes, the National Fuel Gas Code, ANSI Z223.1-Latest Edition) and/or in Canada CAN/CGA B149 Installation Codes (Latest Editions). The warranty for this water heater is in effect only when the water heater is installed, adjusted, and operated in accordance with these Installation and Operating Instructions. The manufacturer will not be held liable for any damage resulting from alteration and/or failure to comply with these instructions.
This water heater is not design certified for installation in a mobile home. Such an installation may create a hazardous condition and will nullify the warranty.
CAUTION
Incorrect operation of this appliance may create a hazard to life and property and will nullify the warranty.
Do not use this appliance if any part has been submerged in water. You should contact a qualified service technician to inspect the appliance and to replace any part of the control system including the combination gas control which has been submerged in water.
DANGER
Do not store or use gasoline or other flammable, combustible, or corrosive vapors and liquids in the vicinity of this or any other appliance.
IMPORTANT
Before proceeding, please inspect the water heater and components for possible damage. DO NOT install any damaged components. If damage is evident then please contact the supplier where the water heater was purchased or the manufacturer listed on the rating plate for replacement parts.
Make sure that you check the rating plate and combination gas control on the water heater to be certain that the type of gas being supplied corresponds with the marking on the rating plate and combination gas control.
A sacrificial anode is used to extend tank life. The removal of this anode, for any reason, will nullify the warranty. In areas where water is unusually active, an odor may occur at the hot water faucet due to a reaction between the sacrificial anode and the impurities in the water. If this should happen, an alternative anode may be purchased from the supplier that installed this water heater. This will minimize the odor while protecting the tank. Additionally, the water heater should be flushed with appropriate dissolvers to eliminate any bacteria.
1
RPV-I&S
INSTALLATION
Locating The Water Heater
WARNING
Water heaters are heat producing appliances. To avoid damage or injury there shall be no materials stored against the water heater or vent-air intake system and proper care shall be taken to avoid unnecessary contact (especially by children) with the water heater and vent-air intake components. UNDER NO CIRCUMSTANCES
SHALL FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THIS WATER HEATER, VENT-AIR INTAKE SYSTEM OR IN ANY LOCATION FROM WHICH FUMES COULD REACH THE WATER HEATER OR VENT-AIR INTAKE SYSTEM.
DO NOT install the water heater in any location where gasoline or flammable vapors are likely to be present.
Water Heaters in residential garages must be installed so that all burner(s) and burner ignition device(s) are located not less than 18 inches (46 cm) above the floor and must be located or protected to avoid physical damage. For other installations refer to local codes. In the absence of local codes, the water heater must be installed in compliance with the National Fuel Gas Code, ANSI Z223.1 - (Latest Edition) and/or in Canada, CAN/CGAB149 Installation Codes (Latest Editions).
The location of this water heater is of the utmost importance. Before installing this water heater, read the installation section of these instructions. After reading these installation and operating instructions, select a location for the water heater where the floor is level and is easily accessible to gas and water supply lines. DO NOT locate the water heater where water lines could
be subjected to freezing temperatures. Make sure the cold water pipes are not located directly above the gas control so that condensate during humid weather does not drip on the controls.
Water heater corrosion and component failure can be caused by the heating and breakdown of airborne chemical vapors. Examples of some typical compounds that are potentially corrosive are: spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes and process chemicals. These materials are corrosive at very low concentration levels with little or no odor to reveal their presence. NOTE: DAMAGE TO THE WATER HEATER CAUSED BY
EXPOSURE TO CORROSIVE VAPORS IS NOT COVERED BY THE WARRANTY. DO NOT OPERATE THE WATER HEATER IF EXPOSURE HAS OR WILL OCCUR. DO NOT STORE ANY POTENTIALLY CORROSIVE COMPOUNDS IN THE VICINITY OF THE WATER HEATER.
WARNING
Liquefied petroleum gases/propane gas are heavier than air and will remain at floor level if there is a leak. Basements, crawl spaces, closets and areas below ground level will serve as pockets for accumulation of leaking gas. Before lighting, smell all around the appliance area for gas. Be sure to smell next to the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
DO NOT OPERATE APPLIANCE UNTIL LEAKAGE IS CORRECTED!
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE
WARNING
NOT CERTAIN OF THE FOLLOWING:
• Liquefied petroleum gases/propane gas and natural gas have an odorant added by the gas supplier that aids in the detection of the gas.
• Most people recognize this odor as a “sulfur” or “rotten egg” smell.
• Other conditions, such as “odorant fade” can cause the odorant to diminish in intensity, or “fade”, and not be as readily detectable.
• If you have a diminished sense of smell, or are in any way unsure of the
presence of gas, immediately contact your gas supplier from a neighbor’s
telephone.
• Gas detectors are available. Contact your gas supplier or plumbing professional, for more information.
The water heater must be located close enough to the outside wall to keep the venting distance within the maximum distance described in the installation instructions. Read the venting section in this installation instruction manual before locating the water heater.
This water heater must be located in an area where leakage of the tank or water line connections and the combination temperature and pressure relief valve will not result in damage to the area adjacent to the water heater or to lower floors of the structure. When such locations cannot be avoided, a suitable drain pan adequately piped for proper drainage must be installed under the water heater. The drain pan must not restrict combustion air flow. The drain pan must be no greater than 1-½ inches (3.8 cm) deep and have a minimum length and width of at least four (4) inches (10.2 cm) measured from the jacket of the water heater. The drain pan, as described above, can be purchased from your plumbing professional. The drain pan must be piped to an adequate drain. The piping must be at least 3/4 inch (1.9 cm) in diameter and pitched for proper drainage.
It is recommended that a minimum clearance of four (4) inches (10.2 cm) be provided on the side of the water heater for servicing and maintenance of the combination temperature and pressure relief valve.
MINIMUM CLEARANCES
WARNING
Failure to adhere to these installation and operating instructions may create a hazard to life and property and will nullify the warranty.
This installation must allow access to the front of the water heater and adequate clearance must be provided for servicing and operating this water heater. The water heater may be installed on either a combustible or non-combustible floor. If the water heater is to be installed directly on carpeting, it must be installed on top of a metal or wood panel extending beyond the full width and depth of the appliance by at least three (3) inches (7.6 cm) in any direction or, if the appliance is to be installed in an alcove or closet, the entire floor must be covered by the panel. The minimum clearances to combustibles for this water heater are: zero (0) inch (0 cm) from the sides and rear, five (5) inches (12.7 cm) from the front of the jacket, zero (0) inch (0 cm) from the vent connector and fifteen (15) inches (38.1 cm) from the jacket top.
VENTING
This venting section is divided into two parts. Part I will cover venting specifications for 48 Gal - 65,000 BTU (181.7 L - 19.1 kW/ Hr), 65 Gal -65,000 BTU (246.1 L - 19.1 kW/Hr), and 75 Gal -
2
RPV-I&S
76,000 BTU (283.9 L - 22.3 kW/Hr) models. Part II will cover venting specifications for 40 Gal - 40,000 BTU (151.4 L - 11.7 kW/ Hr) and 48 gal - 40,000 BTU (181.7 L - 11.7 kW/Hr) models. Refer to the rating plate located on the water heater for correct model identification.
The National Fuel Gas Code ANSI Z223.1-(Latest Edition), CGA/CAN B149 Installation Code, and local codes have specific requirements for the location of the vent terminals on vertical walls. The guide lines listed below are from the National Fuel Gas Code. Consult the local codes, and/or National Fuel Gas Code ANSI Z223.1-(Latest Edition), or CGA/CAN B149 Installation Code to determine if there are any additions or changes to the following specifications.
(A) The vent terminal must terminate at least 3 feet (.91 m) above any
forced air inlet duct located within 10 feet (3 m). Exception: This provision shall not apply to the combustion air intake of a direct vent appliance.
(B) The vent terminal must terminate at least 4 feet (1.2m) below, 4 feet
(1.2 m) horizontally from, or 1 foot (0.31 m) above any door, window, gravity air inlet into the building.
(C) The bottom of the vent terminal must be located at least 1 foot
(0.31 m) above ground and above the anticipated snow level.
(D) The vent terminal must not terminate over a public walkway or over an
area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valve, or other equipment.
(E) The water heater location must provide easy access for the entire
length of the vent connector.
(F) The vent system must be inspected at least once a year to ensure
against leakage of exhaust products.
In order to effectively control condensate from adversely affecting the mechanical components of the water heater several methods may be employed:
1. For horizontal installations the vent pipe can be installed with a downward slope (not less than 1/8" nor greater than 1/2” per foot maximum) and away from the blower motor.
2. In order to prevent condensate from draining back into the blower (vertical or horizontal runs), a fitting and drain hose is available as a condensate trap kit (see Table 1 for service part numbers). The all rubber fitting with drain outlet mounts directly to the blower motor outlet and is secured with two hose clamps (one to the blower motor outlet and the other to the vent connector). The plastic tubing is provided to drain any accumulated condensate away from the water heater and to a suitable drain. The kit comes complete with instructions for proper installation of the fitting.
Table - 1
Model Service Part
2" (5.1 cm) Blower Outlet (exhaust) DRV1200 3" (7.6 cm) Blower Outlet (exhaust) DRV1201
3. In order to prevent condensate from draining back into the blower (vertical or horizontal runs), a drain tee and condensate trap can be installed in the horizontal vent as close as practical to the blower vent connection (see Figure1). The condensate disposal tube should be installed to drain any accumulated condensate away from the water heater and to a suitable drain. The drain tee and condensate hose should be available through your local distributor.
Exceptions For Installations in Canada:
(A) The vent terminal must be located at least 1 foot (0.31 m) from any
window or door which can be opened in any building, any non-mechanical air supply inlet to any building, or the combustion air to any inlet other appliance.
(B) The vent terminal must be located at least 6 feet (1.8 m) from any
mechanical air supply inlet to the building.
(C) The vent terminal must not terminate above a meter/regulator
assembly within 3 feet (0.91 m) horizontally of the vertical center line of the regulator and must be at least 6 feet (1.8 m) from any gas service regulator vent outlet.
(D) The vent terminal must be at least 7 feet (2.1 m) above a paved
sidewalk or a paved driveway located on public property.
(E) The vent terminal must not terminate above a paved sidewalk or a
paved driveway, which is located on private adjacent property.
VENTING SYSTEM CONDENSATION
Condensate formation does not occur in all installations of power vented heaters, but should be protected against on installations where condensation can form in the venting system.
Formation of condensation in the venting system of Power Vented water heaters is dependent upon installation conditions including, but not limited to:
1. Ambient temperature and humidity of installation location;
2. Ambient temperature and humidity of venting space; vent distance and slope;
3. And product usage.
Figure 1
Part I - Venting Specifications for:
48 Gallon, 65,000 BTU input (181.7 L, 19.1 kW/Hr) 65 Gallon, 65,000 BTU input (246.1 L, 19.1 kW/Hr) 75 Gallon, 76,000 BTU input (283.9 L, 22.3 kW/Hr)
This water heater is a power vented appliance and is designed to vent its products of combustion through 3" (7.6 cm) or 4" (10.2 cm) diameter Schedule 40 (solid or cellular core) PVC pipe to the outdoors. This water heater may be either vented through the wall or vertically through the roof. Use a 3" (7.6 cm) to 4" (10.2 cm) reducer to connect to the vent outlet when using 4" (10.2 cm) PVC. Table 2 lists the maximum vent lengths for this water heater using 3" (7.6 cm) PVC. If possible, locate the water heater so that the venting length and number of elbows are kept to the minimum distance necessary to reach the outside. If the installation requires venting lengths that exceed the lengths listed for 3" (7.6 cm) PVC in Table 2, then use 4" (10.2 cm) PVC for the vent connector. Table 3 lists the venting distances allowed with 4" (10.2 cm)
3
RPV-I&S
diameter PVC pipe. When venting with 4" (10.2 cm) PVC, use a 4" (10.2 cm) to 3" (7.6 cm) reducer to exit through the building wall with 3" (7.6 cm) PVC. Use the 3" (7.6 cm) vent terminal supplied with the water heater to terminate on the outside of the building. If the length of 3" (7.6 cm) PVC needed to go through the wall is greater than 14" (35.5 cm), use 4" (10.2 cm) to go through the wall and reduce to 3" (7.6 cm) PVC immediately after exiting the outside wall. Refer to the venting illustrations on the following pages. Make sure the vent pipe terminal elbow fitting is at least 1" (2.5 cm) away from the edge of the wall.
TABLE - 2
VENT CONNECTOR LENGTHS FOR 3" (7.6 cm) DIAMETER PVC
Terminating # of 90° Elbows Maximum Minimum
(excluding vent Length Length
terminal)
Through the Wall 1 40 ft (12.2 m) 2 ft (.6 m) Through the Wall 2 35 ft (10.7 m) 3 ft (.9 m) Through the Wall 3 30 ft (9.1 m) 5 ft (1.5 m) Through the Wall 4 25 ft (7.6 m) 8 ft (2.4 m) Through the Roof 1 40 ft (12.2 m) 2 ft (.6 m) Through the Roof 2 35 ft (10.7 m) 3 ft (.9 m) Through the Roof 3 30 ft (9.1 m) 5 ft (1.5 m) Through the Roof 4 25 ft (7.6 m) 8 ft (2.4 m)
IMPORTANT
All of the Venting connections must be leak checked with a soap and water solution upon initial start up of the water heater. Any leaks must be repaired before continuing operation of the water heater.
NOTE: ABS or CPVC pipes may be substituted for PVC pipe. Do not mix ABS and PVC pipe in the same installation.
THROUGH THE WALL VENTING:
Cut a 3-1/2 inch (8.9 cm) diameter hole in the wall at the point where the vent connector is going to pass through the wall. Use the proper cement to secure the 90° vent terminal provided with the water heater to the vent connector. The distance between the edge of the 90° vent terminal and the exterior wall (see Figure 3) must be 1 inch (2.5 cm). Use the proper cement and assembly procedures to secure the vent connector joints between the terminal and the blower outlet. Provide support brackets for every 3 feet (.91 m) of horizontal vent.
TABLE - 3
VENT CONNECTOR LENGTHS FOR 4" (10.1 cm) DIAMETER PVC
Terminating # of 90° Elbows Maximum Minimum
(excluding vent Length Length
terminal)
Through the Wall 1 70 ft (21.3 m) 2 ft (.6 m) Through the Wall 2 65 ft (19.8 m) 3 ft (.9 m) Through the Wall 3 60 ft (18.3 m) 5 ft (1.5 m) Through the Wall 4 55 ft (16.8 m) 8 ft (2.4 m) Through the Wal 5 50 ft (15.3 m) 12 ft (3.6 m) Through the Roof 1 70 ft (21.3 m) 2 ft (.6 m) Through the Roof 2 65 ft (19.8 m) 3 ft (.9 m) Through the Roof 3 60 ft (18.3 m) 5 ft (1.5 m) Through the Roof 4 55 ft (16.8 m) 8 ft (2.4 m) Through the Roof 5 50 ft (15.3 m) 12 ft (3.6 m)
NOTE: When using 4" (10.1 cm) PVC, use a 4" (10.1 cm) to 3" (7.6 cm) reducer and exit the building wall with 3" (7.6 cm) PVC using the
3" (7.6 cm) 90° vent terminal supplied. Two 45° elbows are equivalent to one 90° elbow.
Figure 2
Figure 3
THROUGH THE ROOF VENTING: (VERTICAL VENTING)
Cut the necessary holes through the roof and ceiling and install the vent connector as shown in Figure 4. Make sure that the installation meets the local codes and/or The National Fuel Gas Code ANSI Z223.1 (Latest Edition) or CGA/ CAN B149 Installation Code.
Figure 4
4
RPV-I&S
NOTE: For installations requiring both horizontal and vertical runs, the following rule must be followed: Total number of feet of straight pipe (both horizontally and vertically) must not exceed the allowable length listed in the “Through The Wall” section of the table for total number of elbows used. Also: Total number of vertical feet of straight pipe must not exceed the allowable length listed in the “Through The Roof” section of the table for total number of elbows used. For angular rises in venting, any angle that is greater than or equal to 45° from the horizontal should be considered a vertical rise.
THROUGH THE WALL VENTING WITH LOW GROUND CLEARANCE:
When venting cannot exit through the wall at a height greater than or equal to 12" (30.5 cm) above the ground, or anticipated snow level, the installation must be modified as shown below (see Figure 5). Refer to Table 4 for maximum venting lengths using 3" (7.6 cm) PVC or Table 5 for maximum lengths using 4" (10.1 cm) PVC.
Figure 5
TABLE - 4
3" (7.6 cm) PVC VENT CONNECTOR LENGTHS FROM INSIDE WALL
FOR LOW GROUND CLEARANCE INSTALLATIONS
Terminating # of Maximum Minimum
Elbows Length Length
(2) 90° Elbows with (1) 90° Elbow 1 30 ft (9.1 m) 5 ft (1.5 m) (2) 90° Elbows with (1) 90° Elbow 2 25 ft (7.6 m) 6 ft (2 m) (2) 90° Elbows with (1) 90° Elbow 3 20 ft (6.1 m) 8 ft (2.5 m) (2) 90° Elbows with (1) 90° Elbow 4 15 ft (4.6 m) 10 ft (3 m)
TABLE - 5
4" (10.1 cm) VENT CONNECTOR LENGTHS FROM INSIDE WALL
FOR LOW GROUND CLEARANCE INSTALLATIONS Terminating (Reduce 4" to 3") # of Maximum Minimum (Reduce 10.1 cm to 7.6 cm) Elbows Length Length
(2) 90° Elbows with (1) 90° Elbow 1 60 ft (18.3 m) 10 ft (3 m) (2) 90° Elbows with (1) 90° Elbow 2 55 ft (16.8 m) 12 ft (3.7 m) (2) 90° Elbows with (1) 90° Elbow 3 50 ft (15.2 m) 15 ft (4.6 m) (2) 90° Elbows with (1) 90° Elbow 4 45 ft (13.7 m) 18 ft (5.5 m) (2) 90° Elbows with (1) 90° Elbow 5 40 ft (12.2 m) 22 ft (6.7 m)
HIGH ALTITUDE INSTALLATIONS FOR ELEVATIONS OVER 3,000 FEET (914.5 m) ABOVE SEA LEVEL
The capacity of the induced draft blower declines with increasing altitude due to a reduction in the air density. In order to assure safe and reliable performance
of the water heater, the following guidelines must be followed. Refer to the venting tables below for maximum distances for the altitudes in your location.
TABLE - 6
HIGH ALTITUDE LENGTHS
Altitude Max. venting Max. venting Modifications to above length reduction length reduction water heater sea level from tables from tables
0-3,000 ft
(0-914.5m)
over 3,000­10,000 ft
(914.5-3048m)
2 & 4 3 & 5
No reduction in vent length required
No reduction in vent length required
No reduction in vent length required
No reduction in vent length required
None
Requires high altitude Kit. Call the supplier or the manufacturer
Part II - Venting Specifications for:
40 Gallon, 40,000 BTU input (151.4 L, 11.7 kW/Hr) 48 Gallon, 40,000 BTU input (189.3 L, 11.7 kW/Hr)
This water heater is a power vented appliance and is designed to vent its products of combustion through 2" (5.1 cm) or 3" (7.6 cm) diameter Schedule 40 (solid or cellular core) PVC pipe to the outdoors. The water heater may be either vented through the wall or vertically through the roof. Use a 3" (7.6 cm) to 2" (5.1 cm) reducer to connect to the vent outlet when using 3" (7.6 cm) PVC. Apply PVC cement at PVC locations. Table 7 lists the maximum vent lengths for this water heater using 2" (5.1 cm) PVC. If possible, locate the water heater so that the venting length and number of elbows are kept to the minimum distance necessary to reach the outside. If the installation requires venting lengths that exceed the lengths listed for 2" (5.1 cm) PVC in Table 7 then use 3" (7.6 cm) PVC for the vent connector. Table 8 lists the venting distances allowed with 3" (7.6 cm) diameter PVC pipe. When venting with 3" (7.6 cm) PVC, use a 3" (7.6 cm) to 2" (5.1 cm) reducer to exit through the building wall with 2" (5.1 cm) PVC. Use the 2" (5.1 cm) vent terminal supplied with the water heater to terminate on the outside of the building. If the length of the 2" (5.1 cm)needed to go through the wall is greater than 14" (35.6 cm), use 3" (7.6 cm) PVC to go through the wall and reduce to 2" (5.1 cm) PVC immediately after exiting the outside wall. Refer to the venting illustrations on the following pages. Make sure the vent pipe terminal is at least 1" (2.5 cm) away from the edge of the wall. To vent horizontally with zero (0) elbows, remove 3 screws from blower housing and rotate the blower housing 90° clockwise (see Figure 7). Replace the three (3) screws once blower housing rotation is complete.
TABLE - 7
VENT CONNECTOR LENGTHS FOR 2" (5.1cm) DIAMETER PVC
Terminating # of 90° Elbows Maximum Minimum
(excluding vent Length Length
terminal)
Through the Wall 0 45 ft (13.7m) 2 ft (.6 m) Through the Wall 1 40 ft (12.2m) 2 ft (.6 m) Through the Wall 2 35 ft (10.7m) 2 ft (.6 m) Through the Wall 3 3 0 ft (9.2 m) 2 ft (.6 m) Through the Wall 4 25 ft (7.6 m) 3 ft (.9 m) Through the Roof 0 31 ft (9.5 m) 3 ft (.9 m) Through the Roof 1 28 ft (8.5 m) 3 ft (.9 m) Through the Roof 2 25 ft (7.6 m) 3 ft (.9 m) Through the Roof 3 22 ft (6.7 m) 3 ft (.9 m) Through the Roof 4 19 ft (5.8 m) 4 ft (1.2 m)
5
Loading...
+ 11 hidden pages