Lochinvar RJC006E User Manual

EXPLOSION-RESISTANT
WATER HEATER
Submittal Sheet
CER-Sub-02
EXPLOSION-RESISTANT COMMERCIAL ELECTRIC WATER HEATERS
JOB NAME ______________________________________________________________________ LOCATION ______________________________________________________________________ ARCH./ENGR.____________________________________________________________________ WHOLESALER __________________________________________________________________ MECH. CONTRACTOR ___________________________________________________________ MODEL NO. _____________________________________________________________________ RECOVERY RATE IN GPH_______________________________________@_________° RISE GALLON CAPACITY_____________________________________________________________ VOLTAGE/PHASE________________________________________________________________ kW_____________________________________________________________________________ NOTES
Standard Features
• Non-CFC Foam Insulation
• High Quality Thermostats
• Magnesium Tank Saver Anode
• Dip Tube
• 300 PSI Tested Tank, 150 psi Working Pressure
• Temperature & Pressure Relief Valve
• Glass-Lined Steel Tank
• Explosion-Resistant Heating Elements
• 3 Year Limited Tank Warranty (See warranty for details)
Optional Equipment
Place an X in the box by all options that apply
Double Element Construction
Six Way Mounting Shelf (6 & 12 Gallon Models)
Explosion-Resistant Commercial Electric Water Heater Dimensions & Specifications
T&P
Outlet Inlet
T&P (Optional)
Junior Models
Tall and Short Models
Model Gallon Shipping Number Capacity A B D Weight
Junior Models
RJC006E 6 16-1/2” 14” 10-1/4” 43 RJC012E 12 27-3/4” 14” 21-1/4” 58 RJC020E 19 24-3/4” 18” 18-1/4” 69
Tall Models
RTA030K 30 47” 18” – 95 RTA040K 40 47” 20” – 113 RTA052K-T 50 57-1/2” 20” 133 RTA052K 50 46-1/2” 22” – 140 RTA066K 65 59-1/4” 22” – 166 RTA082K 80 59” 24” – 193 RTA120K 119 63-3/4” 28” 315
Short Models
RSA030K 30 29-3/4” 22” 24” 106 RSA040K 40 31-3/4” 24” 24-1/4” 135 RSA050K 50 31-3/4” 26” 24-1/4” 163
Notes: Water connections are 3/4” NPT on all models. (RTA120 is standard with 1” water connections) Standard for Short and Tall models: 4500 watts, 240V 1ø. Junior models: 1500 watts, 120V 1ø.
8"
B
Note: Diagram above depicts optional double element availability. (Short and Tall models only).
6"
VOLTAGE
SCHEDULE
C – 120V 1ø J – 208V 1ø A – 240V 1ø V – 480V 1ø
ELEMENT/WATTAGE SCHEDULE
Recovery Rate (GPH @ °F Rise)
Element Wattage 40 50 60 70 80 90 100
E 1500 16 12 10 9 8 7 6 K 4500 47 37 31 27 23 21 19 P 6000 62 50 41 35 31 28 25
A
D
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com
7/11—Printed in U.S.A.