Lochinvar PFN1500PM User Manual

Page 1
POWER-FIN
®
PACKAGE SYSTEM
Submittal Sheet
PFEP-Sub-03
POWER-FIN®GAS WATER HEATERS (1.5, 1.7 & 2.0 MBH MODELS)
Standard Features
• 87% Thermal Efficiency
• 25-100% Infinitely Proportional Firing Rate
• Digital Display w/ Alarm & Status LED’s
• Variable Frequency Drive
• Digital Temperature Control Accurate to 1ºF
• Tamper Resistant Temperature Controls
• Alcromesh Burner with 5-Year Limited Warranty
• Low NOx Operation Exceeds the most Stringent Air Quality Requirements
• Selectable Inlet/Outlet Temperature Controls
• ASME Copper Finned Tube Heat Exchanger
• 160 psi Working Pressure
• Gasketless Heat Exchanger Design
• All Bronze Circulating Pump
• Pump Delay
• Freeze Protection
• Glass-Lined Water Surfaces
• Low Gas Pressure Operation
• Zero Clearance to Combustible Materials
• ASME Temperature & Pressure Relief Valve
• Down Stream Test Valve
• Adjustable High Limit with Manual Reset
• Flow Switch
• Small Footprint
• 24 Volt Circuit Breaker
• Construction Air Filter
• 5 Year Limited Warranty on Heat Exchanger
Optional Equipment
Place an X in the box by all options that apply
Alarm Bell Contacts on any Failure Contacts for Air Louvers Cupro-Nickel Heat Exchanger High Gas Pressure Switch w/ Manual Reset Low Gas Pressure Switch w/ Manual Reset
Low Water Cut-Off
Probe Type Probe Type w/ Manual Reset
HARMONY SEQUENCER
Control
Part Number 1-4 Unit Master Control Module SMP2100 5-12 Unit Extension Module SMP2101
Harmony Sequencer Ordering Information
Sequencing of up to 4 Units requires the following:
1 - SMP2100 Master Control Module
Sequencing of 5 - 12 units requires the following:
1 - SMP2100 Master Control Module
and 1 - SMP2101 Extension Module
Firing Control Systems
M9 HSI (Standard) M13 GE GAP/FM/IRI M7 California Code
Page 2
Power-Fin®Gas-Fired Water Heater Dimensions & Specifications
Venting Options
Electrical Requirements
Heater 15 Amp Circuit Required Pump 15 Amp Circuit Required
*When combined both heater and pump can operate
on a 20 Amp circuit.
Model Btu/hr GPH @ Air Vent Shipping
Number Input 100°F Rise A D E F Inlet Size Size Weight
PFN1500PM 1,500,000 1,582 66-3/4" 52-1/4" 42" 44-1/2" 6" 8" 1,165 PFN1700PM 1,700,000 1,793 71-1/4" 56-3/4" 46-1/2" 49" 7" 8" 1,225 PFN2000PM 2,000,000 2,109 78” 63-1/2" 53-1/4" 55-3/4" 8" 10" 1,325
Notes: Change ‘N’ to ‘L’ for LP Gas Models. No deration on LP models. Performance data is based on manufacturer test results. All gas connections are 1-1/2" NPT. All water connections are 2-1/2".
DirectAire Vertical w/ Sidewall Inlet
DirectAire Horizontal w/ Rooftop Inlet
Direct Vent Vertical
Direct Vent Horizontal
Sidewall
Vertical
Intelligent Venting Solutions
Page 3
Power-Fin®Gas Water Heater Package System Dimensions & Specifications
V1 Configuration H1 Configuration H2 Configuration
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com
2/07—Printed in U.S.A.
HORIZONTAL TANK DIMENSIONS
Gallons H
T
W
T
D
T
Weight
300 50-1/2” 78-1/4” 42-1/4” 1,700 400 50-1/2” 102-1/4” 42-1/4 ” 2,250 500 56-1/2” 90-3/4” 48-1/4” 2,450 600 56-1/2” 114-1/4” 48-1/4 ” 3,350 700 56-1/2” 130-1/4” 48-1/4 ” 4,000
800 62-1/2” 124-1/4” 54-1/4 ” 4,800 1,000 62-1/2” 138-1/4” 54-1/4” 5,100 1,250 68-1/2” 130-1/4” 60-1/4” 5,900 1,500 77-1/2” 126-1/4” 66-1/4” 6,500 2,000 80-1/2” 138-1/4” 72-1/4 ” 9,000 2,500 86-1/2” 144-1/4” 78-1/4 ” 10,000
VERTICAL TANK DIMENSIONS
Gallon H
T
Dia. Weight
119 62-1/2 ” 28” 345 200 77-1/4” 32” 600 257 92” 34” 902 318 81” 40” 993 432 81” 46” 1,269 504 92” 46” 1,373
NOTE: Add heater dimensions to tank dimensions to get overall package dimensions or consult factory if measure­ments are critical.
All package systems are skid mounted.
V1, H1 & H2 Configurations are standard with Round Jacketed Tanks
28"