Lochinvar PFN0751PM User Manual

Page 1
500,000 to 1, 300,000 Btu/hr
Less Than 30 ppm NOx
Up to 87% Thermal Efficiency
High Efficiency Commercial Gas Water Heaters
Page 2
The High-Efficiency, High-Output Compact Water Heater
What's more, unit inputs range as high as 1,300,000 Btu/hr but require just 4.6 sq. ft. of floor space. Only the Power-Fin-with its high efficiency output-can offer such heavyweight performance in a water heater so compact. Plus, with new venting capabilities, the Power-Fin is even more flexible in installation. And it is easy to see how the Power-Fin is performing thanks to a new digital control panel.
Outstanding Thermal Efficiency
Power-Fin water heaters offer up to 87% thermal efficiency and a NOx rating of less than 30 ppm by way of fan-assisted sealed combustion. This means that 87¢ out of every fuel dollar goes into heating the water - dramatically reducing operating costs of the water heater while ensuring clean combustion.
The heat energy from the combustion process is transferred to the water as it passes through the solid copper finned tube heat exchanger. The sealed combustion design eliminates external heat losses, which means that the fuel dollars are used to heat the water, not the mechanical room. It also ensures the jacket stays cooler, providing greater safety and requiring less clearance from combustibles
- zero clearance on each side.
First Power-Fin production model - 1986
DirectAire Vertical w/ Sidewall Inlet*
Vents vertically up to 50 equivalent feet, and directly draws combustion air 50 equivalent feet from a side wall.
Vertical
Vents vertically through the roof.
Sidewall*
Vents horizontally up to 50 equivalent feet, using Category IV approved vent material.
Direct Vent Horizontal*
Vents horizontally up to 50 equivalent feet, using Category IV approved vent material. Directly draws combustion air 50 equivalent feet from a side wall.
Direct Vent Vertical
Vents vertically up to 50 equivalent feet, and directly draws combustion air 50 equivalent feet from the roof top.
DirectAire Horizontal w/ Rooftop Inlet*
Vents horizontally up to 50 equivalent feet, using Category IV approved vent material. Directly draws combustion air 50 equivalent feet from the roof top.
Power-Fin Venting Options
These new models also feature a more flexible two pipe, independent air inlet and exhaust vent piping. When equipped with On/Off firing controls the Power-Fin utilizes Category I, Type B vent material in most cases. When equipped with modulating fire controls the heater utilizes Category IV, AL29-4C corrosion resistant, sealed vent pipe. Factory supplied vent kits are required for some venting configurations - see below.
Modulating (M9) models require Category IV vent material in any venting configuration. On/Off (F9) models require Category IV vent materials when exhausting through a sidewall. Consult I&O manual for exact specifications. *Requires factory supplied vent kits
Exhaust Vent Reducer
Available for installation with Category IV vent systems, the Vent Reducer kits allow the vent diameter of eachPower-Fin model to be reduced by as much as 45%. The vent reducer is made from AL29-4C corrosion resistant material. Because the reduction in vent size creates a “positive” pressure, all reduced vent systems are classified as Category IV systems requiring corrosion resistant, sealed vent pipe.
Reduced Vent Sizes
PFN0501 7” to 4” PFN0751 9” to 5” PFN1001 10” to 6” PFN1300 12” to 8”
Page 3
Designed for Reliability
Lochinvar pioneered gasketless heat exchanger technology in 1989 with the Mini-Fin Boiler. Now we're bringing the same advantages to our vertical chassis Power-Fin - giving you a one piece header design with no gaskets or o-rings to crack and leak. This gasketless design provides enhanced reliability, improved durability and optimizes performance. We're so confident in its performance, we back it up with a 5 year limited warranty against failure and a lifetime warranty against thermal shock.
The interior and exterior of all heat exchangers is
coated with a porcelain glass lining to prevent
external corrosion and provide
clean and clear potable water.
Copper-finned tubes are extruded from a thick copper tube, creating a heating transfer ratio 9 times greater than
regular copper tube - allowing
maximum heat transfer.
Gasketless Heat Exchanger
To ensure fail-safe operation, every major function of the Power-Fin is automatically controlled and checked by a digital control panel with advanced diagnostic features. The large display is easy to read and makes set up's a snap. The digital display, accurate to +/- 1°F, indicates temperature while the LED indicators prove operation and status. This monitoring system not only warns against failures, it can actually help to pinpoint the source of any problems, leading to faster solutions. In addition, all of the components are field replaceable, so down time is reduced.
Modulation with 4:1 Turndown
and Category IV Venting
87% Thermal Efficiency
On/Off Firing
and Category I Venting
85% Thermal Efficiency
On/Off Firing – Standard
Modulating – Optional
Page 4
Time Tested Performance wit
ASME Copper-Finned Tube Heat Exchanger
Gasketless design by the company who pioneered the gasketless heat exchanger. ASME construction built to 160 psi working pressure. Finned copper tubes transfer heat nine times faster than regular copper.
Combustion Air Filter
Creating cleaner combustion the standard size filter is easily replaced by removing from back of the unit.
Service Friendly Design
Power-Fin is designed for easy service and maintenance.
Slide Out Control Panel
For easy and convenient access to controls.
Firing Control System
On/Off (F9) firing is provided as standard equipment. Modulating (M9) with 4:1 turndown is available as an option.
Hot Surface Ignition
Eliminates the need for a standing pilot. Utilizes the latest and most reliable technology in ignition and flame rectification.
Fan Assembly
The Combustion Air Fan draws a precise ratio of gas and air into the combustion chamber based on heat load and
injects the mixture into
a 360° ceramic
burner, which contributes to
the overall quiet operation
of the appliance.
Field Electrical Connections
All models require (2) two 120V, 15 Amp single phase connections for heater and pump operation. Single 30 Amp service may be used.
360° Ceramic Burner
At the center of the combustion chamber is the highly flexible and efficient Power-Fin ceramic burner. The new ceramic burner allows for perfectly even gas and air distribution which results in a NOx Rating of less than 30 ppm - far exceeding the most stringent air quality standards. What's more - the Power-Fin burner is perfect in installations with low supply gas pressure, operating without hesitation as low as four inches of water column.
Page 5
Ultimate Flexibility
Lochinvar's unique "engineered systems" approach to water heating provides the flexibility to match the heating unit (or units) with the exact size and capacity storage tank that is needed for any given application.
For example: Use a low output Power-Fin with a large tank for short term, high draw situations, or team a
high-output water heater with a small tank for applications where the demand is almost constant. Whatever the need, Lochinvar has a Lock-Temp tank to match it-from our 119 gallon vertical to the 2500 gallon horizontal model.
Each package system can be custom-configured to the exact specifications and available space of each job. These Power-Fin package systems are pre-engineered, pre-piped, pre-tested and shipped pre-assembled on "I-Beam" skids ready for installation.
Package System Configurations & Dimensions
V1 Configuration H1 Configuration H2 Configuration
H3 Configuration
HORIZONTAL TANK DIMENSIONS
Gallons H
T WT DT Weight
300 50-1/2 ” 78-1/4” 42-1/4” 1,700 400 50-1/2 ” 102-1/4” 42-1/4” 2,250 500 56-1/2 ” 90-3/4” 48-1/4 ” 2,450 600 56-1/2 ” 114-1/4” 48-1/4 ” 3,350 700 56-1/2 ” 130-1/4” 48-1/4 ” 4,000
800 62-1/2 ” 124-1/4” 54-1/4 ” 4,800 1,000 62-1/2” 138-1/4” 54-1/4 ” 5,100 1,250 68-1/2” 130-1/4” 60-1/4 ” 5,900 1,500 77-1/2” 126-1/4” 66-1/4 ” 6,500 2,000 80-1/2 ” 138-1/4” 72-1/4 ” 9,000 2,500 86-1/2 ” 144-1/4” 78-1/4 ” 10,000
VERTICAL TANK DIMENSIONS
Gallon H
T Dia. Weight
119 62-1/2” 28” 345 200 77-1/4” 32” 600 257 92” 34” 902 318 81” 40” 993 432 81” 46” 1,269 504 92” 46” 1,373
NOTE: Add heater dimensions to tank dimensions to get overall package dimensions or consult factory if measurements are critical.
All package systems are skid mounted.
H3 configuration is offered with Square Jacketed Tank only.
V1, H1 & H2 Configurations are standard with Round Jacketed Tanks
Power-Fin water heaters are custom packaged with our
Lock-Temp tank(s) to meet your exact specifications.
All package systems are completely pre-piped,
pre-tested and shipped on a pre-assembled
I-beam skid – ready for installation.
28"
Page 6
Power-Fin® Water Heater Dimensions & Specifications
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com
PF-09 (Replaces PF-09 2/06)
1/07-Printed In U.S.A.
Standard Features
Up to 87% Thermal Efficiency
Aquastat with Adjustable Differential
Sequential & Diagnostic Control Panel
Radial Ceramic Burner
Digital Display with Alarm Status LEDs
Low NOx Operation Exceeds the most
Stringent Air Quality Requirements
ASME Copper Finned Tube Heat Exchanger
Gasketless Heat Exchanger Design
160 psi Working Pressure
All Bronze Circulating Pump
ASME Temperature & Pressure Relief Valve
Remote Tank Thermostat
Glass-Lined Water Surfaces
Digital Temperature Gauges
Combustion Air Filter
Slide Out Control Panel
Redundant Gas Valves
Hot Surface Ignition
Pump Delay
Freeze Protection
Zero Clearance to Combustible Materials
Adjustable High Limit w/ Manual Reset
Flow Switch
Flame View Port
Small Footprint
24 Volt Control System
5 Year Limited Warranty
on Heat Exchanger (See warranty for details)
Optional Equipment
Alarm Bell
Contacts for Air Louvers
Contacts on any Failure
Cupro-Nickel Heat Exchanger
High and Low Gas Pressure Switch
Low Gas Pressure Switch
Low Water Cut-Off w/ Manual Reset
MP
2
Sequencer (F9 models only)
Harmony Sequencer (M9 models only)
Vent Diameter Reducer
Available Firing Systems
F =On/Off M=Modulating
F9 HSI (Standard) M9 Hot Surface Ignition
with Modulation F/M13 GE GAP/FM/IRI F/M7 California Code
GPH @ Shipping
Model Btu/Hr 100°F Rise D Gas Air Vent Wt.
Number Input (F9) (M9) A (F9) (M9) E F G H I J Conn. Inlet Size (lbs)
PFN0501PM 500,000 515 527 44-1/2” 5-1/4” 3-1/4” 7-3/4” 11-1/4” 33-3/4” 2-1/4” 23-1/4” 6-3/4” 1” 5” 7” 571 PFN0751PM 750,000 773 791 52-1/4” 5-1/4” 3-1/4” 7-3/4” 11-1/4” 41-1/4” 9-3/4” 30-3/4” 7” 1-1/4” 5” 9” 620 PFN1001PM 1,000,000 1,030 1,054 59-1/4” 4-1/4” 3-1/4” 7-3/4” 11-1/4” 48-1/2” 16-3/4” 37-3/4” 7-1/4” 1-1/4” 6” 10” 669 PFN1300PM 1,300,000 1,323 1,371 67-3/4” 4-1/4” 3-1/4” 7-3/4” 19-1/2” 57” 25-1/4” 46-1/4” 8-1/4” 1-1/4” 6” 12” 718
Notes: Change "N" to "L" for LP Gas Model. No deration on LP Gas Models.
Water Connections are 2-1/2" on 6" centers. Performance Data Based on Manufacturer Test Results.
FOR EASE IN ORDERING
BY MODEL NUMBER
PF N 0501 PM F9
This is a 500,000 Btu/hr
natural gas Power-Fin water
heater with F9 firing controls.
Firing
Controls
Pump
Mounted
Natural Gas
Model
MBH Input