Lochinvar PFL0502PM User Manual

POWER-FIN
®
WATER HEATER
Submittal Sheet
PFX-Sub-03b
POWER-FIN® GAS WATER HEATER 502, 752, 1002, 1302, 1501, 1701 & 2001 MODELS
JOB NAME ______________________________________________________________________ LOCATION ______________________________________________________________________ ENGINEER______________________________________________________________________ MECH. CONTRACTOR ___________________________________________________________ MODEL NO. _____________________________________________________________________ TYPE GAS ______________________________________________________________________ Btu/hr INPUT____________________________________________________________________ RECOVERY RATE IN GPH_______________________________________@________°F RISE NOTES
Standard Features
> Up to 87% Thermal Efficiency (M Models)
> Modulating Burner with 5:1 Turndown
> Up to 84% Thermal Efficiency (B/F)
> Modulating Burner with 2:1 Turndown (B
Models)
> On/Off Burner (F Models)
> Fan Assisted Sealed Combustion
> Hot Surface Ignition > Low NOx Operation > Low Gas Pressure Operation
> Venting Flexibility
> Category I (B & F) > Category IV Venting (M) > Optional Combined Venting Cat. II (M)
> ASME Copper-Finned Tube Heat Exchanger
> ASME Certified, “HLW” Stamped > 150 psi ASME T & P Relief Valve > Gasketless design > 160 psi working pressure > On/Off Switch > Adjustable High Limit w/ Manual Reset > Flow Switch > Low Air Pressure Switch > Flue Temperature Sensor > Downstream Test Cocks > Combustion Air Filtration > All Bronze Circulating Pump > Zero Clearances to Combustible Material > 1 Year Warranty on Parts > 5 Year Limited Warranty (See Warranty for Details)
> SMART SYSTEM Operating Control
> 2 line, 16 Character Display > Dual Level Password Security > Built in Cascading Sequencer for
up to 8 Water Heaters
> Building Management System Integration
with 0-10 VDC Input > Low Water Flow Safety Control & Indication > Inlet & Outlet Temperature Readout > Product Service Indicator > Freeze Protection > Service Reminder > Time Clock
> Data Logging
> Ignition Attempts > Last 10 Lockouts
> Programmable System Efficiency Optimizers
> Night Setback > Pump Control
> Domestic Hot Water Pump
> High Voltage Terminal Strip
> 120 VAC/ 60 Hertz/ 1 Phase Power Supply > Pump Contacts with Pump Relays
> Low Voltage Terminal Strip
> 24 VAC Auxiliary Device Relay > Auxiliary Proving Switch Contacts > Flow Switch Contacts > Alarm on Any Failure Contacts > Runtime Contacts > Cascade Contacts > 0-10 VDC BMS External Control Contact
Optional Equipment
> Alarm Bell > MODBUS Communication
> BMS Gateway to LON or BacNet > Cupro-Nickel Heat Exchanger
> High & Low Gas Pressure Switches
w/ Manual Reset > Low Water Cutoff w/Manual Reset & Test > SMART SYSTEM PC Software > Vent Kits:
- Horizontal Exhaust Cap
- Horizontal Air Intake Cap
- Horizontal Direct Vent Kit
- Category IV to Category II Conversion Kit
Firing Control Systems
> M Indicates 5:1 Turndown, Category IV > B Indicates 2:1 Turndown, Category I > F Indicates 100% On/Off Fire, Category I
> M9 Standard > B9 or F9 Special Order, Factory Trimmed > M7, B7 or F7 California Code
Power-Fin Water Heater Dimensions & Specifications
J
K
M
B
G
P
L
N
C
GPH @ Model Btu/Hr 100°F Rise E E Number Input (F) (M) A B C D (B)/(F) (M) F G H J
PFN0502PM 500,000 515 527 44-1/2” 28-1/2” 23-1/4” 34” 17-3/4” 19-1/2” 6-1/2” 6” 8” 7-3/4” PFN0752PM 750,000 773 791 52” 28-1/2” 23-1/4” 41-1/2” 17-3/4” 19-1/2” 6-3/4” 6” 8” 7-3/4” PFN1002PM 999,999 1,030 1,054 59-1/4” 28-1/2” 23-1/4” 48-3/4” 17-3/4” 19-1/2” 7-1/4” 6” 8” 7-3/4” PFN1302PM 1,300,000 1,323 1,371 67-3/4” 28-1/2” 23-1/4” 57-1/4” 17-3/4” 19-1/2” 8-1/4” 6” 8” 7-3/4” PFN1501PM 1,500,000 1,527 1,582 65-1/2” 29-3/4” 27-1/4” 58-3/4” 21” 21” 13-1/2” 8” 10” 9-1/2” PFN1701PM 1,700,000 1,731 1,793 70” 29-3/4” 27-1/4” 63-1/4” 21” 21” 13-1/2” 8” 10” 9-1/2”
PFN2001PM 2,000,000 2,036 2,109 76-3/4” 29-3/4” 27-1/4” 70” 21” 21” 13-1/2” 8” 10” 9-1/2”
Vent Sizes Model P P Gas Air Cat I Cat II Cat IV Wt. Number K L M N (B)/(F) (M) Conn. Inlet (B)/(F) (M) (M) (lbs)
PFN0502PM 23” 11-1/2” 11-1/4” 17-1/2” 15-1/4” 15-1/4” 1” 5” 7” 7” 4” 571 PFN0752PM 30-1/2” 11-1/2” 11-1/4” 17-1/2” 15-1/4” 15-1/4” 1-1/4” 5” 9” 9” 5” 620 PFN1002PM 37-3/4” 11-1/2” 11-1/4” 17-1/2” 15-1/4” 15-1/4” 1-1/4” 6” 10” 10” 6” 669 PFN1302PM 46-1/4” 11-1/2” 19-1/2” 17-1/2” 15-1/4” 15-1/4” 1-1/4” 6” 12” 12” 8” 718 PFN1501PM 43-1/2” 5-3/4” 22-1/4” 21-1/2” 24-1/2” 19-1/2” 1-1/2” 6” 12” 8” 6” 1,115 PFN1701PM 48” 5-3/4” 25” 21-1/2” 24-1/2” 19-1/2” 1-1/2” 7” 14” 9” 7” 1,150
PFN2001PM 54-3/4” 5-3/4” 27-1/2” 21-1/2” 24-1/2” 19-1/2” 1-1/2” 8” 14” 10” 8” 1,184
Notes: Change ‘N’ to ‘L’ for LP Gas Model. No deration on LP models. Temperature rise calculations based on firing rate of 100% All water connections are 2-1/2”
Venting Options
Sidewall Vertical DirectAire Vertical w/ Sidewall Inlet DirectAire Horizontal w/ Rooftop Inlet Direct Vent Horizontal Direct Vent Vertical Intelligent Venting Solutions
Lochinvar, LLC 300 Maddox Simpson Parkway Lebanon, Tennessee 37090 P: 615.889.8900 / F: 615.547.1000
www.Lochinvar.com
HLW
10/14—Printed in U.S.A.