Lochinvar Knight 50-210 User Manual

Service Manual
Models: 50 - 210
This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Knight Wall Mount Installation and Operation Manual, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
WARNING
Save this manual for future reference.
2
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Hazard Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PLEASE READ BEFORE PROCEEDING . . . . . . . . . . . . 3
Handling Ceramic Fiber Materials . . . . . . . . . . . . . . . . . . . 3
When servicing boiler . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Boiler operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Boiler water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Freeze protection fluids . . . . . . . . . . . . . . . . . . . . . . . . 4
WHAT IS IN THIS MANUAL . . . . . . . . . . . . . . . . . . . . . . . 5
1. SERVICE
Near Boiler Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
The Knight Wall Mount Display . . . . . . . . . . . . . . . . . . . . . 7
Control Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Control Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
General Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 11-12
Display Panel Menu Access . . . . . . . . . . . . . . . . . . . . . . 13
Display Panel Parameter Access . . . . . . . . . . . . . . . . . . 14
Parameter Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16
Viewable and Changeable Control Parameters . . . . . . . 17-22
2. MAINTENANCE
Maintenance and Annual Startup . . . . . . . . . . . . . . . . . . 23-27
3. TROUBLESHOOTING
Before Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Check Control Module Fuses . . . . . . . . . . . . . . . . . . . . . 28
Table 3A - Troubleshooting Chart - No Display . . . . . . . . 29
Checking Temperature Sensors . . . . . . . . . . . . . . . . . . . 30
Table 3E - Troubleshooting Chart - Noisy System . . . . . 31
Table 3F - Troubleshooting Chart - Fault Messages . . . . 32-39
Combustion Analysis Procedure . . . . . . . . . . . . . . . . . . . 40
Table 3G - Troubleshooting Chart - Combustion Levels 40
Table 3H - Flue Products . . . . . . . . . . . . . . . . . . . . . . . . . 40
Gas Valve Adjustment Procedure . . . . . . . . . . . . . . . . . . 41
Revision Notes . . . . . . . . . . . . . . . . . . . . . . . . . Back Cover
Contents
Service Manual
Please read before proceeding
Installer – Read all instructions, including this manual and the Knight Wall Mount Installation and Operation Manual, before installing. Perform steps in the order given.
User – This manual is for use only by a qualified heating installer/service technician. Refer to the Knight Wall Mount User’s Information Manual for your reference.
Have this boiler serviced/inspected by a qualified service technician at least annually.
Failure to comply with the above could result in severe personal injury, death or substantial property damage.
When calling or writing about the boiler – Please have the boiler model and serial number from the boiler rating plate.
Consider piping and installation when determining boiler location (see the Knight Wall Mount Installation and Operation Manual).
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
3
Handling ceramic fiber materials
REMOVAL OF COMBUSTION CHAMBER LINING
The combustion chamber door insulation in this product contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica inhaled in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).”:
Avoid breathing dust and contact with skin and eyes.
• Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH website at http://www.cdc.gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and phone numbers are also listed on this website.
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Apply enough water to the combustion chamber lining to prevent airborne dust.
Remove the combustion chamber lining from the boiler and place it in a plastic bag for disposal.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer
thoroughly.
NIOSH stated First Aid.
Eye: Irrigate immediately.Breathing: Fresh air.
WARNING
NOTICE
WARNING
4
Service Manual
Please read before proceeding
When servicing boiler –
• To avoid electric shock, disconnect electrical supply before performing maintenance.
• To avoid severe burns, allow boiler to cool before performing maintenance.
Boiler operation –
• Do not block flow of combustion or ventilation air to the boiler.
• Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to circulator. Instead, shut off the gas supply at a location external to the appliance.
• Do not use this boiler if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
Boiler water –
• Thoroughly flush the system (without boiler connected) to remove sediment. The high-efficiency heat exchanger can be damaged by build-up or corrosion due to sediment.
• Do not use petroleum-based cleaning or sealing compounds in the boiler system. Gaskets and seals in the system may be damaged. This can result in substantial property damage.
• Do not use “homemade cures” or “boiler patent medicines”. Serious damage to the boiler, personnel, and/or property may result.
• Continual fresh make-up water will reduce boiler life. Mineral buildup in the heat exchanger reduces heat transfer, overheats the stainless steel heat exchanger, and causes failure. Addition of oxygen carried in by makeup water can cause internal corrosion. Leaks in boiler piping must be repaired at once to prevent the introduction of makeup water.
Freeze protection fluids –
• NEVER use automotive antifreeze. Use only inhibited propylene glycol solutions which are specifically formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems.
Service Manual
5
What is in this manual?
Service
Near boiler piping
• Typical system components
The Knight wall mount boiler display
• Display panel readout, buttons and their functions
Control module inputs
• Control module inputs and options
Control module outputs
• Control module outputs and options
General
• How the boiler operates
• How the control module operates
• Access modes -- user and installer
• Sequence of operation -- Domestic Hot Water (DHW)/space heating
Control panel menu access
• Accessing programming mode and locating menus
(See separate guide covering the PC interface.)
Control panel parameter access
• Accessing and changing parameters from the display panel
Quick start information -- parameter table
• An index of available adjustments and readouts, where to access them and where to find detailed information.
Knight wall mount boiler operation
• A: General
• B: Temperature Setting
• C: Data Logging
• D: Functions
• E: DHW Settings
• F: Outdoor Air Reset Curve
• G: Anti-cycling
• H: Control Modes
• I: Circulation Pumps
• J: Service Notification
Maintenance
• Service and maintenance schedules
• Address reported problems
• Inspect boiler area and boiler interior
• Clean condensate trap
• Check all piping for leaks
• Check air openings
• Flue vent system and air piping
• Check water system
• Check expansion tank
• Check boiler relief valve
• Inspect ignition electrode
• Check ignition ground wiring
• Check all boiler wiring
• Check control settings
• Perform start-up and checks
• Check burner flame
• Check flame signal
• Check flue gas temperature
• General maintenance
• Review with owner
• Cleaning boiler heat exchanger
• Oiled bearing circulators
Troubleshooting
• Troubleshooting table - No display
• Checking temperature sensors
• Sensor tables
• Troubleshooting table - Fault messages displayed on boiler interface
• Combustion analysis procedure
• Gas valve adjustment procedure
1 Service
6
Service Manual
Near boiler piping
This piping reference is included to specify the Near Boiler Piping specific to the Knight wall mount boiler. This piping scheme is important for proper operation of the SMART SYSTEM control. See the Knight Wall Mount Installation and Operation Manual for more detailed piping diagrams.
1 Service
Service Manual
7
1 Service (continued)
The Knight wall mount display
1 Service
8
Service Manual
1 Service
Control inputs
GAS PRESSURE SWITCH
DHW THERMOSTAT
ROOM THERMOSTAT /
ZONE CONTROL
FLOW SWITCH
SYSTEM SENSOR
OUTDOOR SENSOR
LOW VOLTAGE
CONNECTION
BOARD
SEQUENCER / BUILDING
MANAGMENT SYSTEM
LOW WATER CUTOFF
INLET TEMPERATURE
SENSOR
OUTLET TEMPERATURE /
HIGH LIMIT SENSOR
FLUE GAS SENSOR
AIR PRESSURE SWITCH
FLAME SENSOR
BLOCKED DRAIN SWITCH
SMART CONTROL
MODULE
PC INTERFACE
DISPLAY PANEL
1 Service
Service Manual
9
1 Service (continued)
Control outputs
1 Service
10
Service Manual
1 Service
General Operation
How the boiler operates
The Knight wall mount boiler uses an advanced stainless steel heat exchanger and an electronic control module that allows fully condensing operation. The blower pulls in gas and air and pushes flue products out of the boiler through the heat exchanger and flue piping. The control module regulates blower speed to control boiler firing rate. The gas valve senses the amount of air flowing into the boiler and allows only the right amount of gas to flow.
How the control module operates
The Knight wall mount control module receives input from boiler sensors. The control module activates and controls the blower and gas valve to regulate heat input and switches boiler, DHW and system pumps on and off as needed. The user/installer programs the module to meet system needs by adjusting control parameters. These parameters set operating temperatures and boiler operating modes. Boiler operation can be based on boiler outlet water temperature, boiler return water temperature or system supply temperature, depending on the parameter setting.
Sequence of operation
Table 1 shows control module normal sequences of operation for space heating and DHW operation. The combined operation sequence is for a typical application, programmed to provide DHW priority.
Access modes
User
The user can adjust space heating set point using the UP and DOWN buttons at any time during normal operation. By entering the USER code (0704), the user can also change temperature units, time and date, and night setback settings. In user mode, the following parameters can be viewed but not changed: Boiler outlet water temperature in DHW mode; boiler model number; software version; total operating hours, and total cycles.
Installer
Most parameters are available only to the installer, accessible only by entering the installer access code (5309).
Saving parameters
To save parameters:
Press the ENTER/RESET button.
To keep parameter settings only for a current operating cycle:
Press the MENU/EXIT button 1 time to return to the parameter listings; press again to return to the menu listings.
1 Service
Service Manual
11
1 Service (continued)
Sequence of operation
Table 1A Sequence of operation - space heating and DHW
OPERATION DISPLAY
1. Upon a call for heat, the control turns on the appropriate pumps (system and boiler pumps for space heating call; DHW pump for DHW call).
BLR: Standby OUT: 123.8F(129)
2. The control connects 120 vac to the blower. The blower does not run at this time.
• If the unit is equipped with a flow switch or low water cutoff, it
must close before the control powers up the blower.
• If the unit is equipped with a manual reset high limit it must be
closed before the control powers up the blower.
• If the unit is equipped with a solenoid valve and/or a vent
valve, they will be energized along with the blower.
• If the unit is equipped with a gas pressure switch, it must close
at this time.
• If there is an auxiliary device connected to the unit, the unit
will then provide 24 vac to its enable relay. If the auxiliary
device has a proving switch, it must close before the
sequence continues.
BLR: Standby OUT: 123.8F(129)
3. The control then starts a 10 second prepurge cycle.
BLR: PREPURGE OUT: 123.9F(129)
4. Once the prepurge cycle is complete, and the blocked drain switch and auto-reset high limit are closed, the control starts the 5 second trial for ignition by sending spark voltage to the spark electrode and opening the gas valve.
BLR: IGNITION OUT: 123.9F(129)
5. If the control does not detect flame by the end of the trial for ignition, the control performs a 10 second postpurge, another prepurge and tries to light the burner again. If the burner does not light after 4 trials, the control locks out for 1 hour and then tries another set of 4 trials.
BLR: POSTPURGE, PREPURGE OUT: 123.9F(129)
6. If the control detects a flame before the trial for ignition ends, it begins to modulate the burner in order to maintain the set point. If the boiler lights due to a space heating call for heat, and the ramp delay function is active (default is off), the modulation will be held to a series of increasing limits after the burner has lit.
BLR: SH 20% RATE OUT: 124.8F(129)
7. If the space heating call for heat is active, and the DHW thermostat closes, the control will turn on the DHW pump, wait 2 seconds, and then turn off the boiler pump. This will divert the hot water away from the heating zone(s) and send it to the DHW tank instead. The control will then modulate to maintain the outlet temperature to the DHW boiler set point.
BLR: DHW 85% RATE OUT: 177.8(180)
1 Service
12
Service Manual
1 Service
Sequence of operation (continued)
Table 1A (continued from previous page) Sequence of operation - space heating and DHW
OPERATION DISPLAY
8. If the DHW thermostat remains on for more than 30 minutes, and the space heating call for heat is also on, then the control will turn on the boiler pump, turn off the DHW pump after 2 seconds, and resume modulating based on the space heating set point. As long as both the space heating and DHW calls for heat remain active, the control will switch back and forth between the two modes until one of them is satisfied.
BLR: SH 41% RATE OUT: 123.0F(129)
9. Once both calls for heat are satisfied, the control will turn off the burner. The blower will remain on for the 10 second postpurge cycle. Any pumps that are running will continue to run for their respective pump delay times, then turn off.
BLR: POSTPURGE OUT: 127.4F(129)
10. Boiler pump off, system pump continues its delay if longer.
BLR: Standby OUT: 124.7F(129)
11. System pump off.
BLR: Standby OUT: 122.9F(129)
1 Service
Service Manual
13
1 Service (continued)
Display panel menu access
Table 1B Use this procedure to access menus from the display panel
1 Service
14
Service Manual
1 Service
Display panel parameter access
Table 1C This is a typical example of accessing a parameter, shown for parameter I2, boiler pump delay