Lochinvar FBN1500 User Manual

CREST
COMMERCIAL BOILER
Submittal Sheet
FBN-Sub-03a
CREST COMMERCIAL CONDENSING BOILER
JOB NAME ______________________________________________________________________ LOCATION ______________________________________________________________________ ARCH./ENGR.____________________________________________________________________ WHOLESALER __________________________________________________________________ MECH. CONTRACTOR ___________________________________________________________ MODEL NO. _____________________________________________________________________ TYPE GAS ______________________________________________________________________ Btu/hr INPUT_____________________________________________________________________ Btu/hr OUTPUT___________________________________________________________________ NOTES
Smart Touch™ Features
> SMART TOUCH™ Touchscreen Operating Control > Full-Color 8” Touchscreen LCD Display > Built-in Cascading Sequencer for up to 8 Boilers
> Cascade Multiple Sized Boilers > Lead/Lag Cascade > Efficiency Optimized Cascade
> Front-End Loading Capability with CopperFin II and
Powerfin Boilers
> Building Management System Integration with
0-10 VDC Input > Modbus Communications > Outdoor Reset Control with Outdoor Air Sensor > Password Security
Domestic Hot Water Prioritization Low Water Flow Safety Control & Indication Inlet & Outlet Temperature Readout Freeze Protection Service Reminder Time Clock
> Data Logging
Hours Running, Space Heating Hours Running, Domestic Hot Water Hours Running, Modulation Rate Ignition Attempts Last 10 Lockouts
> Programmable System Efficiency Optimizers
Night Setback Anti-Cycling Outdoor Air Reset Curve Ramp Delay Boost Temperature & Time
> Three Pump Control
System Pump Boiler Pump Domestic Hot Water Pump
> High-Voltage Terminal Strip
120 VAC / 60 Hertz / 1 Phase Power Supply
(FB1500-3500)
208 VAC / 60 Hertz / 3 Phase Power Supply
(FB4000-5000) System Pump, Boiler Pump and DHW Pump
Power
> Low-Voltage Terminal Strip
24 VAC Auxiliary Device Relay Auxiliary Proving Switch Contacts Alarm on Any Failure Contacts Runtime Contacts DHW Thermostat Contacts Unit Enable/Disable Contacts System Sensor Contacts DHW Tank Sensor Contacts Outdoor Air Sensor Contacts Cascade Contacts 0-10 VDC BMS External Control Contact
Standard Features
Up to 93% Thermal Efficiency (AHRI) Up to 99% Thermal Efficiency in Low
Temperature Applications Modulating Burner with up to 25:1 Turndown Direct-Spark Ignition Low-NOx Operation Sealed Combustion Low Gas Pressure Operation Vertical or Horizontal Venting Category IV Venting up to 100 Feet ASME “H” Stamped Heat Exchanger 316L Stainless Steel Fire Tubes 160 psi Working Pressure On/Off Switch Adjustable High Limit with Manual Reset Low Water Cutoff with Manual Reset & Test High & Low Gas Pressure Switches w/Manual Reset Low Air Pressure Switches Condensate Trap w/ Blocked Drain Switch
Drain Valve System Sensor Outdoor Air Sensor Inlet & Outlet Temperature Sensors High Voltage Terminal Strip Low Voltage Terminal Strip Downstream Gas Test Cocks
50 psi ASME Relief Valve Temperature & Pressure Gauge Zero Clearances to Combustible Materials 10-Year Limited Warranty (See Warranty for
Details)
1-Year Warranty on Parts (See Warranty for
Details)
Optional Equipment
Alarm Bell BMS Gateway - BACnet or LonWorks Condensate Neutralization Kit SMART TOUCH PC Software Common Vent Kits (Consult Factory on FB4000 and 5000) Dual Fuel Gas Train* Electrical Options (Shipped Loose):
208V/3Ø/60Hz (Models FB1500-3500 only) 480V/3Ø/60Hz
600V/3Ø/60Hz
*(Available on FB1500-3500
Coming Soon on FB4000-5000)
Codes & Registrations
ANSI Z21.13/CSA Certified ASME certified, “H” Stamp / National Board California Code Compliant CSD1 / Factory Mutual / GE Gap Compliant South Coast Air Quality Management
District Qualified Canadian Registration Number (CRN) AHRI Certified
CREST Commercial Boiler Dimensions & Specifications
H
HIGH VOLTAGE
DRAIN
J
K
SIDE
Crest Heating Boiler Dimensions and Specifications
Model Input Input AHRI NET Number MBH MBH Thermal Output I=B=R Turndown Min. Max. % MBH MBH
FBN1500 60 1,500 92.0% 1,380 1,200 25:1 FBN2000 80 2,000 92.0% 1,840 1,600 25:1 FBN2500 125 2,500 92.0% 2,300 2,000 20:1 FBN3000 150 3,000 92.0% 2,760 2,400 20:1 FBN3500 200 3,500 92.0% 3,220 2,800 18:1 FBN4000 335 4,000 93.0% 3,720 3,235 12:1 FBN5000 500 5,000 93.0% 4,650 4,043 10:1
Notes: Indoor installation only. All information subject to change. Change "N" to "L" for LP gas models. Low NOx on FB2500 - FB5000 models, consult factory. *Turndown rate reduced on LP gas models.
WATER OUTLET
WATER INLET
LOW VOLTAGE
*
RELIEF VALVE
4" FLG OUTLET
80"
66-5/8"
4" FLG INLET
11"
8"
CONDENSATE DRAIN
14-7/8"
DRAIN
10 -1/4"
BACK
Gas Air Vent Operating Shipping A B C D E F G H J K Conn. Inlet Size Wt. (lbs.) Wt. (lbs.)
VENT
B
C
D
E
G
A
TOP
30 3/4” 71-1/2” 65-3/4” 14-3/8” 22-3/8” 8-1/2” 25-1/4” 8-1/8” 72-5/8” 77-5/8” 1-1/2” 7” 7” 2,496 1,900 30 3/4” 71-1/8” 65-1/8” 14-7/8” 22-3/8” 8-1/4” 25-3/8” 9-5/8” 71-7/8” 76-7/8” 1-1/2” 8” 8” 3,054 2,150 34 1/4” 76-3/8” 70-1/4” 17-3/4” 26-1/8” 9-3/4” 27-3/8” 11-3/8” 78” 83” 2” 8” 9” 3,652 2,560 40 1/2” 83-5/8” 76-3/8” 17-3/8” 31-3/8” 9-7/8” 34-3/4” 11-1/2” 82-1/8” 87-1/8” 2” 10” 10” 4,126 2,920 40 1/2” 83-1/4” 75-5/8” 17-1/4” 31-3/8” 9-7/8” 34-3/4” 12-7/8” 81-1/8” 86-1/8” 2” 10” 10” 4,744 3,225 53-1/2” 109” 100-3/4” 31-1/4” 40-3/4” 14-1/2” 45-3/4” 12-3/4” 109-1/4” 108-1/4” 2-1/2” 12” 12” 6,900 4,750 53-1/2” 109” 100-3/4” 28” 40-3/4” 11” 45-1/2” 12-3/4” 109-1/4” 108-1/4” 2-1/2” 14” 14” 8,000 5,550
LOW VOLTAGE
HIGH VOLTAGE
AIR
GAS
F
Venting Options
Direct Vent Vertical
Direct Vent Horizontal
Vertical Vent with Sidewall Air Intake
Sidewall Vent with Rooftop Air Intake
Vertical Vent with Optional Room Air
Sidewall Vent with Optional Room Air
Lochinvar, LLC • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com