Lochinvar FBD2001 Service Manual

FBII-SER _100208044_2000004590_Rev F
Service Manual
w/CON•X•US Interface
Models: 751 - 2001
WARNING
Save this manual for future reference.
This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Crest Installation and Operation Manual, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
Contents
CONTENTS ........................................................................ 2
Hazard Definitions .............................................................. 2
PLEASE READ BEFORE PROCEEDING ........................ 3
Handling Ceramic Fiber Materials ...................................... 3
When servicing boiler ................................................... 4
Boiler operation ............................................................ 4
Boiler water ................................................................... 4
Freeze protection fluids ................................................ 4
WHAT IS IN THIS MANUAL .............................................. 5
1. SERVICE
Boiler Piping ....................................................................... 6
SMART TOUCH w/CON•X•US Interface ........................... 7
General Operation ......................................................... 8
Control Inputs ............................................................... 9
Control Outputs ........................................................... 10
Table 1A - Sequence of Operation .................................. 11
Initial Setup Screen ........................................................... 12
Viewable and Changeable Control Parameters ............... 13
Set Point Screens .................................................. 13-15
Outdoor Reset Screen ........................................... 16-17
Ramp Delay Screen .............................................. 18-19
BMS Screens .......................................................... 20-22
Advanced Setup Screen ......................................... 23-24
Night Setback Screen ................................................... 25
Pump Screen ........................................................... 26-27
Cascade Screens ....................................................28-30
Service Screen.........................................................31-32
Graph Screens .............................................................. 33
History Screens........................................................34-35
2. MAINTENANCE
Maintenance and Annual Startup ................................ 36-40
3. TROUBLESHOOTING
Before Troubleshooting .................................................... 41
Check Control Module Fuses .......................................... 41
Table 3A - Troubleshooting Chart - No Display ............... 42
Checking Temperature Sensors ...................................... 43
Table 3F - Troubleshooting Chart - Noisy System .......... 44
Table 3G - Troubleshooting Chart - Fault Messages . 46-56
Combustion Analysis Procedure ................................. 57-58
Table 3H - Flue Products ................................................. 57
Table 3I - Troubleshooting Chart - Combustion Levels . 58
Gas Valve Adjustment Procedure .................................... 59
Revision Notes .................................................. Back Cover
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
2
Please read before proceeding
Service Manual
WARNING
Installer – Read all instructions, including this manual and the Crest Installation and Operation Manual, before installing. Perform steps in the order given.
User – This manual is for use only by a qualified heating installer/service technician. Refer to the Crest User’s Information Manual for your reference.
Have this boiler serviced/inspected by a qualified service technician at least annually.
Failure to comply with the above could result in severe personal injury, death or substantial property damage.
NOTICE
Handling ceramic fiber materials
REMOVAL OF COMBUSTION CHAMBER LINING
WARNING
The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created to convert the ceramic fibers in this appliance to cristobalite.
When calling or writing about the boiler – Please have the boiler model and serial number from the boiler rating plate.
Consider piping and installation when determining boiler location (see the Crest Installation and Operation Manual).
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines.
Avoid breathing dust and contact with skin and eyes.
• Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH website at http://www.cdc.gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and phone numbers are also listed on this website.
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Apply enough water to the combustion chamber lining to prevent airborne dust.
Remove the combustion chamber lining from the appliance and place it in a plastic bag for disposal.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer
thoroughly.
NIOSH stated First Aid.
Eye: Irrigate immediately. Breathing: Fresh air.
3
Please read before proceeding
When servicing boiler –
• To avoid electric shock, disconnect electrical supply before performing maintenance.
• To avoid severe burns, allow boiler to cool before performing maintenance.
Boiler operation –
• Do not block flow of combustion or ventilation air to the boiler.
• Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to circulator. Instead, shut off the gas supply at a location external to the appliance.
• Do not use this boiler if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
Service Manual
Boiler water –
• Thoroughly flush the system (without boiler connected) to remove sediment. The high-efficiency heat exchanger can be damaged by build-up or corrosion due to sediment.
• Do not use petroleum-based cleaning or sealing compounds in the boiler system. Gaskets and seals in the system may be damaged. This can result in substantial property damage.
• Do not use “homemade cures” or “boiler patent medicines”. Serious damage to the boiler, personnel, and/or property may result.
• Continual fresh make-up water will reduce boiler life. Mineral buildup in the heat exchanger reduces heat transfer, overheats the stainless steel heat exchanger, and causes failure. Addition of oxygen carried in by makeup water can cause internal corrosion. Leaks in boiler piping must be repaired at once to prevent the introduction of makeup water.
Freeze protection fluids –
• NEVER use automotive antifreeze. Use only inhibited propylene glycol solutions which are specifically formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems.
4
What is in this manual?
Service Manual
Service
Near boiler piping
• Typical system components
The Crest boiler display
• Display panel readout, buttons and their functions
Control module inputs
• Control module inputs and options
Control module outputs
• Control module outputs and options
General
• How the boiler operates
• How the control module operates
• Access modes -- user and installer
• Sequence of operation -- HW/space heating
Control panel menu access
• Accessing programming mode and locating menus (See separate guide covering the PC interface.)
Maintenance
• Service and maintenance schedules
• Address reported problems
• Inspect boiler area and boiler interior
• Clean condensate trap
• Check all piping for leaks
• Check air openings
• Flue vent system and air piping
• Check water system
• Check expansion tank
• Check boiler relief valve
• Inspect ignition electrode
• Check ignition ground wiring
• Check all boiler wiring
• Check control settings
• Perform start-up and checks
• Check burner flame
• Check flame signal
• Check flue gas temperature
• General maintenance
• Review with owner
• Cleaning boiler heat exchanger
• Oiled bearing circulators
Control panel parameter access
• Accessing and changing parameters from the display panel
Quick start information -- parameter table
• An index of available adjustments and readouts, where to access them and where to find detailed information.
Crest boiler operation
• Initial Setup
• Set Points
• Outdoor Reset
• Ramp Delay
• BMS
• Advanced Setup
• SH Night Setback
• HW Night Setback
• Cascade
• Pumps
• Service Notification
Troubleshooting
• Troubleshooting table - No display
• Checking temperature sensors
• Sensor tables
• Troubleshooting table - Fault messages displayed on boiler interface
• Combustion analysis procedure
• Gas valve adjustment procedure
5
Service Manual
1 Service
Boiler piping
This piping reference is included to specify the Boiler Piping specific to the Crest boiler. This piping scheme is important for proper operation of the SMART TOUCH control. See the Crest Installation and Operation Manual for more detailed piping diagrams.
Single Boiler - Recommended - Primary / Secondary Piping with a Hot Water Generator
FROM SYSTEM
SYSTEM RETURN
HOT WATER
GENERATOR
RELIEF
VALVE
SENSOR
12"
MAX
BALL VALVE (TYPICAL)
AIR SEPERATOR
DRAIN PORT (TYPICAL)
SYSTEM SUPPLY SENSOR
SYSTEM CIRCULATOR
BOILER
DRAIN
WATER
GENERATOR
CIRCULATOR
FLOW CHECK VALVE (TYPICAL)
BOILER PUMP
Single Boiler - Alternate - Full Flow System Piping
RELIEF
VALVE
BALL VALVE
(TYPICAL)
FROM SYSTEM
BOILER DRAIN
Y-STRA INER
(RECOMMENDED)
Y-STRA INER (RECOMMENDED)
EXPANSION
TANK
PRESSURE REDUCING VALVE
PRESSURE GAUGE
AIR SEPERATOR
DRAIN PORT (TYPICAL)
SYSTEM CIRCULATOR
BACK FLOW PREVENTER
TO SYSTEM
MAKE UP WATER
IMG01035
PRESSURE REDUCING VALVE
(OPTIONAL)
BYPASS
EXPANSION
TANK
PRESSURE
GAUGE
PRESSURE REDUCING VALVE
BACK FLOW PREVENTER
TO SYSTEM
MAKE UP WATER
IMG01038
6
Service Manual
1 Service (continued)
w/CON•X•US Interface
The Home Screen displays status, modulation rate, outlet water temperature, inlet water temperature, flue temperature, system supply temperature, system return temperature, outdoor air temperature, and domestic hot water tank temperature.
The boiler can be started and stopped by pressing the ON/OFF button. The Boiler Status Screen and Main Menu Screen can be accessed by pressing the appropriate button.
Figure 1-1 Home Screen
When the ON/OFF switch is turned to the ON position, the first screen visible on the LCD display will be the Home Screen. This screen displays the current status of the Crest boiler. The following items can be viewed or interacted with on the Home Screen:
On/Off button - Pressing this button allows the boiler to be placed in either Manual Shutdown Mode or Standby Mode.
Status - This line shows the current operating status of the Crest boiler and the current set point.
Outlet Water Temperature - This is the boiler outlet temperature.
Inlet Water Temperature - This is the boiler inlet temperature.
System Supply Temperature - This is the water temperature
as measured by the system supply sensor located in the downstream piping (if connected).
System Return Temperature - This is the water temperature measured by the system return sensor located in the upstream piping (if connected).
Outside Air Temperature - This is the outdoor air temperature (if connected).
HW Temperature - This is the temperature as measured by the tank sensor in the hot water storage tank (if connected).
Flue Temperature - Temperature measured by the flue sensor.
Time - The time is displayed in the lower left-hand corner
of the display. Reference this manual for Night Setback parameters and more information regarding adjusting the date and time.
Modulation Percentage - Displays the current boiler firing rate.
7
1 Service
General Operation
Service Manual
How the boiler operates
The Crest uses an advanced stainless steel heat exchanger and electronic control module that allows fully condensing operation. The blowers pull in air and push flue products out of the boiler through the heat exchanger and flue piping. The control module regulates blower speeds to control the boiler firing rate. The gas valves sense the amount of air flowing into the boiler and allow only the right amount of gas to flow.
How the control modules operate
The Crest boiler is equipped with a SMART TOUCH CON•X•US Interface. The control module receives inputs from boiler sensors and external devices. The control module activates and controls the blowers and gas valves to regulate heat input and switches the boiler, Hot Water Generator (HW), and system pumps on and off as needed. The user programs the control module to meet system needs by adjusting control parameters through the SMART TOUCH CON•X•US Interface. These parameters set operating temperatures and boiler operating modes.
Sequence of operation
Table 1A (page 11) shows control module normal sequences of operation for space heating and HW operation. The combined operation sequence is for a typical application, programmed to provide HW priority.
Access modes
User
The USER can set the SH set point, HW set point, turn the unit OFF and ON and set up WiFi.
Installer
Most parameters are available only to the INSTALLER, accessible only by entering the installer password (5309) when selecting the Setup Section.
Note: The password will timeout after an hour from entry.
8
1 Service
1 Service (continued)
Control inputs
HWG THERMOSTAT /
SENSOR
ENABLING DEVICE
CASCADE
LOUVER PROVING SWITCH
SYSTEM SENSOR -
SUPPLY
SYSTEM SENSOR -
RETURN
Service Manual
LOW VOLTAGE
CONNECTION
BOARD
OUTDOOR SENSOR
SEQUENCER / BUILDING
MANAGEMENT SYSTEM
AUX SWITCH 1 & 2
0-10 INPUT FROM
SYSTEM PUMP
INLET TEMPERATURE
SENSOR
OUTLET TEMPERATURE /
HI-LIMIT SENSOR
FLUE GAS SENSOR
INLET AIR SENSOR
AIR PRESSURE SWITCH
MANUAL RESET
HIGH LIMIT
FLAME SENSOR 1 & 2
BLOCKED DRAIN SWITCH
BAS BOARD
SMART CONTROL
MODULE
GAS PRESSURE SWITCHES
LOW WATER CUTOFF
AIR METERING VALVE PRESSURE SWITCH
VENT DAMPER
PROVING SWITCH
AIR METERING VALVE PROVING SWITCHES
DISPLAY PANEL
PC INTERFACE
9
1 Service
1 Service
Control outputs
Service Manual
0-10V OUTPUT TO
BOILER PUMP
ALARM CONTACTS
LOW VOLTAGE
CONNECTION
BOARD
LINE VOLTAGE
TERMINAL
STRIP
NL
SUPPLY
120V
SYSTEM PUMP BOILER PUMP DHW PUMP
MAX. 1.5 AMPS PER CONNECTION
FIELD SUPPLIED CONTACTOR MUST
BE INSTALLED
LOUVER RELAY
RUN TIME CONTACTS
BOILER RATE OUTPUT
SEQUENCER / BUILDING
MANAGEMENT SYSTEM
BOILER PUMP
CONTACTOR
SYSTEM PUMP
CONTACTOR
HWG PUMP
CONTACTOR
IGNITOR
BLOWER
GAS VALVES
10
SMART CONTROL
MODULE
VENT DAMPER
DISPLAY PANEL
PC INTERFACE
AIR METERING VALVE
Service Manual
1 Service (continued)
Table 1A Sequence of Operation
Sequence of operation
Note: This unit is equipped with two (2) gas train systems. Gas Train 1 will fire first. If the demand cannot be met by the first gas train, the second gas train (Gas Train 2) will fire.
Upon a call for heat, the control turns on the appropriate pumps (system and boiler pumps for a space heating call,
1.
HW pump for a hot water generator call).
The control confirms that the low water cutoff contacts are closed and energizes the louvers (optional) and damper
2.
(optional) relays.
The control confirms that the gas pressure switch, blocked drain switch, limits, louver proving switch (optional) and
3.
damper proving switch (optional) contacts close. The Pre-Purge cycle begins.
The control confirms the blower is up to the desired speed, and the air pressure switch is closed.
4.
5.
6.
7.
8.
9.
10.
11.
Once the Pre-Purge cycle is complete, the control lowers the blower speed, closes the air metering valve, initiates sparking of the ignition electrode, and opens gas valve 1.
After a short wait, the control stops sparking and checks for the presence of flame current through the flame sense electrodes.
If flame is not detected after the sparking ends, the control will perform a postpurge, then start another prepurge cycle and try to light the burner again.
If the control detects flame current, the control will hold the blower speed constant for a few seconds to allow the flame to stabilize, then begin modulating the firing rate in order to maintain the controlling sensor to the desired set point temperature.
If the current call for heat is for space heating and a HW call for heat becomes active, the control will turn on the HW pump relay output, then turn off the boiler pump. It will then modulate the blower speed in order to maintain the outlet temperature to the desired HW outlet set point temperature (Normal Mode Only).
If the boiler is unable to maintain the desired set point using gas valve 1, control will transition to the larger gas valve
2. The blower will modulate to a fixed speed and the air metering valve will start to open. As it opens, gas valve 2 will be turned on and gas valve 1 will be turned off. If the flame should be lost at any time during this process, the control will immediately try to reignite the burner. Once the air metering valve is fully open and the flame is confirmed to be present, the control will hold the fan speed constant for a few seconds in order to allow the flame to stabilize. The fan speed will then modulate as needed to maintain the set point. If the flame is not present when the air metering valve is fully open, the boiler will go through a complete shutdown and restart of the burner. If the heat load should decrease sufficiently, a similar process is used to transition from gas valve 2 to gas valve 1.
Once both the space heating and HW calls for heat are satisfied, the control will turn off the gas valve and begin the Post-Purge cycle. Any pumps that are running will begin their respective Pump Delay cycles. The air metering valve will be opened.
12.
13.
At the end of the Post-Purge cycle, the louver relay contacts will de-energize.
At the end of the Pump Delay cycle(s), the pump(s) will be turned off.
11
1 Service
Initial Setup Screen
Figure 1-2 Rapid Setup A
Service Manual
Initial Setup
Clock and Date
The control uses an internal clock for the night setback feature and for logging of events. For these features to work correctly, the clock must be set when the boiler is first installed or anytime the boiler has been powered off for more than four (4) hours. This parameter must be accessed to set the clock. If the unit is connected to the internet, the time will adjust based on the time zone selected.
Temperature units (°C / °F)
The control can be configured to display temperature in either °C or °F.
12
Service Manual
1 Service (continued)
Viewable and changeable control parameters
CAUTION
Set Point Screens
Figure 1-3 Set points HW_Screen A
Before changing parameters, note the settings so that the unit can be returned to its original operating parameters.
Figure 1-4 Set points HW_Screen B
13
1 Service
Figure 1-5 Set points SH_Screen A
Service Manual
Table 1B Set Points (This table lists control module parameters; use the sub-tab under the Setup tab to access
them.
Menu
SET POINTS
Parameter Name
(as shown on the LCD screen)
Space Heat 1 Set point: Set point 32 185 120
Space Heat 1 Set point: Min 32 185 32
Space Heat 1 Set point: Max 32 185 185
Space Heat 1 Set point: Offset 0 36 9.9
Space Heat 1 Set point: Diff 0 72 19.8
System Pump Anti-Seize Time 0 40 0.33
High Limit: ARHL 32 200 199.4
High Limit: MRHL 0 90 0
HW Boiler Set point: Set point N/A N/A N/A
HW Boiler Set point: Offset N/A N/A N/A
HW Boiler Set point: Differential N/A N/A N/A
HW Tank Set pont: Set point N/A N/A N/A
HW Tank Set point: Min N/A N/A N/A
Min
Value Value Value
Max
Default
HW Tank Set point: Max N/A N/A N/A
HW Tank Set point: Diff N/A N/A N/A
14
1 Service (continued)
Service Manual
Set Points
Space Heat 1 Set Point: Set point
The SH set point sets the water temperature set point used during space heating calls.
Space Heat 1 Set Point: Min
The SH minimum set point sets the minimum water temperature set point that can be used for space heating operation. The user or installer will not be able to program the control with a lower SH set point.
Space Heat 1 Set Point: Max
The SH maximum set point sets the maximum water temperature set point that can be used for space heating. The user or installer will not be able to program the control with a higher SH set point.
Space Heat 1 Set Point: Offset
The SH offset sets how many degrees above set point the temperature can go before the boiler will shut off.
Space Heat 1 Set Point: Differential
The SH differential sets how many degrees below the offset the temperature has to drop before the boiler turns back on.
High Limit: ARHL
The SMART TOUCH control contains an integral Auto Reset High Limit (ARHL) on the outlet of the heat exchanger. Once the outlet temperature exceeds the ARHL set point, the boiler will shut down and lock out. Once the outlet temperature has dropped below this set point, the RESET button on the LCD display can be pressed to reset this lockout. If RESET is not pressed, the control will automatically reset the lockout after five (5) minutes.
HW Boiler Set Point: Set point
When a HW call for heat becomes active, the control will use the HW boiler set point to determine the firing rate of the boiler based on the boiler outlet water temperature.
HW Boiler Set Point: Offset
This parameter reflects the degrees above HW boiler set point the outlet temperature can go before the boiler will shut off.
HW Boiler Set Point: Differential
This parameter reflects the degrees below HW boiler offset the outlet temperature has to go before the boiler turns on.
HW Tank Set Point: Set Point
By installing a tank sensor, the SMART TOUCH control can perform the tank thermostat function. The SMART TOUCH control automatically detects the presence of this sensor, and generates a call for heat when the tank temperature drops below the tank set point minus the differential, and finishes the call for heat when the tank temperature reaches tank set point.
HW Tank Set Point: Min
This setting controls the minimum user set point for the tank temperature.
HW Tank Set Point: Max
This setting controls the maximum user set point for the tank temperature.
HW Tank Set Point: Differential
When a tank sensor is installed, the tank temperature must drop this amount below the tank set point before the boiler will turn on.
High Limit: MRHL
The SMART TOUCH control contains an integral Manual Reset High Limit (MRHL) on the outlet of the heat exchanger. Once the outlet temperature exceeds the MRHL set point, the boiler will shut down and lock out. Once the outlet temperature has dropped below this set point, the RESET button on the LCD display must be pressed to clear this lockout.
15
1 Service
Outdoor Reset Screen
Figure 1-6 Outdoor Reset A
Service Manual
Table 1C Outdoor Reset (This table lists control module parameters; use the sub-tab under the Setup tab to access
them.)
Max
Default
Menu
Set point Max 32 185 180
Set point Min 32 185 68
Outdoor Temperature: Min -22 86 23
Outdoor Temperature: Max -22 86 86
Outdoor Temp: Shutdown 32 122 79.7
Outdoor Temp: Diff 32 122 79.7
Shift OA Reset Curve -27 27 0
OUTDOOR RESET
Boost Time 0 250 20
Boost Temperature 0 25 0
Parameter Name
(as shown on the LCD screen)
Min
Value Value Value
16
1 Service (continued)
Service Manual
Outdoor Reset
Outdoor Reset Curve
The Outdoor Temp Min and Set Point Max define the upper point of the Outdoor Reset Curve. The lower point is defined by the Outdoor Temp Max and Set Point Min. The curve will level out at Set Point Min for temperature warmer than Outdoor Temp Max. The curve will continue on if the set point (set on Set Points Screen) is above the Set Point Max. The curve will be shortened if the set point is below Set Point Max.
Outdoor Temperature: Shutdown
When the outdoor temperature rises above this point, the control will block all SH demands (HW demands will still be active).
Outdoor Temperature: Differential
The outdoor air shutdown differential parameter is the number of degrees below parameter the outdoor air temperature must go before the boiler will respond to a SH demand.
Boost Temperature
If a SH demand lasts longer than the programmed boost time delay setting and there have been no HW demands, the control will increase the water temperature set point by the amount in this parameter. If the SH demand continues through another time period, the set point will be increased again. This will continue until either the SH demand ends, a maximum of 20 increases has occurred, or the maximum set point has been reached. Once the SH demand has been satisfied the set point will revert back to its calculated setting.
Shift OA Reset Curve
The shift reset curve parameter shifts the actual set point above or below the calculated set point by the number of degrees in this parameter.
Boost Time
The boost time parameter sets the amount of time that must elapse with a SH demand before the water temperature calculated set point will be increased.
17
1 Service
Ramp Delay Screen
Figure 1-7 Ramp Delay
Service Manual
Table 1D Ramp Delay (This table lists control module parameters; use the sub-tab under the Setup tab to access
them.)
Max
Default
Menu
RAMP DELAY
Parameter Name
(as shown on the LCD screen)
Ramp Delay Mode N/A N/A N/A
Step 1: Ramp Delay Time 1 40 2
Step 1: Ramp Delay Limit (%) 10 100 20
Step 2: Ramp Delay Time 1 40 2
Step 2: Ramp Delay Limit (%) 10 100 30
Step 3: Ramp Delay Time 1 40 2
Step 3: Ramp Delay Limit (%) 10 100 40
Step 4: Ramp Delay Time 1 40 1
Step 4: Ramp Delay Limit (%) 10 100 55
Step 5: Ramp Delay Time 1 40 1
Step 5: Ramp Delay Limit (%) 10 100 75
Step 6: Ramp Delay Time 1 40 1
Step 6: Ramp Delay Limit (%) 10 100 100
Min
Value Value Value
18
Loading...
+ 42 hidden pages