Lochinvar EWL200PM User Manual

EFFICIENCY+® PACKAGED
WATER HEATER
Submittal Sheet
EFFICIENCY+® GAS WATER HEATER PACKAGE SYSTEM (MODELS EW 150-300)
JOB NAME ______________________________________________________________________ LOCATION ______________________________________________________________________ ENGINEER_______________________________________________________________________ WHOLESALER __________________________________________________________________ MECH. CONTRACTOR ___________________________________________________________ MODEL NO. _____________________________________________________________________ TYPE GAS ______________________________________________________________________ Btu/hr INPUT_____________________________________________________________________ RECOVERY RATE IN GPH_______________________________________@________°F RISE GALLON CAPACITY _______________________________________________ TANK LINING___________________________________________________________________ NOTES
Standard Features
• 84% Thermal Efficiency
• Sealed Combustion Chamber
• Stainless Steel Burners
• Low NOx Operation Exceeds the most Stringent Air Quality Requirements
• ASME Copper Finned Tube Heat Exchanger
• 160 psi Working Pressure
• Gasketless Heat Exchanger Design
• All Bronze Circulating Pump
• Pump Delay w/ Freeze Protection
• Manual Reset High Limit
• Remote Tank Thermostat
• Glass-Lined Water Surfaces
• Loch-Heat Ceramic Tile Combustion Chamber
• Hot Surface Ignition
• ASME Temperature & Pressure Relief Valve
• 24 Volt Control System
• 3 Year Limited Warranty on Heat Exchanger (See warranty for details)
Optional Equipment
Place an X in the box by all options that apply
Alarm Bell Contacts on any Failure Cupro-Nickel Heat Exchanger Flow Switch Freeze Protection Low Water Cut-Off Probe Type Probe Type w/ Manual Reset Adjustable High Limit w/ Manual Reset Stack Frame
Firing Control Systems
F9 Hot Surface Ignition w/ Electronic Supervision
(Standard) F7 California Code
Efficiency+® Gas Water Heater Dimensions & Specifications
Model Btu/hr GPH @ Vent Gas Shipping Number Input 100°F Rise B D E G Size* Conn. Weight
EWN150PM 150,000 153 19-3/4 16 7-1/4 11-3/4 5 3/4 295 EWN200PM 199,999 204 23-3/4 20 9 1/4 11 3/4 5 3/4 318 EWN250PM 250,000 255 27-1/2 23-3/4 11 11 3/4 6 3/4 341 EWN300PM 300,000 305 31-1/4 27-1/2 13 11 3/4 6 3/4 363
Note: Change ‘N’ to ‘L’ for LP gas models. Water connections for models (EW 150-300) are 2” NPT on 6-1/4” centers.
Air inlet equals vent diameter. All models approved for indoor applications only. Performance data based on manufacturer test results. * Vent size is for conventional venting, venting options require 1” smaller vent diameter.
Venting Options
Direct Vent Horizontal Direct Vent Vertical E+ DirectAire Vent Conventional Outdoor
FIRING CONTROLS
F-9 (Single Stage)
MODEL NO.
AMP DRAW DATA
150,000 thru 300,000 Btu Models
PUMP AMPS 150-300
5.8
FAN
1.15
VALVE/ CON TROLS
3.97
MAXIMUM TOTAL AMPS @ 120 VAC
5.12
Horizontal Direct Vent Inlet and Outlet Cap
DIM “A”
DIM “B”
DIM “C”
DIM “D”
DIM “E”
EW 150-200 EW 250-300
9-1/8” 9-5/8”
8-7/8” 9-3/8”
7-1/8” 7-5/8”
7-3/8” 7-3/4”
4-3/8” 3-1/2”
Loading...
+ 1 hidden pages