Lochinvar CFL0402PM User Manual

COPPER-FIN II
®
WATER HEATER
Submittal Sheet
CFE-Sub-07
COPPER-FIN II® GAS WATER HEATERS (MODELS 402-2072)
Standard Features
> 85% Thermal Efficiency > Proportional Firing up to 4:1 Turndown
> Hot Surface Ignition > Low NOx Operation > Sealed Combustion > Low Gas Pressure Operation > Vertical & Horizontal Venting > Category I Venting > Double Wall “B” Vent Material > Category IV Venting > AL29-4C Stainless Steel Vent Material
> ASME Copper Finned Tube Heat Exchanger
> ASME Certified, “HLW” Stamped > Gasketless design > 160 psi working pressure > On/Off Switch > Combustible Floor Rated (CF 0992-2072) > Adjustable High Limit w/ Manual Reset > Low Lead Circulating Pump > Flow Switch > Low Air Pressure Switch > Inlet & Outlet Temperature Sensors > Easy Access Terminal Strips > Downstream Test Cocks > 150 psi ASME Temperature and Pressure Relief Valve > 1 Year Warranty on Parts (See Warranty for Details) > 5 Year Limited Warranty (See Warranty for Details)
Smart System™ Features
> SMART SYSTEM™ Operating Control
> 2 Line/16 Character LCD Display > Built in Cascading Sequencer for up to 8 water heaters > Front-End Loading Capability with Armor Water Heaters > Building Management System Integration with 0-10 VDC Input > 0-10 VDC Rate Output > Password Security
> Low Water Flow Control & Indication > Inlet & Outlet Temperature Readout > Freeze Protection > Condensing Protection > Service Reminder > Time Clock
> Data Logging
> Hours Running > Ignition Attempts > Last 10 Lockouts
> Programmable System Efficiency Optimizers
> Night Setback > Pump Control
> Water Heater Pump > Recirculation Pump
> High Voltage Terminal Strip
> 120 VAC / 60 Hertz / 1 Phase Power Supply > Pump Contacts with Pump Relay
> Low Voltage Terminal Strip
> 24 VAC Auxiliary Device Relay Output - Louvers > Auxiliary Proving Switch Contacts - Louvers > Alarm on Any Failure Contacts
> Runtime Contacts > Unit Enable/Disable Contacts > Tank Sensor Contacts > Contacts for Air Louvers > Contacts on Any Failure > Cascade Contacts > 0-10 VDC BMS External Control Contact > 0-10 VDC Rate Output Contacts
Optional Equipment
> Alarm
> High & Low Gas Pressure Switches w/ Manual Reset > Cupro-Nickel Heat Exchanger > Low Water Cut Off, Probe Type w/ Manual Reset & Test > Modbus Communications > BMS Gateway - BACnet or LonWorks > Combustible Floor Kit (CF 0402-0752) > Stack Frame
Firing Codes
> M7 Firing Code - California Code
> M9 Firing Code - Hot Surface Ignition with Electronic Supervision
Certifications
> ANSI Z21.10.3/CSA 4.3 certified
> South Coast Air Quality Management District > Texas Commission on Environmental Quality
Copper-Fin II® Gas Water Heater Dimensions & Specifications
HLW
E
GAS CONNECTION
0402-0752
A
INLET AIR
FILTER
B
G
D
F
OUTLET
H
GAS CONNECTION 0992-2072
G
INLET
C
Copper-Fin II Water Heater Dimensions & Spec i fi ca tions
Model Input GPH @ Vent Air Gas Shipping Number MBH 100°F Rise A B C D E F G H Size Inlet Conn Weight
CFN0402PM 399 412 31-1/2" 37-3/4" 22-1/4" 12-1/2" 7" 7" 29" 6-1/2" 6" 6" 1-1/4" 454 CFN0502PM 500 515 31-1/2" 45-1/2" 22-1/4" 12-1/2" 7" 7" 29" 6-1/2" 6" 6" 1-1/4" 467 CFN0652PM 650 670 31-1/2" 56-3/4" 22-1/4" 12-1/2" 8-1/2" 8-1/4" 29" 6-1/2" 8" 8" 1-1/4" 551 CFN0752PM 750 773 31-1/2" 64" 22-1/4" 12-1/2" 8-1/2" 8-1/4" 29" 6-1/2" 8" 8" 1-1/4" 611 CFN0992PM 990 1,020 36" 48-1/4" 33-1/2" 15-3/4" 8-1/2" 8-1/2" 33-3/4" 8-3/4" 10" 10" 2" 843 CFN1262PM 1,260 1,298 36" 58-1/2" 33-1/2" 15-3/4" 10-1/2" 9-1/2" 33-3/4" 8-3/4" 12" 12" 2" 939 CFN1442PM 1,440 1,484 36" 68-3/4" 33-1/2" 15-3/4" 10-1/2" 10-1/2" 33-3/4" 8-3/4" 12" 12" 2" 1,035 CFN1802PM 1,800 1,855 36" 82-1/4" 33-1/2" 15-3/4" 11" 11" 33-3/4" 8-3/4" 14" 12" 2" 1,168 CFN2072PM 2,070 2,133 36" 92-1/2" 33-1/2" 15-3/4" 11" 11" 33-3/4" 8-3/4" 14" 12" 2" 1,285
Notes: Change ‘N’ to ‘L’ for LP gas models. No deration on LP models Water connections for models CF 0402-0752 are 2” NPT on 6-1/2” centers. Header increases “B” dimension 3-1/2” for models CF 0402-0752 and 6-1/4” for models CF 0992-2072 Water connections for models CF 0992-2072 are 2-1/2” NPT on 11-1/4” centers. Pump and flanges are shipped loose for field installation. Performance data is based on manufacturer test results.
Venting Options
Aire-LockTM Direct Vent Sealed Combustion
DirectAire® Vertical
DirectAire® Vertical w/ Sidewall Inlet
Outdoor Installation
Power DirectAire® Horizontal
Powered Side Wall
Sidewall
Lochinvar, LLC 300 Maddox Simpson Parkway Lebanon, Tennessee 37090 P: 615.889.8900 / F: 615.547.1000
Lochinvar.com
4/16—Printed in U.S.A.
Loading...