WATER HEATER PRODUCT SUMMAR
(CF) 400,000 - 2,070,000 BTU/HR
CF-402 CF-502 CF-652 CF-752 CF-0992 CF-1262 CF-1442 CF-1802 CF-2072
WATER
GALLON CAPACITY 1.5 1.7 1.9 2.0 3.4 3.7 4.1 4.5 4.8 HEATING SURFACE (SQ. FT.) 46.9 59.0 76.8 88.1 96.0 120.2 144.0 176.0 200.0 WATER CONNECTIONS 2” 2” 2” 2” 2-1/2” 2-1/2” 2-1/2” 2-1/2” 2-1/2” DRAIN 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” WATER FLOW RATE (GPM) 55555555909090 90 90 HEAD LOSS (FT. OF HD.) 6.4 6.5 6.7 6.8 5.8 6.6 7.2 8.4 9.2 MAX. WORKING PRESSURE (PSI) 160 160 160 160 160 160 160 160 160 MAX. WATER HARDNESS (GRAINS) 25 25 25 25 25 25 25 25 25 GPH @ 70°F RISE 589 736 957 1,104 1,457 1,855 2,120 2,650 3,047 GPH @ 100°F RISE 412 515 670 773 1,020 1,298 1,484 1,855 2,133 GPH @ 140°F RISE 294 368 479 552 729 927 1,060 1,325 1,524 # OF RELIEF VALVES 1111111 1 2 RELIEF VALVE SIZE 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” RELIEF VALVE RATING (MBH) 500 1,912 1,912 1,912 1,912 1,912 1,912 1,912 1,912 RELIEF VALVE PRESSURE RATING (PSI) 150 150 150 150 150 150 150 150 150 RELIEF VALVE TEMPERATURE RATING (°F) 210 210 210 210 210 210 210 210 210
GAS
INLET CONNECTION 1-1/4” 1-1/4” 1-1/4” 1-1/4” 2” 2” 2” 2” 2” MAX. INLET PRESSURE, NAT 14” w.c. 14” w.c. 14” w.c. 14” w.c. 14” w.c. 14” w.c. 14” w.c. 14” w.c. 14” w.c. MIN. INLET PRESSURE, NAT 4.5” w.c. 4.5” w.c. 4.5” w.c. 4.5” w.c. 4.5” w.c. 4.5” w.c. 4.5” w.c. 4.5” w.c. 4.5” w.c. MANIFOLD PRESSURE, NAT 1.8” w.c. 1.8” w.c. 1.8” w.c. 1.8” w.c. 1.2” w.c. 1.2” w.c. 1.2” w.c. 1.2” w.c. 1.2” w.c. MAX. INLET PRESSURE, LP 14” w.c. 14” w.c. 14” w.c. 14” w.c. 14” w.c. 14” w.c. 14” w.c. 14” w.c. 14” w.c. MIN. INLET PRESSURE, LP 8.0” w.c. 8.0” w.c. 8.0” w.c. 8.0” w.c. 8.0” w.c. 8.0” w.c. 8.0” w.c. 8.0” w.c. 8.0” w.c. MANIFOLD PRESSURE, LP 4.6” w.c. 4.6” w.c. 4.6” w.c. 4.6” w.c. 4.6” w.c. 4.6” w.c. 4.6” w.c. 4.6” w.c. 4.6” w.c. BTU/HR INPUT 399,999 500,000 650,000 750,000 990,000 1,260,000 1,440,000 1,800,000 2,070,000
ELECTRICAL
VOLTAGE/HEATER 120 120 120 120 120 120 120 120 120 VOLTAGE/PUMP 120 120 120 120 120 120 120 120 120 VOLTAGE/CONTROL 24242424242424 24 24 TOTAL AMPS W/PUMP 12.1 12.1 14.6 14.6 17.9 17.9 21.4 21.4 21.4
DIMENSIONS
HEIGHT 31-1/2” 31-1/2” 31-1/2” 31-1/2” 36” 36” 36” 36” 36” WIDTH (INCLUDES PUMP) 56-1/4” 64” 75-1/4” 82-1/2” 68-3/4” 79” 89-1/4” 102-3/4” 113” DEPTH 22-1/4” 22-1/4” 22-1/4” 22-1/4” 33-1/2” 33-1/2” 33-1/2” 33-1/2” 33-1/2”
SERVICE CLEARANCES
FRONT 30” 30” 30” 30” 30” 30” 30” 30” 30” BACK 3” 3” 3” 3” 3” 3” 3” 3” 3” RIGHT SIDE 3” 3” 3” 3” 3” 3” 3” 3” 3” LEFT SIDE (PIPING) 24” 24” 24” 24” 24” 24” 24” 24” 24” TOP 3”3”3”3”3”3”3” 3” 3
VENTING
SIZE 6” 6” 8” 8” 10” 12” 12” 14” 14” VENT CATEGORY IIIIIII I I VENT MATERIAL B-VENT B-VENT B-VENT B-VENT B-VENT B-VENT B-VENT B-VENT B-VENT MAXIMUM DRAFT -0.08” w.c. -0.08” w.c. -0.08” w.c. -0.08” w.c. -0.08” w.c. -0.08” w.c. -0.08” w.c. -0.08” w.c. -0.08” w.c. MINIMUM DRAFT -0.02” w.c. -0.02” w.c. -0.02” w.c. -0.02” w.c. -0.02” w.c. -0.02” w.c. -0.02” w.c. -0.02” w.c. -0.02” w.c.
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
CF-PS-07 (Replaces CF-PS-06 05/11)
www.Lochinvar.com
6/11-Printed in U.S.A.