Lochinvar CBN045, CBN075, CBN090, CBN135, CBN180 Installation Manual

...
Page 1
SBRX-I-S_100161690_2000017139_Rev G
Installation & Service Manual
Models: 45,000 - 260,000 Btu/hr
This manual supplies information for the installation, operation, and servicing of the appliance. It is strongly recommended that this manual be reviewed completely before proceeding with an installation. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
Save this manual for future reference.
Page 2
Contents
HAZARD DEFINITIONS .................................................... 2
PLEASE READ BEFORE PROCEEDING ..................... 3-4
RATINGS ........................................................................... 5
THE SOLUTION -- HOW IT WORKS................................... 6-8
1. DETERMINE BOILER LOCATION
Location of Unit .................................................................. 9
Clearances ......................................................................... 9
Combustion and Ventilation Air .................................. 10-12
2. VENTING
A Conventional Negative Draft Venting System ......... 13-14
Vertical Vent Termination Clearances ............................. 15
Masonry Chimney Installation .......................................... 16
Inspection of a Masonry Chimney .............................. 16
Automatic Vent Damper ................................................... 17
3. GAS CONNECTIONS
Gas Supply ....................................................................... 18
Gas Pressure Test ........................................................... 18
Gas Connection ............................................................... 18
Gas Piping ........................................................................ 19
Gas Manifold Pressure Adjustment Procedure ................ 20
Checking Gas Supply Pressure ....................................... 21
Combination Gas Valves .................................................. 22
4. WATER CONNECTIONS
Relief Valve ...................................................................... 23
Water Flow Switch (if equipped) ...................................... 23
Low Water Cutoff (if equipped) ........................................ 24
Typical Heating Boiler Installations ............................. 24-25
Piping of the Boiler System .............................................. 25
Performance Loop ............................................................ 27
Primary/Secondary Boiler Piping ................................ 27-28
Low Temperature Bypass Requirements ......................... 28
Boiler Flow Rates ............................................................. 28
Primary / Secondary Piping ................................... 29-31
Full System Flow ........................................................ 32
5. ELECTRICAL CONNECTIONS
Room Thermostat or Remote Thermostat Connection .... 33
Auxiliary Device Connection to Terminal Strip ................. 33
Pump Wiring for a Heating Boiler .................................... 34
Boiler Operating Temperature Control ............................. 34
Additional Temperature Controls ................................ 34-35
Temperature Adjustment .................................................. 35
Temperature Control Settings .......................................... 36
Maximum Set Point Determination .................................. 36
Wiring of the Outdoor Air Sensor ..................................... 38
6. STARTUP
Initial Startup .................................................................... 39
Lighting Instructions for Spark Ignition Pilot Models (M9) ....... 39
Safety Shutoff Test for Spark Ignition Pilot System ............ 40
Water Treatment ............................................................................. 41
Intermittent Pilot Spark Ignition System (M9) ........................ 43
Freeze Protection ........................................................................... 43
7. MAINTENANCE
Maintenance and Annual Startup ................................ 44-49
8. TROUBLESHOOTING
Checking Temperature Sensors ...................................... 50
Troubleshooting Guide: M9 Solution Boilers .................. 51
9. DIAGRAMS .................................................................. 52
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
2
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
Page 3
Please read before proceeding
Installation & Service Manual
NOTICE
WARNING
This is a gas appliance and should be installed by a licensed electrician and/or certified gas supplier. Service must be performed by a qualified service installer, service agency or the gas supplier.
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.
This appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present, unless the installation is such to eliminate the probable ignition of gasoline or flammable vapors.
What to do if you smell gas –
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a near by phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
WARNING
Improper installation, adjustment, alteration, service or maintenance can result in severe personal injury, death, or substantial property damage. Refer to this manual for assistance or additional information, consult a qualified installer, service agency or the gas supplier.
Checking equipment –
Upon receiving equipment, check for signs of shipping damage. Pay particular attention to parts accompanying the appliances which may show signs of being hit or otherwise being mishandled. Verify total number of pieces shown on the packing slip with those actually received. In case there is damage or a shortage, immediately notify the carrier.
Do not use this appliance if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
Owner warning –
NOTE: Retain this manual for future reference.
The information contained in this manual is intended for use by qualified professional installers, service technicians, or gas suppliers. Consult your local expert for proper installation
or service procedures.
Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
Warranty –
Installation and service must be performed by a qualified service installer, service agency or the gas supplier.
Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated.
Experience has shown that improper installation or system design, rather than faulty equipment, is the cause of most operating problems.
1. Excessive water hardness causing a lime/scale build-up in the copper tube is not the fault of the equipment and is not covered under the manufacturer’s warranty (see Water Treatment and Water Chemistry).
2. Excessive pitting and erosion on the inside of the copper tube may be caused by too much water velocity through the tubes and is not covered by the manufacturer’s warranty (see Boiler Flow Rates and Temperature Rise for flow requirements).
IMPORTANT
Your conventionally vented gas appliance must have a supply of fresh air circulating around it during burner operation for proper gas combustion and proper venting.
WARNING
Consult and follow all local Building and Fire Regulations and other Safety Codes that apply to this installation. Consult your local gas utility company to authorize and inspect all gas and flue connections.
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
33
Page 4
Please read before proceeding
Installation & Service Manual
WARNING
To minimize the possibility of serious personal injury, fire, or damage to your appliance, never violate the following safety rules:
1. Boilers are heat producing appliances. To avoid damage or injury, do not store materials against the appliance or the vent-air intake system. Use proper care to avoid unnecessary contact (especially children) with the appliance and vent-air intake components.
2. Never cover your appliance, lean anything against it, store trash or debris near it, stand on it or in any way block the flow of fresh air to your appliance.
3. UNDER NO CIRCUMSTANCES must flammable materials such as gasoline or paint thinner be used or stored in the vicinity of this appliance, vent-air intake system or any location from which fumes could reach the appliance or vent-air intake system.
Codes –
The equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made. In the absence of such requirements, the installation shall conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1. All boilers conform to the latest edition of the ASME Boiler and Pressure Vessel Code, Section IV. Where required by the authority having jurisdiction, the installation must comply with the Canadian Association Code, CAN/CGA-B149.1 and/or B149.2 and/or local codes.
This appliance meets the safe lighting performance criteria with the gas manifold and control assembly provided as specified in the ANSI standards for gas-fired appliances, ANSI Z21.13 and ANSI Z21.10.3.
Boiler water –
Thoroughly flush the system to remove debris. Use an approved pre-commissioning cleaner (see Start-Up Section), without the boiler connected, to clean the system and remove sediment. The high-efficiency heat exchanger can be damaged by build-up or corrosion due to sediment.
NOTE: Cleaners are designed for either new systems or pre-existing systems. Choose accordingly.
Prevention of freezing –
Heat exchangers and headers damaged by freezing are not covered by warranty.
See Section 6, Start-Up - Freeze Protection for more information.
4
Page 5
Ratings
Installation & Service Manual
Solution Boiler
AHRI Rating
Model Number
Note: Change
“N” to “L”
for LP gas
models
CBN045 23 45 37 32
CBN075 38 75 62 54
CBN090 45 90 75 65
CBN135 68 135 112 97
CBN180 90 180 149 130
CBN215 108 215 178 155
CBN260 130 260 216 188
NOTICE
Maximum allowed working pressure is located on the rating plate.
Input MBH
(Note 4)
Min Max
Gross
Output
MBH
(Note 1,5)
Net
AHRI
Ratings
Water,
MBH
(Note 1,5)
Other Specifications
Boiler Water
Content Gallons
0.87 1 1/2" 1/2" 4"
0.91 1 1/2" 1/2" 5"
0.91 1 1/2" 1/2" 5"
0.95 1 1/2" 1/2" 6"
0.99 1 1/2" 3/4" 7"
1.02 1 1/2" 3/4" 7"
1.06 2" 3/4" 8"
Water
Connections
Gas
Connections
Vent Size
(Note 3)
Notes:
1. The ratings are based on standard test procedures prescribed by the United States Department of Energy.
2. Net AHRI ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15.
3. Use only the vent materials and methods specified in the Installation and Service Manual.
4. The Solution is orificed for operation up to 2000 feet altitude. The ap pli ance will be derated 4% per 1000 feet above 2000 feet el e va tion. Consult the factory for installations above 2000 feet elevation.
5. Ratings have been confirmed by the Hydronics Section of AHRI.
UNIT EQUIPPED FOR
HIGH ALTITUDE
UP TO 2000 FT.
Figure A High Altitude Label Location
5
Page 6
The Solution - How it works...
Installation & Service Manual
1. Control panel cover
The control panel cover provides access to the thermostat, ignition module, and transformer.
2. Burner (not shown)
The burner is a cylindrical stainless steel tube used to regulate burner flame.
3. Drain port
Location from which the heat exchanger can be drained.
4. Flue outlet
The flue outlet allows the connection of the vent pipe to the unit.
5. Gas connection
The gas pipe connection on this appliance is 1/2", or 3/4" NPT. To deliver the correct amount of gas volume to the appliance it may be necessary to have a larger gas line reduced at the appliance. Please reference the National Fuel Gas Code charts for more details.
6. Gas valve
The gas valve allows the proper amount of gas to pass into the burner for combustion.
7. Heat exchanger
The heat exchanger allows system water to flow through specially designed tubes for maximum heat transfer. The glass lined headers and copper finned tubing are encased in a jacket that contains the combustion process.
8. High limit sensor
Device that monitors the outlet water temperature to ensure safe operation. If the temperature exceeds its setting, it will break
the control circuit, shutting the appliance down.
9. Ignition module
The ignition module responds to a call for heat signal to provide burner operation.
16. Sight Glass
The sight glass provides a view of the burner surface, burner flame,
and the pilot flame.
17. Temperature and pressure gauge
The temperature and pressure gauge monitors the outlet temperature of the appliance as well as the system water pressure.
18. Temperature sensor
This sensor monitors inlet water temperature. If selected as the controlling sensor, the appliance will maintain the set point at this sensor.
19. Terminal strip
The boiler is equipped with a terminal strip on the left side of the unit to allow easy connection to contact points.
20. Top panel
Removable panel to gain access to the internal components.
21. Thermostat
The thermostat monitors the water temperature via a temperature sensor and will initiate a call for heat when the water temperature drops below the set point plus the differential on the thermostat.
22. Transformer The transformer reduces 120 VAC supply voltage to 24 VAC for the
control circuit.
23. Water inlet (system return)
The water inlet is a 1 1/2" pipe connection that receives water from the system and delivers it to the heat exchanger.
24. Water outlet (system supply)
The water outlet is a 1 1/2" pipe connection that supplies water to the system with connections for a flow switch, a relief valve, and a temperature and pressure gauge.
10. Junction box
The junction box contains the connection points for the line voltage power and all pumps.
11. Performance loop
A pumped bypass provides constant flow through the heat exchanger when the building system flow is reduced.
12. Performance Loop Pump
The pump ensures adequate flow to operate the unit.
13. Pilot (not shown) The pilot is a spark ignition device used to light a pilot flame which
in turn is used to light the main burners.
14. Pump relay
The pump relay energizes the pump on a call for heat.
15. Relief valve
The relief valve is a safety device that ensures the maximum pressure of the appliance is not exceeded.
6
25. Gas manifold pipe
Delivers gas from the gas valve to the main burners through a number of orifices.
Page 7
The Solution - How it works... (continued)
Installation & Service Manual
10
17
15
8
3
5
Models 45,000 - 90,000 Btu/hr Front View
4
20
1
19
Models 45,000 - 90,000 Rear View
23
11
14
16
25
22
21
7
18
9
12
6
24
Models 45,000 - 90,000 Right Side (inside unit)
Models 45,000 - 90,000 Left Side (inside unit)
7
Page 8
The Solution - How it works...
Installation & Service Manual
10
17
15
8
3
5
Models 135,000 - 260,000 Btu/hr Front View
4
1
19
20
Models 135,000 - 260,000 Btu/hr Rear View
11
23
14
21
25
22
Models 135,000 - 260,000 Btu/hr Right Side (inside unit)
7
9
3
3
Models 135,000 - 260,000 Btu/hr Left Side (inside unit)
18
12
6
24
8
Page 9
1 Determine boiler location
Installation & Service Manual
Location of unit
1. Locate the appliance so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict combustion air flow. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this appliance, or any of its components.
2. The appliance must be installed indoors where it is protected from exposure to wind, rain and weather.
3. The appliance must be installed so that the ignition system components are protected from water (dripping, spraying, rain, etc.,) during appliance operation and service (circulator replacement, control replacement, etc.,).
4. Appliances located in a residential garage and in adjacent spaces that open to the garage and are not part of the living space of a dwelling unit must be installed so that all burners and burner ignition devices have a minimum clearance of not less than 18" (46cm) above the floor. The appliance must be located or protected so that it is not subject to physical damage by a moving vehicle.
Recommended Service Clearances:
Left - 24” Front - 24”
14" TOP
6 " RIGHT
6 " REAR
18 " FRONT
18 " LEFT
Figure 1-1_Alcove Installation - Models 45,000 - 180,000 Btu/hr
Recommended Service Clearances:
Left - 24” Front - 24”
5. DO NOT install this appliance in any location where gasoline or flammable vapors are likely to be present.
6. All units have been approved for alcove installation (an ALCOVE is a closet enclosure without a front door).
7. The appliance must not be installed on carpet.
8. All units have been approved for use on combustible surfaces.
9. Allow sufficient space for servicing pipe connections, pump and other auxiliary equipment, as well as the appliance.
NOTICE
Clearances from combustible construction are noted on the appliance rating plate.
29" TOP
6 " RIGHT
6 " REAR
18 " FRONT
18 " LEFT
Figure 1-2_Alcove Installation - Models 215,000 - 260,000 Btu/hr
9
Page 10
1 Determine boiler location
Combustion and ventilation air requirements for conventionally vented appliances
Provisions for combustion and ventilation air must be in accordance with, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
The room where the appliance is installed MUST be provided with properly sized openings to assure adequate combustion air and proper ventilation when the appliance is installed with conventional venting.
Installation & Service Manual
Figure 1-4_Combustion Air Through Ducts
2. If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the room where the appliance is installed, each of the two openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr (11cm2 per kW) (see FIG. 1-4).
Figure 1-3_Combustion Air Direct from Outside
1. If air is taken directly from outside the building with no duct, provide two permanent openings (see FIG. 1-3):
(a) Combustion air opening, with a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm2 per kW). This opening must be located within 12" (30 cm) of the floor.
(b) Ventilation air opening, with a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm located within 12" (30 cm) of the ceiling.
2
per kW). This opening must be
Figure 1-5_Combustion Air from Interior Space
3. If air is taken from another interior space that is adequately ventilated, each of the two openings specified above should have a net free area of one square inch for each 1000 Btu/ hr (22cm2 per kW) of input, but not less than 100 square inches (645cm2) (see FIG. 1-5).
10
Page 11
Installation & Service Manual
1 Determine boiler location (continued)
Figure 1-6_Combustion Air from Outside Single Opening
4. If a single combustion air opening is provided to bring combustion air in directly from the outdoors, the opening must be sized based on a minimum free area of one square inch per 3000 Btu/hr (7 cm2 per kW). This opening must be located within 12" (30 cm) of the top of the enclosure (see FIG. 1-6).
Combustion air require ments are based on the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada refer to National Standard CAN B149.1. Check all local code re quire ments for combustion air.
All dimensions are based on net free area in square inch es. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers. Where two openings are pro vid ed, one must be within 12" (30 cm) of the ceiling and one must be within 12" (30 cm) of the floor of the room where the appliance is installed. Each opening must have a net free area as specified in Table 1B (on page 12). Single openings shall be located with in 12" (30 cm) of the ceiling.
CAUTION
The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as freon, tricholorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the heat exchanger finned tubes, headers, flue collectors, and the vent system. The result is improper combustion and a non-warrantable, premature appliance failure.
The result is improper combustion and a non-warrantable, premature appliance failure.
EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a downdraft in the venting system. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be immediately corrected. If a fan is used to supply combustion air to the equipment room, the installer must make sure that it does not cause drafts which could lead to nuisance operational problems with the appliance.
Under no circumstances should the room where the appliance is installed ever be under a negative pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the appliance.
11
Page 12
1 Determine boiler location
TABLE - 1B
MINIMUM RECOMMENDED COMBUSTION
AIR SUPPLY TO EQUIPMENT ROOM
Installation & Service Manual
Input
Btu/hr
45,000
75,000
90,000
135,000
180,000
215,000
260,000
*Outside Air from
2 Openings Directly from
Outdoors
Top
Opening, in
12
(78 cm2)
19
(123 cm2)
23
(148 cm2)
34
(220 cm2)
45
(291 cm2)
54
(349 cm2)
65
(420 cm2)
Bottom
2
Opening, in
(78 cm2)
(123 cm2)
(148 cm2)
(220 cm2)
(291 cm2)
(349 cm2)
(420 cm2)
12
19
23
34
45
54
65
*Outside Air from 1 Opening Directly from Outdoors, in
2
15
(97 cm2)
25
(162 cm2)
30
(194 cm2)
45
(291 cm2)
60
(388 cm2)
72
(465 cm2)
87
(562 cm2)
2
*Outside Air from
2 Ducts Delivered from
Outdoors
Top
Opening, in
23
(149 cm2)
38
(246 cm2)
45
(291 cm2)
68
(439 cm2)
90
(581 cm2)
108
(697 cm2)
130
(839 cm2)
Bottom
2
Opening, in
(149 cm2)
(246 cm2)
(291 cm2)
(439 cm2)
(581 cm2)
(697 cm2)
(839 cm2)
23
38
45
68
90
108
130
**Inside Air from
2 Ducts Delivered from
Interior Space
Top
2
Opening, in
(646 cm2)
(646 cm2)
(646 cm2)
(871 cm2)
(1,162 cm2)
(1,388 cm2)
(1,678 cm2)
100
100
100
135
180
215
260
2
Bottom
Opening, in
100
(646 cm2)
100
(646 cm2)
100
(646 cm2)
135
(871 cm2)
180
(1,162 cm2)
215
(1,388 cm2)
260
(1,678 cm2)
2
*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings. The above requirements are for the boiler only; additional gas fired appliances in the equipment room will require an increase in the net free area to supply adequate combustion air for all appliances.
**Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction”. For buildings of *“Tight Construction”, provide air openings into the building from outside.
*No combustion air openings are needed when the water heater is installed in a space with a volume NO LESS than 50 cubic feet per 1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction”.
*”Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour).
Vent installations for connection to gas vents or chimneys must be in accordance with “Vent ing of Equipment,” of the latest edition of the Na tion al Fuel Gas Code, ANSI Z223.1, in Canada, the latest edi tion of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment or applicable pro vi sions of the local building codes.
Adequate combustion and ventilation air must be sup plied to the room where the appliance is installed in accordance with the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Stan dard B149 Installation Code for Gas Burning Ap pli anc es
The distance of the vent terminal from adjacent build ings, windows that open and building open ings MUST comply with the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 In stal la tion Code for Gas Burn ing Appliances and Equip­ment.
Vent connection is made directly to the top of the ap pli ance. This appliance is designed with a built-in draft diverter. No additional external draft hood is re quired. The connection from the appliance vent to the common vent or
chimney must be made as direct as possible. and Equipment, or applicable pro vi sions of the local building codes.
12
Page 13
2 Venting
Installation & Service Manual
A Conventional Negative Draft Venting System
The negative draft in a conventional vent in stal la tion must be within the range of a negative 0.02 to 0.05 inches water column to ensure proper operation. All draft read­ings are made while the appliance is in stable op er a tion (approximately 2 to 5 minutes).
Multiple appliance installations with combined vent ing or common venting with other negative draft ap pli anc es require that each appliance must have draft with in the proper range. If the draft mea sured above the appliance’s built-in draft diverter ex ceeds the specified range in a dedicated chimney for a single appliance installation or in combined venting with other negative draft appliances, a baro met ric damper
must be in stalled to control draft.
TABLE - 2A
VENT PIPE SIZES
Input Btu/hr Flue Size
45,000 4"
75,000 5"
90,000 5"
135,000 6"
180,000 7"
215,000 7"
260,000 8"
On a conventionally vented, negative draft ap pli ance, the connection from the vent to the chimney or vent termination on the outside of the building MUST be made with listed Type “B” double wall (or equivalent) vent connectors and must be direct as possible with no reduction in diameter. Use the National Fuel Gas Code venting tables for dou ble wall vent to properly size all vent connectors and stacks. The Type “B” vent and accessories, such as firestop spacers, thim bles, caps, etc., MUST be installed in accordance with the manufacturer’s list ing. The vent connector and firestop must provide correct spacing to combustible surfaces and seal to the vent connector on the upper and lower sides of each floor or ceiling through which the vent connector passes.
Figure 2-1_Conventional Negative Draft Vertical Venting
Any vent materials used must be listed by a na tion al ly recognized test agency for use as vent ma te ri al.
13
Page 14
2 Venting
Locate appliance as close as possible to a chimney or gas vent.
Avoid long horizontal runs of the vent pipe, 90° el bows, reductions and restrictions. Horizontal por tions of the venting system shall be supported to prevent sagging. Horizontal runs must slope up wards not less than 1/4 inch per foot (21 mm/m) from the appliance to the vent terminal. Follow manufacturer’s instructions.
Do not use an existing chimney as a raceway for a flue pipe if another appliance or fireplace is vented through the chimney.
The weight of the venting system must not rest on the appliance. Adequate support of the venting sys tem must be provided in compliance with local codes and other applicable codes. All connections should be secured with rustproof sheet metal screws.
Vent connectors serving appliances vented by nat u ral draft shall not be connected to any portion of a me chan i cal draft system operating under positive pres sure. Connection to a positive pressure chim ney may cause flue products to be discharged into the living space causing serious health injury.
Common venting systems may be too large when an existing appliance is removed. At the time of removal of an existing appliance, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while other appliances remaining con nect ed to the common venting system are not in operation.
Installation & Service Manual
(e) Test for spillage at the draft hood/relief opening after
5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
(f) After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and other gas burning ap pli anc es to their previous conditions of use.
(g) Any improper operation of the common venting
system should be corrected so that the installation conforms to the latest edition of the Na tion al Fuel Gas Code, ANSI Z223.1. In Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment. When resizing any por tion of the common venting system, the common venting system should be resized to ap proach the min i mum size as determined using the appropriate tables in Part 11 in the latest edition of the National Fuel Gas Code, ANSI Z223.1. In Canada, the latest edition of CGA Stan dard B149 Installation Code for Gas Burning Appliances and Equipment.
(a) Seal any unused opening in the common venting
system.
(b) Visually inspect the venting system for proper size
and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
(c) Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any other appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer ex haust fan. Close fireplace dampers.
(d) Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
14
Page 15
Y
2 Venting (continued)
Vertical Vent Termination Clearances
Installation & Service Manual
10' OR LESS
10' OR LESS
10' OR LESS
2' MIN
RIDGE
CHIMNEY
3' MIN
Figure 2-2_Vent Termination from Peaked Roof 10' or Less from Ridge
MORE THAN 10'
10'
2' MIN
RIDGE
CHIMNE
3' MIN
2' MIN
CHIMMEY
WALL OR PARAPET
2' MIN
3' MIN
CHIMMEY
Figure 2-4_Vent Termination from Flat Roof 10' or Less from Parapet Wall
10' OR MORE
3'
NOTE: NO HEIGHT ABOVE PARAPET REQUIRED WHEN DISTANCE FROM WALLS OR PARAPETS IS MORE THAN 10'.
Figure 2-3_Vent Termination from Peaked Roof More than 10' from Ridge
The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.61m) above the high est point of the roof within a 10 foot (3.05m) radius of the termination. The vertical termination must be a minimum of 3 feet (0.91m) above the point of exit.
A vertical terminal less than 10 feet (3.05m) from a parapet wall must be a minimum of 2 feet (0.61m) higher than the parapet wall.
The vent cap should have a minimum clearance of 4 feet (1.22m) horizontally from and in no case above or below, unless a 4 foot (1.22m) horizontal distance is maintained from electric meters, gas meters, reg u la tors and relief equipment.
The venting system shall terminate at least 3 feet (0.9m) above any forced air inlet within 10 feet (3.05m).
The venting system shall terminate at least 4 feet (1.2m) below, 4 feet (1.2m) horizontally from, or 1 foot (30cm) above any door, window or gravity air inlet into any building.
WALL OR PARAPET
CHIMNEY
Figure 2-5_Vent Termination from Flat Roof More Than 10' from Parapet Wall
Do not terminate the vent in a window well, stair well, alcove, courtyard or other recessed area. The vent can not terminate below grade. The bot tom of the vent terminal shall be located at least 12 inches (30cm) above grade.
To avoid a blocked vent condition, keep the vent cap clear of snow, ice, leaves, debris, etc.
Flue gases will form a white plume in winter. Plume could obstruct window view.
Flue gas condensate can freeze on exterior sur fac es or on the vent cap. Frozen condensate on the vent cap can result in a blocked vent condition. Flue gas condensate can cause discoloration of exterior build ing surfaces. Adjacent brick or masonry sur fac es should be protected with a rust resistant sheet metal plate.
NOTICE
Examine the venting system at least once a year. Check all joints and vent pipe con nec tions for tightness. Also check for corrosion or de te ri o ra tion. Immediately correct any problems ob served in the venting system.
15
Page 16
2 Venting
Installation & Service Manual
Masonry Chimney Installation
A masonry chimney must be properly sized for the installation of a gas fired appliance. Venting of an appliance into a cold or oversized masonry chimney can result in op er a tion al and safety problems. Exterior masonry chim neys, with one or more sides exposed to cold out door tem per a tures, are more likely to have venting problems. The temperature of the flue gases from an appliance may not be able to suf fi cient ly heat the ma son ry structure of the chim ney to generate proper draft. This will result in condensing of flue gases, damage the masonry flue/tile, insufficient draft and possible spill age of flue gases into an occupied living space. Care ful ly in spect all chimney systems before installation. If there is any doubt about the sizing or condition of a masonry chimney, it must be relined with a prop er ly sized and approved chimney liner system.
Inspection of a Masonry Chimney
A masonry chimney must be carefully inspected to determine its suitability for the venting of flue gas es. A clay tile lined chimney must be structurally sound, straight and free of misaligned tile, gaps between liner sections, missing sections of liner or any signs of con den sate drainage at the breaching or clean out. If there is any doubt about the condition of a masonry chimney, it must be relined. An unlined masonry chimney must not be used to vent flue gases from this appliance. An unlined chimney must be relined with an approved chimney liner system when a new appliance is be ing attached to it. Metallic liner systems (Type “B” double wall or flexible or rigid metallic liners) are recommended. Consult with local code officials to determine code requirements or the advisability of using or relining a masonry chimney.
Sidewall Venting - Negative Draft
This appliance is NOT approved for sidewall venting as shipped from the factory. If installation requires that the flue gases be vented out a sidewall, either an induced draft fan or a power venter MUST be used. A power venter that plugs directly into the vent damper plug is available for models up to 135,000 Btu/hr and may be used for both sidewall and vertical venting configurations, see Fan Assisted Venting. Larger models may use an induced draft fan, which will connect to the terminal strip on the side of the boiler, see Auxiliary Power Venting Connection to Terminal Strip, page 33 for more information. A properly sized and in stalled induced draft fan may also be used to vent the flue gases ver ti cal ly if required by jobsite re stric tions. The induced draft fan must be listed by a nationally recognized test agency, be properly sized and installed per the rec om men da tions of the in duced draft fan manufacturer and meet local code requirements. Use care to ensure that the me chan i cal ly supplied draft operates within the range of a negative 0.02 to 0.05 inches water column to ensure proper operation.
If draft exceeds the spec i fied range, the fan must be adjusted
or the installation of a baro met ric damper in the flue may be
required to prop er ly control draft. An induced draft fan MUST
be interlocked into the appliance’s control circuit to start when
the appliance calls for heat. The in duced draft fan MUST also
be equipped with a prov ing switch, properly interlocked into
the ap pli ance’s con trol circuit to prove fan operation before
the main burn ers are allowed to fire. A vertical or sidewall vent
termination for an induced draft fan MUST be in stalled per the
recommendations of the fan manufacturer and provide proper
clearances from any combustion or ventilation openings,
win dows, doors or other open ings into the building. All
induced draft fan in stal la tions must comply with local code
requirements.
Fan Assisted Venting
A Power Venter Kit is available on Models 45,000 - 135,000 Btu/hr only
(see Table 2B).
TABLE 2B - VENT MATERIALS
Kit
Number
KIT3103
KIT3104
Minimum Vent Length = 12 Equivalent Feet*
Maximum Vent Length = 25 Equivalent Feet*
CAUTION
NOTE: In Canada, CPVC and PVC vent pipe,  ttings and
cement/primer must be ULC-S636 certi ed.
WARNING
Figure 2-6_Unit with Fan Assisted Venting
Input
Btu/hr
45,000 PVC Rated (CPVC Optional) 75,000 PVC Rated (CPVC Optional) 90,000 CPVC Rated
135,000 CPVC Rated
(ALL UNITS)
(ALL UNITS)
* Equivalent Feet: 90° Elbow = 5 Feet 45° Elbow = 3 Feet
DO NOT use Radel or cellular (foam) core PVC or CPVC pipe.
DO NOT insulate PVC or CPVC venting materials. Use of insulation will cuase increased vent wall temperatures, which could result in vent pipe failure.
Material
16
Page 17
D
2 Venting (continued)
Automatic Vent Damper
Installation & Service Manual
This heating boiler is design certified for use with the automatic vent damper (FIG. 15) part number printed on the boiler’s rating plate. A vent damper must be installed on all residential heating boilers with inputs of less than 300,000 Btu/hr to comply with minimum efficiency requirements. A vent damper is factory supplied with residential heating boilers with inputs of 45,000 - 260,000 Btu/hr.
The vent damper is a useful tool for saving energy when installed inside the living space where air can cir cu late freely around the appliance. The vent damper will not save as much, if any, energy if it is installed in locations such as:
- Unheated garage
- Attic
- Crawlspace
- Mechanical room that is vented outdoors
For installation and maintenance on the vent damper, refer to the instructions supplied with the vent damper.
Residential heating boilers with inputs of less than 300,000 Btu/hr must have the vent damper prop er ly installed and the vent damper wire harness plugged into the ter mi nal block on the side of the control panel to allow the boiler to function.
CAUTION
Do not install the vent damper within 6" (152 mm) of combustible materials.
Install the vent damper to service only the single ap pli ance for which it is intended. If improperly installed, a hazardous condition such as an ex plo sion or carbon monoxide poisoning could result.
VENT DAMPER
SECURE EXCESS SLACK WITH WIRE CLIP (PICTURED) OR ZIP TIES
DIR #2000556517 00
IR #2000556517 00
Figure 2-7_Vent Damper and Vent Damper Terminal Block
WARNING
The vent damper must be installed directly on the flue outlet located on the top of the draft hood (see FIG. 2-7). Do not alter the wire har ness sup plied with the vent damper. Follow the instructions supplied with the vent damper.
CAUTION
An appliance which is shut down or will not operate may experience freezing due to con vec­tive air flow down the flue pipe connected to the unit. Proper freeze protection must be pro vid ed, see Freeze Pro tec tion.
The damper position indicator must be in a visible lo ca tion with access for service following in stal la tion. The damper must be in an open position when appliance main burners are operating.
If there is excess slack in the vent damper wire after vent damper installation, use the kit-provided wire clip or zip ties to secure the wire. If using the kit-provided wire clip, fasten the wire clip to the side of the boiler using the kit-provided screw. Loop the excess wire and secure it in the wire clip. If using the kit-provided zip ties, loop the excess slack and secure it with the zip ties.
The part number for the automatic vent damper required on this heating boiler is printed on the rating plate. Vent damper regulations are design certified per the latest edition of ANSI Z21.66.
17
Page 18
3 Gas connections
Installation & Service Manual
Gas Supply
Verify that the appliance is supplied with the type gas spec i fied on the rating plate. This appliance is orificed for operation up to 2000 feet altitude. The ap pli ance will be derated 4% per 1000 feet above 2000 feet el e va tion. Consult the factory for installations above 2000 feet elevation. Field conversions for operation at high altitude must be performed by certified per son nel only. The appliance will be marked to indicate suitability for high al ti tude operation.
GAS SUPPLY PRESSURE: Measured at the inlet pres­sure tap located upstream of the combination gas valve(s) see FIG. 3-5, page 22.
TABLE - 3A
GAS SUPPLY PRESSURE
Natural Gas LP Gas
Max. (Inches Water Column)
Min. (Inches Water Column) 4.5 11
Maximum inlet gas pressure must not exceed the val ue specified. Minimum value listed is for the purposes of input adjustment.
14 14
Gas Pressure Test
1. The appliance must be disconnected from the gas supply piping system during any pressure testing of that system at a test pressure in excess of 1/2 PSIG (3.5kPa).
2. The appliance must be isolated from the gas supply piping system by closing a manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.5kPa).
3. The appliance and its gas connection must be leak-tested before placing it in operation.
Gas Connection
1. Safe operation of the appliance requires properly sized gas supply piping. See data in Table 3C.
2. Gas pipe size may be larger than appliance gas connection.
3. Installation of a union is suggested for ease of service, see FIG. 3-1 on page 19.
4. Install a manual main gas shutoff valve, outside of the appliance gas connection and before the gas valve or manifold connection, when local codes require.
MANIFOLD PRESSURE: Measured at the pres sure tap on the downstream side of the com bi na tion gas valve(s) (see FIG. 3-5, page 22). The gas regulator settings for single stage and two stage operation are factory set to supply proper manifold pressure for normal operation. To check manifold pressure, see Manifold Ad just ment Procedure. Do not increase manifold pressure beyond spec i fied pressure settings shown below in Table 3B.
TABLE - 3B
MANIFOLD PRESSURE
Single and Two-Stage
Input Gas
Btu/hr
45,000 3.5" 10" 0.9" 2.5"
75,000 2.4" 7" 0.9" 2.5"
90,000 - 180,000 3.5" 10" 0.9" 2.5"
215,000 - 260,000 3.5" 10" 0.9" 2.5"
Full or High Fire
Settings
Natural
Gas
LP Gas
Two Stage
Low Fire Settings
Natural
Gas
LP Gas
5. A trap (drip leg) MUST be provided by the installer in the inlet of the gas connection to the appliance, see FIG. 3-1 on page 19.
6. The combination gas valve has an integral vent lim it ing device and does not require venting to atmosphere, outside the building.
7. Optional gas controls may require routing of bleeds and vents to the atmosphere, outside the building when required by local codes.
TABLE - 3C
FITTINGS TO EQUIVALENT STRAIGHT PIPE
Diameter Pipe (inches)
3/4 1 1 1/4 1 1/2 2 3 4 5
Equivalent Length of Straight Pipe (feet)
2 2 3 4 5 10 14 20
TABLE - 3D
GAS CONNECTIONS
18
Btu/hr
INPUT
45,000 - 135,000 1/2"
180,000 - 260,000 3/4"
Pipe Size
Page 19
Installation & Service Manual
3 Gas connections (continued)
TABLE 3E - GAS PIPING SIZE CHART
Capacity of Schedule 40 Metallic Pipe in Cubic Feet of Natural Gas Per Hour
(based on .60 specific gravity, 0.30" w.c. pressure drop)
Pipe
Size
(Inches)
1/2 131 90 72 62 55 N/A N/A N/A N/A N/A N/A N/A N/A N/A
3/4 273 188 151 129 114 104 95 89 83 79 70 63 58 N/A
1 514 353 284 243 215 195 179 167 157 148 131 119 109 102
1 1/4 1,060 726 583 499 442 400 368 343 322 304 269 244 224 209
1 1/2 1,580 1,090 873 747 662 600 552 514 482 455 403 366 336 313
2 3,050 2,090 1,680 1,440 1,280 1,160 1,060 989 928 877 777 704 648 602
2 1/2 4,860 3,340 2,680 2,290 2,030 1,840 1,690 1,580 1,480 1,400 1,240 1,120 1,030 960
3 8,580 5,900 4,740 4,050 3,590 3,260 3,000 2,790 2,610 2,470 2,190 1,980 1,820 1,700
4 17,500 12,000 9,660 8,270 7,330 6,640 6,110 5,680 5,330 5,040 4,460 4,050 3,720 3,460
10 20 30 40 50 60 70 80 90 100 125 150 175 200
Length of Pipe in Straight Feet
Gas Piping
GAS VALVE
GAS SHUTOFF VALVE
TRAP (DRIP LEG)
Figure 3-1_Gas Line Connection
All gas connections must be made with pipe joint com pound resistant to the action of liquefied pe tro leum and natural gas. All piping must comply with local codes. Tubing installations must com ply with ap proved standards and practices. Reference FIG. 3-1 for a typical installation.
2. Use new, properly threaded black iron pipe free from chips. If tubing is used, make sure the ends are cut squared, deburred and clean. All tubing bends must be smooth and without deformation. Avoid flexible gas connections. Internal diameter of flexible lines may not provide proper volume of gas.
3. Run pipe or tubing to the gas valve or manifold inlet. If tubing is used, obtain a tube to pipe coupling to connect the tubing to the gas valve or man i fold inlet.
4. DO NOT OVER-TIGHTEN. Over-tightening may result in damage to the gas valves. Valve distortion or malfunction may result if the pipe is inserted too deeply into the gas valve.
5. Apply a moderate amount of good quality pipe compound (DO NOT use Teflon tape) to pipe only, leaving two end threads bare.
6. Remove seal over gas valve or manifold inlet.
7. Connect pipe to gas valve or manifold inlet. Use wrench to square ends of the gas valve (FIG. 3-2).
Install Piping to Control
1. The gas line should be a separate line direct from the meter unless the existing gas line is of sufficient capacity. Verify pipe size with your gas sup pli er.
19
Page 20
3 Gas connections
Installation & Service Manual
WHEN FLANGE
IS USED
WHEN FLANGE IS
NOT USED
APPLY WRENCH
TO FLANGE ONLY
APPLY WRENCH FROM TOP OR B OTTOM
OF GAS CONTROL TO EITHER SHADED AREA
Figure 3-2_Wrench
8. For L.P. gas, consult your L.P. gas supplier for expert installation.
IMPORTANT
Upon completion of any piping con­nec tions to the gas system, leak test all gas con nec tions with a soap solution while system is un der pressure. Immediately repair any leaks found in the gas train or related components. Do Not op er ate an appliance with a leak in the gas train, valves or related piping.
Gas Manifold Pressure Adjustment Procedure
PRESSURE REGULATOR ADJUSTME NT (UNDER CAP SCREW)
INLET PRESSURE TAP
OUTLET PRESSURE TAP
1. Turn the power “OFF” at the main dis con nect switch.
2. Turn gas valve control knob to “OFF” po si tion.
3. Remove the 1/8" hex plug located on the out let side of the gas valve and install a fitting suitable to connect to a manometer or magnahelic gauge. See FIG. 3-3. Minimum range of scale should be up to 5" w.c. for Natural gas mod els and 10" w.c. for L.P. gas models.
4. Remove the pressure regulator adjustment cap screw on the gas valve. See FIG. 3-3 for location.
5. Turn the power “ON” at the main dis con nect switch.
6. Turn gas valve control knob to “ON” po si tion.
7. Set the thermostat(s) to call for heat.
8. Observe gas regulator pressure when all burn ers are firing. See Table 3B, Manifold Pressure (page 18) for proper regulator pressure settings.
9. If adjustment is necessary, turn regulator ad just ment screw clockwise to raise regulator gas pres sure, counterclockwise to lower gas pres sure, to proper setting.
Note: Adjustment fitting is plas tic and may require
slightly greater turning force than a metal fitting.
10. Turn the power “OFF” at the main dis con nect switch.
NOTICE
Do not increase regulator pres sure beyond specified pressure setting.
11. Turn gas valve control knob to “OFF” position.
12. Remove fitting from the gas valve and re place the 1/8" hex plug that was previously removed and tighten.
PILOT OUTLET
GAS CONTROL KNOB
RED RESET BUTTON
MANOMETER
3.5"
GAS VALVE
Figure 3-3_Manifold Pressure Adjustment
20
13. Turn the gas valve control knob to “ON” position.
14. Turn the power “ON” at the main dis con nect switch. The appliance is now ready to op er ate.
If manifold pressure can not be properly adjusted, use the procedure on page 21 to check gas supply pressure with a manometer connected to the inlet pressure tap on the gas control.
Page 21
3 Gas connections (continued)
Installation & Service Manual
Checking Gas Supply Pressure
GAS SUPPLY PRESSURE
MANOMETER
GAS VALVE
Figure 3-4_Gas Supply Pressure
1. Turn the power “OFF” at the main dis con nect switch.
2. Turn gas valve control knob to the “OFF” position.
3. Shut off gas supply at the manual valve in the gas piping to the appliance. If fuel supply is L.P. gas, shut off gas supply at the tank.
4. Remove the 1/8" hex plug, located on the “inlet” side of the gas valve and install a fitting suitable to connect to a manometer or magnahelic gauge. Range of scale should be 14" w.c. or greater to check inlet pressure. See FIG.’s 3-3 and 3-4 for location.
5. Turn on gas supply at the manual valve, turn on L.P. gas at tank if required.
6. Turn the power “ON” at the main dis con nect switch.
7. Follow the “Lighting Instructions” in Section 6 - Startup to light the pilot . Turn gas valve control knob to the “ON” position.
8. Set the thermostat(s) to call for heat.
9. Observe the gas supply pressure with all burn ers firing. Ensure inlet pressure is within specified range. Check gas supply pressure with all other gas fired appliances in operation to en sure prop er gas volume during periods of peak gas usage.
10. If gas pressure is out of range, contact gas utility, gas supplier, qualified installer or service agen cy to determine necessary steps to provide prop er gas pressure to the control.
11. If the gas supply pressure is within the spec i fied range, proceed with the following steps to return the appliance to service.
12. Turn the power “OFF” at the main dis con nect switch.
13. Turn gas valve control knob to “OFF” position.
14. Shut off gas supply at the manual valve in the gas piping to the appliance. If fuel supply is L.P. Gas, shut off gas supply at the tank.
15. Remove the manometer and related fittings from the “inlet” side of the gas valve, replace 1/8" hex plug in gas valve.
16. Turn on gas supply at the manual valve, turn on L.P. Gas at tank if required.
17. Turn the power “ON” at the main dis con nect switch.
18. Turn the gas valve control knob to the “ON” position. Spark ignition models will au to mat i cal ly light the pilot on a call for heat.
19. Set the thermostat to call for heat. The appliance is now ready to operate.
IMPORTANT
Upon completion of any testing on the gas system, leak test all gas connections with a soap solution while main burners are operating. Im me di ate ly repair any leak found in the gas train or re lat ed components. Do Not operate an appliance with a leak in the gas train, valves or related piping.
Check burner performance by cycling the system while you observe burner response. Burners should ignite promptly. Flame pattern should be stable, see the “Main te nance Section
-Normal Flame Pattern”. Turn system off and allow burners to cool, then cycle burners again to en sure proper ignition and flame characteristics.
21
Page 22
3 Gas connections
Combination Gas Valves
PRESSURE REGULATOR ADJUSTMENT (UNDER CAP SCREW)
INLET PRESSURE TAP
GAS CONTROL KNOB
Figure 3-5_M9 Gas Valve
Each unit has a combination gas valve to control the gas supply to the burners. The com bi na tion valve con sists of a gas regulator and two valve seats to meet the requirements for redundant gas valves. The valve has a gas control knob that must remain in the open po si tion at all times when the appliance is in service. Each gas valve has pres sure taps located on the inlet and outlet sides. Manifold pressure is adjusted using the regulator located on the valve. The manifold pres sure is pre set at the factory and adjustment is not usu al ly re quired. If the manifold pressure is to be ad just ed, follow the “Gas Manifold Pressure Ad just ment Pro ce dure”, page 20 for proper adjustment.
WIRING TERMINALS
OUTLET PRESSURE TAP
PILOT OUTLET
Installation & Service Manual
Venting of Combination Gas Valves
The combination gas valve regulator used on all mod els is equipped with an integral vent limiting orifice. The vent limiter ensures that the volume of gas emitted from the valve does not exceed the maximum safe leak age rate allowed by agency re quire ments. Com bi na tion gas valve/regulators equipped with integral vent limiters are not re quired to have vent or relief lines piped to the outdoors. A dust cap is provided at the vent termination point on the valve to prevent block age of the vent limiter by foreign material. The com bi na­tion gas valve regulator with an integral vent limiter complies with the safety code requirements of CSD­1, CF-190(a) as shipped from the manufacturer with out the in stal la tion of additional vent lines.
Two Stage Burner Control System
The 45,000 thru 260,000 Btu/hr boilers (M9) are equipped with a two stage burner control system.
22
Page 23
4 Water connections
Installation & Service Manual
Relief Valve
RELIEF VALVE
Figure 4-1_Relief Valve
This appliance is supplied with a relief valve(s) sized in accordance with ASME Boiler and Pressure Ves sel Code, Section IV (“Heating Boilers”). The re lief valve(s) is mounted directly into the heat ex chang er inside the header (see FIG. 4-1). To pre vent water damage, the dis charge from the relief valve shall be piped to a suit able floor drain for disposal when relief occurs. No reducing couplings or other restrictions shall be installed in the discharge line. The discharge line shall allow complete drainage of the valve and line. Relief valves should be manually operated at least once a year.
CAUTION
Avoid contact with hot discharge water.
Water Flow Switch (if equipped)
FLOW SWITCH
FLOW
Figure 4-2_Water Flow Switch - Top Connections
A water flow switch is available as a factory sup plied option on all heating boilers (see FIG. 4-2). The flow switch should be wired between terminals X and B. Remove the jumper between the X and B terminals on the terminal strip. This wiring connection installs the flow switch in the 24 VAC safety cir cuit to prove water flow before main burner ig ni tion. A flow switch installed with the fac to ry sup plied minimum adjustment setting requires a spe cif ic minimum flow to make the switch and start burner operation. The flow rate required is a function of the diameter of pipe and tee used for installation. Ensure that the pump installed on the boiler will supply adequate flow to make the flow switch con tacts and operate the boil er.
A water flow switch meets most code re quire ments for a low water cut off device on boil ers requiring forced cir cu la tion for operation.
23
Page 24
4 Water connections
Installation & Service Manual
Low Water Cutoff (if equipped)
A hot water boiler installed above radiation level must be provided with a low water cutoff device either as part of the unit or installed at the time the boiler is installed. An electronic low water cutoff is available as a kit on all units. Low water cutoffs should be in spect ed every six months, including flushing of float types.
TABLE - 4A
MINIMUM REQUIRED FLOW
FOR HEATING BOILER
Input Btu/hr GPM Flow
45,000 1.9
75,000 3.1
90,000 3.7
135,000 5.6
180,000 7.4
215,000 8.9
260,000 10.7
NOTICE
Minimum flow is based on a 40°F tem per a ture rise across the boiler. Minimum flow may not prove a flow switch installed in the boiler piping. Use care when operating a boiler at or near the min i mum recommended flow because conditions unique to the installation (system pressure, operation of multiple zone valves, glycol, variations in flow, etc.,) may result in overheating of the boiler water caus ing noise or nui sance operation of safety limit con trols. Typical heat ing boiler applications will op er ate with a 20°F to 30°F temperature rise across the boiler.
Typical Heating Boiler Installations
General Plumbing Rules
1. Check all local codes.
2. For serviceability of the boiler, always install unions.
3. Always pipe pressure relief valves to an open drain.
4. Locate system air vents at the highest point of the system.
5. Expansion tank must be installed near the boil er and on the suction side of the pump.
6. Support all water piping.
Placing the Boiler in Operation
Filling the System: All air must be purged from the system for proper operation. An air scoop and air vent must be located close to the boiler outlet and there should be a minimum distance between the cold water feed and the system purge valve.
1. Close all drain cocks and air vents.
2. Open the makeup water valve and slowly fill the system.
3. If a makeup water pump is employed, ad just the pressure to provide a minimum of 12 psi at the highest point in the system. If a pressure regulator is also installed in the line, it should be adjusted to the same pressure.
4. Close all valves. Purge one circuit at a time as follows:
A. Open one circuit drain valve and let the water drain
for at least five minutes. Ensure that there are no air bubbles visible in the wa ter stream before closing the drain valve.
B. Repeat this procedure for each circuit.
5. Open all valves after all circuits have been purged. Make sure there are no system leaks.
24
NOTICE
6. Run the system circulating pump for a min i mum of 30 minutes with the boiler turned off.
7. Open all strainers in the system and check for debris.
8. Recheck all air vents as described in step 4, General Plumbing Rules.
Do not use petroleum based stop leak products. All system leaks must be repaired. The constant addition of make-up water can cause damage to the boiler heat exchanger due to scale accumulation. Scale reduces flow and heat transfer, causing overheating of the heat exchanger.
Page 25
4 Water connections (continued)
Installation & Service Manual
9. Inspect the liquid level in the expansion tank. The system must be full and under normal operating pressure to ensure proper water level in the expansion tank. Ensure that diaphragm type ex pan sion tanks are properly charged and not water logged.
10. Start the boiler according to the Section 6 - “Start-Up Instructions” in this manual. Operate the system, including the pump, boiler and radiation units, for one hour.
11. Recheck the water level in the expansion tank. If it exceeds half the tank volume, open the tank to reduce the water level. Recheck pres sure charge on diaphragm type tanks.
12. Shut down the entire system and vent all ra di a tion units and high points in the system.
13. Close the water makeup valve and check the strainer and pressure reducing valve for sediment or debris. Reopen the water makeup valve.
14. Verify system pressure with the boiler pres sure gauge before beginning regular operation.
15. Within three days of start-up, recheck and bleed all air vents and the expansion tank using these instructions.
Piping of the Boiler System
The drawings in this section (see FIG’s 4-5 thru 4-9) show typical heating boil er piping installations. Before beginning the in stal la tion, consult local codes for specific plumb ing re quire ments. The installation should provide unions and valves at the inlet and outlet of the boil er so it can be isolated for service. The boiler cir cu lat ing pump, air sep a ra tor, expansion tank and oth er components required for proper installation must be purchased locally. An air separation device must be supplied in the in stal la tion piping to eliminate trapped air in the system. Lo cate a system air vent at the highest point in the sys tem. The system must also have a properly sized expansion tank installed. Typically, an air charged di a phragm-type expansion tank is used. The expansion tank must be installed close to the boiler and on the suction side of the system pump to ensure proper op er a tion. A water meter to monitor makeup water is recommended. Makeup water volume should not exceed 5% of total system per year. Install a Y-strainer or equivalent multi-purpose strainer just before the boiler pump at the inlet of the heat exchanger. This item is used to remove system debris from older hydronic systems and to protect newer systems.
CAUTION
This boiler system should not be operated at less than 12 PSIG (83 kPa) (Non-metallic system piping must have an oxygen barrier to be considered a closed loop)..
TABLE - 4B
SYSTEM TEMPERATURE RISE CHART
Based on Boiler Output in Btu/hr
Btu/hr
Input Output GPM Ft/hd GPM Ft/hd GPM Ft/hd GPM Ft/hd
45,000 36,900 7.4 0.6 3.7 0.2 2.5 0.2 1.9 0.2
75,000 61,500 12.3 1.3 6.2 0.4 4.1 0.3 3.1 0.2
90,000 73,800 14.9 1.4 7.4 0.5 5.0 0.3 3.7 0.2
135,000 110,700 22.3 3.2 11.1 1.2 7.4 0.6 5.6 0.3
180,000 147,600 29.7 5.1 14.9 1.6 9.9 0.7 7.4 0.4
215,000 176,300 -- -- 17.0 1.3 11.8 0.8 8.9 0.4
260,000 213,200 -- -- 21.5 2.1 14.3 0.9 10.7 0.5
10°F T 20°F T 30°F T 40°F T
25
Page 26
Head Loss, FT/HD
Flow Rate, GPM
CB135
CB180
CB260
0.0
1.0
2.0
3.0
4.0
5.0
0 5 10 15 20 25 30
CB045
CB075
CB090
CB215
0.0
0.5
1.0
1.5
0 5 10 15 20
4 Water connections
Installation & Service Manual
Hot water pip ing must be supported by suitable hangers or floor stands, NOT by the boiler. Copper pipe systems will be subject to considerable expansion and con trac tion. Rigid pipe hangers could allow the pipe to slide in the hanger resulting in noise transmitted into the system. Padding is recommended on rigid hangers installed with a copper system. The boiler pressure relief valve must be piped to a suitable floor drain. See the relief valve section on page 23 of this manual.
CAUTION
A leak in a boiler system will cause the system to intake fresh water constantly, which will cause the tubes to accumulate a lime/scale build up. This will cause a NON-WARRANTABLE FAILURE.
Water Connections
Heating Boilers with inputs of 45,000 - 260,000 Btu/hr have 1 1/2" NPT inlet and outlet connections.
CAUTION
Field installed reducing bushings may de crease flow re sult ing in boiler noise or flashing to steam.
TABLE - 4C
HEAT EXCHANGER PRESSURE DROP CHART
Circulator Pump Requirements
This is a low mass, high efficiency hot water boil er which must have adequate flow for quiet, efficient op er a tion. The boiler circulating pump must be field supplied. The boiler circulator pump must operate con tin u ous ly while the boiler is firing. Pump selection is critical to achieve proper op er a tion. A pump should be selected to achieve proper system design water temperature rise. A heat ex chang er pressure drop chart (Table 4C) is provided to assist in proper pump selection. Also provided is a System Temperature Rise Chart (Table 4B on page 25). This table provides GPM and boiler head-loss at various temperature rises for each boiler based on Btu/hr input. Temperature rise is the difference in boiler inlet temperature and boiler outlet temperature while the boiler is firing.
Example: The boiler inlet tem per a ture is 160°F and the boiler outlet temperature is 180°F, this means that there is a 20°F tem per a ture rise across the boiler.
26
Page 27
4 Water connections (continued)
Installation & Service Manual
PUMP INSTALLATION AND MAIN TE NANCE: The boiler circulating pump must be purchased lo cal ly. For installation and maintenance information on the circulator pump, refer to the pump man u fac tur ers in struc tion package included with the pump.
Circulator Pump Specifications
1. Maximum operating pressure for the pump must exceed system operating pressure.
2. Maximum water temperature should not ex ceed nameplate rating.
3. Cast iron circulators may be used for closed loop systems.
4. A properly sized expansion tank must be in stalled near the boiler and located on the suction side of the pump.
Circulator Pump Operation
Boilers are equipped with a relay for controlling the circulation pump for the hot water loop. The operating temperature control will energize the pump relay, which energizes the pump on a call for heat. The relay turns ON and OFF in response to the “W1” input from the wall thermostat or zone control. The pump will operate whenever the “W1” terminal is energized.
On boilers with the system pump delay option, the temperature control will de-energize the pump relay approximately 30 seconds after the call for heat ends.
The field installed boiler pump MUST NOT exceed 1 h.p. For continuous pump operation, wire the system pump to the 120V supply. The pump should be connected at the junction box as shown in FIG. 4-3.
See Pump Wiring for a Heating Boiler, on page 34 for additional information.
120V
SUPPLY
PERFORMANCE LOOP
These units are equipped with an integral performance loop, which is designed to provide efficiency optimization by maintaining a constant flow through the unit’s heat exchanger loop when building system flow is reduced. The performance
loop assembly is standard equipment and is NOT to be used as a system or boiler pump.
NOTICE
It is acceptable to remove the performance loop as long as the following requirements are met:
1. The boiler is piped to the system in primary/secondary fashion.
2. The system set point is 140°F or higher.
3. The boiler circulating pump is sized for the appropriate flow through the boiler.
4. The system sensor is installed in an acceptable location for sensing the system supply temperature.
5. If water temperature is below 140°F a low temperature bypass must be installed, (VAL30000 - 1 1/2" LTV Valve Kit) and follow the piping diagram in FIG. 4-5.
NOTICE
WARNING
The performance loop is dedicated to the unit and does not affect the building’s system or primary/secondary flow characteristics and will not circulate the building.
If removal of the performance loop is necessary, consult the manufacturer for a Solution Without a Performance Loop (KIT30068).
Failure to install the system sensor can cause operation problems such as nuisance high limit trips.
Primary/Secondary Boiler Piping
TO
UNIT
TO
CIRCULATION
PUMP
TO PERFORMANCE
LOOP PUMP
Figure 4-3_Boiler Wiring - Circulation Pump to Junction Box
A pri ma ry/secondary pip ing system may also be in stalled to ensure proper boiler flow rates. Primary/sec ond ary piping is also ideal for systems using a mixture of propylene glycol and water. A primary/secondary piping system uses a dedicated pump to supply flow to the boiler only. This pump is sized based on de sired boiler flow rate, boiler head loss and head loss in the sec ond ary system piping only. The secondary pump, in stalled in the boiler piping, ensures a constant wa ter flow rate to the boiler for proper operation. Boiler installation with a primary/ secondary piping sys tem can prevent noise problems caused by low sys tem water flows. A primary/secondary piping system is recommended on any boiler where low water flow conditions may present an operational problem.
27
Page 28
4 Water connections
Primary/Secondary Boiler Piping (continued)
Installation & Service Manual
A primary/secondary piping system is ideal for systems filled with a propylene glycol and water mixture. A glycol and water mixture is more dense than water only and may result in a lower boiler flow rate. A lower boiler flow may cause noisy operation or short cycling of the burners. A larger secondary pump may be used on a primary/sec ond ary system to pro vide an increased boiler flow rate. A glycol and water system may require from 10 to 20% more flow to compensate for the in creased density of the glycol and its effect on the heat transfer process in the boiler. The exact in crease in flow that may be required is based on the type and percentage of glycol added to the boiler system. Consult the manufacturer of the glycol for additional recommendations when using a gly col and water fill for your boiler system.
The installer must ensure that the boiler has adequate flow without excessive temperature rise. The temperature rise on a multiple zone system should be made when only the zone with the longest length and/or high est head loss is open. Low system flow can result in overheating of the boiler water which can cause short burner on cycles, system noise and in extreme cases, a knocking flash to steam. System noise may also indicate an oversized boiler.
Low Temperature Bypass Requirements
For systems which require lower operating temperatures, a bypass must be installed to guarantee the boiler inlet water temperature is above 140°F (60°C). Inlet water temperatures below 140°F (60°C) can excessively cool the prod ucts of combustion re sult ing in condensation on the heat exchanger and in the flue. Condensation can cause operational problems, bad combustion, sooting, flue gas spillage and reduced service life of the vent system and related components. The bypass allows part of the boiler discharge water to be mixed with the cooler boiler return water to in crease the boiler inlet temperature above 140°F (60°C). This should prevent the prod ucts of com bus tion from condensing in most in stallations.
Systems requiring a low temperature bypass should use the provided system sensor and VAL30000 (1 1/2" LTV Valve Kit) piped in a Primary/ Secondary arrangement as shown in FIG. 4-5. It is recommended to install the system sensor a minimum distance of 10 pipe diameters from the boiler piping. The Low Temperature Valve (LTV) is ready to install with a non-adjustable 140°F return temperature setting. It is important thtat the valve is installed with the proper port orientation. Failure to observe port markings on the valve body prior to installation could result in damage to the unit. The recommended maximum high temperature to the valve is 175°F (79°C).
Boiler Flow Rates
CAUTION
A boiler operated with an inlet temperature of less than 140°F (60°C) must have a bypass to prevent problems with condensation. A bypass as shown in FIG. 4-5 (see page 30) must be piped into the system at the time of installation.
At no time should the system pressure be less than 12 PSIG.
Full Flow Application
It is acceptable for the Solution boiler to be installed in a full flow application, as long as the following requirements are met:
1. The performance loop is in place and functional.
2. The system flow is not lower than the minimum boiler flow.
3. The boiler set point is 140°F or higher.
4. Boiler return water temperatures are 140°F or higher.
WARNING
Varying the flow through a Solution boiler can cause harmonic noises and high limit trips if the flow is below the minimum boiler flow rate found in Table 4A.
TABLE - 4D
MAXIMUM FLOW FOR HEATING BOILER
The maximum flow rate through the boiler with a copper
heat exchanger must not exceed the following:
Model Maximum Flow
45,000 - 260,000 30 GPM 38 GPM
The heat exchanger is generally capable of op er at ing within the flow rates of a residential heating system. Should the flow rate exceed the maximum allowable flow rate through the boiler 30 GPM) an external bypass must be installed. The bypass should be fully sized with a balancing valve to al low for proper ad just ment of flow. Flow rate can be determined by measuring the temperature rise through the boiler.
The basic guide for minimum flow in this boiler is based on a 40°F temperature rise in most in stal la tions. Low­er flow and a higher temperature rise is acceptable if the boiler system is specifically de signed for the char ac ter is tics of a higher tem per a ture rise. A system not specifically designed for a higher temperature rise may experience over heat ing of the boiler water. This can cause short burn er on cycles, system noise and in ex treme cases, a knocking flash to steam. These con di tions can lead to operational problems and non-war rant able fail ures of the boiler. High temperature rise systems must be designed by a qualified engineer.
Maximum Flow for
CuNi Heat Exchanger
28
Page 29
4 Water connections (continued)
Primary / Secondary Piping
Figure 4-4_Primary / Secondary Piping of a Single Boiler
Installation & Service Manual
MAKE UP
WATER
TO
SYSTEM
PRESSURE
REDUCING VALVE
WATER METER
BACKFLOW
PREVENTER
SYSTEM
CIRCULATOR
BALL VALVE
(TYPICAL)
AIR
SEPARATOR
PRESSURE
GAUGE
EXPANSION
MINIMUM 10 PIPE
SYSTEM
SENSOR
(OPTIONAL)
TANK
UNION
(TYPICAL)
ø
FROM
MAX 4 PIPE
OR 12" APART
FLOW
CHECK
VALVE
Y-STRAINER
ø
SYSTEM
TEMPERATURE
& PRESSURE
GAUGE
(PROVIDED)
PRESSURE
RELIEF VALVE
(PROVIDED)
DRAIN
BOILER
CIRCULATOR
SOLUTION
BOILER
DIR #2000548532 00
29
Page 30
Installation & Service Manual
4 Water connections
Primary / Secondary Piping
Figure 4-5_Single Boiler - Primary / Secondary with Low Temperature Bypass
WATER METER
MAKE UP
WATER
TO
SYSTEM
BALL VALVE
(TYPICAL)
PRESSURE
REDUCING VALVE
BACKFLOW
PREVENTER
SEPARATOR
SYSTEM
CIRCULATOR
AIR
PRESSURE
GAUGE
EXPANSION
MINIMUM 10 PIPE
SYSTEM
SENSOR
(REQUIRED)
TANK
UNION
(TYPICAL)
MAX 4 PIPE
OR 12" APART
ø
ø
FROM
SYSTEM
LOW TEMP.
BYPASS
(LTV VALVE)
FLOW CHECK
VALVE
Y-STRAINER
30
TEMPERATURE
& PRESSURE
GAUGE
(PROVIDED)
PRESSURE
RELIEF VALVE
(PROVIDED)
DRAIN
SOLUTION
BOILER
BOILER
CIRCULATOR
DIR #2000548527 00
Page 31
4 Water connections (continued)
Primary / Secondary Piping
Figure 4-6_Multiple Boilers Zoned with Circulators
ZONE #1
Installation & Service Manual
MINIMUM 10 PIPE
(OPTIONAL)
UNION
(TYPICAL)
PRESSURE
RELIEF VALVE
(PROVIDED)
MAKE UP
SYSTEM SENSOR
PREVENTER
WATER METER
WATER
MAX 4 PIPE
OR 12" APART
ø
BACKFLOW
EXPANSION
DRAIN POINT
(TYPICAL)
BOILER
CIRCULATOR
AIR SEPARATOR
TANK
ø
MAY SUBSTITUTE
LOW LOSS HEADER
PRESSURE
REDUCING VALVE
PRESSURE
GAUGE
FLOW
CHECK
VALVE
Y-STRAINER
(TYPICAL)
TEMPERATURE
& PRESSURE
GAUGE
(PROVIDED)
ZONE CIRCULATORS
(TYPICAL)
RELIEF
VALVE
BALL VALVE
(TYPICAL)
ZONE #2
HOT
WATER
OUT
TANK
AQUASTAT
ZONE #3 ZONE #4
COLD
WATER
IN
ANTI-SCALD
MIXING VALVE
RECIRCULATION
LOOP
(RECOMMENDED)
NOTICE
COLD
WATER
IN
BOILER 2
BOILER 1
INDIRECT
DHW TANK
DIR #2000548535 00
Please note that systems using DHW priority MUST use mixing valves to protect low temperature zones.
31
Page 32
4 Water connections
Full System Flow
Figure 4-7_Single Boiler Full System Flow
PRESSURE
REDUCING VALVE
WATER METER
MAKE UP
WATER
TO
SYSTEM
BACKFLOW
PREVENTER
SYSTEM
CIRCULATOR
BALL VALVE
(TYPICAL)
AIR
SEPARATOR
PRESSURE
GAUGE
MINIMUM 10 PIPE
SYSTEM
SENSOR
(OPTIONAL)
Installation & Service Manual
ø
FROM
SYSTEM
EXPANSION
TANK
(TYPICAL)
DRAIN
TEMPERATURE
& PRESSURE
GAUGE
(PROVIDED)
PRESSURE
RELIEF VALVE
(PROVIDED)
UNION
Y-STRAINER
32
SOLUTION
BOILER
DIR #2000548531 00
Page 33
5 Electrical connections
Installation & Service Manual
This appliance is wired for 120 VAC service. The appliance, when installed, must be electrically ground ed in accordance with the requirements of the authority having jurisdiction or in the absence of such re quire ments, with the latest edition of the National Electrical Code ANSI/NFPA No. 70. When the unit is in stalled in Canada, it must conform to the CSA C22.1, Ca na di an Electrical Code, Part 1 and/or local Electrical Codes.
1. All wiring between the appliance and field in stalled devices shall be made with type T wire [63° F(35° C) rise].
2. Line voltage wire exterior to the appliance must be enclosed in approved conduit or approved metal clad cable.
3. The pump must run continuously when the appliance is being fired.
4. To avoid serious damage, DO NOT en er gize the appliance until the system is full of water. Serious damage may result.
5. Provide the unit with proper overload protection.
6. Install a wall thermostat on the inside wall. DO NOT install the thermostat in an area affected by drafts, sunlight, light fixtures, hot or cold water pipes or near a fireplace. See “Room Thermostat or Remote Thermostat Connection to Terminal Strip” (this page), for prop er wiring con nec tion.
Room Thermostat or Remote Thermostat Connection to Terminal Strip
A room thermostat or remote temperature control may be connected to the boiler. The room ther mo stat should be installed on an inside wall, away from the influences of drafts, hot or cold water pipes, lighting fixtures, televisions, sun rays or fire plac es. Follow the manufacturers instructions supplied with the ther mo stat for proper installation and ad just ment. The boiler is equipped with a terminal strip on the left side of the control panel to allow easy connection (FIG. 5-1, inset A).
Remove the jumper between the R1 and W1 terminals on the terminal strip. Refer to the chart in this section (Table 5A) to determine maximum allowable length and wire gauge recommended to connect the switching con tacts of the room thermostat to the R1 and W1 terminals on the terminal strip. Connection to the terminal strip will allow the room thermostat to make and break the 24VAC boiler control circuit turning the boiler on and off based on the room ambient temperature re quire ments. Set the boiler operating temperature control as described in Temperature Control Settings on page 36.
A
B
IMG00278
Figure 5-1_Terminal Strip Connections
TABLE - 5A
TERMINAL STRIP WIRING
Wire Gauge
Allowable Length
12 GA 100 ft.
14 GA 75 ft.
16 GA 50 ft.
18 GA 30 ft.
Auxiliary Power Venting Connection to Terminal Strip
A terminal connection strip is provided for ease of connection of auxiliary power venting systems, see FIG. 5-1, inset B. A field supplied power venter can be interlocked into the appliance’s control circuit via a 24 VAC relay, which will be powered from this location when a call for heat has been established. A device proving switch can be interlocked back to the appliance to ensure its operation before the appliance is allowed to fire. For additional information, reference the wiring diagram on page 51 of this manual.
Maximum
33
Page 34
5 Electrical connections
Pump Wiring for a Heating Boiler
The heating boiler circulating pump must be purchased locally. Follow all manufacturer’s installation and maintenance instructions provided with the pump. Solution boilers are equipped with a pump relay, located near the two-stage thermostat in the control panel (FIG. 5-2). The temperature controller energizes the pump relay, which operates the pump on a call for heat. The pump will operate either continuously from a 120V supply, or whenever the “W1” terminal from the wall thermostat or zone control is energized. The maximum load for the pump switched by the internal pump relay must not exceed 1 HP. The current draw for a field installed 120 VAC pump MUST be added to the boiler’s current draw to determine the minimum wire size for 120 volt service. Reference Table 5B for boiler operating control current draw data.
IGNITION MODULE
TST20036-2
Installation & Service Manual
The installation of outdoor air reset is necessary to comply with the United States Energy Policy and Conservation Act, and the boiler will not function if both boards are not installed. In the event that the outdoor air sensor is not functioning, a flashing red light will indicate fault and the boiler operating temperature will default to maximum set point.
DHW Priority
A boiler used in water heating applications should be piped as a hot water loop (zone) in a Primary/Secondary piping arrangement (see FIG. 4-6 on page 31). A DHW priority function on the Solution boiler is available by connecting a field supplied tank Aquastat to the upper control board (TST20036-
2). When the control receives a DHW call for heat, the boiler set point will change to 180°F (82°C). The boiler will operate at this set point until the DHW demand is satisfied. In the absence of water heating demand, the operating set point is based on the outdoor air reset curve. For boilers using DHW priority, mixing valves are required for the protection of low temperature zones.
Additional Temperature Controls
MANUAL RESET
HIGH LIMIT
(IF EQUIPPED)
PUMP RELAY
TST20036-1
TRANSFORMER
IMG00280
Figure 5-2_Intermittent Pilot System M9 Control Panel
TABLE - 5B
AMP DRAW DATA
45,000 thru 260,000 Btu/hr Models
MAXIMUM
FIRING CONTROLS
M9 with Performance Loop Pump 1.25
Boiler Operating Temperature Control
The two-stage thermostat is located in the control panel, behind the control panel front access door. To access the temperature control, remove the control panel door on the front of the unit. The temperature controller operates a two-stage firing system, which increases system efficiency by starting the boiler on low fire and turning on high fire only when extra capacity is needed. After the water temperature reaches the operating set point, the temperature control shuts off the burners.
The Solution boiler is also equipped with outdoor air reset, a feature that saves energy by reducing the boiler water temperature as the heating load decreases (reference Temperature Adjustment section on page 35). The thermostat control consists of two interconnected boards. The upper board controls outdoor air reset and DHW priority functions, while the lower board manages burner and pump operation.
TOTAL AMPS
@ 120 VAC
High Water Temperature Limit Control
The appliance is supplied with a fixed setting, auto-reset high water temperature limit control. The setting of this control limits maximum discharge water temperature. If water temperature exceeds the setting, the limit will break the control circuit and shut down the appliance. The limit control will only be reset after the water temperature has cooled well below the setting of the limit. The auto-reset high water temperature limit control is mounted in the outlet side of the front header.
Blocked Vent and Flame Roll-Out / Flame Interlock
All units are equipped with manual reset blocked vent and flame roll-out / flame interlock switches. These temperature switches are located in the controls compartment and in the relief opening of the boiler’s built-in draft hood. Each switch has a red reset button. In the event the system has actuated to shut off the main burner gas supply, wait for the boiler to cool, then press the red reset to return the boiler to operation. Operation of a blocked vent and/or flame roll-out / interlock switch usually indicates a problem with the venting system, obstruction of the heat exchanger flue gas passageway and/or a combustion air supply problem. The cause for operation of the blocked vent and/or flame roll-out / interlock switch must be determined and corrected. If the boiler cannot be restored to normal operation, contact a qualified service installer, service agency or the gas supplier.
34
Page 35
5 Electrical connections (continued)
17
0
18
0
10
Installation & Service Manual
Figure 5-3_Blocked Vent Switch Location
BLOCKED VENT SWITCH
DETAIL A
DRAFT HOOD
(INVERTED TO SHOW RESET UNDERNEATH)
A
T
I
N
U
F
O
T
N
O
R
F
IMG00281
Figure 5-4_Flame Roll-Out / Flame Interlock Switch Location
UPPER FRONT JACKET PANEL
OUTER AIR DEFLECTOR
FLAME ROLL-OUT / INTERLOCK SWITCH
DETAIL A
LOWER FRONT JACKET PANEL
IMG00282
HEX FILLER BRACKET
A
Temperature Adjustment
NOTICE
The temperature controller is pre-set at the factory with test settings. You may need to adjust the settings to meet your specific needs.
In Compliance with Energy Conservation Standards, the Solution boiler comes equipped with outdoor air reset, a feature that increases the temperature setting of the boiler as outside temperatures drop and decreases the boiler set point as outdoor temperatures rise. To use this feature, the outdoor air sensor provided with the boiler must be properly installed. If the sensor or sensor wiring is defective, a flashing LED light on the controller will signify the feature is not functioning (FIG. 5-5). A boiler that is not receiving input from the outdoor air sensor will operate at maximum set point until the sensor is reconnected.
The temperature controller calculates boiler set point using the outdoor air temperature and the outdoor air reset curve. The curve is adjustable and defined by the maximum and minimum set points. An appropriate operating set point is based on individual system’s requirements. Refer to Temperature Control Settings for help with set point determination.
The boiler water sensing element is factory installed in the inlet bulbwell on the heat exchanger. An optional system sensor may be installed for use as a remote sensor in a boiler system. The boiler set point can be adjusted by using the maximum set point dial to modify the outdoor air reset curve. To ensure proper operation, use the temperature and pressure gauge located in the header of the heat exchanger to observe the boiler discharge temperature and system water pressure after set point adjustment.
OUTDOOR AIR SENSOR
CN2
LED1
W3
W2
W1
5
0 HIGH-FIRE OFFSET °F
FAULT INDICATION
CN3
INLET
PROBE
CN4
CN5
SYS/
TANK
CN6
CN9
15
20
IMG00275
TST20036-1
TST20036-2
(c)2002 L.C.
(c)2002 L.C.
CN7
PUMP
RELAY
CN8
CN12
CN1
160
150
OFF
MAX SETPOINT °F
190
200
MIN SETPOINT °F
CN11CN10
OUTDOOR
TANK
SENSOR
AQUA-
STAT
FAULT
125
120 130
115
110 140
135
TST20036
Figure 5-5_Two-Stage Thermostat
WARNING
Return water temperatures must not be less than 140°F. If lower return water temperatures are required, follow the instructions for Low Temperature Bypass Requirements, see page 28.
35
Page 36
5 Electrical connections
Temperature Control Settings
Residential heating boilers with inputs of less than 300,000 Btu/hr must be equipped with a control that automatically adjusts boiler water temperature in reference to heat load. The Solution boiler is equipped with outdoor air reset, a feature that increases the temperature setting of the boiler as outside temperatures drop and decreases the boiler set point as outdoor temperatures rise. The temperature control settings on the Solution boiler can be customized to meet system requirements.
The two-stage thermostat allows knob adjustment of up to three parameters: Maximum Set Point (at Low Outdoor Air), Minimum Set Point (at High Outdoor Air), and High Fire Offset. The low and high outdoor air temperatures are factory set at 0°F (-18°C) and 70°F (21°C) respectively. The heating boiler operating set point is dependent upon the outdoor air temperature and the outdoor air reset curve. The reset curve can be designed to meet system requirements by specifying the target boiler water temperature at low and high outdoor air temperatures. Reference FIG. 5-6 and Table 5C to help determine the proper settings for your system. If return water temperatures of less than 140°F are required, follow the instructions for Low Temperature Bypass Requirements.
Installation & Service Manual
Maximum Set Point (Low Outdoor Air Temperature)
Figure 5-6_Outdoor Air Reset Curve
°F
BOILER
SET POINT
Max. Set Point
(Low Outdoor Air Temp.)
150° - 200°F
Max. Set Point Range
110° - 140°F
Min. Set Point Range
Low Outdoor Air
Temp.= 0°F
OUTDOOR AIR TEMPERATURE
When the outdoor temperature drops to 0°F (-18°C), the boiler water temperature will be at the maximum set point. This is the maximum heating boiler set point and can be set using the left-hand knob on the temperature control (FIG. 5-5). If outdoor temperatures continue to drop, the temperature control will not continue to increase boiler set point. The temperature range of this parameter is 150°F (66°C) to 200°F
Min. Set Point
(High Outdoor Air Temp.)
(93°C). If DHW priority is used, the controller will change boiler set point to 180°F (82°C) until water heating demand is satisfied.
High Outdoor Air
°F
Temp.= 70° F
IMG00274
36
Page 37
5 Electrical connections (continued)
Installation & Service Manual
Minimum Set Point (High Outdoor Air Temperature)
If the inlet sensor is used to determine set point, the minimum set point is fixed at 140°F (60°C). If a system sensor is used the range of this parameter is 110°F (43°C) to 140°F (60°C) and can be adjusted using the middle knob on the temperature controller. The two-stage thermostat will apply the outdoor air reset set point to the system sensor, while also applying a fixed 140°F (60°C) set point to the inlet sensor. If inlet water temperature drops below 140°F (60°C) the temperature controller will force the boiler to high fire. Requiring a minimum 140°F (60°C) inlet water temperature will help prevent problems with condensation. For systems requiring return temperatures less than 140°F (60°C), a bypass must be installed. Reference Low Temperature Bypass Requirements for additional information.
High Fire Offset
The temperature controller operates a two-stage firing system, which enables the boiler to start on low fire and continue on to high fire when there is a greater heat demand. High fire operates all burners at full rate, while low fire operates the burners at approximately one-half rate. Operating at high fire only when extra capacity is needed increases overall system efficiency. The High Fire Offset knob specifies the number of degrees below boiler set point that the high fire stage shuts down. At that point, the unit will continue to operate at the low fire stage until the set point is reached. The High Fire Offset knob has temperature settings between 0°F and 20°F. If the control is set above 0°F, the high fire delay will be 120 seconds. If the control is set to 0°F, the high fire offset is disabled and the unit will operate at high fire until the set point is reached.
Differential
The differential specifies the number of degrees below the set point the control will allow the water temperature to drop before it brings the unit back on again. The differential is factory set at 12°F (7°C).
Temperature Control Sensors
The two-stage temperature control regulates the burner ignition and pump functions, and can measure up to four (4) different sensor inputs. Standard boiler units are equipped with an inlet water temperature sensor and an outside air temperature sensor. A system sensor is also provided for use as a remote sensor. If this sensor is connected to the control board, the boiler will operate based on system water temperature set point. A field supplied tank Aquastat may also be used for water heating applications. The four available sensor inputs are as follows:
1. Inlet Water Temperature Sensor
2. System Sensor
3. Outside Air Temperature Sensor
4. Tank Aquastat
Inlet Water Temperature Sensor
This sensor measures the inlet water temperature coming into the unit. The inlet water temperature sensor is placed into the inlet bulbwell on the boiler. This sensor is installed by the factory in new units and should not be removed. A fixed 140°F minimum set point is applied to this sensor.
System Sensor
This sensor can be used as a remote system sensor in a boiler system. When this sensor is connected the temperature control applies the outdoor air reset set point to the system sensor and a minimum 140°F set point to the inlet sensor. Systems requiring return temperatures less than 140°F should install a low temperature bypass. A bypass allows the unit to operate at a lower system set point, while maintaining the minimum inlet water temperature. Connect the system sensor to the SYS/ TANK contacts on the control board. For more information, reference the Installation of System Sensor section on page 38.
Outdoor Air Temperature Sensor
This sensor ties boiler operating set point to the outdoor air temperature. As outdoor temperatures drop and there is greater heat demand, the control will increase the temperature setting of the boiler. The boiler set point will decrease as outdoor temperatures rise, resulting in more energy efficient operation. The sensor comes with a housing that helps protect the sensor from the elements. Mount the air sensor housing outdoors, under the eve of the roof. Make sure the housing is out of direct sunlight. This will ensure that the sensor will accurately read the true outdoor temperature. Connect the outdoor air temperature sensor to the terminal block on the upper temperature control board. In the event the outdoor air sensor is not functioning, the temperature control will indicate a fault with a flashing red light and the boiler set point will default to Maximum Set Point. For more information on wiring the sensor, see Wiring of the Outdoor Air Sensor on page 38.
Tank Aquastat
An indirect water heater can be connected to the boiler with a field supplied Aquastat. When there is a water heating demand the temperature control will increase boiler set point to 180°F (82°C). Follow the manufacturer’s instructions supplied with the Aquastat for proper installation and adjustment. Determine the location of the tank and measure the amount of wire needed to connect the Aquastat to the control. Reference the terminal strip wiring chart (Table 5A) to determine maximum allowable length and wire gauge recommended. Ensure all wire insulation is trimmed to reveal at least 3/8" of exposed wire. Feed the wires through the access hole located on the side of the unit and secure the connectors to the Tank Aquastat terminal block CN10 on the upper temperature control board. Reference the Wiring of Outdoor Air Sensor section for additional wiring guidelines.
37
Page 38
5 Electrical connections
Wiring of Outdoor Air Sensor
Follow the guidelines in this section when wiring remote sensors. Use shielded, 2-wire twisted pair cable. Take care to correctly wire sensors to the unit. Erratic temperature readings can be caused by poor wiring practices. If the outdoor air sensor is unable to provide input to the control, the boiler will default to the maximum set point. For proper boiler operation it is important to follow all wiring guidelines.
1. Turn OFF the main electrical power and the main manual gas shutoff to the appliance.
2. Remove the upper front door panel from the appliance to gain access to the temperature control.
3. Locate the outdoor air temperature sensor provided in the kit. Determine the location of the remote sensor and measure the amount of wire needed to connect the sensor to the thermostat. The sensor should be placed on a north wall, under the eve of the roof. Make sure the housing is out of direct sunlight.
4. Do not route temperature sensor wiring with building power wiring.
5. Do not locate temperature sensor wiring next to control contactors.
6. Do not locate temperature sensor wiring near electric motors.
7. Do not locate temperature sensor wiring near welding equipment.
8. Make sure good mechanical connections are made to the sensor, any interconnecting wiring and the controller.
9. Do not mount sensor with lead wire end pointing up in an area where condensation can occur.
10. Use 18 gauge or larger shielded, twisted pair cable to connect the sensor to the control. This provides protection against some types of electrical interferences.
11. Remove the cover of the outdoor air temperature sensor and route the wires through either the bottom or the back of the sensor. Connect the wires to the sensor and replace the cover (FIG. 5-8).
12. Run the shielded sensor wiring through the access hole located on the back of the unit to CN11 on the upper control board TST20036-2.
Figure 5-7_Outdoor Air Temperature Sensor (TST2311)
OUTDOOR AIR RESET SENSOR (TST2311)
ROUTE TO CN11 ON TST20036-2
Installation & Service Manual
NOTICE
13. Replace the side access panel.
14. Turn ON the main electrical power and the main manual gas shutoff to the appliance.
Installation of System Sensor
1. Turn OFF the main electrical power and the main manual
gas shutoff to the appliance.
2. Remove the side access panel from the appliance to gain
access to the thermostat.
3. Locate the sensor provided in the kit. Determine the
location of the remote sensor and measure the amount of wire needed to connect the sensor to the thermostat. See Wiring of the Outdoor Air Sensor for guidelines.
4. Use twisted pair wire, minimum 18 gauge or larger.
Ensure all wire insulation is trimmed to reveal at least 3/8" of exposed wire.
5. Connect the measured wire to the sensor wire using wire
caps. Install .250 x .032 insulated female quick connect terminals to the end of the wires. Feed the wires through the access hole located on the back of the unit and secure the connectors to the thermostat connections (SYS/TANK) CN5 and CN6 located in the upper right-hand of the thermostat.
6. Turn on the electrical power and the main manual gas
shutoff to the appliance.
7. Replace the side access panel.
8. Fire the appliance and resume operation.
Figure 5-8_Installation of Remote Sensors
ACCESS HOLE
CONNECT
OUTDOOR AIR
SENSOR AND TANK AQUASTAT
TO TST20036-2
Ground the cable shield at the connection to the boiler temperature control only. Do not ground the shielded cable at the sensor end.
To maintain temperature accuracy, sensor wires should be 18 AWG two conductor (18/2). Use shielded wire.
38
CONNECT
SYSTEM
SENSOR TO
TST20036-1
IMG00279
IMG00276
Page 39
6 Start-up
Initial Start-up
Follow the Lighting Instructions on the label applied to the appliance.
A. On boilers with the system pump delay option,
the operating temperature control will energize the pump relay which energizes the pump on a call for heat. The operating temperature control will de-energize the pump relay approximately 30 seconds after the call for heat ends. If either the inlet sensor or the optional multi-purpose temperature sensor reads below 40°F, the pump relay will turn ON. When the temperature rises above 50°F the pump relay will turn OFF.
On boilers, the pump will operate whenever the “W”
terminal is energized.
Installation & Service Manual
6. Verify that properly sized combustion and ven ti la tion air openings are provided and not obstructed in any way.
7. Check carefully for gas leaks.
8. Read the appliance’s safety warnings, light ing instructions and check out procedure carefully, be fore firing the system.
Lighting Instructions for Spark Ignition Pilot Models
FOR YOUR SAFETY READ BEFORE OPERATING
B. Location - The appliance should be located within
a room having a temperature safely above freezing [32°F(0°C)].
C. Shutdown and Draining - If, for any rea son,
the appliance is shut off, the following pre cau tion ary measures must be taken:
1. Shut off gas supply,
2. Shut off water supply.
3. Shut off electrical supply.
4. Drain the heat exchanger completely. Re move one 3/8” NPT plug or bulbwell from the inlet side and one from the outlet side of the front head er of the heat exchanger.
5. Drain the pump. Remove the 3/4" plug in the performance loop.
Pre-start Checklist
1. Inspect the burners to be sure they are prop er ly aligned.
2. Inspect the pilot gas line, thermocouple leads, ignition
leads and wire connections to the gas valve to be sure none were damaged during shipment.
3. Check to ensure that gas connections have been made
properly and the gas line is purged of air.
4. Check to ensure that water connections are tight and the
appliance and piping system have been properly filled.
5. Ensure that discharge from the relief valve has been
piped to a floor drain.
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to light the pilot by hand.
B. BEFORE OPERATING, smell around the appliance
area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle to the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone
in your building.
Immediately call your gas supplier from a near by
phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire
department.
C. Use only your hand to turn the gas control knob.
Never use tools. If the knob will not turn by hand, don’t try to repair it, call a qualified ser vice technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance. The pos si ble damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
39
Page 40
6 Start-up
Installation & Service Manual
Operating Instructions
1. STOP! Read the safety information first.
2. Remove the control panel door.
3. Set the thermostat to the lowest setting (OFF).
4. Turn off all electrical power to the appliance.
5. This appliance is equipped with an ignition device which automatically lights the pilot. DO NOT try to light the pilot by hand.
6a. 45,000 - 135,000 Btu/hr models, rotate the gas control
knob on the gas valve clockwise to the “OFF” position.
6b. 180,000 - 260,000 Btu/hr models, rotate the gas control
knob on the gas valve clockwise to the line on the collar around the knob. Depress the knob and continue rotation to the “OFF” position.
7. Wait five (5) minutes to clear out any gas, then smell for gas, including near the floor. If you smell gas, STOP! Follow the steps in the “What To Do If You Smell Gas” section in the safety information on page 39. If you do not smell gas go on to the next step.
8a. 45,000 - 135,000 Btu/hr models, rotate the gas control
knob on the gas valve counterclockwise to the “ON” position.
To Turn Off Gas to Appliance
1. Set the thermostat to the OFF position.
2. Turn off all electric power to the appliance if service is to be performed.
3a. 45,000 - 135,000 Btu/hr models, rotate the gas control
knob on the gas valve clockwise to the “OFF” position. Do not force.
3b. 180,000 - 260,000 Btu/hr models, rotate the gas control
knob on the gas valve clockwise to the line on the collar around the knob. Depress the knob and continue rotation to the “OFF” position. Do not force.
WARNING
Should overheating occur or the gas fail to shut off, turn off the external manual gas valve to the appliance.
Safety Shutoff Test for Spark Ignition Pilot System
1. Turn “OFF” gas supply to the appliance.
2. Turn the minimum set point to the lowest setting and the maximum set point to the highest setting to initiate a call for heat.
3. Turn electric power “ON”.
8b. 180,000 - 260,000 Btu/hr models, rotate the gas control
knob on the gas valve counterclockwise to the line on the collar around the knob. Al low the knob to “pop” up, and continue rotation to the “ON” position.
9. Turn on all electric power to the appliance.
10. Set the thermostat to the desired setting.
11. Re-install the control panel door.
12. If the appliance will not operate, follow the instructions “To Turn Off Gas To Appliance” and call your service technician or gas supplier.
4. Pump relay pulls in to start pump.
5. The ignition will begin sparking at the pilot.
6. The ignition module will lock out after the trial for ignition period.
7. Immediately call a qualified serviceman or in stall er to repair an ignition system that fails to lock out and properly shut down burner operation.
8. After successful completion of the test, re ad just the thermostat to normal setting.
9. Turn “ON” gas supply.
10. Turn power “OFF” then “ON” to reset ignition module.
11. If ignition system fails to operate properly, re pair work must be performed by a qualified serviceman or installer.
40
Page 41
6 Start-up (continued)
Installation & Service Manual
Pre-Commissioning Cleaning
1. Prior to fill and start-up, flush the entire heating system.
2. Clean the entire heating system with an approved pre­commissioning cleaner (comparable to Sentinel X300 or Fernox F3) in accordance with the manufacturer’s recommendation to remove debris and prolong the life of the heat exchanger.
3. Clean all water filtering devices in the system.
4. Flush the cleaning solution out of the entire system and refill.
Fill water
Check/control fill water chemistry
IMPORTANT
The manufacturer recommends the following for properly filling your boiler with the appropriate water chemistry for closed loop boilers. Good fill water quality will help extend the life of the appliance by reducing the effects of lime scale buildup and corrosion in closed loop systems.
Hardness between 5 and 15 grains per gallon
1. Consult local water treatment companies for hard water areas (above 15 grains per gallon hardness).
2. Hardness levels that are above 15 grains/gallon can lead to lime scale buildup throughout the boiler system. If the fill water is below 5 grains/gallons, usually due to use of a water softener, it is recommended to mix in some potable water at the inlet to increase the hardness of the water to above 5 grains/gallons.
pH between 6.5 and 8.5
1. pH levels below 6.5 can cause an increase in the rate of corrosion. pH of 8.5 or higher can potentially cause lime scale buildup.
Total Dissolved Solids (TDS) less than 350 ppm
1. Total dissolved solids are all minerals, salts, metals, and charged particles that are dissolved in water.
2. The greater the amounts of TDS present, the higher the corrosion potential due to increased conductivity in the water.
Chlorine concentration less than 150 ppm
1. Do not fill boiler or operate with water containing chlorine in excess of 150 ppm.
2. Filling with fresh drinking water should be acceptable.
3. Do not use the boiler to directly heat swimming pool or spa water.
Conduct water quality testing prior to installing the appliance. Various solutions are available to adjust water quality.
Boiler water
CAUTION
Table 6A Boiler Water Chemistry
Speci cation Range
Dissolved Solids < 2000 ppm
• Monitoring pH, chlorides, TDS, and hardness levels can prolong the life of the appliance by reducing lime scale buildup, corrosion, and erosion. Check for leaks to ensure that fresh water is not entering the system.
Continual fresh makeup water will reduce boiler life.
Mineral buildup in the heat exchanger reduces heat transfer, overheats the stainless steel heat exchanger, and causes failure.
The addition of oxygen carried in by makeup water can cause internal corrosion in system components.
• Leaks in the boiler or piping must be repaired at once to prevent excessive makeup water. For this purpose, it is recommended to install a water meter to easily check the amount of makeup water entering the system. Makeup water volume should not exceed 5% of the total system volume per year. NOTE: When makeup water is added, make sure the chemical additives are added to maintain the correct level.
• An approved multi-metal corrosion inhibitor (comparable to Sentinel X100 or Fernox F1) is recommended at the correct concentration and in the manner recommended by the manufacturer.
Do not use petroleum based cleaning or sealing compounds in the boiler system. Gaskets and seals in the system may be damaged. This can result in substantial property damage.
DO NOT use "homemade cures" or "boiler patent medicines". Serious damage to boiler, personnel, and/or property may result.
BOILER WATER CHEMISTRY
pH Level 6.5 to 9.5
Chloride < 150 ppm
Freeze protection for a heating boiler system (if required)
WARNING
Ethylene glycol is toxic, DO NOT use as your freeze protection. Ethylene glycol has a sweet aroma which children and pets could mistake as food and ingest; leading to death.
41
Page 42
6 Start-up
1. Use glycol only if needed for freeze protection.
Installation & Service Manual
Fill and test water system
2. Propylene glycol is the recommended freeze protection.
3. Make sure to flush the boiler system before adding glycol.
4. Determine the freeze protection fluid quantity using system water content, following the fluid manufacturer's instructions. Boiler water content is listed on page 6. Remember to include expansion tank water content.
5. Local codes may require a backflow preventer or actual disconnect from city water supply.
6. When using freeze protection fluid with automatic fill, it is suggested to install a water meter to monitor water makeup. Freeze protection fluid may leak before the water begins to leak, causing the concentration to drop, which reduces the freeze protection level.
7. The freeze protection set points may be lowered when freeze protection fluid is used .
8. Consult the glycol manufacturer for details on the suggested mix of glycol and water for the desired freeze protection level and the de-rate effect it will have on the boiler output.
Test / replace freeze protection fluid
1. For systems using freeze protection fluids, follow the fluid manufacturer's instructions.
2. Freeze protection fluid must be replaced periodically due to degradation of inhibitors over time.
3. It is recommended to test the glycol concentration annually and adjust within the desired set points.
Oxygen prevention
CAUTION
Dissolved oxygen can have a negative effect on the boiler system. Oxygen can cause iron oxide to generate iron deposits. Oxygen may also increase the rate of corrosion on non-stainless steel parts of the system. A low pH level combined with oxygen further enhances its corrosive effects. After boiler installation, check for air leaks in the following areas:
• Suction gasket
Pump
• Air valve
• O-ring gaskets
Precautions include installing a water meter to evaluate the fresh water volume entering the system (should be no more than 5% system volume). Additional volumes of fresh water could indicate that a leak is present.
Eliminate all system leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in the heat exchanger, reducing heat transfer, overheating the heat exchanger, and causing heat exchanger failure.
1. Fill system only after ensuring the water meets the requirements of this manual.
2. Close automatic and manual air vents and boiler drain valve.
3. Fill to correct system pressure. Correct pressure will vary with each application.
a. The minimum cold water fill pressure for a system is
12 psi.
b. Pressure will rise when the boiler is turned ON and
system water temperature increases.
4. At initial fill and during boiler startup and testing, check the system thoroughly for any leaks. Repair all leaks before proceeding further.
Purge air from water system
1. Purge air from system:
a. Connect a hose to the purge valve (see purge/drain
valve in the piping diagrams on pages 29 through 32). Route the hose to an area where water can drain and be seen.
b. Close the boiler or system isolation valve between the
purge valve and fill connection to the system.
c. Close zone isolation valves. d. Open the quick-fill valve on the cold water makeup
line.
e. Open purge valve. f. Open the isolation valves one zone at a time. Allow
water to run through the zone, pushing out the air. Run until no noticeable air flow is present. Close the zone isolation valves and proceed with the next zone. Follow this procedure until all zones are purged.
g. Close the quick-fill water valve and purge valve and
remove the hose. Open all isolation valves. Watch that system pressure rises to correct cold-fill pressure.
h. After the system has operated for a while, eliminate
any residual air by using the manual air vents located throughout the system.
i. If purge valves are not installed in the system, open the
manual air vents in the system one at a time, beginning with the lowest floor. Close the vent when water squirts out. Repeat with remaining vents.
2. Open the automatic air vent (diaphragm-type or bladder type expansion tank systems only) one turn.
3. Open other vents:
a. Starting on the lowest floor, open air vents one at a
time until water squirts out.
b. Repeat with remaining vents.
4. Refill to correct pressure.
42
Page 43
6 Start-up (continued)
Installation & Service Manual
Check for gas leaks
WARNING
WARNING
Before starting the boiler, and during initial operation, smell near the floor and around the boiler for gas odorant or any unusual odor. Remove the front access panel and smell the interior of the boiler enclosure. Do not proceed with startup if there is any indication of a gas leak. Use an approved leak detection solution. Repair any leaks at once.
Propane boilers only – Your propane supplier mixes an odorant with the propane to make its presence detectable. In some instances, the odorant can fade, and the gas may no longer have an odor. Before startup (and periodically thereafter), have the propane supplier verify the correct odorant level in the gas.
Intermittent Pilot Spark Ignition System
WARNING
The ignition module is not repairable. Any mod i fi ca tion or repairs will invalidate the warranty and may create hazardous conditions that result in prop er ty damage, personal injury, fire, explosion and/or toxic gases. A faulty ignition module must be re placed with a new module.
Freeze Protection
1. For boilers with the pump delay option, if either the inlet sensor or the optional multi-purpose temperature sensor reads below 40°F, the pump relay will turn ON. When the temperature rises above 50°F the pump relay will turn OFF.
2. Location - Heating boilers must be located in a room having a temperature safely above freezing [32°F(0°C)].
3. Caution - A room where the appliance is installed and operating under a negative pressure may experience a downdraft in the flue of an appliance which is not firing. The cold outside air pulled down the flue may freeze a heat exchanger. This condition must be cor rect ed to provide adequate freeze protection.
4. Freeze protection for a heating boiler or hot water supply boiler using an indirect coil can be provided by using hydronic system antifreeze. Follow the manufacturers instructions. DO NOT use un di lut ed or automotive type antifreeze.
5. A snow screen should be installed to pre vent snow and ice accumulation around the appliance vent ing system in cold climates.
6. Shut-down and Draining - If for any rea son, the appliance is to be shut off, the following precautionary measures must be taken:
(a) Shut off gas supply.
(b) Shut off water supply.
(c) Shut off electrical supply.
(d) Drain the unit completely. Remove one threaded
plug or bulbwell from the inlet side of the front header and one from the outlet side of the front header on the heat exchanger. Blow all wa ter out of the heat exchanger.
(e) Drain pump and piping.
43
Page 44
7 Maintenance
Maintenance and annual startup
Table 7A_Service and Maintenance Schedules
Installation & Service Manual
Service technician
(see the following pages for instructions)
General:
• Address reported problems
• Inspect interior; clean and vacuum if necessary;
Check for leaks (water, gas, flue)
• Examine venting system
Check system water pressure/system piping/expansion tank
Check fill water meter
Test boiler water. When test indicates, clean system water with approved system restorer following manufacturer’s information.
ANNUAL START-UP
• Check control settings
Owner maintenance
(see the User’s Information Manual for instructions)
• Check appliance area
Daily
Monthly
Check pressure/temperature gauge
• Check vent piping
• Check relief valve
Check wiring and connections
• Flame inspection (stable, uniform)
• Check flue gas passageways
Inspect and clean the burners
• Perform start-up checkout and performance verification per Section 6 - Start-up.
If combustion or performance indicate need:
• Clean heat exchanger
Remove and wash burners
44
Periodically
Every
6 months
End
of season
months
• Test low water cutoff (if used)
• Reset button (low water cutoff)
Check appliance piping (gas and water) for leaks
• Operate relief valve
Shut appliance down (unless boiler used for domestic hot water)
Page 45
7 Maintenance (continued)
Installation & Service Manual
WARNING
WARNING
WARNING
CAUTION
Follow the service and maintenance procedures given throughout this manual and in component literature shipped with the appliance. Failure to perform the service and maintenance could result in damage to the appliance or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death, or substantial property damage.
The appliance should be inspected annually only by a qualified service technician. In addition, the maintenance and care of the appliance designated in Table 7A and explained on the following pages must be performed to assure maximum appliance efficiency and reliability. Failure to service and maintain the appliance and system could result in equipment failure.
Electrical shock hazard – Turn off power to the appliance before any service operation on the appliance except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.
Label all wires prior to dis con nec tion when servicing controls. Wiring errors can cause improp er and dangerous operation.
Address reported problems
1. Inspect any problems reported by the owner and correct before proceeding.
Inspect appliance area
1. Verify that appliance area is free of any combustible materials, gasoline and other flammable vapors and liquids.
Inspect appliance interior
1. Remove the outer access panels and inspect the interior of the appliance.
2. Vacuum any sediment from inside the appliance and components. Remove any obstructions.
Flue vent system and air supply
1. Examine the venting system at least once a year. Check more often in the first year to de ter mine in spec tion interval. Check all joints and pipe connections for tightness, corrosion or deterioration. Clean louvers and/or screens in the combustion air intake system as required. Have the entire system, including the venting system, periodically inspected by a qualified service agency.
2. Check for gastight seal at every connection, seam of air piping, and vent piping periodically inspected by a qualified service agency.
WARNING
Venting system must be sealed gastight to prevent flue gas spillage and carbon monoxide emissions, which will result in severe personal injury or death.
Check all piping for leaks
Listed below are items that must be checked to en sure safe reliable operation. Verify proper op er a tion after servicing.
WARNING
1. Inspect all water and gas piping and verify to be leak free.
2. Look for signs of leaking lines and correct any problems found.
3. Check gas line using the procedure found in Section 3 - Gas Connections.
Eliminate all system or appliance leaks. Continual fresh makeup water will reduce appliance life. Minerals can build up in sections, reducing heat transfer, overheating heat exchanger, and causing heat exchanger failure. Leaking water may also cause severe property damage.
Check water system
1. Verify all system components are correctly installed and operational.
2. Check the cold fill pressure for the system. Verify it is correct (must be a minimum of 12 PSI).
3. Watch the system pressure as the boiler heats up (during testing) to ensure pressure does not rise too high. Excessive pressure rise indicates expansion tank sizing or performance problem.
4. Inspect automatic air vents and air separators. Remove air vent caps and briefly press push valve to flush vent. Replace caps. Make sure vents do not leak. Replace any leaking vents.
45
Page 46
7 Maintenance
Installation & Service Manual
Check Expansion Tank
1. Expansion tanks provide space for water to move in and out as the heating system water expands due to temperature increase or contracts as the water cools. Tanks may be open, closed, diaphragm or bladder type. See Section 4 - Water Connections for suggested best location of expansion tanks and air eliminators.
Check fill water meter
1. Check fill water meter for water usage. If the amount exceeds 5% of your system volume, you could have a leak. Have the system checked for leaks and fixed by a qualified service technician.
Test boiler water
1. Test boiler water. Reference the Copper-Fin Installation and Operation Manual for guidelines. When test indicates, clean system water with approved system restorer following the manufacturer’s information.
Check Relief Valve
WARNING
2. After following the above warning directions, if the relief valve weeps or will not seat properly, replace the relief valve. Ensure that the reason for relief valve weeping is the valve and not over-pressurization of the system due to expansion tank waterlogging or undersizing.
Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal. Otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down the appliance until a new relief valve has been installed.
1. Inspect the relief valve and lift the lever to verify flow. Before operating any relief valve, ensure that it is piped with its discharge in a safe area to avoid severe scald potential. Read Section 4 - Water Connections before proceeding further.
WARNING
Safety relief valves should be re-inspected AT LEAST ONCE EVERY THREE YEARS, by a licensed plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency – not by the owner. Failure to re-inspect the boiler relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage.
46
Page 47
7 Maintenance (continued)
Installation & Service Manual
Check All Wiring
1. Inspect all wiring, making sure wires are in good condition and securely attached.
Check Control Settings
1. Adjust settings if necessary. See Section 5 - Electrical Connections for adjustment procedures.
2. Check settings of external limit controls (if any) and adjust if necessary.
Perform Start-up and Checks
1. Start appliance and perform checks and tests specified in
Section 6 - Start-up.
2. Verify cold fill pressure is correct and that operating
pressure does not go too high.
Check Burner Flame
Visually check main burner flames at each start-up after long shutdown periods or at least every six months. A burner viewport is located on the burner mounting flange.
WARNING
The area around the burner viewport is hot and direct contact could result in burns.
Combustion Air
This ap pli ance uses an atmospheric combustion process. Combustion air is provided to the burners by the gas injection pressure into the venturi of the burn ers. The burners do not have an adjustable air shutter. Ad e quate combustion air must be supplied to the room where the appliance is installed to ensure proper burner operation. Check frequently to be sure the flow of com bus tion and ventilation air to the unit is not obstructed. When the main burn ers light, observe the burn er flame. Flames should be light blue in color with slight yellow tips; flames should be settled on burner head with no lifting when supplied with correct vol ume of combustion air.
Check Flue Gas Passageways
Any sign of soot around the outer jacket, at the burn ers or in the areas between the fins on the cop per heat exchanger indicates a need for cleaning. The following cleaning procedure must only be per formed by a qualified serviceman or installer. Prop er service is required to maintain safe operation. Properly installed and ad just ed appliances sel dom need flue cleaning.
NOTICE
All gaskets on disassembled components must be replaced with new gaskets on re as sem bly. Gasket kits are available from your distributor.
Heat Exchanger / Burner Access
WARNING: The area around the burners is hot and direct contact could result in burns!
NORMAL
A
C
YELLOW FLAME
YELLOW TIP
B
D
FLAME LIFT
Figure 7-1_Flame Pattern Illustration
Normal Flame: A normal flame is blue, with slight yellow tips, with a well defined inner cone and no flame lifting.
Yellow Tip: Yellow tip can be caused by blockage or partial obstruction of air flow to the burner(s).
Yellow Flames: Yellow flames can be caused by blockage of primary air flow to the burner(s) or excessive gas input. This condition MUST be cor rect ed immediately.
Lifting Flames: Lifting flames can be caused by over firing the burner(s) or excessive primary air.
WARNING
The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline Silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created to convert the ceramic fibers in this appliance to cristobalite.
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines:
If improper flame is observed, examine the venting system, ensure proper gas supply and adequate supply of combustion and ventilation air.
47
Page 48
7 Maintenance
Installation & Service Manual
Avoid breathing dust and contact with skin and eyes.
• Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the jobsite conditions. Current NIOSH recommendations can be found on the NIOSH website at (http://www.cdc.gov/niosh/homepage.html). NIOSH approved respirators, manufacturers and phone numbers are also listed on this website.
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Apply enough water to the combustion chamber lining to
prevent airborne dust.
Remove combustion chamber lining from the appliance
and place it in a plastic bag for disposal.
Wash potentially contaminated clothes separately from
other clothing. Rinse clothes thoroughly.
NIOSH stated First Aid:
Eye: Irrigate immediately.
Breathing: Fresh air.
a. Turn “OFF” main power to the appliance.
Inspection and Cleaning
j. Check the heat exchanger surface for sooting. The
external surfaces of the copper tubes should be free of any soot deposits. (A slight black smudge is normal with some types of gases.) If abnormal soot deposits are present, the heat exchanger must be cleaned and the cause of the soot problem corrected. Proceed as follows:
k. Remove soot from burners and bottom of the finned
tubes with a stiff bristle brush. Dirt may also be removed from burner ports by rinsing the burner thor ough ly with water. Drain and dry burners before re-installing. Damaged burners must be re placed.
An appliance installed in a dust or dirt con tam i nat ed atmosphere will require cleaning of the burners on a 3 to 6 month schedule or more often, based on severity of contamination. Contaminants can be drawn in with the combustion air. Non-combustible particulate mat ter such as dust, dirt, concrete dust or dry wall dust can block burner ports and cause non-warrantable failure. Use extreme care when operating an appliance for temporary heat during new construction. The burners will probably re quire a thorough cleaning before the appliance is placed in service.
b. Turn “OFF” external manual gas shutoff valve to
appliance.
c. Remove the control panel door.
d. Remove the outer air deflector (FIG. 7-2)
e. Disconnect gas valve wiring and remove gas manifold
assembly.
f. Remove ignition wire leading to the pilot assembly
from the ignition module.
g. Disconnect the wiring from the flame rollout/interlock
switch, see FIG. 7-2, page 49.
h. Remove the lower front jacket panel.
i. Remove the control panel mounting screws. When
removing the control panel, lay the control panel to the side with the wiring intact, being careful not to damage any of the wiring.
Remove the combustion chamber door. Use caution
to prevent damage to burn ers, refractory, pilot or wiring.
l. Remove gas manifold as described in steps a. thru e. in
“Heat Exchanger/Burner Access.”
m. Loosen mounting screws and remove front control
panel.
n. Loosen screws on the upper front jack et panel and
remove toward front of the appliance. Use caution to prevent damage to re frac to ry on the doors inner surface.
o. Check “V” baffles on top of the heat ex chang er.
Remove and clean if necessary.
p. Remove soot from the heat exchanger with a stiff
bristle brush. Soot may also be re moved from the heat exchanger by washing thoroughly with detergent and water. Remove the heat exchanger before using water for cleaning. Rinse thoroughly and dry before re-installing. Use a vacuum to remove loose soot from surfaces and in ner chamber.
q. Remove the heat exchanger (HEX) filler bracket
(FIG. 7-2).
r. The heat exchanger can be removed by sliding towards
the front of the appliance. Once the heat exchanger is removed from the ap pli ance, a garden hose can be used to wash the tubes to ensure that all soot is removed from the heat exchanger surfaces.
48
Page 49
7 Maintenance (continued)
Installation & Service Manual
s. Ensure that all burner ports are cleaned to remove
any soot. See Inspection and Cleaning Procedure, page 48.
t. Carefully re-install the heat exchanger, “V” baffles,
jacket panels, and wires.
u. Reassemble all gas and water piping. Test for gas
leaks.
v. Cycle the appliance and check for prop er operation.
UPPER FRONT JACKET PANEL
OUTER AIR DEFLECTOR
FLAME ROLLOUT / INTERLOCK SWITCH
HEX FILLER BRACKET
A
IMG00282
DETAIL A
LOWER FRONT JACKET PANEL
Figure 7-2_Outer Air Deflector and HEX Filler Bracket
Water Circulating Pump
Inspection of Heat Exchanger Waterways
Appliances operated in hard water areas should have periodic inspections of the tubes to be sure that no sediment or scale accumulates on the heat transfer sur fac es. Inspection plugs are located at both ends of the heat exchanger. In spec tion plugs should be removed and tubes inspected at the end of the first 45 days of operation and again at the end of 90 days of operation. If no scale accumulation is ob served, inspections can be made at the end of each six months of op er a tion.
IMPORTANT
Upon completion of any testing on the gas system, leak test all gas connections with a soap solution while main burners are operating. Im me di ate ly repair any leak found in the gas train or re lat­ed components. Do Not operate an appliance with a leak in the gas train, valves or related piping.
Gas Train and Controls
GAS FLOW
Inspect pump ev ery 6 months and oil if required. Use SAE 30 non-detergent oil or lubricant specified by pump man u fac tur er.
Clear Area
1. Keep appliance area clear and free from com bus ti ble
materials, gasoline and other flammable vapors and liquids.
2. Check frequently to be sure the flow of com bus tion and
ventilation air to the boiler is not obstructed.
Figure 7-3_Gas Train
Review with owner
1. Review the User’s Information Manual with the owner.
2. Emphasize the need to perform the maintenance schedule specified in the User’s Information Manual (and in this manual as well).
3. Remind the owner of the need to call a licensed contractor should the appliance or system exhibit any unusual behavior.
4. Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.
49
Page 50
Installation & Service Manual
8 Troubleshooting
Checking Temperature Sensors
The boiler temperature sensors (inlet water, system water, and outdoor air) are all resistance type devices. The following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor.
Table 8-1A - Inlet Water/System Sensor Resistance vs. Temperature
Temperature Resistance Temperature Resistance
50 19,553 158 2,004
68 12,690 176 1,464
86 8,406 194 1,084
104 5,715 212 816
122 3,958
140 2,786
Table 8-1B - Outdoor Air Sensor Resistance vs. Temperature
Temperature Resistance Temperature Resistance
-50 490,813 20 46,218
-40 336,606 30 34,558
-30 234,196 40 26,099
-20 165,180 50 19,900 10 118,018 60 15,311
0 85,362 70 11,883
10 62,465 80 9,299
50
Page 51
8 Troubleshooting (continued)
Troubleshooting Guide: M9 Solution Boilers
Installation & Service Manual
Step 1:
Step 2:
Step 3:
Are Wires W1 – W3 on TST20036-2
plugged into CN9 on TST20036-1 (see FIG. 5-5)?
YES
Is the Spark
Ignitor sparking?
YES
Is the pilot staying
on?
YES
NO
•Check the pilot tube for gas
•Check draft
NO
NO
NO
Is there continuity on the
Spark cable?
•Check for 24 VAC on 24V terminal (Gray Wire) on Ignition Module
NO
Is there 24 VAC (Purple Wire)
NO
Is there 24 VAC
at R1 and W1 on
the terminal strip?
on the 4-Pin connector plug
(CN1) on TST20036-1 (see FIG. 5-5)?
YES
Plug connector into
controller
Replace
YES
Ignition
Module
Step 4:
•Check voltage to and from the transformer
•Check incoming 120 VAC
Is the gas valve
getting 24 VAC
to the MV
terminal?
YES
•Check gas pressure
•Make sure Gas Valve knob is "ON"
NO
Replace
Ignition Module
YES
Check each of
the following for
an open:
•Brown and Purple Wire on the LWCO plug
•Rollout Switch
•Manual Reset High Limit
•Spill Switch If any of these
devices are
open, press the
reset button
Is there 24 VAC
(Tan Wire) on the
4-Pin connector plug
(CN1) on TST20036-1
(see FIG. 5-5)?
YES
Check each of
the following for
an open:
•X and B on terminal strip
•Purple and Black Wires on the Vent Damper Plug
•V and P on terminal strip
•Auto-Reset High Limit
NO
Check for an
open sensor
•If there is no open sensor, make sure there's a call for heat
•If a call for heat is present, replace the temperature controller
IMG00286
51
Page 52
17
18
10
9 Diagrams
Installation & Service Manual
Schematic Diagram - M9 Unit
45,000 - 260,000 Btu/hr Models
CN12-2
G
W
W
W BN
Y
SPILL
SWITCH
B
C
P
GND
SPARK
BL
PILOT
120V
NEUTRAL
CN12-1
PR
Y
GY
Y
CHASSIS GROUND
W
PR
120V
120V
LINE
GROUND
G
GROUND
BK
BL
BL
BL
24VDC RELAY
PUMP DELAY
BK
24VAC RELAY
BYPASS PUMP
BK
PK
PK
BK
BL
CN1-1 CN1-2
OPERATOR
1
LOW WATER
CUTOFF
BK
120V
24V
2
CIRCULATION
PUMP
BYPASS PUMP
PK
TRANSFORMER
Y
Y
Y
MOT
MOT
W
Y
TANK
AQUASTAT
BL
CN10-1
Y
CN10-2
OPERATOR
CN12-3
2
BN
LOW WATER
3
DAMPER
5
CUTOFF
VENT
3
R
4
PR
BN
PR
R1
PR
ROLLOUT
SWITCH
THERMOSTAT
24VAC RELAY
BYPASS PUMP
MANUAL
RESET
HIGH LIMIT
C
W1
R
1
PR
PR
OPERATOR
CN1-4
PR
24V
IGNITION MODULE
R
OPERATOR
CN2-1
LBL20293 REV A
=
BK
=
BL
=
BN
=
G
4
BLACK BLUE BROWN GREEN
POWER
VENTER
VENT
DAMPER
GY
PV
BL
MV
CN2-2
CN3
CN4
CN5
CN6
CN7
CN8
CN11-1
CN11-2
CN1-3
R
24VDC RELAY
GY OR
PK PR
T
1
BK
AUTO-RESET
HIGH LIMIT
GAS VALVE
PV
PILOT
MV
LOW
HIGH
OR
BK
INLET SENSOR
BK
SYSTEM SENSOR
PUMP DELAY
OUTDOOR SENSOR
=
GRAY
=
ORANGE
=
PINK
=
PURPLE
X
PR
W
R T
Y
C
R
=
RED
=
TAN
=
WHITE
=
YELLOW
FLOW
SWITCH
C
POWER VENTER
V
W
GROUND
W2
P
R2
T
T
T
NO
VENTER RELAY
R
VENTER PROVING
GY
IGNITION
MV/
MODULE
PV
BURNER
GND
HIGH
FIRE
BOX DEPICTS
OPTIONAL ITEMS
Wiring Diagram - M9 Unit
45,000 - 260,000 Btu/hr Models
MODULE
MV
PV
MV/PV
R
W
BL
IGNITION
GND
24V
Y
GY
SPARK
BURNER GND
G
Y
GY G
R
W
BL
MV
C
PV
HI
GAS
VALVE
P
W2R2
R
FLOW
SWITCH
NOC
X
R1
R
B
W1
T
W
PR
HIGH FIRE
OR
T
Y
R
W
BL
SENSOR
OUTDOOR
R OR
OR
W3W1
W2
LED1
CN11CN10
FAULT
SENSOR
OUTDOOR
STAT
TANK
AQUA-
R
R
T
Y
W
BL
TST20036-2
CN12
R
BN
R
W
W
C
12
PR
TANK
AQUASTAT
BN
SPILL
RESET
MANUAL
HIGH LIMIT
PR
SWITCH
ROLLOUT
PR
Y
BN
PR YBN
PR
Y
PR
24VAC
RELAY
(GRAY)
TRANSFORMER
BK
PK
BK PK
SWITCH
PR
T Y
BL
Y
BL
BL Y
BN
PR
Y
BL
W
BK
W
W
BYPASS PUMP
PK
W
W
BK
PK
W
BK
PK
BK
PILOT
BOX DEPICTS
OPTIONAL TE MS
BL
LBL20294 REV A
Y
Y
HIGH LIMIT
AUTO-RESET
C
Y
P
GY
V
BK
Y
BK
CN2
OR
Y GYPR
BK
BL PR
YBKBNBN OR
PRBL R Y BK
54321
VENT
PLUG
DAMPER
BK
SYS/
TANK
INLET
PROBE
FIRE
HIGH
FIRE
LOW
PUMP
RELAY
OR
CN1
T
Y
BL
PR
R
POWER
VENTER
POWER
VENTER
VENT
DAMPER
INLET
SENSOR
SYSTEM
SENSOR
CN9
15
20
HIGH-FIRE
0
OFFSET °F
5
135
125
TST20036
110 140
120 130
115
MIN SETPOINT °F
TST20036-1
190
200
OFF
150
MAX SETPOINT °F
160
DISCONNECT POWER BEFORE SERVICING
T
PLUG
P2 A
CUTOFF
LOW WATER
1
2
3
W
4
BK
W
G
G
JUNCTION BOX
POWER SUPPLY
RESET
MANUAL
BK
Y
21P1
OR
BN
1
YOR BKBNYOR BK
2
3
4
BN
PUMP
DELAY
PK
OR
OR
AUTO
RESET
LOW WATER CUTOFF
OR
OR
24VDC
RELAY
BK
W
CIRCULATION
BK
TEMPERATURE AND GAUGE
WIRE OF EQUAL OR HIGHER
WHEN REPLACING W IRING, USE
(BLACK)
YELLOW
RED
TAN
WHITE =
=
=
= T
Y
R
W
GRAY
ORANGE
PINK
PURPLE
=
=
=
=
PK
PR
GY
OR
PUMP
BLACK
BLUE
BROWN
GREEN
=
=
=
= G
BL
BK
BN
52
Page 53
Notes
53
Page 54
Notes
54
Page 55
Notes
55
Page 56
Revision A (ECO #C11102) initial release Revision B (ECO C12077) reflects the update of ignition timing
information on pages. 40 and 41. Revision C (ECO C13462) reflects the addition of the Checking
Temperature Sensors Section on page 48. Revision D (ECO C14226) reflects the addition of cautionary statements
and notes on page 16 beneath the “Vent Materials” table. Revision E (ECO C17014) reflects the update of Table 3E on page 19. Revision F (PCP #3000021634 / CN #500011858) reflects changes
made to water chemistry information on pages 4, 25, 28-32, 41-44, and 46.
Revision G (PCP #3000023937 / CN #500013881) reflects an update to the vent damper information on page 17.
SBRX-I-S_MM #100161690_DIR #2000017139_Rev G
04/18
Loading...