Lochinvar CBL0497 User Manual

COPPER-FIN
®
BOILER
Submittal Sheet
CB-Sub-12
COPPER-FIN® GAS BOILERS (MODELS CB 0497-2067)
Standard Features
• 81% Thermal Efficiency
• Electronic Temperature Control
• Fan Assisted Combustion
• Sealed Combustion Chamber
• Stainless Steel Burners
• Low NOx Operation Exceeds the Most Stringent Air Quality Requirements
• ASME Copper Finned Tube Heat Exchanger
• 160 psi Working Pressure
• Gasketless Heat Exchanger Design
• Pump Relay w/ Delay
• Down Stream Test Valve
• Referenced Gas Valves
• Loch-Heat Ceramic Tile Combustion Chamber
• Hot Surface Ignition
• Adjustable High Limit w/ Manual Reset
• 50 psi ASME Relief Valve
• Temperature & Pressure Gauge
• Flow Switch
• 24 Volt Control System
• BMS Terminal Strip
• Combustion Air Filter
• Freeze Protection
• 10 Year Limited Warranty on Heat Exchanger (See warranty for details)
Optional Equipment
Alarm Bell Contacts on any Failure Contacts for Air Louvers Cupro-Nickel Heat Exchanger High & Low Gas Pressure Switch w/ Manual Reset Outdoor Reset Control Manual Reset Low Water Cut-Off w/ test Stack Frame MP2 Sequencer 30 psi ASME Relief Valve
75 psi ASME Relief Valve 100 psi ASME Relief Valve 125 psi ASME Relief Valve 150 psi ASME Relief Valve
Available Firing Systems
M9 Hot Surface Ignition with Electronic Supervision (Standard) M13 GE GAP/FM/CSD1 M7 California Code
Registered under U.S. Patent # 5,989,020
Copper-Fin® Gas Boiler Dimensions & Specifications
Copper-Fin Heating Boiler Dimensions & Spec i fi ca tions
Input Heating Net AHRI Model Max Thermal Capacity Rating Gas Vent Shipping Number MBH Efficiency MBH MBH A B C D E F G Conn. Size Weight
CBN0497 495 81% 401 349 31-1/2” 45-1/4” 22-1/4” 12-1/2” 9-1/2” 22-3/4” 29-1/2” 1-1/4” 6” 440 CBN0647 645 81% 522 454 31-1/2” 56-3/4” 22-1/4” 12-1/2” 9-1/2” 28-1/2” 29-1/2” 1-1/4” 8” 510 CBN0747 745 81% 603 524 31-1/2” 64” 22-1/4” 12-1/2” 9-1/2” 32” 29-1/2” 1-1/4” 8” 550 CBN0987 985 81% 798 694 36” 48-1/4” 33-1/2” 15-3/4” 8-1/2” 8-1/2” 33-3/4” 2” 10” 845 CBN1257 1255 81% 1,017 884 36” 58-1/2” 33-1/2” 15-3/4” 9-1/2” 10-1/2” 33-3/4” 2” 12” 905 CBN1437 1435 81% 1,162 1,010 36” 68-3/4” 33-1/2” 15-3/4” 10-1/2” 10-1/2” 33-3/4” 2” 12” 1050 CBN1797 1795 81% 1,454 1,264 36” 82-1/4” 33-1/2” 15-3/4” 11” 11” 33-3/4” 2” 14” 1193 CBN2067 2065 81% 1,673 1,455 36” 92-1/2” 33-1/2” 15-3/4” 11” 11” 33-3/4” 2” 14” 1350
Notes: Change ‘N’ to ‘L’ for LP gas models. Water connections for models CB 0497-747 are 2” NPT on 6-1/2” centers. No deration on LP models. Water connections for models CB 0987-2067 are 2-1/2” NPT on 11-1/4” centers. Performance data based on manufacturer test results.
Venting Options
Outdoor Vent Cap
Lochinvar, LLC 300 Maddox Simpson Parkway Lebanon, Tennessee 37090 P: 615.889.8900 / F: 615.547.1000
Approx. Model No. Fans Controls Total Amps
497 3.6 3.6 7.2 647 3.6 3.6 7.2 747 3.6 3.6 7.2 987 3.4 4.6 8.0 1257 3.4 4.6 8.0 1437 3.8 4.6 8.4 1797 3.8 4.6 8.4 2067 3.8 4.6 8.4