Lochinvar CB1256 Installation Manual

Page 1
DESIGNER’S GUIDE COPPER-FIN®BOILER
495,000 – 2,065,000 Btu/hr
Page 2
Dear Specifier/Project Manager,
At Lochinvar, we have long recognized the importance of innovation to any product or service. Those who enter into business must also accept the challenge of meeting constantly changing needs.
All information has been organized and presented in a succinct, easy-to-use manner, so you can use and share information confidently and with minimal effort.
However, it is important to remember that this guide is not intended to replace our installation manual. Installers should still refer to our installation manual for specific installation instructions.
We hope this manual will make your work easier and more productive. As always, we greatly appreciate your input on additional improvements for the future.
Thanks once again for specifying the Lochinvar family of quality standard and custom-built boilers and boilers.
Sincerely,
Lochinvar Corporation
Nashville, TN • 615-889-8900 • Fax: 615-547-1000
Page 3
Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 1
Table of Contents
Air Removal . . . . . . . . . . . . . . . . . . . . . .16
Boiler Operating Temperature Control . . . .16
Circulator Pump Operation . . . . . . . . . . .12
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Combustion & Ventilation Air . . . . . . . . . . .5
Contaminants . . . . . . . . . . . . . . . . . . . . . .6
Determining Total “Free Area” . . . . . . . . . .7
Electrical Requirements . . . . . . . . . . . . . . .17
Gas Supply . . . . . . . . . . . . . . . . . . . . . .10
General Venting . . . . . . . . . . . . . . . . . . . .6
Location of Unit . . . . . . . . . . . . . . . . . . . . .2
Low System Water Volume . . . . . . . . . . . .16
Low Water Temperature System . . . . . . . .14
Outdoor Use . . . . . . . . . . . . . . . . . . . . . . .3
Outdoor Installation . . . . . . . . . . . . . . . . . .9
Primary/Secondary Piping . . . . . . . . . . . .13
Relief Valve . . . . . . . . . . . . . . . . . . . . . . .14
Remote Temperature Control . . . . . . . . . . .17
Special Design Applications . . . . . . . . . . .15
Variable Speed Pumping . . . . . . . . . . . . .16
Venting Options . . . . . . . . . . . . . . . . . . . .8
Water Flow Requirements . . . . . . . . . . . .12
Water Velocity Control . . . . . . . . . . . . . . .12
Figures & Tables Index
FIG. 1 Models CB 495-2066
Requirements For Installation
Over Combustible Floor . . . . . . .3
FIG. 2 Boiler Equipment &
Control Orientation . . . . . . . . . . .4
FIG. 3-6 Combustion & Ventilation Air . .5, 6 FIG. 7 Barometric Damper Installation . .8
FIG. 8 Multiple Unit Barometric
Damper Installation . . . . . . . . . . .9
FIG. 9 Outdoor Venting . . . . . . . . . . . . .9
FIG. 10 Heat Exchanger Head Loss
Models CB 495-745 . . . . . . . . .9
FIG. 11 Heat Exchanger Head Loss
Models CB 986-2066 . . . . . . . .9
FIG. 12 Primary/Secondary
System Piping . . . . . . . . . . . . . .13
FIG. 13 High Flow System Piping . . . . . .14
FIG. 14 Low Temperature Bypass
System Piping . . . . . . . . . . . . . .15
FIG. 15 Low Temperature Bypass Piping
On/Off . . . . . . . . . . . . . . . . . .15
FIG. 16 Low Temperature Bypass Piping
Stage Firing . . . . . . . . . . . . . . .15
FIG. 17 Heating/Chilled
Water System . . . . . . . . . . . . . .16
FIG. 18 Buffer Tank Piping . . . . . . . . . . .17
TABLE A. Clearances From
Combustibles . . . . . . . . . . . . . .3
TABLE B. Flue Sizes and
Combustion Air Pipe Sizes . . . . .8
TABLE C. Outdoor Kits . . . . . . . . . . . . . .10
TABLE D. Gas Supply Pipe Sizing . . . . . .11
TABLE E. Inlet Gas Pressure . . . . . . . . . .11
TABLE F. Water Flow Requirements . . . . .12
TABLE G. Minimum and Maximum
Boiler Flow Rates . . . . . . . . . . .12
TABLE H. Amp Draw Data . . . . . . . . . . . .17
Boiler Piping Diagrams
Primary/Secondary Boiler Piping . . . . . . .A1
Multiple Unit Primary/Secondary Piping . .A2 Low Temperature Boiler Bypass Piping . . .A3 Low Temperature Boiler Bypass Piping
with 3-way Valve . . . . . . . . . . . . . . . .A4
Page 4
CODES
The equipment shall be installed in accordance with those installation regulations in effect in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
In the absence of such requirements, the installation shall conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to
American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1.
Where required by the authority having jurisdiction, the installation must comply with the Canadian Association Code, CAN/CGA- B149.1 and/or B149.2 and/or local codes.
LOCATION OF UNIT
Locate the unit so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the unit. The pan must not restrict combustion air flow.
2 Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900
1.
Lochinvar
o
Water Velocity
(See page 12 for Minimum
and Maximum Flow Rates.)
o
Piping Requirements
and Specialities
(See page 12 for
Water Flow Requirements
and system piping.)
o
Low Water Temperature
System
(See page 14 & 15 for
piping and design
recommendations.)
o
System and Boiler Control
(See page 16 for Control
Connections and
Operator Settings.)
o
Air Elimination and
Expansion Tank Placement
(See page 16 for Air
Removal Information.)
In designing a boiler system,
pay special attention to:
Under no circumstances is the manufacturer to be held responsible for water damage in connection with this unit or any of its components.
Page 5
The indoor units must be installed so that the ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.).
The appliance must be installed on a level, non-combustible floor. Concrete over wood is not considered a non-combustible floor. Maintain required clearances from combustible surfaces.
For installation on a combustible floor only when installed on special base: Units installed over a
combustible floor must use the Special Combustible Floor Base. The unit must be centered on the base as shown in FIG. 1.
• Provide a base of hollow clay tile or concrete blocks from 8 to 12 inches thick and extending 24 inches beyond the sides.
• The blocks must be placed in line so that the holes line up horizontally to provide a clear passage through the blocks.
This procedure should also be
followed if electrical conduit or radiant heat distribution piping runs through the floor and beneath the appliance.
• Ensure that combustible floor base meets local fire code requirements.
Outdoor models require the installation of an optional vent cap. Instructions for placement of the vent cap are included in the venting section.
Outdoor models must not be installed directly on the ground. The outdoor unit must be installed on a concrete brick, block or other non-combustible pad.
SPECIAL LOCATION: OUTDOOR USE
Outdoor models have additional location and clearance requirements. These requirements must be adhered to carefully, since wind, rain, snow and cold cannot be controlled in outdoor applications. See
Outdoor Installation on page 9.
2.
4.
3.
Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 3
(FIG. 1) CB 495-2066 REQUIREMENTS FOR INSTALLATION OVER COMBUSTIBLE FLOOR
5.
(TABLE A) – CLEARANCES FROM
COMBUSTIBLE CONSTRUCTION
CLEARANCES CB 495-2066 Right Side 3" Rear 3" Left Side 3"
(30" for Service)
Front ALCOVE*
(24" for Service) Top 3" Flue 1"+
* Alcove is a closet without a door. + Consult local codes and/or vent material manufacturer.
Page 6
4 Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900
Lochinvar
(FIG. 2) BOILER EQUIPMENT AND CONTROL ORIENTATION.
RIGHT SIDE
FLUE PRODUCTS VENT
TERMINAL
STRIP
HOT WATER
OUTLET
COLD WATER
INLET
BURNER INSPECTION PORT
FRONT
GAS
CONNECTION
HOT WATER
OUTLET
COLD WATER
INLET
BURNER
INSPECTION PORT
FRONT
AIR
INLET
FRESH AIR
INLET
RIGHT SIDE
FLUE PRODUCTS VENT
BACK
DRAIN
LEFT SIDE
BACK
120V ELECTRICAL
CONNECTION
ON/OFF SWITCH
OPERATOR
TERMINAL STRIP
ON/OFF SWITCH
LEFT SIDE
DRAIN
RELIEF VALVE
TAPPING
INLET GAS
CONNECTION
CB 495-745
CB 986-2066
Page 7
Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 5
COMBUSTION & VENTILATION AIR
Provisions for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1; in Canada, the latest edition of CGA Standard B149 Installation
Code for Gas Burning Appliances and Equipment; or applicable provisions of the
local building codes.
The equipment room must be provided with properly sized openings to assure adequate combustion air and proper ventilation when the unit is installed with conventional venting or sidewall venting.
If air is taken directly from outside the building with no duct, provide two
permanent openings:
A. Combustion air opening with a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm
2
per kW). This
opening must be located within 12 inches (30 cm) of the bottom of the enclosure.
B. Ventilation air opening with a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm
2
per kW). This
opening must be located within 12 inches (30 cm) of the top of the enclosure.
If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the mechanical room, each of the two
openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr input (11 cm
2
per kW).
If air is taken from another interior space, each of the two openings
specified above should have a net free
1.
2.
3.
(FIG. 3) COMBUSTION AIR DIRECT FROM OUTSIDE
(FIG. 4) COMBUSTION AIR THROUGH DUCTWORK
(FIG. 5) COMBUSTION AIR FROM AN
INTERIOR SPACE
CAUTION: Under no circumstances should the equipment room be under a negative pressure when atmospheric combustion equipment is installed in the room.
EXAMPLE OF
SIZING FOR
COMBUSTION
& VENTILATION
AIR OPENINGS
(BOILER WITH
2,065,000 Btu/hr
INPUT):
When combustion and
ventilated air is taken
from directly outside the
building (FIG. 4), divide
the total BTU’s by 4,000.
This yields 516.25 sq.in.
of “Free Area” without
restriction.
(2,065,000 ÷ 4000 =
516.25 sq.in.)
Since the air opening is
50% closed due to
screens and louvers, the
total opening must be
multiplied by 2.
(516.25 sq. in. x 2 =
1,032 sq.in.)
This project requires one
Ventilation Air Opening
with net “Area” of
1,032 square inches with
louver dimensions of 30
x 35and one
Combustion Air Opening
with net “Area” of
1,032 square inches with
louver dimensions
of 30x 35”.
Page 8
6 Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900
area of one square inch for each 1000 Btu/hr (22 cm
2
per kW) of input, but not
less than 100 square inches (645 cm
2
).
If a single combustion air opening is provided to bring combustion air in directly from the outdoors,
the opening must be sized based on a minimum free area of one square inch per 3000 Btu/hr input (7 cm
2
per kW).
This opening must be located within 12 inches (30 cm) of the top of the enclosure.
CONTAMINANTS
Combustion air drawn from an interior or exterior space must be free of any chemical fumes which could be corrosive to the boiler. Burning chemical fumes results in the formation of corrosive acids which attack the boiler, cause improper combustion and premature failure of the boiler and vent. These fumes are often present in areas where refrigerants, salts, and solvents are used. Therefore, be aware of swimming pool equipment, water softening, and cooling system placement.
VENTING
General
These boilers are classified as Category I appliances when tested to the latest ANSI Standard. This classification requires all conventionally vented combustion products to be vented using Category I listed vent pipe.
Additionally, it is recommended that this vent material be double wall construction or insulated in the field. A Category I appliance operates with a non-positive static vent pressure and with flue loss greater than 17 percent.
Vent installations for connection to gas vents or chimneys must be in accordance with Part 7, “Venting of Equipment,” of the latest edition of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the local building codes.
The connection from the appliance vent to the stack must be as direct as possible and sized correctly. The horizontal breeching of a vent must have at least 1/4rise per linear foot. The horizontal portions should also be supported for the design and weight of the material employed to maintain clearances, prevent physical damage and separation of joints.
The connection from the appliance vent to the stack or vent termination outside the building must be made with listed
Lochinvar
4.
(FIG. 6) COMBUSTION AIR FROM OUTSIDE,
SINGLE OPENING
CAUTION!
EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a down draft in the venting system. If a fan is used to supply combustion air to the equipment room, it must by sized such to make sure that it does not cause drafts which could lead to nuisance operational problems with the boiler.
Page 9
Category I double wall vent (or equivalent) connectors and sized according to vent sizing tables (FAN column) in the latest edition of the National Fuel Gas Code.
The Category I vent and accessories, such as firestop spacers, thimbles, caps, etc., must be installed in accordance with the vent manufacturer’s listing. The vent connector and firestop must provide correct spacing to combustible surfaces and seal to the vent connector on the upper and lower sides of each floor or ceiling through which the vent connector passes.
Any improper operation of the common venting system in an existing building should be corrected when new equipment is installed, so the installation conforms to the latest edition of the National Fuel Gas Code, ANSI Z223.1.
When resizing any portion of the common venting system, it should be resized to approach the minimum size as determined using the appropriate tables in the National Fuel Gas Code.
The weight of the venting system must not rest on the boiler. The venting system must be adequately supported in compliance with local codes and other applicable codes.
Vent Terminations
The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.6 m) above the highest point of the roof when within a 10 foot (3.05 m) radius.
Additionally, vertical terminations must be a minimum of 3 feet (0.9 m) above the roof line, and when less than 10 feet (3.05 m) from a parapet wall must be a minimum of 2 feet (0.61 m) higher than the parapet wall.
Vent caps should have a minimum clearance of 4 feet (1.2 m) horizontally from, and in no case above or below [unless a 4 feet (1.2 m) horizontal distance is maintained], electric meters, gas meters, regulators and relief equipment.
Maintain a distance of at least 3 feet (0.9 m) above any forced air inlet within 10 feet (3.05 m) and a distance of at least 4 feet (1.2 m) below, 4 feet (1.2 m) horizontally from, or 1 foot (30 cm) above any door, window or gravity air inlet.
Do not terminate the vent in a window well, stairwell, alcove, courtyard or other recessed area. The vent can not terminate below grade. The bottom of the vent terminal shall be located at least 12 inches (30 cm) above grade and clear of snow, ice, leaves or other debris.
The distance of the vent terminal from adjacent public walkways, adjacent buildings, windows, and building openings
Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 7
Page 10
8 Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900
must be consistent with the National Fuel Gas Code Z223.1 or in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment.
VENTING OPTIONS
Conventional Venting
A conventional venting system utilizes the natural buoyancy of the heated flue products to generate a negative draft. This draft forces flue products to rise vertically through a rooftop flue termination. The vent connection is made directly to the top of the unit and combustion air supplied from the mechanical room. Properly sizing vent material and the use of a barometric damper (when required) will lead to proper vent operation.
The minimum flue pipe diameters for all models, utilizing negative draft venting are as follows:
Size vent material using the “FAN” category of vent sizing tables in the latest edition of the National Fuel Gas Code. “FAN” applies to fan-assisted combustion appliances in Category I.
Barometric Dampers
A barometric damper is required when draft exceeds 0.08 inches of negative water column. When installed and adjusted properly, a barometric damper will maintain draft between 0.02 and 0.08 inches of negative water column ensuring proper operation.
Multiple unit installations with combined venting also require barometric dampers to regulate draft at each unit. Again, the negative draft must be within the range of
0.02 to 0.08 inches of negative water column to ensure proper operation.
Lochinvar
NOTE:
Flue gases will form a
white plume in winter.
Plume could obstruct
window view. Flue gas
condensate can freeze
on exterior surfaces or
on the vent cap. Flue
gas condensate can
cause discoloration of
exterior building
surfaces. Adjacent brick
or masonry surfaces
should be protected with
a rust resistant sheet
metal plate.
(FIG. 7) BAROMETRIC DAMPER INSTALLATION
(TABLE B)
FLUE SIZES AND COMBUSTION AIR PIPE SIZES
MODEL FLUE SIZE
NUMBER
CB495 6"
CB645 8"
CB745 8"
CB986 10"
CB1256 12"
CB1436 12"
CB1796 14"
CB2066 14"
Page 11
For this type of installation, it is best to use a draft control for each boiler located on the riser between the vent outlet and the breeching - Location “A”. When this riser is too short to permit the installation of a draft control, locate a separate control for each boiler on the main breeching as illustrated in Location “B”. If, because of general crowding or other reasons, neither of these locations are possible, use a single large control in the breeching between the boiler nearest the chimney and the chimney, as shown in Location “C”.
All draft readings are made while unit is in stable operation (approximately 5 minutes running time).
Masonry Chimney
A masonry chimney must be properly sized for the installation of a high efficiency gas fired appliance. Exterior masonry chimneys, with one or more sides exposed to cold outdoor temperatures, are more likely to have venting problems. The temperature of the flue products from a high efficiency appliance may not be able to sufficiently heat the masonry structure of the chimney to
generate proper draft. This will result in condensing of flue products, damage of the masonry flue/tile, insufficient draft and possible spillage of flue products into an occupied living space.
Carefully inspect all chimney systems during the project design phase. If there is any doubt about the sizing or condition of a masonry chimney, it is prudent to reline the chimney with a properly sized and approved chimney liner system. Metallic liner systems (Type “B” doublewall or flexible or rigid metallic liners) are recommended. Consult with local code officials to determine code requirements or the advisability of using or relining a masonry chimney.
OUTDOOR INSTALLATION
Units are self venting and can be used outdoors when installed with the optional Outdoor Cap. This cap mounts directly to the top of the boiler and covers the flue outlet and combustion air inlet openings on the jacket. No additional vent piping is required. Maintain a minimum clearance of 3 inches (76 mm) to combustible surfaces
Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 9
NOTE:
Common venting
systems may be too
large when an existing
unit is removed. Be
careful to resize any
common venting system
when new appliances
are installed or existing
appliances are replaced.
(FIG. 8) MULTIPLE UNIT BAROMETRIC
DAMPER INSTALLATION
(FIG. 9) OUTDOOR VENTING
NOTE:
Venting of a high
efficiency appliance into
a cold or oversized
masonry chimney can
result in operational and
safety problems.
Page 12
10 Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900
and a minimum of 3 inches (76 mm) clearance to the air inlet.
An outdoor unit should not be located so that high winds can deflect off of adjacent walls, buildings or shrubbery causing recirculation. Recirculation of flue products may cause operational problems, bad combustion or damage to controls. The unit should be located at least 3 feet (0.91m) from any wall or vertical surface to prevent adverse wind conditions from affecting performance.
Multiple unit outdoor installations require 48 inches (1.22 m) clearance between each vent cap. The outdoor cap must be located 4 feet (1.22 m) below and 4 feet (1.22 m) horizontally from any window, door, walkway or gravity air intake.
The combustion air inlet of the outdoor cap must be located at least one foot (0.30 m) above grade and above normal snow levels. The boiler must be at least 10 feet (3.05 m) away from any forced air inlet and at least 3 feet (0.91 m) outside any overhang.
Do not install in locations where rain from building runoff drains will spill onto the boiler.
Lochinvar must furnish an outdoor vent kit in accordance with CSA international requirements. Each kit includes the flue outlet/combustion air inlet, assembly, gasket and pump cover.
Freeze Protection­Outdoor Installation
A snow screen should be installed to prevent snow and ice accumulation around the appliance or its venting system.
If for any reason the unit is to be shut off:
(a.) Shut off water supply. (b.) Drain unit completely. (c.) Drain pump and piping.
If freeze protection is not provided for the system, a low ambient temperature alarm or automatic drain system is recommended.
GAS SUPPLY
Safe operation of unit requires properly sized gas supply piping (See TABLE D).
Gas pipe size may be larger than the heater connection.
A gas pressure regulator is suggested to help assure proper inlet gas pressure. If upstream pressure exceeds 6 oz. (10.5 inches of water column), an intermediate gas pressure regulator, of the lockup type, must be installed.
Installation of a union is suggested for ease of service.
Lochinvar
(TABLE C) - OUTDOOR VENT KIT PART NUMBERS
MODEL
NUMBER PART NUMBER
CB495 ODK3023
CB645 ODK3024
CB745 ODK3024
CB986 ODK3046
CB1256 ODK3047
CB1436 ODK3047
CB1796 ODK3048
CB2066 ODK3048
1.
2.
3.
4.
Page 13
Install a manual main gas shut-off valve with test plug, outside of the appliance gas connection and before the gas valve, when local codes require.
A trap (drip leg) should be provided in the inlet of the gas connection to the unit.
High Altitude Applications
Atmospheric pressure decreases as the height above sea level increases. At any altitude above sea level, a cubic foot will contain less gas than a cubic foot at sea level. Thus, the heating value of a cubic foot of fuel gas will decrease as height above sea level increases.
Specific gravity of a gas with respect to sea level also decreases with altitude. These changes in heating value and specific gravity tend to offset each other.
However, as elevation above sea level is increased, there is less oxygen per cubic foot of air. Therefore, heat input rate should be
reduced in an appliance above 2000 feet. Ratings should be reduced at the rate of 4 percent for each 1000 feet above sea level.
WATER CONNECTIONS
Inlet and Outlet Water Connections
For ease of service, install unions on inlet and outlet of the boiler.
The connection on the unit marked “Inlet” should be used for return water from the storage tank. The connection on the header marked “Outlet” should be connected to the inlet of the storage tank. (See Appendix A for Boiler Piping Diagrams).
Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 11
5.
6.
(TABLE D) – GAS SUPPLY PIPE SIZING
Length of Pipe In Straight Feet
Nominal Iron Pipe Size, Inches 10 20 30 40 50 60 70 80 90 100 125 150 175 200
369 256 205 174 155 141 128 121 113 106 95 86 79 74
697 477 384 328 292 267 256 246 210 200 179 164 149 138
1,400 974 789 677 595 543 502 472 441 410 369 333 308 287
2,150 1,500 1,210 1,020 923 830 769 707 666 636 564 513 472 441
4,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974 871 820
6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 1,300
11,200 7,900 6,400 5,400 4,870 4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340
23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720
Maximum capacity of pipe in thousands of BTU’s per hour for gas pressures of 14” Inches Water Column (0.5 PSIG) or less and a total system pressure drop of 0.05 Inch Water Column (Based on NAT GAS, 1025 BTU’s per Cubic Foot of Gas and 0.60 Specific Gravity).
11/
4
3
/
4
11/2
1
2
1
/
2
31/2
3
2
(TABLE E) – INLET GAS PRESSURE
MODELS NAT. GAS
LPG GAS
CB 495-645
Minimum Allowable 5 11 Maximum Allowable 10.5 13
CB 745
Minimum Allowable 5.5 11 Maximum Allowable 10.5 13
CB 986-2066
Minimum Allowable 4.5 8” Maximum Allowable 10.5 13
EXAMPLE OF
HIGH ALTITUDE
APPLICATIONS
For example, if a unit’s
input is 100,000 Btu/hr
at sea level, the rated
input at 4000 feet of
elevation can be calculated
by derating input 4% per
1000 feet above sea
level.
[Btu/hr Input]
[1.00 - (Elevation/ 1000
ft. x 0.04)] = Btu/hr
Input at specified
elevation.
[100,000][1.00 - (4000
ft. /1000 ft. x 0.04)]
= Btu/hr Input 4000’
elevation.
[100,000][0.84] =
84,000 Btu/hr Input at
4000 ft. elevation.
Page 14
WATER VELOCITY CONTROL
IMPORTANT
To ensure proper velocity through the heat exchanger, it is necessary to regulate the temperature rise across the heat exchanger from inlet to outlet. (This must be done on initial installation and periodically rechecked).
With the correct temperature rise across the heat exchanger (See TABLE F), you may be assured of the proper velocity in the tubes and long life and economical operation from the boiler.
CIRCULATOR PUMP OPERATION
A pump control relay is optional on CB 495-2066 heating boilers. When designing a system to utilize primary/ secondary operation, specify a pump control relay for intermittent pump operation.
WATER FLOW REQUIREMENTS and SYSTEM PIPING
Lochinvar boilers are generally capable of operating within the design flow rates for the building heating system. To ensure the most efficient operation, a boiler needs adequate water flow. Pump sizing, pipe sizing, and piping layout must be taken into
consideration for proper system flow. (TABLE F) provides Gallons Per Minute and boiler head-loss at various temperature rises for each boiler based on Btu/hr input. (TABLE G) provides maximum and minimum flow data for each model. These two charts
will provide assistance in system flow design.
Variable Speed System Pump
High efficiency boilers require minimum flow rates through the heat exchangers to operate safely and efficiently. A variable speed pump that reduces the flow rate, in the main system piping loop, below the minimum requirements of the total boiler system must not be installed.
Lochinvar
12 Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900
(TABLE F) – WATER FLOW REQUIREMENTS
TEMPERATURE RISE 15ºF ΔΔT 20ºF ΔΔT 25ºF ΔΔT 30ºF ΔΔT 35ºF ΔΔT 40ºF ΔΔT
INPUT OUTPUT GPM FT.HD GPM FT.HD GPM FT.HD GPM FT.HD GPM FT.HD GPM FT.HD
495,000 400,950 53.5 5.3 41.0 4.1 32.1 1.9 27.0 1.6 22.9 0.8 20.0 0.7
645,000 522,450 69.7 6.7 53.0 5.1 41.8 3.6 35.0 3.0 29.9 1.8 27.0 1.6
745,000 603,450 70.0* 8.9 61.0* 6.1 48.3 4.8 41.0 4.1 34.5 2.6 31.0 2.3
985,000 797,850 81.0 5.2 63.9 3.0 54.0 2.5 45.6 1.7 41.0 1.5
1,255,000 1,016,550 103.0* 7.3 81.4 5.1 69.0 4.3 58.1 3.0 52.0 2.7
1,435,000 1,162,350 103.0* 6.7 79.0 6.3 66.4 4.2 59.0 3.7
1,795,000 1,453,950 97.0* 7.9 83.1 7.3 74.0 6.5
2,065,000 1,672,650 105.2* 9.2 85.0 8.8
(TABLE G) – MINIMUM & MAXIMUM
BOILER FLOW RATES
MODEL MINIMUM MAXIMUM
NUMBER FLOW (GPM) FLOW (GPM)
CB495 20.5 75
CB645 21.0 75
CB745 25.0 75
CB986 32.0 90
CB1256 41.0 90
CB1436 47.0 90
CB1796 59.0 90
CB2066 68.0 90
NOTE: In Table F * indicates flows in excess of maximum flow rating for copper tube HEX. Cupronickel tube HEX are recommended for these flow rates.
IMPORTANT!
EXAMPLE
OF VARIABLE
SPEED PUMP
REQUIREMENTS:
4 - CBN2066
(Min. Flow = 68 GPM)
The combined "minimum"
flow for the boiler
system is
68 GPM x 4 = 272 GPM.
A variable speed pump
must not reduce the
system flow rate below
272 GPM.
Page 15
Primary/Secondary Piping
Using a primary/secondary piping arrangement
can solve system flow complications. This piping arrangement uses a dedicated pump to supply flow to the boiler. The pump is sized based on the required boiler flow rate, boiler head-loss and head-loss in the secondary system piping. A separate pump is used to provide the desired flow for the system. Primary/Secondary piping allows the system and the boiler(s) to operate at their optimum flow rate. The system works best when the boiler(s) are supplied with pump control relays which are used to cycle the secondary pump(s). When piped correctly, the secondary pump helps to prevent flow
through the boiler(s) when they are not firing. Use of a primary/secondary system will eliminate the need for a System or Boiler
Bypass. (FIGURE 12) depicts one example of primary/secondary piping.
Water Flow Switch
Due to the low water content (between 1 and 6 gallons) of the copper finned tube heat exchanger, a flow switch is factory installed as a low water cutoff device on all CB models. The flow switch is installed in the outlet piping of the boiler and wired into the ignition system. Per ASME CSD1 and in most localities, a flow switch is accepted as a low water cutoff for boilers requiring forced circulation. (See CSD1 CW-210, Part A) It is prudent to verify preference with the local code official.
A specially sealed flow switch and conduit are furnished for outdoor installations.
Low Water Cutoff
If this boiler is installed above radiation level, a low water cutoff device must be installed at the time of boiler installation (option, available from factory).
Relief Valve
This boiler is supplied with a pressure relief valve(s) sized in accordance with ASME
Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 13
(FIG. 12) PRIMARY/SECONDARY SYSTEM PIPING
HEATING SUPPLY
LOOP
*12” MAX
TO FLOOR
DRAIN
MAKE-UP WATER
LIT0476
HEATING RETURN LOOP
HEAT EXCHANGER HEAD LOSS CHART
Models 401-751
Pressure Drop in Feet Head
Pressure Drop in Feet Head
HEAT EXCHANGER HEAD LOSS CHART
Models 991-2071
(FIG. 10) BOILER HEAD LOSS CB 495-745
(FIG. 11) BOILER HEAD LOSS CB 986-2066
Page 16
14 Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900
Lochinvar
Low Flow Systems
When the system flow rate is less than the minimum flow required for proper boiler operation, the boiler should be installed with a primary/secondary piping system.
This will allow the installation of a secondary circulating pump sized specifically to provide a higher flow rate through the boiler and the secondary loop piping to ensure proper operation. See “Primary/Secondary Piping” for installation and piping requirements.
High Flow Systems
When the flow rate of the system exceeds the maximum allowable flow rate through the boiler (TABLE G), boiler bypass piping should be installed. The bypass will divert the required portion of the system flow to the boiler and bypass excess system flow. This will effectively reduce boiler flow to an acceptable rate and increase system flow. The bypass piping should be sized equal to the system piping. (FIGURE 13) depicts the proper piping arrangement for the boiler bypass.
Low Water Temperature System
Any boiler system operating at a temperature of less than 140°F is considered a “low water temperature system” and must be piped with a low temperature bypass. There are a number of hydronic boiler applications that call for system water temperatures in the range of 60°F to 100°F. Typical applications are: Radiant heating systems; Water source heat pump systems; Greenhouse soil heating and irrigation systems; Process and manufacturing operations. These installations often incur problems resulting from boiler condensation, thermal stresses and poor overall system efficiency.
Copper-tube boilers are particularly adaptable to these applications for several reasons:
A copper-tube boiler is an instantaneous boiler, requiring virtually no heat-up time, and having no temperature “overshoot.” Result - High system efficiency.
The boiler’s unique construction prevents the transfer of heat exchanger thermal stresses to other boiler components, reducing wear and tear while increasing equipment life.
Its compact, simple design and low boiler mass permits a simple bypass arrangement which will allow the system to be operated at any temperature above 60°F.
A boiler operated with an inlet temperature of
less than 140°F (60°C) must have a bypass
to prevent problems with condensation.
IMPORTANT:
Operation of this boiler
on low temperature
systems requires
special piping to insure
correct operation.
Consult low temperature
system section for
piping details.
(FIG. 13) HIGH FLOW SYSTEM PIPING
HEATING SUPPLY
LOOP
TO FLOOR
DRAIN
MAKE-UP WATER
HEATING RETURN LOOP
LIT0471
2.
3.
1.
Page 17
A Low Temperature bypass as shown in Figure 14 must be piped into all ON/OFF boilers at the time of installation. This piping is like a primary/secondary boiler installation with a bypass in the secondary boiler piping. Inlet water temperatures below 140°F (60°C) can excessively cool the products of combustion resulting in condensation on the heat exchanger and in the flue. The bypass allows part of the boiler discharge water to be mixed with the cooler boiler return water to increase the boiler inlet temperature to at least 140°F (60°C). This will prevent the products of combustion from condensing in most installations. Size Low Temperature bypass piping equal to system piping, and use fully ported control valves.
To prevent system return water temperature below 140° F from entering the inlet in a proportional stage-fired boiler, a quick acting, self contained, 3-way valve, set at 140°F, or an electric actuated 3-way valve with a sensor located on the boiler inlet pipe must be provided. To prevent manual reset high limit problems, 3-way valve minimum
flow stops or a valve leak-through should be evaluated. The installation of a 3-way valve in the piping system as shown in Figure 15 should not restrict or vary the water flow through the boiler. Constant water flow through the boiler must be provided at all times when the boiler is operating. The boiler's operating temperature sensor can be remote mounted in a bulb well installed in the system water flow to control boiler operation at a low temperature range.
SPECIAL DESIGN APPLICATIONS
Air Conditioning Re-Heat System
When used in connection with a refrigeration system, the boiler must be installed so the chilled medium is piped in parallel with the boiler and with appropriate valves to prevent the chilled medium from entering the boiler.
Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 15
(FIG. 14) LOW TEMPERATURE BYPASS
SYSTEM PIPING
HEATING SUPPLY
LOOP
TO FLOOR
DRAIN
MAKE-UP WATER
HEATING RETURN LOOP
LIT0473
CAUTION!
For proper
operation the
system should
not be operated
at less than
12 PSIG.
(FIG. 15) LOW TEMPERATURE BYPASS SYSTEM PIPING
ON/OFF FIRING ONLY
(FIG. 16) LOW TEMPERATURE BYPASS SYSTEM PIPING
PROPORTIONAL STAGED-FIRING
Page 18
The piping system of the hot water boiler (when connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation) must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
The heating coil must be vented at the high point, and the hot water from the boiler must enter the coil at this point. Due to the fast heating capacity of the boiler, it is not necessary to provide a duct-stat to delay circulator operation; also, omit thermal flow checks, as the boiler is cold when the heating thermostat is satisfied. This provides greater economy overall by maintaining standby heat.
AIR REMOVAL
An air separation device should be placed in the installation piping, on the suction side of the system pump, to eliminate trapped air in the system. Locate a system air vent at the highest point in the system. Additionally, a properly sized expansion tank is required. Air charged, diaphragm-type compression tanks are common. The expansion tank must be installed close to the boiler and on the suction side of the system pump to ensure proper operation.
TEMPERATURE/PRESSURE GAUGE
This boiler is equipped with a dial type temperature/pressure gauge. This gauge is factory installed in the outlet side of the heat exchanger. The gauge has one scale for reading system pressure and a separate scale for water temperature in degrees Fahrenheit.
LOW SYSTEM WATER VOLUME
System run time is very important to overall operating efficiency of the boiler. Short cycling of the boiler creates problems with condensation in the vent stack, condensation on the heat exchanger, system temperature spikes, and mechanical component failures. To prevent short cycling of the boiler, it is important to limit the boiler cycles to six or fewer per hour. A Buffer Tank is an effective way to enhance a small system load and increase heating system efficiency. Buffer tanks add water volume to the system and act as a flywheel to absorb the additional Btu's provided by the boiler when only a single zone of a large system is calling for heat.
To calculate the proper buffer tank size for a multiple zone system:
(Run Cycle) (Output - Minimum System Load)
(Temp. Rise) (8.33)(60 Min.)
BOILER OPERATING TEMPERATURE CONTROL
In the absence of a remote temperature control, a digital operator controls the boiler operating temperature. The sensing element for the operator is placed in a bulb well, installed in the inlet side of the heat exchanger front header. Due to the location of the temperature sensor, the operator will generally require a
16 Lochinvar
DESIGNE RS GUIDE COPPER- FIN BOILER 615-889-8900
Lochinvar
R.
.
(FIG. 17) HEATING/CHILLED WATER SYSTEM
EXAMPLE
OF BUFFER
TANK:
CBN1256 Boiler Run cycle = 10 min. Temp. rise = 10°F Min. load = 100,000 Btu/hr
(10)(1,016,000 -
100,000) divided by
40 x 8.33 x 60
= 485 gallons
LOW WATER
FLOW SWITCH
IN
OUT
R
BOILER
GRAM NOTES:
ALVES "D" AND "C" MAY BE MANUAL OR AUTOMATIC- TO SUIT. ROVIDE DRAIN FOR RELIEF VALVE "R" TO SAFE PLACE.
EXPANSION
TANK
HEATING &
COOLING
PUMP
COIL
SUPPLY
A
C
GAS
B
D
WATER SUPPLY
E
3. CLOSE BOTH "A" AND "C" VALVES WHEN RUNNING CHILLE
4. CLOSE BOTH "B" AND "D" VALVES WHEN RUNNING BOILER
5. WATER SUPPLY VALVE REMAINS OPEN AT ALL TIMES.
CHILLER
Page 19
Lochinvar
DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 17
lower temperature setpoint to achieve the desired discharge water temperature from the boiler. This sensing element location allows a boiler operating with a low to moderate flow rate to sustain longer burner “ON” cycles, based on high discharge water temperatures. For example, a boiler operating with a 180°F discharge and a 20°F temperature rise would require approximately a 160°F to 165°F set point with the temperature sensor installed on the inlet side of the heat exchanger. The exact temperature set point is based on system requirements.
REMOTE TEMPERATURE CONTROL, CONNECTION TO TERMINAL STRIP
A remote temperature control may be connected to the boiler. The boiler is equipped with a terminal strip to allow easy connection. Connection to the terminal strip will allow the remote temperature control to make and break the 24 VAC boiler control circuit, turning the boiler on and off based on building and system demands.
ELECTRICAL REQUIREMENTS
(North America)
The appliance is wired for 120 volts.
All wiring between the unit and field installed devices shall be made of type T wire [63°F (35°C) rise].
The pump must run continuously when the unit is firing.
It is recommended that the boiler and pump be wired on separate circuits with properly sized circuit breakers.
(FIG. 18) BUFFER TANK PIPING
2.
3.
1.
(TABLE I) – AMP DRAW DATA
MODEL FAN(S) CONTROLS APPROX. TOTAL AMPS
NUMBER @ 120 VAC
CB495 3.6 3.6 7.2 CB645 3.6 3.6 7.2 CB745 3.6 3.6 7.2 CB986 3.4 4.6 8.0 CB1256 3.4 4.6 8.0 CB1436 3.8 4.6 8.4 CB1796 3.8 4.6 8.4 CB2066 3.8 4.6 8.4
NOTE:
When the unit is
installed in Canada,
it MUST conform to
the CAE C22.1,
Canadian Electrical
Code, Part 1
and/or local Electrical
Codes.
Page 20
A1 Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900
PIPING DIAGRAM PRIMARY/SECONDARY BOILER PIPING
PRESSURE
REDUCING VALVE
FULL PORT
BALL VALVE
RELIEF VALVE CHECK VALVE TEE ELBOW
EXPANSION TANK TANK FITTING SYSTEM PUMP LOW WATER
CUTOFF
UNION AIR SEPARATOR
LEGEND
12MAX*
HEATING RETURN LOOP
HEATING SUPPLY LOOP
*AS CLOSE AS PRACTICAL – 12OR 4 PIPE DIAMETERS MAXIMUM DISTANCE BETWEEN MANIFOLD CONNECTIONS TO SYSTEM.
MAKE-UP WATER
TO FLOOR DRAIN
LIT0476
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
BOILER PIPING DIAGRAMS
Page 21
Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 A2
PIPING DIAGRAM MULTIPLE UNIT PRIMARY/SECONDARY PIPING
PRESSURE
REDUCING VALVE
FULL PORT
BALL VALVE
RELIEF VALVE CHECK VALVE TEE ELBOW
EXPANSION TANK TANK FITTING SYSTEM PUMP LOW WATER
CUTOFF
UNION AIR SEPARATOR
LEGEND
12MAX*
FROM SYSTEM
RETURN
*AS CLOSE AS PRACTICAL – 12OR 4 PIPE DIAMETERS MAXIMUM DISTANCE BETWEEN MANIFOLD CONNECTIONS TO SYSTEM.
TO SYSTEM SUPPLY
MAKE-UP WATER
CAP EACH MANIFOLD
LIT0475
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
Page 22
A3 Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900
PIPING DIAGRAM LOW TEMPERATURE BOILER-BYPASS PIPING
PRESSURE
REDUCING VALVE
FULL PORT
BALL VALVE
RELIEF VALVE CHECK VALVE TEE ELBOW
EXPANSION TANK TANK FITTING SYSTEM PUMP LOW WATER
CUTOFF
UNION AIR SEPARATOR
LEGEND
MAKE-UP WATER
HEATING RETURN
LOOP
HEATING SUPPLY
LOOP
PRIMARY - SECONDARY BOILER PIPING WITH BYPASS FOR LOW TEMPERATURE OPERATION
*AS CLOSE AS PRACTICAL – 12
OR 4 PIPE DIAMETERS MAXIMUM
DISTANCE BETWEEN MANIFOLD CONNECTIONS TO SYSTEM.
TO FLOOR
DRAIN
*12
MAX
LIT0473
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
BYPASS
Page 23
Lochinvar
DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 A4
PIPING DIAGRAM LOW TEMPERATURE BOILER-BYPASS PIPING W/ 3-WAY VALVE
PRESSURE
REDUCING VALVE
FULL PORT
BALL VALVE
RELIEF VALVE CHECK VALVE TEE ELBOW
EXPANSION TANK TANK FITTING SYSTEM PUMP LOW WATER
CUTOFF
UNION AIR SEPARATOR
LEGEND
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
Page 24
Lochinvar Corporation • Lebanon, TN • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com
CB-DG-06 5M-1/06-Printed in U.S.A.
Loading...