Lochinvar CB1256 Installation Manual

DESIGNER’S GUIDE COPPER-FIN®BOILER
495,000 – 2,065,000 Btu/hr
Dear Specifier/Project Manager,
At Lochinvar, we have long recognized the importance of innovation to any product or service. Those who enter into business must also accept the challenge of meeting constantly changing needs.
All information has been organized and presented in a succinct, easy-to-use manner, so you can use and share information confidently and with minimal effort.
However, it is important to remember that this guide is not intended to replace our installation manual. Installers should still refer to our installation manual for specific installation instructions.
We hope this manual will make your work easier and more productive. As always, we greatly appreciate your input on additional improvements for the future.
Thanks once again for specifying the Lochinvar family of quality standard and custom-built boilers and boilers.
Sincerely,
Lochinvar Corporation
Nashville, TN • 615-889-8900 • Fax: 615-547-1000
Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 1
Table of Contents
Air Removal . . . . . . . . . . . . . . . . . . . . . .16
Boiler Operating Temperature Control . . . .16
Circulator Pump Operation . . . . . . . . . . .12
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Combustion & Ventilation Air . . . . . . . . . . .5
Contaminants . . . . . . . . . . . . . . . . . . . . . .6
Determining Total “Free Area” . . . . . . . . . .7
Electrical Requirements . . . . . . . . . . . . . . .17
Gas Supply . . . . . . . . . . . . . . . . . . . . . .10
General Venting . . . . . . . . . . . . . . . . . . . .6
Location of Unit . . . . . . . . . . . . . . . . . . . . .2
Low System Water Volume . . . . . . . . . . . .16
Low Water Temperature System . . . . . . . .14
Outdoor Use . . . . . . . . . . . . . . . . . . . . . . .3
Outdoor Installation . . . . . . . . . . . . . . . . . .9
Primary/Secondary Piping . . . . . . . . . . . .13
Relief Valve . . . . . . . . . . . . . . . . . . . . . . .14
Remote Temperature Control . . . . . . . . . . .17
Special Design Applications . . . . . . . . . . .15
Variable Speed Pumping . . . . . . . . . . . . .16
Venting Options . . . . . . . . . . . . . . . . . . . .8
Water Flow Requirements . . . . . . . . . . . .12
Water Velocity Control . . . . . . . . . . . . . . .12
Figures & Tables Index
FIG. 1 Models CB 495-2066
Requirements For Installation
Over Combustible Floor . . . . . . .3
FIG. 2 Boiler Equipment &
Control Orientation . . . . . . . . . . .4
FIG. 3-6 Combustion & Ventilation Air . .5, 6 FIG. 7 Barometric Damper Installation . .8
FIG. 8 Multiple Unit Barometric
Damper Installation . . . . . . . . . . .9
FIG. 9 Outdoor Venting . . . . . . . . . . . . .9
FIG. 10 Heat Exchanger Head Loss
Models CB 495-745 . . . . . . . . .9
FIG. 11 Heat Exchanger Head Loss
Models CB 986-2066 . . . . . . . .9
FIG. 12 Primary/Secondary
System Piping . . . . . . . . . . . . . .13
FIG. 13 High Flow System Piping . . . . . .14
FIG. 14 Low Temperature Bypass
System Piping . . . . . . . . . . . . . .15
FIG. 15 Low Temperature Bypass Piping
On/Off . . . . . . . . . . . . . . . . . .15
FIG. 16 Low Temperature Bypass Piping
Stage Firing . . . . . . . . . . . . . . .15
FIG. 17 Heating/Chilled
Water System . . . . . . . . . . . . . .16
FIG. 18 Buffer Tank Piping . . . . . . . . . . .17
TABLE A. Clearances From
Combustibles . . . . . . . . . . . . . .3
TABLE B. Flue Sizes and
Combustion Air Pipe Sizes . . . . .8
TABLE C. Outdoor Kits . . . . . . . . . . . . . .10
TABLE D. Gas Supply Pipe Sizing . . . . . .11
TABLE E. Inlet Gas Pressure . . . . . . . . . .11
TABLE F. Water Flow Requirements . . . . .12
TABLE G. Minimum and Maximum
Boiler Flow Rates . . . . . . . . . . .12
TABLE H. Amp Draw Data . . . . . . . . . . . .17
Boiler Piping Diagrams
Primary/Secondary Boiler Piping . . . . . . .A1
Multiple Unit Primary/Secondary Piping . .A2 Low Temperature Boiler Bypass Piping . . .A3 Low Temperature Boiler Bypass Piping
with 3-way Valve . . . . . . . . . . . . . . . .A4
CODES
The equipment shall be installed in accordance with those installation regulations in effect in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
In the absence of such requirements, the installation shall conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to
American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1.
Where required by the authority having jurisdiction, the installation must comply with the Canadian Association Code, CAN/CGA- B149.1 and/or B149.2 and/or local codes.
LOCATION OF UNIT
Locate the unit so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the unit. The pan must not restrict combustion air flow.
2 Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900
1.
Lochinvar
o
Water Velocity
(See page 12 for Minimum
and Maximum Flow Rates.)
o
Piping Requirements
and Specialities
(See page 12 for
Water Flow Requirements
and system piping.)
o
Low Water Temperature
System
(See page 14 & 15 for
piping and design
recommendations.)
o
System and Boiler Control
(See page 16 for Control
Connections and
Operator Settings.)
o
Air Elimination and
Expansion Tank Placement
(See page 16 for Air
Removal Information.)
In designing a boiler system,
pay special attention to:
Under no circumstances is the manufacturer to be held responsible for water damage in connection with this unit or any of its components.
The indoor units must be installed so that the ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.).
The appliance must be installed on a level, non-combustible floor. Concrete over wood is not considered a non-combustible floor. Maintain required clearances from combustible surfaces.
For installation on a combustible floor only when installed on special base: Units installed over a
combustible floor must use the Special Combustible Floor Base. The unit must be centered on the base as shown in FIG. 1.
• Provide a base of hollow clay tile or concrete blocks from 8 to 12 inches thick and extending 24 inches beyond the sides.
• The blocks must be placed in line so that the holes line up horizontally to provide a clear passage through the blocks.
This procedure should also be
followed if electrical conduit or radiant heat distribution piping runs through the floor and beneath the appliance.
• Ensure that combustible floor base meets local fire code requirements.
Outdoor models require the installation of an optional vent cap. Instructions for placement of the vent cap are included in the venting section.
Outdoor models must not be installed directly on the ground. The outdoor unit must be installed on a concrete brick, block or other non-combustible pad.
SPECIAL LOCATION: OUTDOOR USE
Outdoor models have additional location and clearance requirements. These requirements must be adhered to carefully, since wind, rain, snow and cold cannot be controlled in outdoor applications. See
Outdoor Installation on page 9.
2.
4.
3.
Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 3
(FIG. 1) CB 495-2066 REQUIREMENTS FOR INSTALLATION OVER COMBUSTIBLE FLOOR
5.
(TABLE A) – CLEARANCES FROM
COMBUSTIBLE CONSTRUCTION
CLEARANCES CB 495-2066 Right Side 3" Rear 3" Left Side 3"
(30" for Service)
Front ALCOVE*
(24" for Service) Top 3" Flue 1"+
* Alcove is a closet without a door. + Consult local codes and/or vent material manufacturer.
4 Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900
Lochinvar
(FIG. 2) BOILER EQUIPMENT AND CONTROL ORIENTATION.
RIGHT SIDE
FLUE PRODUCTS VENT
TERMINAL
STRIP
HOT WATER
OUTLET
COLD WATER
INLET
BURNER INSPECTION PORT
FRONT
GAS
CONNECTION
HOT WATER
OUTLET
COLD WATER
INLET
BURNER
INSPECTION PORT
FRONT
AIR
INLET
FRESH AIR
INLET
RIGHT SIDE
FLUE PRODUCTS VENT
BACK
DRAIN
LEFT SIDE
BACK
120V ELECTRICAL
CONNECTION
ON/OFF SWITCH
OPERATOR
TERMINAL STRIP
ON/OFF SWITCH
LEFT SIDE
DRAIN
RELIEF VALVE
TAPPING
INLET GAS
CONNECTION
CB 495-745
CB 986-2066
Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900 5
COMBUSTION & VENTILATION AIR
Provisions for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1; in Canada, the latest edition of CGA Standard B149 Installation
Code for Gas Burning Appliances and Equipment; or applicable provisions of the
local building codes.
The equipment room must be provided with properly sized openings to assure adequate combustion air and proper ventilation when the unit is installed with conventional venting or sidewall venting.
If air is taken directly from outside the building with no duct, provide two
permanent openings:
A. Combustion air opening with a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm
2
per kW). This
opening must be located within 12 inches (30 cm) of the bottom of the enclosure.
B. Ventilation air opening with a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm
2
per kW). This
opening must be located within 12 inches (30 cm) of the top of the enclosure.
If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the mechanical room, each of the two
openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr input (11 cm
2
per kW).
If air is taken from another interior space, each of the two openings
specified above should have a net free
1.
2.
3.
(FIG. 3) COMBUSTION AIR DIRECT FROM OUTSIDE
(FIG. 4) COMBUSTION AIR THROUGH DUCTWORK
(FIG. 5) COMBUSTION AIR FROM AN
INTERIOR SPACE
CAUTION: Under no circumstances should the equipment room be under a negative pressure when atmospheric combustion equipment is installed in the room.
EXAMPLE OF
SIZING FOR
COMBUSTION
& VENTILATION
AIR OPENINGS
(BOILER WITH
2,065,000 Btu/hr
INPUT):
When combustion and
ventilated air is taken
from directly outside the
building (FIG. 4), divide
the total BTU’s by 4,000.
This yields 516.25 sq.in.
of “Free Area” without
restriction.
(2,065,000 ÷ 4000 =
516.25 sq.in.)
Since the air opening is
50% closed due to
screens and louvers, the
total opening must be
multiplied by 2.
(516.25 sq. in. x 2 =
1,032 sq.in.)
This project requires one
Ventilation Air Opening
with net “Area” of
1,032 square inches with
louver dimensions of 30
x 35and one
Combustion Air Opening
with net “Area” of
1,032 square inches with
louver dimensions
of 30x 35”.
6 Lochinvar DESIGNERS GUIDE COPPER- FIN BOILER 615-889-8900
area of one square inch for each 1000 Btu/hr (22 cm
2
per kW) of input, but not
less than 100 square inches (645 cm
2
).
If a single combustion air opening is provided to bring combustion air in directly from the outdoors,
the opening must be sized based on a minimum free area of one square inch per 3000 Btu/hr input (7 cm
2
per kW).
This opening must be located within 12 inches (30 cm) of the top of the enclosure.
CONTAMINANTS
Combustion air drawn from an interior or exterior space must be free of any chemical fumes which could be corrosive to the boiler. Burning chemical fumes results in the formation of corrosive acids which attack the boiler, cause improper combustion and premature failure of the boiler and vent. These fumes are often present in areas where refrigerants, salts, and solvents are used. Therefore, be aware of swimming pool equipment, water softening, and cooling system placement.
VENTING
General
These boilers are classified as Category I appliances when tested to the latest ANSI Standard. This classification requires all conventionally vented combustion products to be vented using Category I listed vent pipe.
Additionally, it is recommended that this vent material be double wall construction or insulated in the field. A Category I appliance operates with a non-positive static vent pressure and with flue loss greater than 17 percent.
Vent installations for connection to gas vents or chimneys must be in accordance with Part 7, “Venting of Equipment,” of the latest edition of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the local building codes.
The connection from the appliance vent to the stack must be as direct as possible and sized correctly. The horizontal breeching of a vent must have at least 1/4rise per linear foot. The horizontal portions should also be supported for the design and weight of the material employed to maintain clearances, prevent physical damage and separation of joints.
The connection from the appliance vent to the stack or vent termination outside the building must be made with listed
Lochinvar
4.
(FIG. 6) COMBUSTION AIR FROM OUTSIDE,
SINGLE OPENING
CAUTION!
EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a down draft in the venting system. If a fan is used to supply combustion air to the equipment room, it must by sized such to make sure that it does not cause drafts which could lead to nuisance operational problems with the boiler.
Loading...
+ 16 hidden pages