Lochinvar C 402 - 2072 User Manual

Page 1
WARNING: If the information in these instructions is not
followed exactly, a fire or explosion may result causing property damage, personal injury or death.
-- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
-- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a near by phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
-- Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
CFX-CHX-I-O Rev A
Installation & Operation Manual
Models: 402 - 2072
WARNING:
This manual supplies information for the installation, operation, and servicing of the appliance. It is strongly recommended that this manual and the Copper-fin II Service Manual be reviewed completely before proceeding with an installation. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
Save this manual for future reference.
Page 2
Contents
HAZARD DEFINITIONS ..................................................... 2
PLEASE READ BEFORE PROCEEDING ......................... 3
SAFETY INFORMATION ................................................... 4
THE COPPER-FIN II -- HOW IT WORKS ...................... 5-7
RATINGS ........................................................................... 8
1. DETERMINE UNIT LOCATION
Location of Unit .................................................................. 9
Recommended Service Clearances .................................. 9
Non-Combustible / Combustible Flooring ........................ 10
Combustion Air Options .............................................. 10-13
2. VENTING
Before You Begin ............................................................. 13
Vent System Options ....................................................... 14
General Venting Information ............................................ 15
Conventional Negative Draft Venting .......................... 16-18
Vertical DirectAire Venting .......................................... 19-21
Sidewall Venting .......................................................... 22-24
Horizontal DirectAire Venting ........................................... 25
Direct Venting .............................................................. 26-29
Outdoor Installation .......................................................... 30
3. GAS CONNECTIONS
Connecting to Gas Supply ............................................... 31
Gas Pressure Test ........................................................... 31
Checking Manifold Gas Pressure .................................... 31
Combination Gas Valves .................................................. 32
Checking Gas Supply Pressure ....................................... 33
4. WATER CONNECTIONS
Inlet & Outlet Connections ............................................... 34
Relief Valve ...................................................................... 35
Heating Boiler Installations .......................................... 35-36
Low Temperature Return Water Systems ........................ 36
Low Temperature Bypass Requirements ......................... 36
Three Way Valves in System ........................................... 37
Radiant Floor and Snow Melt Heating Systems .............. 37
Typical Heating Boiler Installations .................................. 38
Installation with a Chilled Water System .......................... 38
Primary/Secondary Piping of a Single Boiler .............. 39
Primary/Secondary Piping of Multiple Boilers ............ 40
Boiler w/Low Temperature Bypass Piping .................. 41
Primary/Secondary Piping with Buffer Tank ............... 42
5. ELECTRICAL CONNECTIONS
Boiler Operating Control Module ...................................... 43
Line Voltage Connections ................................................ 44
Low Voltage Connections ................................................ 44
Wiring of the Cascade ...................................................... 45
Low Voltage Field Wiring Connections ............................ 46
6. STARTUP
Check/Control Water Chemistry ....................................... 47
Freeze Protection (when used) ........................................ 47
Fill and Test Water System .............................................. 47
Purge Air from Water System .......................................... 47
Check for Gas Leaks ....................................................... 47
Check Thermostat Circuit(s) ............................................ 48
Check Vent and Air Piping ............................................... 48
Placing the Boiler in Operation ........................................ 48
Start the Boiler ................................................................. 48
If Boiler Does Not Start Correctly ..................................... 48
Set Space heating Operation (boiler only) ....................... 48
Operating Instructions ...................................................... 49
Set DHW Operation ......................................................... 50
7. OPERATING INFORMATION
General ........................................................................ 51-53
Cascade ...................................................................... 53-54
Sequence of Operation ............................................... 55-56
Copper-fin II Control Module ............................................ 56
Access Modes ............................................................ 57
Saving Parameters ..................................................... 57
Status Display Screens ............................................... 58-61
8. DOMESTIC WATER HEATERS
Initial Setup of Maximum Water Flow .............................. 62
Water Chemistry............................................................... 63
Typical Water Heater Piping w/Storage Tank(s) ......... 64-65
Multiple Water Heater Piping w/Storage Tank(s) ........ 66-67
Pump Operation ............................................................... 68
Minimum Water Temperatures (domestic hot water) ....... 69
9. MAINTENANCE ......................................................71-75
10. CONNECTION DIAGRAM ................................... 76-77
11. LADDER DIAGRAM .............................................. 78-79
Revision Notes .................................................. Back Cover
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
2
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
Page 3
Please read before proceeding
Special instructions
Installation & Operation Manual
NOTICE
WARNING
WARNING
This is a gas appliance and should be installed by a licensed electrician and/or certified gas supplier. Service must be performed by a qualified service installer, service agency or the gas supplier.
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.
This appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present, unless the installation is such to eliminate the probable ignition of gasoline or flammable vapors.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for assistance or additional information, consult a qualified installer, service agency or the gas supplier.
Checking equipment –
Upon receiving equipment, check for signs of shipping damage. Pay particular attention to parts accompanying the appliances which may show signs of being hit or otherwise being mishandled. Verify total number of pieces shown on packing slip with those actually received. In case there is damage or a shortage, immediately notify the carrier.
Do not use this appliance if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
NOTICE
REMOVAL OF COMBUSTION CHAMBER LINING OR BASE PANELS:
Avoid breathing dust and contact with skin and eyes.
Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH website at http://www.cdc.gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and phone numbers are also listed on this website.
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic materials it is advisable that the installer follow these safety guides.
Apply enough water to the combustion chamber lining to prevent airborne dust.
Remove the combustion chamber lining from the appliance and place it in a plastic bag for disposal.
• NIOSH stated First Aid: Eye: Irrigate immediately.
Breathing: Fresh air.
WARNING
The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created to convert the ceramic fibers in this appliance to cristobalite.
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines.
Warranty –
Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated.
Experience has shown that improper installation or system design, rather than faulty equipment, is the cause of most operating problems.
1. Excessive water hardness causing a lime/scale build-up in the copper tube is not the fault of the equipment and is not covered under the manufacturer’s warranty (see Water Treatment and Water Chemistry).
2. Excessive pitting and erosion on the inside of the copper tube may be caused by too much water velocity through the tubes and is not covered by the manufacturer’s warranty (see Boiler Flow Rates and Temperature Rise for flow requirements).
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
33
Page 4
Please read before proceeding
Safety information
Installation & Operation Manual
Owner warning –
The information contained in this manual is intended for use by qualified professional installers, service technicians, or gas suppliers.
NOTICE
A gas appliance that draws combustion air from the equipment room where it is installed must have a supply of fresh air circulating around it during burner operation for proper gas combustion and proper venting.
WARNING
Consult and follow all local Building and Fire Regulations and other Safety Codes that apply to this installation. Consult local gas utility company to authorize and inspect all gas and flue connections.
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
Prevention of freezing –
Heat exchangers and headers damaged by freezing are not covered by warranty.
See Section 7, Operating Information - Freeze Protection for more information.
Codes –
The equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made. In the absence of such requirements, the installation shall conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1. All boilers conform to the latest edition of the ASME Boiler and Pressure Vessel Code, Section IV. Where required by the authority having jurisdiction, the installation must comply with the Canadian Gas Association Code, CAN/CGA-B149.1 and/ or B149.2 and/or local codes. This appliance meets the safe lighting performance criteria with the gas manifold and control assembly provided, as specified in the ANSI standards for gas­fired hot water boilers, ANSI Z21.13 and gas water heaters, ANSI Z21.10.3.
WARNING
1. This unit is only for use with the type of gas indicated on the rating plate.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in your building
• immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier, call the fire department
3. Boilers and water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the appliance or the vent-air intake system. Use proper care to avoid unnecessary contact (especially children) with the appliance and vent-air intake components.
4. Never cover your unit, lean anything against it, store trash or debris near it, stand on it or in any way block the flow of fresh air to your unit.
5. UNDER NO CIRCUMSTANCES MUST FLAMMABLE MATERIALS SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THIS APPLIANCE, VENT-AIR INTAKE SYSTEM OR ANY LOCATION FROM WHICH FUMES COULD REACH THE APPLIANCE OR VENT-AIR INTAKE SYSTEM.
6. Appliance surfaces become hot during operation. Be careful not to touch hot surfaces. Keep all adults, children, and animals away from operation of the hot unit. Severe burns can occur.
7. You must take adequate care to prevent scald injury when storing water at elevated temperatures for domestic use.
8. This unit must have an adequate supply of fresh air during operation for proper gas combustion and venting.
9. Make sure all exhaust venting is properly installed and maintained. Improper venting of this unit could lead to increased levels of carbon monoxide.
10. Do not use this boiler if any part has been under water. Immediately call a qualified service technician to replace the boiler. The possible damage to a flooded boiler can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
11. Do not alter this unit in any way. Any change to this unit or its controls can be dangerous.
To minimize the possibility of serious personal injury, fire or damage to your unit, never violate the following safety rules.
4
Page 5
The Copper-fin II - How it works...
Installation & Operation Manual
1. Heat exchanger
The heat exchanger allows system water to flow through specially designed tubes for maximum heat transfer. The glass lined headers and copper fined tubing are encased in a jacket that contains the combustion process.
2. Heat exchanger access cover
The heat exchanger access cover is a galvanized steel door which allows access for service, maintenance, and removal of the heat exchanger from inside the combustion chamber.
3. Blower
The blower pulls in and injects air into the individual burners along with gas from the gas manifold where the mix is burned inside the combustion chamber.
4. Gas valve
The gas valves (reference) have a dual purpose; changing the gas supply pressure to manifold pressure, and the reference side of the gas valve is designed to allow chamber pressure to change the volume of gas through the valve and measured as net manifold pressure. This is not a design to compensate for gas supply pressure issues.
5. System / tank temperature sensor (not shown)
When connected, this sensor can be used as a system sensor or a tank sensor.
6. Outlet/limit temperature sensor
This sensor monitors the outlet water temperature. If selected as the controlling sensor and a system supply sensor is not connected, the appliance will maintain set point by adjusting the firing rate of the unit according to this sensor.
7. Inlet temperature sensor
This sensor monitors inlet water temperature. If selected as the controlling sensor and a system return sensor is not connected, the appliance will maintain set point by adjusting the firing rate of the unit according to this sensor.
8. Temperature and pressure gauge (boilers only)
The temperature and pressure gauge monitors the outlet temperature of the appliance as well as the system water pressure.
9. Electronic display
The electronic display consists of 6 buttons and a two-line 16-character liquid crystal display used to monitor the operation of the heater as well as enter and view the programming of the main control board.
10. Burner
The burner is a ported stainless steel construction which uses a gas air mix to operate at a fixed input. Banks of burners turn on or off to vary the firing rate.
11. Water outlet (system supply)
The water outlet is a 2 or 2 1/2" (depending on model) pipe connection that supplies water to the system with connections for a flow switch (see #26), a relief valve (see #23), and a temperature and pressure gauge (boilers only) (see #8).
12. Water inlet (system return)
The water inlet is a 2 or 2 1/2" (depending on model) pipe connection that receives water from the system and delivers it to the heat exchanger.
13. Gas supply pipe
The gas supply pipe on this appliance is 1 1/4 or 2" (depending on model) diameter NPT. Please reference the National Fuel Gas Code charts for connection details.
14. SMART SYSTEM Control Module
The SMART System Control Module is the main control for the appliance. This module contains the programming that operates the blower, gas valve, and pumps in addition to other programmable features.
15. Air intake
Fresh air for combustion is drawn through a filter provided at the air intake, located at either the rear or right side of the appliance.
16. Line voltage terminal strip
The line voltage terminal strip provides a location to connect all of the line voltage (120 VAC) contact points to the unit.
17. Low voltage connection board(s)
The low voltage connection board provides a location to connect all of the low voltage devices to the appliance. This is where most of the external safety controls are connected.
18. Front doors - upper and lower
The front doors provide access to the gas train as well as the blower, burners and other key components for service and maintenance.
19. Hot surface igniter (HSI)
The hot surface igniter is a device that is used to ignite the air/gas mixture as well as monitor the performance of the flame during operation. This device acts as a flame sense electrode.
20. Flame inspection window (sight glass)
The flame inspection windows, located on either side of the appliance, allow for visual inspection of the burners and flame during operation.
21. Gas shut off valve (downstream test cock) (boiler only)
The downstream test cock is provided in the gas train to ensure complete shut off of the gas to the burner in case of
maintenance, inspection, or testing of the valve.
22. Manual reset high limit sensor
This device monitors the outlet water temperature to ensure safe operation. If the temperature exceeds its setting (field adjustable), it will break the control circuit, shutting the appliance down. Manual reset is performed through the display.
23. Relief valve
The relief valve is a safety device that ensures the maximum pressure of the appliance is not exceeded. Boilers operate on pressure only and are shipped from the factory at a rating of 50 PSI. Water heaters operate on temperature and pressure and are shipped standard as 150 PSI and 210°F (98.9°C).
24. Power switch
The power switch is used to engage and disengage power to the appliance on the 120 VAC circuit.
25. Air pressure switch
The air pressure switch is a safety device which ensures proper blower operation. The air pressure switch is wired in series with the low voltage control circuit in such a way that if the fan does not engage or shuts down prematurely the device will break the control circuit and the unit will shut down.
26. Flow switch
The flow switch is a safety device that ensures flow through the heat exchanger during operation. This appliance is low mass and should never be operated without flow. The flow switch makes contact when flow is detected and allows the unit to operate. If flow is discontinued during operation for any reason the flow switch will break the control circuit and the unit will shut down.
27. Drain port(s)
The drain ports are located underneath the front header.
28. Manual shutoff valve (not shown)
Manual valve used to isolate the unit from the gas supply.
5
Page 6
The Copper-fin II - How it works...
18
13
27
18
15
23
26
4
25
24
16
14
3
17
10
19
21
2
7
12
8
6
22
11
20
1
9
Installation & Operation Manual
13
27
18
Models 402 - 752 Front View
18
15
23
26
Models 402 - 752 Rear View
14
17
16
24
10
19
21
Models 402 - 752 Right Side (inside unit)
6
22
25
11
Models 402 - 752 Left Side (inside unit)
12
20
Page 7
Installation & Operation Manual
18
13
27
18
15
26
23
8
3
4
2
21
19
10
24
16
25
17
14
6
22
7
9
1
20
12
11
8
The Copper-fin II - How it works... (continued)
13
27
18
18
Models 992 - 2072 Front View
15
26
23
Models 992 - 2072 Rear View
14
25
17
16
24
10
Models 992 - 2072 Right Side (inside unit)
19
21
11
Models 992 - 2072 Left Side (inside unit)
22
12
20
7
Page 8
Ratings
Installation & Operation Manual
Copper-fin II
I=B=R Rating
Model Number
Note: Change “N” to
“L” for L.P. gas models.
CFN0402 250 399 339 295 CFN0502 250 500 425 370 CFN0652 250 650 553 481 CFN0752 250 750 638 555 CFN0992 360 990 842 732 CFN1262 360 1260 1071 931 CFN1442 360 1440 1224 1064 CFN1802 360 1800 1530 1330 CFN2072 630 2070 1760 1530
CHN0402 250 399 339 295 CHN0502 250 500 425 370 CHN0652 250 650 553 481 CHN0752 250 750 638 555 CHN0992 360 990 842 732 CHN1262 360 1260 1071 931 CHN1442 360 1440 1224 1064 CHN1802 360 1800 1530 1330 CHN2072 630 2070 1760 1530
Min Max
Input MBH
(Note 4)
Gross
Output
MBH
(Note 1)
Net
I=B=R
Ratings
Water,
MBH
(Note 2)
Other Specifications
Appliance
Water Content Gallons
1.6 2" 1-1/4" 6"
1.7 2" 1-1/4" 6"
2.0 2" 1-1/4" 8"
2.1 2" 1-1/4" 8"
2.2 2-1/2" 2" 10"
2.6 2-1/2" 2" 12"
2.9 2-1/2" 2" 12"
3.3 2-1/2" 2" 12"/14"
3.6 2-1/2" 2" 12"/14"
1.6 2" 1-1/4" 6"
1.7 2" 1-1/4" 6"
2.0 2" 1-1/4" 8"
2.1 2" 1-1/4" 8"
2.2 2-1/2" 2" 10"
2.6 2-1/2" 2" 12"
2.9 2-1/2" 2" 12"
3.3 2-1/2" 2" 12"/14"
3.6 2-1/2" 2" 12"/14"
Water
Connections
Gas
Connections
Air / Vent
Sizes
(Note 3)
NOTICE
Maximum allowed working pressure is located on the rating plate.
Notes:
1. The ratings are based on standard test procedures prescribed by the United States Department of Energy.
2. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15.
8
3. Copper-fin II’s require special gas venting. Use only the vent materials and methods specified in the Copper-fin II Installation and Operation Manual.
4. The Copper-fin II is orificed for operation up to 2000 feet altitude, and including up to 4,500 feet, with no field adjustments. The appliance will de-rate by 4% for each 1000 feet above sea level up to 4,500 feet. Consult the factory for installations above 4,500 feet elevation.
Page 9
1 Determine unit location
Location of unit
This unit meets the safe lighting performance criteria with the gas manifold and control assembly provided, as specified in the ANSI standards for gas-fired units, ANSI Z21.13/CSA 4.9 and ANSI Z21.10.3/CSA 4.3 - latest edition.
1. Maintain all clearances from combustible construction when locating appliance. See Clearances from Combustible Construction, this page.
2. Locate the appliance so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the unit. The pan must not restrict combustion airflow. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this unit, or any of its components.
3. The appliance must be installed so that the ignition system components are protected from water (dripping, spraying, rain, etc.,) during appliance operation and service (circulator replacement, control replacement, etc.,).
4. Appliances located in a residential garage and in adjacent spaces that open to the garage and are not part of the living space of a dwelling unit must be installed so that all burners and burner ignition devices have a minimum clearance of not less than 18" (46 cm) above the floor. The appliance must be located or protected so that it is not subject to physical damage by a moving vehicle.
5. DO NOT install this appliance in any location where gasoline or flammable vapors are likely to be present.
6. The appliance must be installed on a level floor.
7. Combustible floor installation:
a. Models 402 - 752 require an approved floor kit for
installation on combustible flooring (reference Table 1A).
b. Models 992 - 2072 are approved for installation
on combustible flooring without a floor kit. Note: Concrete block over wood flooring is not considered non-combustible.
8. DO NOT install this appliance directly on carpeting or other combustible material.
9. Maintain required clearances from combustible surfaces, reference the Indoor Clearances from Combustible Construction Section, this page.
10. For outdoor models, you must install an optional vent cap. Instructions for mounting the vent cap are included in the venting section of this manual. Do not install outdoor models directly on the ground. You must install the outdoor unit on a concrete, brick, block, or other non-combustible pad. Outdoor models have additional special location and clearance requirements. See Outdoor Installation Venting, page 30. A wind proof cabinet protects the unit from weather.
Indoor clearances from combustible construction
Maintain minimum specified clearances for adequate operation. Allow sufficient space for servicing pipe connections, pump and other auxiliary equipment, as well as the unit. See rating plate for specific service clearance requirements.
Installation & Operation Manual
Right Side 3" (7.5 cm)
Rear 3" (7.5 cm) (3" min. from any surface)*
Left Side 6" (15 cm) (24" (0.61 m) suggested for
service)
Front Alcove* (30" (0.76m) suggested for service)
Top 3" (7.5 cm)
Flue 1" (25.4 mm)
Hot Water Pipes 1" (25.4 mm)
*An Alcove is a closet without a door. Thirty-six inches (36") to rear required for outdoor installation.
Note: No additional clearance is needed on the right side of the unit for the observation port. An observation port is located on both the right and left side of the unit.
Figure 1-1_Indoor clearances from combustible construction
3" MIN TOP
3" MIN RIGHT SIDE
6" MIN LEFT SIDE
NOTICE
3" MIN REAR
30" MIN FRONT
Clearances from combustible construction are noted on the appliance rating plate.
TABLE - 1A
COMBUSTIBLE FLOOR KITS
Model Kit Number
402 CFK3301 502 CFK3302
652 CFK3303 752 CFK3304
Freeze protection
Although these units are CSA International design-certifi ed for outdoor installations, such installations are not recommended in areas where the danger of freezing exists. You must provide proper freeze protection for outdoor installations, units installed in unheated mechanical rooms or where temperatures may drop to the freezing point or lower. If freeze protection is not provided for the system, a low ambient temperature alarm is recommended for the mechanical room. Damage to the unit by freezing is non-warrantable.
9
Page 10
1 Determine unit location
Anytime the inlet temperature drops below 45°F, the control turns on the pump contact. If the inlet temperature is below 37°F, and the unit is in the ON Mode, the fi rst stage will fi re.
Location
Locate indoor boilers and water heaters in a room having a tem­perature safely above freezing [32°F (0°C)].
Installation & Operation Manual
CAUTION
A mechanical room operating under a negative draft pressure may experience a down draft in the flue of a boiler when it is not firing. The cold outside air pulled down the flue may freeze a heat exchanger. This condition must be corrected to provide adequate freeze protection.
Hydronic systems anti-freeze
Freeze protection for a heating boiler or hot water supply boiler using an indirect coil can be provided by using hydronic system antifreeze. Follow the appliance manufacturers instructions. Do not use undiluted or automotive type antifreeze (see page 47).
Outdoor boiler installation
Adequate hydronic system antifreeze must be used. A snow screen should be installed to prevent snow and ice accumulation around the unit or its venting system.
Combustion and ventilation air
Provisions for combustion and ventilation air must be in accordance with Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA-B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
Provide properly-sized openings to the equipment room to assure adequate combustion air and proper ventilation when the unit is installed with conventional venting or sidewall venting.
Combustion air options
CAUTION
This unit has four combustion air options.
1. Outside Combustion Air, No Ducts
You can direct outside combustion air to this unit using either one or two permanent openings (see FIG. 1-2).
Under no circumstances should the equipment room ever be under a negative pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the unit.
Figure 1-2_Outside Combustion Air - Single Opening
Two Openings
The combustion air opening must have a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm2 per kW). You must locate this opening within 12" (30 cm) of the bottom of the enclosure (see FIG. 1-3).
The ventilation air opening must have a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm2 per kW). You must locate this opening within 12" (30 cm) of the top of the enclosure.
Figure 1-3_Outside Combustion Air - Two Openings
2. Outside Combustion Air, Using Ducts
You can direct outside combustion air to this unit using two air ducts to deliver the air to the boiler room (see FIG. 1-5).
Each of the two openings must have a minimum free area of one square inch per 2000 Btu input (11cm2 per kW).
3. Combustion Air from Interior Space
You can direct combustion air to this unit using air from an adjoining interior space. You must provide two openings from the boiler room to the adjoining room (see FIG. 1-4).
Each of the two openings must have a net free area of one square inch per 1000 Btu input (22cm2 per kW), but not less than 100 square inches (645cm2).
One Opening
The opening must have a minimum free area of one square inch per 3000 Btu input (7 cm2 per kW). You must locate this opening within 12" (30 cm) of the top of the enclosure.
10
Figure 1-4_Combustion Air from Interior Space
Page 11
1 Determine unit location (continued)
All dimensions are based on net free area in square inches. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers. Where two openings are provided, one must be within 12" (30 cm) of the ceiling and one must be within 12" (30 cm) of the floor of the equipment room. Each opening must have a minimum net free area as specified in TABLE 1C, page 11. Single openings shall be installed within 12" (30 cm) of the ceiling.
Installation & Operation Manual
Figure 1-5_Outside Combustion Air Through Ducts
4. Outside Combustion Air - Using Direct Venting
With this option, you can connect combustion air vent piping directly to the unit. See the information under Direct Venting starting on page 26 for specific information regarding this option.
TABLE - 1C
MINIMUM RECOMMENDED COMBUSTION
AIR SUPPLY TO EQUIPMENT ROOM
*Outside Air from
Model
Number
402
502
652
752
992
1262
1442
1802
2072
2 Openings Directly from
Outdoors
Top
Opening, in
100
(645 cm2)
125
(806 cm2)
163
(1052 cm2)
188
(1213 cm2)
248
(1600 cm2)
315
(2032cm2)
360
(2323cm2)
450
(2903cm2)
518
(3342cm2)
Bottom
2
Opening, in
(645 cm2)
(806 cm2)
(1052 cm2)
(1213 cm2)
(1600 cm2)
(2032cm2)
(2323cm2)
(2903cm2)
(3342cm2)
100
125
163
188
248
315
360
450
518
*Outside Air from 1 Opening Directly from Outdoors, in
2
133
(858 cm2)
167
(1077 cm2)
217
(1400 cm2)
250
(1613 cm2)
330
(2129 cm2)
420
(2710 cm2)
480
(3097 cm2)
600
(3871 cm2)
690
(4452 cm2)
2
CAUTION
The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as Freon, trichlorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the heat exchanger finned tubes, headers, flue collectors, and the vent system. The result is improper combustion and a non­warrantable, premature unit failure.
Inside Air from
2 Ducts Delivered from
Outdoors
Top
Opening, in
2
Opening, in
Bottom
200
(1291 cm2)
(1291 cm2)
250
(1613 cm2)
(1613 cm2)
325
(2097 cm2)
(2097 cm2)
375
(2420 cm2)
(2420 cm2)
495
(3194 cm2)
(3194 cm2)
630
(4065 cm2)
(4065 cm2)
720
(4646 cm2)
(4646 cm2)
900
(5807 cm2)
(5807 cm2)
1035
(6678 cm2)
(6678 cm2)
200
250
325
375
495
630
720
900
1035
Inside Air from
2 Ducts Delivered from Interior
Space
2
Opening, in
(2581 cm2)
(3226 cm2)
(4194 cm2)
(4839 cm2)
(6388 cm2)
(8130 cm2)
(9291 cm2)
(11614 cm2)
(13356 cm2)
Top
400
500
650
750
990
1260
1440
1800
2070
2
Opening, in
(2581 cm2)
(3226 cm2)
(4194 cm2)
(4839 cm2)
(6388 cm2)
(8130 cm2)
(9291 cm2)
(11614 cm2)
(13356 cm2)
Bottom
400
500
650
750
990
1260
1440
1800
2070
2
*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings. The above requirements are for the boiler only; additional gas fired appliances in the equipment room will require an increase in the net free area to supply adequate combustion air for all appliances.
11
Page 12
1 Determine unit location
Installation & Operation Manual
Exhaust fans
Any fan or equipment which exhausts air from the boiler room may deplete the combustion air supply and/or cause a down draft in the venting system. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be immediately corrected. If a fan is used to supply combustion air to the boiler room, the installer must make sure that it does not cause drafts which could lead to nuisance operational problems with the boiler.
Vertical DirectAire™, Horizontal DirectAire™, and Direct Vent venting systems have specific requirements for combustion air ducts from the outside which are directly connected to the unit. See the requirements for combustion air duct in the venting section.
NOTICE
Use of filters having MERV (Minimum Efficiency Reporting Value) ratings higher than
4 is not recommended. Higher efficiency low-micron filters can limit combustion air leading to either nuisance problems or potential component damage if used over prolonged periods of time. Filters having a MERV rating of 5 to 6 may be used on a limited basis during the construction phase of a project provided they are replaced once filter loading becomes apparent. After the construction phase is completed, it is recommended that the filter be changed to a 4 or lower MERV disposable type filter.
Combustion air filter
This unit has a standard air filter located at the combustion air inlet. This filter helps ensure clean air is used for the combustion process. Check this filter every month and replace when it becomes dirty. The filter size on Models 402 - 752 is 12" x 12" x 1" (30.5cm x 30.5cm x 2.5cm) and 16" x 16" x 1" (40.6cm x
40.6cm x 2.5 cm) on Models 992 - 2072. You can find these commercially available filters at any home center or HVAC supply store.
For convenience and flexibility, you can direct the combustion air inlet from either the back or right side of the unit. To arrange the combustion air inlet for side entry, follow the steps below:
1. Remove the metal panel from the unit’s side wall (see FIG. 1-6).
2. Remove screws from the air filter/bracket assembly.
3. Move the filter/bracket assembly from the rear of unit to the side opening (see FIG. 1-7).
4. Attach filter/bracket assembly to the unit’s side using the pre-drilled screw holes.
5. Attach the metal panel to the rear combustion air opening to seal it off.
Figure 1-6_Metal Panel Covering Side Combustion Air Inlet
NOTICE
CAUTION
During construction the air filter should be checked more frequently to ensure it does not become clogged with combustion dirt and debris.
Sustained operation of an appliance with a clogged filter may result in nuisance operational problems, bad combustion, and non-warrantable component failures.
12
Figure 1-7_Moving Air Filter / Bracket Assembly from
Rear of Unit to Side
Page 13
Installation & Operation Manual
2 Venting
BEFORE YOU BEGIN
Identify your appliance’s vent system:
This manual covers venting requirements for CAT I models and CAT IV vent materials. Be sure to correctly identify the type of vent system your appliance requires before proceeding.
C(F,H) (N,L)0402 C(F,H) (N,L)0502 C(F,H) (N,L)0652 C(F,H) (N,L)0752 C(F,H) (N,L)0992 C(F,H) (N,L)1262
C(F,H) (N,L)1442 C(F,H) (N,L)1802 C(F,H) (N,L)2072
Venting options:
A B C
E
F
= Direct Vent Options CAT IV
= Outdoor Vent Option
D
= B-Vent Material CAT I
DANGER
Failure to use correct venting materials can result in loss of life from flue gas spillage into working or living space.
Venting Category Definitions: (Reference National Fuel Gas Code ANSI Z223.1)
CAT I: Negative pressure non-condensing
An appliance that operates with a non-positive vent static pressure with a vent gas temperature that avoids excessive condensate production in the vent.
CAT IV: Positive pressure condensing
An appliance that operates with a positive vent static pressure with a vent gas temperature that may cause excessive condensate production in the vent.
CAT IV Flue pipe materials
The following manufacturers supply flue materials suitable for these models when installed as CAT IV. All materials are made with AL29-4C stainless steel.
Heat-Fab Inc., Saf-T CI Vent with AL29-4C stainless steel
Protech Systems Inc., Fas N Seal Vent with AL29-4C stainless steel
Metal-Fab Inc., Corr/Guard Vent with AL29-4C stainless steel
Or other listed Category IV vent systems suitable for a condensing, positive pressure, gas fired appliance.
A Category IV flue MUST have all vent joints and seams sealed gastight and have provisions for a drain to properly collect and dispose of condensate that may occur in the venting system.
13
Page 14
12"
MIN
3'
MIN
Installation & Operation Manual
2 Venting
Vent system options: (Note: Installations shown below are representative, actual installations may vary from those shown.)
This option uses a vertical rooftop flue termination with air supplied from the equipment room - see
A
CONVENTIONAL NEGATIVE DRAFT VENTING
page 16.
This option uses a vertical conventional vent for flue products with air supplied by a pipe from the
B
VERTICAL DIRECTAIRE VENTING
sidewall or rooftop - see page 19.
This option uses a powered vent assembly to exhaust the flue products out a sidewall with air
D
HORIZONTAL DIRECTAIRE VENTING
supplied by a pipe from the sidewall - see page 25.
3'
MIN
12"
MIN
This option uses a sealed AL29-4C flue and a separate combustion air pipe to the outdoors.
E
This system terminates both the flue and combustion air inlet in the same pressure zone
DIRECT VENT
- see page 26.
NOTE: CAT I B-VENT MATERIALS MAY BE USED WHEN THE POWERED VENT IS CONNECTED DIRECTLY TO THE OUTSIDE VENT CAP. IF THE POWERED VENT IS NOT CONNECTED DIRECTLY TO THE OUTSIDE VENT CAP, THEN CAT IV - AL29-4C VENT MATERIALS MUST BE USED FROM THE POWERED VENT TO THE OUTSIDE VENT CAP.
3'
This option uses the installation of a special air inlet / vent cap on top of the unit - see page 30.
C
This option uses a powered vent assembly to exhaust the flue products out a sidewall vent termination with air supplied from the
F
equipment room - see page 22.
SIDEWALL VENTING
NOTE: CAT I B-VENT MATERIALS MAY BE USED WHEN THE POWERED VENT I S CONNECTED DIRECTLY TO THE OUTSIDE VENT CAP. IF THE POW ERED VENT IS NOT CONNECTED DIRECTLY TO THE OUTSIDE VENT CAP, THEN CAT IV - AL29-4C VENT MATERIALS MUST BE USED FROM THE POWERED VENT TO THE OUTSIDE VENT CAP.
OUTDOOR VENTING
14
Page 15
Installation & Operation Manual
2 Venting (continued)
General information
You must supply adequate combustion and ventilation air to this unit. You must provide minimum clearances for the vent terminal from adjacent buildings, windows that open, and building openings. Follow all requirements set forth in the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment or applicable local building codes. Vent installations for connection to gas vents or chimneys must be in accordance with “Venting of Equipment” of the above-mentioned standards.
NOTICE
Examine the venting system at least once each year. Check all joints and vent pipe connections for tightness. Also check for corrosion or deterioration. If you find any problems, correct them at once.
Venting support
Support horizontal portions of the venting system to prevent sagging. Provide an upward slope of at least 1/4 inch per foot (21mm/m) on all horizontal runs from the unit to the vertical flue run or to the vent terminal on sidewall venting installations.
Do not use an existing chimney as a raceway if another appliance or fireplace is vented through the chimney. The weight of the venting system must not rest on the unit. Provide adequate support of the venting system. Follow all local and applicable codes. Secure and seal all vent connections. Follow the installation instructions from the vent material manufacturer.
Barometric damper location
Any venting system option that requires a barometric damper must adhere to the following directions for optimum performance. The preferred location for the barometric damper is in a tee or collar installed in the vertical pipe rising from the unit’s flue outlet. The barometric damper MUST NOT be installed in a bull head tee installed on the unit’s flue outlet. The tee or collar containing the barometric damper should be approximately three feet vertically above the connection to the unit’s flue outlet. This location ensures that any positive velocity pressure from the unit’s internal combustion fan is dissipated and the flue products are rising due to buoyancy generated from the temperature of the flue products. Adjust the weights on the damper to ensure that draft is maintained within the specified range.
TABLE - 2A
FLUE AND AIR INLET PIPE SIZES
MODEL FLUE SIZE AIR INLET SIZE MODEL FLUE SIZE AIR INLET SIZE*
402 6" 6" 992 10" 10" 502 6" 6" 1262 12" 12"
652 8" 8" 1442 12" 12" 752 8" 8" 1802 14" 12"
-- -- -- 2072 14" 12"
*Minimum diameter for air inlet pipe. Installer may increase diameter one pipe size for ease of installation, if needed.
15
Page 16
2 Venting
Conventional negative draft venting - see page 14.
A
NOTICE
This option uses Type-B double-wall flue outlet piping. The blower brings in combustion air. The buoyancy of the heated flue products cause them to rise up through the flue pipe. The flue outlet terminates at the rooftop.
Negative draft
The negative draft in a conventional vent installation must be within the range of 0.02 to 0.08 inches w.c. to ensure proper operation. Make all draft readings while the unit is in stable operation (approximately 2 to 5 minutes).
Connect the flue vent directly to the flue outlet opening on the top of the unit. No additional draft diverter or barometric damper is needed on single unit installations with a dedicated stack and a negative draft within the specified range of 0.02 to 0.08 inches w.c. If the draft in a dedicated stack for a single unit installation exceeds the maximum specified draft, you must install a barometric damper to control draft. Multiple unit installations with combined venting or common venting with other Category I negative draft appliances require each boiler to have a barometric damper installed to regulate draft within the proper range.
Do not connect vent connectors serving appliances vented by natural draft (negative draft) to any portion of a mechanical draft system operating under positive pressure. Connecting to a positive pressure stack may cause flue products to be discharged into the living space causing serious health injury.
Installation & Operation Manual
Before installing a venting system, follow requirements found in the General Venting section.
Flue outlet piping
With this venting option, you must use Type-B double-wall vent materials. Vent materials must be listed by a nationally-recognized test agency for use as vent materials. Make the connections from the unit vent to the outside stack as direct as possible with no reduction in diameter. Use the National Fuel Gas Code venting tables for double­wall vent to properly size all vent connectors and stacks. Follow the vent manufacturer’s instructions when installing Type-B vents and accessories, such as firestop spacers, vent connectors, thimbles, caps, etc.
Provide adequate clearance to combustibles for the vent connector and firestop.
When planning the venting system, avoid possible contact with plumbing or electrical wiring inside walls, ceilings, and floors. Locate the unit as close as possible to a chimney or gas vent.
Avoid long horizontal runs of the vent pipe, 90° elbows, reductions and restrictions.
No additional draft diverter or barometric damper is required on single unit installations with a dedicated stack and a negative draft maintained between 0.02 to 0.08 inches w.c.
Common Venting Systems
You can combine the flue with the vent from any other negative draft, Category I appliance. Using common venting for multiple negative draft appliances requires you to install a barometric damper with each unit. This will regulate draft within the proper range. You must size the common vent and connectors from multiple units per the venting tables for Type-B double-wall vents in the latest edition of the National Fuel Gas Code, ANSI Z223.1 and/or CAN/ CGA-B149 Installation Code.
16
Common venting systems may be too large when an existing unit is removed.
At the time of removal of an existing appliance, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused opening in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch. Make sure there is no blockage or restriction, leakage, corrosion and other unsafe conditions.
3. If possible, close all building doors and windows. Close all doors between the space in which the appliances remaining connected to the common venting system are located and other building spaces.
Page 17
Installation & Operation Manual
2 Venting (continued)
4. Turn on clothes dryers and any other appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan.
5. Close fireplace dampers.
6. Place in operation the unit being inspected. Follow the lighting instructions. Adjust thermostat so unit will operate continuously.
7. Test for spillage at the draft hood/relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
8. After making sure that each appliance remaining connected to the common venting system properly vents when tested as above, return doors, windows, exhaust fans, fireplace dampers and other gas burning appliances to their previous conditions of use.
9. Correct any improper operation of the common venting system so that the installation conforms to the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA-B149 Installation Code for Gas Burning Appliances and Equipment. When resizing any portion of the common venting system, resize to approach the minimum size as determined using the appropriate tables of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA-B149 Installation Code for Gas Burning Appliances and Equipment.
Masonry chimney installations
A masonry chimney must be properly sized for the installation of a high efficiency gas-fired appliance. Venting of a high efficiency appliance into a cold or oversized masonry chimney can result in operational and safety problems. Exterior masonry chimneys, with one or more sides exposed to cold outdoor temperatures, are more likely to have venting problems. The temperature of the flue products from a high efficiency appliance may not be able to sufficiently heat the masonry structure of the chimney to generate proper draft. This will result in condensing of flue products, damage to the masonry flue/tile, insufficient draft and possible spillage of flue products into an occupied living space. Carefully inspect all chimney systems before installation.
WARNING
NOTICE
Inspection of a masonry chimney
A masonry chimney must be carefully inspected to determine its suitability for the venting of flue products. A clay-tile-lined chimney must be structurally sound, straight and free of misaligned tile, gaps between liner sections, missing sections of liner or any signs of condensate drainage at the breaching or clean out. If there is any doubt about the condition of a masonry chimney, it must be relined with a properly-sized and approved chimney liner system. An unlined masonry chimney must not be used to vent flue products from this high-efficiency unit. An unlined chimney must be relined with an approved chimney liner system when a new appliance is being attached to it. Metallic liner systems (Type-B double-wall or flexible or rigid metallic liners) are recommended. Consult with local code officials to determine code requirements or the advisability of using or relining a masonry chimney.
Do not vent this unit into a masonry chimney without a sealed stainless steel liner system. Any breaks, leaks, or damage to the masonry flue/tile will allow the flue products to leak from the chimney and into occupied living spaces. This could cause serious injury or death due to carbon monoxide poisoning and other harmful flue products.
Check with local code officials to determine code requirements or the advisability of using a masonry chimney with a sealed corrosion-resistant liner system.
Vertical vent termination clearances and location
The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.61m) above the highest point of the roof within a 10 foot (3.05m) radius of the termination.
The vertical termination must be a minimum of 3 feet (0.91m) above the point of exit.
A vertical termination less than 10 feet (3.05m) from a parapet wall must be a minimum of 2 feet (0.61m) higher than the parapet wall.
Keep the vent cap clear of snow, ice, leaves, and debris to avoid blocking the flue.
17
Page 18
2 Venting
Installation & Operation Manual
Figure 2-1_Vent Termination from Peaked Roof - 10 ft. or Less From Ridge
NOTICE
Figure 2-3_Vent Termination from Flat Roof - 10 ft. or Less From Parapet Wall
Vent terminations are not shown in FIG.’s 2-1 thru 2-4. Make sure all vertical vents are installed with vent terminations recommended by the vent manufacturer.
Figure 2-2_Vent Termination from Peaked Roof - 10 ft. or More From Ridge
Figure 2-4_Vent Termination from Flat Roof - 10 ft. or More From Parapet Wall
18
Page 19
2 Venting (continued)
Vertical DirectAire ™ venting - see page 14.
NOTICE
B
Combustion air inlet piping
The Vertical DirectAire™ vent system is the same as the Conventional Negative Draft vent system, except it pulls combustion air from the outdoors through a separate air inlet pipe. Follow all requirements in the Conventional Negative Draft Venting section on page 16.
The Vertical DirectAire™ vent system requires you to install two pipes directly to the unit; one vertical pipe with a rooftop termination for the flue products and one pipe for combustion air. For this venting option, you must purchase the DV box adapter from the appliance manufacturer. The DV box attaches to the air inlet of the unit. The pipe for combustion air attaches to the DV box (see FIG. 2-11 on page 28). Reference page 28 for a list of approved air intake materials.
Before installing a venting system, follow requirements found in the General Venting section.
Installation & Operation Manual
WARNING
The sidewall or vertical rooftop DirectAire™ combustion air supply system has specific material and installation requirements. The air inlet pipe connects directly to the unit to supply combustion air. In most installations, the combustion air inlet pipe will be a dedicated system with one air inlet pipe per unit. You can combine multiple air inlets if the guidelines in Combined Air Inlet Points, page 20 are followed. The air inlet pipe will be connected to a combustion air inlet cap as specified in this section.
For normal installations, this system uses a single-wall pipe to supply combustion air from outdoors directly to the unit.
In cold climates, use a Type-B double-wall vent pipe or an insulated single-wall pipe for combustion air. This will help prevent moisture in the cool incoming air from condensing and leaking from the inlet pipe.
Length of air inlet pipe
The installed length of air inlet pipe from the unit to the outside air inlet cap must not exceed 50 equivalent feet (15.2m). Subtract 5 feet (1.5m) of equivalent length for each 90° elbow. Subtract 2.5 feet (0.7m) of equivalent length for each 45° elbow.
Do not exceed the limits for the combustion air inlet piping lengths.
Sidewall air inlet
The sidewall air inlet cap is supplied in the Sidewall Air Inlet Kit. Order the kit from the appliance manufacturer. This sidewall cap supplies combustion air for a single unit only. See Table 2B, page 21, for kit numbers.
Locate the unit as close as possible to the sidewall where you will install the combustion air supply system.
Locate and install the combustion air inlet cap correctly. Failure to do so can allow the discharge of flue products to be drawn into the combustion process. This can result in incomplete combustion and potentially hazardous levels of carbon monoxide in the flue products. This will cause operational problems and the spillage of flue products. Spillage of flue products can cause personal injury or death due to carbon monoxide poisoning.
Figure 2-5_Sidewall Combustion Air Inlet
Figure 2-6_Air Inlet Cap for Sidewall Termination
19
Page 20
Installation & Operation Manual
2 Venting
To prevent recirculation of flue products from an adjacent vent cap into the combustion air inlet, follow all applicable clearance requirements in the latest edition of the National Fuel Gas Code and/or CAN/CGA-B149 Installation Code and instructions in the Installation and Operation Manual.
Clearances
You must install the combustion air inlet cap at least one foot (0.30m) above ground level and above normal snow levels.
The point of termination for the combustion air inlet cap must be at least 3 feet (0.91m) below the point of flue gas termination if it is located within 10 feet (3.05m) of the flue outlet. Make sure to properly install the air inlet cap assembly on the air inlet pipe.
Do not install the combustion air inlet cap closer than 10 feet (3.05m) from an inside corner of an L-shaped structure.
Vertical Rooftop Air Inlet
Use the vertical air inlet terminations available from the appliance manufacturer, recommended and/or supplied by the vent manufacturer, or use two 90° elbows as described on page 29.
3' MIN
12" MIN
You must locate the air inlet termination elbow at least 12" (30cm) above the roof or above normal snow levels.
If the air inlet cap is within a 10-foot (3.05m) radius of the flue outlet, the point of termination for the combustion air inlet cap must be at least 3 feet (0.91m) below the point of flue gas termination (vent cap).
Do not install the combustion air inlet cap closer than 10 feet (3.05m) from an inside corner of an L-shaped structure.
Combined air inlet points
The air inlet pipes from multiple boilers can be combined to a single common connection if the common air inlet pipe has a cross sectional area equal to or larger than the total area of all air inlet pipes connected to the common air inlet pipe.
Example: Two 10" air inlet pipes (78.5 in2 area each) have a total
Figure 2-7_Rooftop Combustion Air Inlet
The air inlet point for multiple boiler air inlets must be provided with an exterior opening which has a free area equal to or greater than the total area of all air inlet pipes connected to the common air inlet. This exterior opening for combustion air must connect directly to the outdoors. The total length of the combined air inlet pipe must not exceed a maximum of 50 (15.2m) equivalent feet. Subtract 5 feet (1.5m) for each 90° elbow in the air inlet pipe. You must deduct the restriction in area provided by any screens, grills or louvers installed in the common air inlet point. These are common on the sidewall air inlet openings. Screens, grills or louvers installed in the common air inlet can reduce the free area of the opening from 25% to 75% based on the materials used.
area of 157 in2 and will require a 15" (176.7 in2 area) common air inlet pipe.
You can terminate the combustion air pipe either horizontally with a sidewall air inlet or vertically with a rooftop air inlet. The installed length of air inlet pipe from the unit to the outside air inlet cap must not exceed 50 equivalent feet (15.2m).
20
Page 21
2 Venting (continued)
Installation & Operation Manual
WARNING
3' MIN
12" MIN
Figure 2-8_Vertical DirectAire™ Installation w/Rooftop Combustion Air Inlet
Only use a sidewall air inlet cap supplied by the appliance manufacturer or a rooftop air inlet cap supplied by either the vent or appliance manufacturer. Using any other air inlet cap for single unit installations or using a common air inlet cap for multiple units with insufficient free area and/or protections from wind and weather may result in operational problems and the spillage of flue products. Spillage of flue products can cause personal injury or death due to carbon monoxide poisoning.
For single unit installations with sidewall air inlet you must order the sidewall air inlet kit from the appliance manufacturer. The part number for each SVK kit is listed by unit size in Table 2B.
For single unit installations with rooftop air inlet (see FIG. 2-8), you must order the rooftop air inlet kit from the appliance manufacturer. The part number for each VDK kit is listed by unit size in Table 2B. Purchase the flue pipe, rooftop flue termination, and air inlet pipe locally.
There is no vent kit for combined air supply systems for multiple units. Make sure the air inlet cap is properly sized. You must purchase this cap locally.
Venting of flue products
For venting flue products vertically to the outdoors, follow all requirements in the installation instructions for conventional venting in this manual.
Follow all clearance requirements in Vertical Vent Termination Clearances and Location on page 17.
A barometric damper is not required in the flue on Vertical DirectAire™ installations if the draft is within the negative 0.02 to 0.08 inches w.c. required for proper operation. If the draft exceeds this range, install a barometric damper.
TABLE - 2B
DIRECTAIRE KITS
MODEL HORIZONTAL KIT* VERTICAL KIT*
402 SVK3047 VDK3026 502 SVK3047 VDK3026 652 SVK3048 VDK3027 752 SVK3048 VDK3027
992 SVK3040 VDK3023 1262 SVK3041 VDK3024 1442 SVK3041 VDK3024 1802 SVK3041 VDK3024 2072 SVK3041 VDK3024
*The SVK kits include a DV box adapter and sidewall air inlet cap. The VDK kits include a DV box adapter and a rooftop air inlet cap.
21
Page 22
2 Venting
Sidewall venting - see page 14.
Installation & Operation Manual
C
NOTICE
This option uses a powered vent assembly which pulls the flue products out of the stack. This fan generates a negative draft at the unit. Combustion air is drawn from the equipment room (see Combustion and Ventilation Air on 10).
Sidewall with fan
The sidewall fan can be mounted on the inside/outside (depending upon model) with a sidewall vent hood installed on the exterior wall. The sidewall fan and accessories are included in a venting kit provided by the appliance manufacturer. See Table 2C on page 24 for kit numbers.
The venting kit includes the sidewall fan, vent hood, tapered vent adapter, barometric damper (992 - 2072 Models), proving switch and all necessary relays to interlock with the heaters control system. The tapered vent adapter reduces the vent size at the inlet to the fan. There should be no reduction in vent diameter from the unit’s flue outlet to the sidewall fan. The barometric damper must be installed on the flue and adjusted to supply a negative draft within the range of 0.04 to 0.08 inches w.c. while unit is operating.
Flue outlet piping
With this venting option, you must use Type-B double-wall (or equivalent) vent materials. Vent materials must be listed by a nationally-recognized test agency for use as vent materials. Make the connections from the unit vent to the sidewall fan/cap as direct as possible with no reduction in diameter. Use the National Fuel Gas Code venting tables for double-wall vent to properly size all vent connectors and stacks. Follow the vent manufacturer’s instructions when installing Type-B vents and accessories, such as firestop spacers, vent connectors, thimbles, caps, etc.
When planning the venting system, avoid possible contact with plumbing or electrical wiring inside walls.
Before installing a venting system, follow all requirements found in the General Venting section.
The maximum installed length of sidewall vent pipe with an induced draft fan must not exceed 100 feet (30.5m). Subtract 5 feet (1.5m) for each 90° elbow. Subtract 2.5 feet (0.7m) for each 45° elbow.
Sidewall venting termination
The sidewall vent cap must be installed on an exterior sidewall. The sidewall fan/powered sidewall vent cap and accessories are included in a venting kit which is furnished by the appliance manufacturer in accordance with CSA International requirements. This venting kit includes the powered sidewall fan/cap, proving switch and all necessary relays to interlock with the heaters control system.
The sidewall fan/powered vent cap must be interlocked with the units control system to start the fan on a call for heat and prove fan operation before the boiler fires. Plug-in and terminal strip connections are provided on the unit for easy connection of the factory supplied vent kit and control package for the sidewall vent fan. See the installation instructions provided with the vent kit.
Sidewall vent termination clearances and location
Locate the bottom of the vent terminal at least 12 inches (30cm) above grade and above normal snow levels. Locate the bottom of the vent terminal at least 7 feet (2.13m) above grade when located adjacent to public walkways. Do not terminate directly above a public walkway.
Do not terminate the venting system in a window well, stairwell, alcove, courtyard, or other recessed area. Do not terminate the venting system below grade.
Locate vent termination at least 3 feet (0.91m) from an inside corner of an L-shaped structure.
Provide a minimum clearance of 4 feet (1.2m) horizontally from electric meters, gas meters, regulators, and relief equipment. Never locate vent cap above or below electric meters, gas meters, regulators, and relief equipment unless a 4 foot (1.2m) horizontal clearance is maintained.
22
Page 23
Installation & Operation Manual
2 Venting (continued)
Terminate the venting system at least 3 feet (0.9m) above any forced air inlet within 10 feet (3.05m).
Terminate the venting system at least 4 feet (1.2m) below, 4 feet (1.2m) beside, or 1 foot (30cm) above any door, window, or gravity air inlet into any building.
Locate vent termination at least 8 feet (2.4m) horizontally from any combustion air intake located above the sidewall termination cap.
CAUTION
Sidewall venting without fan
For Models 402 - 752 which are approved for sidewall venting without an external power vent fan, you must install specific vent kits and venting materials (reference Table 2C on page 24 for kit numbers).
The following is a detailed explanation of Sidewall Venting Without an External Power Vent Fan installation requirements.
Flue outlet piping
Venting Guidelines
Units which are shut down or will not operate may experience freezing due to convective air flow in the flue pipe, through the air inlet, or from negative pressure in the equipment room. In cold climates, operate the pump continuously to help prevent freezing of boiler water. Provide proper freeze protection. See Freeze Protection, page 47.
If using this venting option, a sealed AL29-4C venting system for flue products is required on all models of this appliance. This venting system operates with a positive pressure in the vent. The internal combustion air blower generates this positive pressure which operates the combustion process and also exhausts the flue products from the building.
This vent system has specific vent material and installation requirements. Only use listed sealed AL29-4C vent system materials. Follow all installation requirements. See Table 2A for proper pipe size for your unit. A list of sealed AL29-4C flue pipe manufacturers is located on page 15.
Seal all vent joints and seams gas-tight.
Drain tee installation
A drain tee must be installed in the vent pipe to collect and dispose of any condensate that may occur in the vent system. The drain tee must be installed as the first fitting after the horizontal ell on the top of the unit (see FIG. 2-9). Plastic drain tubing, sized per the vent manufacturer’s instructions, shall be provided as a drain line from the tee. The drain tubing must have a trap provided by a 3" (7.6cm) diameter circular trap loop in the drain tubing. Prime the trap loop by pouring a small quantity of water into the drain hose before assembly to the vent. Secure the trap loop in position with nylon wire ties. Use caution not to collapse or restrict the condensate drain line with the nylon wire ties. The condensate drain must be routed to a suitable drain for disposal of condensate that may occur in the direct vent system. Refer to the condensate drain installation instructions as supplied by the manufacturer of the vent material.
Figure 2-9_Sidewall Vent - Models 402 - 752 (Only)
23
Page 24
2 Venting
Installation & Operation Manual
WARNING
Connect the flue vent directly to the flue outlet opening on the top of the unit. Make the connections from the unit vent to the outside stack as direct as possible with no reduction in diameter. Provide adequate clearance to combustibles for the vent connector and firestop. Follow the vent manufacturer’s instructions when installing sealed AL29-4C vents and accessories, such as firestop spacers, vent connectors, thimbles, caps, etc.
Provide adequate clearance to combustibles for the vent connector and firestop.
When planning the venting system, avoid possible contact with plumbing or electrical wiring inside walls, ceilings, and floors.
Locate the unit as close as possible to chimney or gas vent. When a vent system is disconnected for any reason, the flue must be reassembled and resealed according to the vent manufacturer’s instructions.
The installed length of flue from the unit to the outside point of termination must not exceed 50 equivalent feet (15.2m). Subtract 5 feet (1.5m) of equivalent length for each 90° elbow. Subtract 2.5 feet (0.7m) of equivalent length for each 45° elbow.
Sidewall vent termination clearances and location
Follow all sidewall venting termination information for clearances and location under Sidewall Vent Termination Clearances and Location on page 22.
Do not combine the flue from this unit with the vent from any other appliance. Do not combine flues from multiple appliances into a common vent. The flue from this unit must be a dedicated stack.
TABLE - 2C
SIDEWALL VENT KITS
MODEL
402 SVK3006 100 ft. SVK3043 50 ft.
502 SVK3006 100 ft. SVK3043 50 ft.
652 SVK3008 100 ft. SVK3044 50 ft.
752 SVK3008 100 ft. SVK3044 50 ft.
992 SVK3009* 100 ft. N/A N/A
1262 SVK3010* 100 ft. N/A N/A
1442 SVK3010* 100 ft. N/A N/A
1802 SVK3012* 100 ft. N/A N/A
2072 SVK3012* 100 ft. N/A N/A
*These kits include a barometric damper.
(W/POWER FAN ASSY.)
KIT
MAX. VENT
LENGTH
VENT TERMINATION
ONLY
(MODELS 402 - 752)
MAX. VENT
LENGTH
24
Page 25
Installation & Operation Manual
12" MIN
3'
MIN
2 Venting (continued)
Horizontal DirectAire™ venting (Powered Venting) - see page 14.
NOTICE
Before installing a venting system, follow all requirements found in the General Venting section.
D
The Horizontal DirectAire™ vent system is the same as the Sidewall Venting system, except it pulls combustion air from the outdoors through a sidewall air inlet. Follow all requirements in Sidewall Venting section on page 22.
The Horizontal DirectAire™ vent system requires you to install two pipes directly to the unit; one pipe for flue products and one for combustion air. Install both pipes horizontally with a sidewall termination point. For this venting option, you must purchase the DV box accessory from the appliance manufacturer. The DV box attaches to the air inlet of the unit. The pipe for combustion air attaches to the DV box (see FIG. 2-11 on page 28). Reference page 28 for a list of approved air intake materials.
Make vent connection directly to the top of the unit. No additional draft diverter or barometric damper is required on single unit installations with a dedicated stack and a negative draft maintained between 0.04 to 0.08 inches w.c.
The Horizontal DirectAire™ combustion air supply system has specific vent material and installation requirements. The air inlet pipe connects directly to the boiler to supply combustion air. The combustion air inlet pipe is a dedicated system with one air inlet pipe per boiler. You must connect the air inlet pipe to a combustion air inlet cap as specified in this section.
Combustion air supplied from outdoors must be free of contaminants (see the Combustion and Ventilation Air section on page 10).
You must order the Horizontal DirectAire™ Vent Kit for sidewall installation from the appliance manufacturer. See Table 2D for kit numbers. Each kit includes a sidewall powered vent cap fan, proving switch, controls, combustion air inlet cap to supply air to a single unit, the transition adapter to attach the field supplied single wall air inlet pipe to the unit and installation instructions. Purchase flue pipe and air inlet pipe locally.
The sidewall air inlet cap supplied in the Horizontal DirectAire™ Vent Kit is used to supply combustion air to a single boiler. Combustion air supply pipes from multiple units can not be combined into a single air inlet pipe and inlet point.
WARNING
Only use the sidewall air inlet cap recommended by the appliance manufacturer. Using another sidewall air inlet cap may result in operational problems and the spillage of flue products. Spillage of flue products can cause personal injury or death due to carbon monoxide poisoning.
Venting of flue products
For venting flue products horizontally, follow all requirements in the installation instructions for sidewall venting.
Termination point for the flue products must follow the clearance requirements in the Sidewall Venting Termination section on page 22.
For proper operation, a barometric damper is provided for Horizontal DirectAire™ installations. The damper will help to ensure a draft between negative 0.04 to 0.08 inches w.c.
TABLE - 2D
HORIZONTAL DIRECTAIRE™ KITS
MODEL KIT MODEL KIT
402 HDK3031 992 HDK3026* 502 HDK3031 1262 HDK3027*
652 HDK3032 1442 HDK3027* 752 HDK3032 1802 HDK3028*
-- -- 2072 HDK3028*
*These kits include a barometric damper.
25
Page 26
2 Venting
12" MIN
3'
MIN
Direct venting - see page 14.
Installation & Operation Manual
E
NOTICE
Before installing a venting system, follow all requirements found in the General Venting section.
This option uses sealed AL29-4C vent materials for the flue outlet piping and separate combustion air inlet piping. This system terminates both the flue and combustion air inlet in the same pressure zone. The flue outlet and
3'
combustion air intake may terminate at either a sidewall or the rooftop.
To use the optional Direct Vent system, you must install specific vent kits and venting materials. The following is a detailed explanation of Direct Vent installation requirements, including the components used and vent kit part numbers (reference Table 2E on page 27 for kit numbers).
Flue outlet piping
Venting Guidelines
If using this venting option, a sealed AL29-4C venting system for flue products is required on all models of this appliance. This venting system operates with a positive pressure in the vent. The internal combustion air blower generates this positive pressure which operates the combustion process and also exhausts the flue products from the building.
This vent system has specific vent material and installation requirements. Only use listed sealed AL29-4C vent system materials. Follow all installation requirements. See Table 2A, page 15 for proper pipe size for your unit.
Seal all vent joints and seams gas-tight.
Drain tee installation
A drain tee must be installed in the vent pipe to collect and dispose of any condensate that may occur in the vent system. The drain tee must be installed as the first fitting after the horizontal ell on the top of the unit (see FIG. 2-9 on page 23). Plastic drain tubing, sized per the vent manufacturer’s instructions, shall be provided as a drain line from the tee. The drain tubing must have a trap provided by a 3" (7.6cm) diameter circular trap loop in the drain tubing. Prime the trap loop by pouring a small quantity of water into the drain hose before assembly to the vent. Secure the trap loop in position with nylon wire ties. Use caution not to collapse or restrict the condensate drain line with the nylon wire ties. The condensate drain must be routed to a suitable drain for disposal of condensate that may occur in the direct vent system. Refer to the condensate drain installation instructions as supplied by the manufacturer of the vent material.
WARNING
Do not combine the flue from this unit with the vent from any other appliance. Do not combine flues from multiple appliances into a common vent. The flue from this unit must be a dedicated stack.
Connect the flue vent directly to the flue outlet opening on the top of the unit. Make the connections from the unit vent to the outside stack as direct as possible with no reduction in diameter. Provide adequate clearance to combustibles for the vent connector and firestop. Follow the vent manufacturer’s instructions when installing sealed AL29-4C vents and accessories, such as firestop spacers, vent connectors, thimbles, caps, etc.
Provide adequate clearance to combustibles for the vent connector and firestop.
When planning the venting system, avoid possible contact with plumbing or electrical wiring inside walls, ceilings, and floors. Locate the unit as close as possible to chimney or gas vent.
When a vent system is disconnected for any reason, the flue must be reassembled and resealed according to the vent manufacturer’s instructions.
The installed length of flue from the unit to the outside point of termination must not exceed 50 equivalent feet (15.2m). Subtract 5 feet (1.5m) of equivalent length for each 90° elbow. Subtract 2.5 feet (0.7m) of equivalent length for each 45° elbow.
Vertical DV venting termination
You must use the vent termination recommended by the vent manufacturer for vertical direct vent terminations. Follow all vertical venting termination information for clearances and location under the Vertical Vent Termination Clearances and Location section on pages 17 - 18.
26
Page 27
Installation & Operation Manual
2 Venting (continued)
Masonry chimney installation
Do not use a standard masonry chimney to directly vent the combustion products from this unit.
To use a masonry chimney, the chimney must use a sealed, corrosion-resistant liner system. Sealed, corrosion-resistant liner systems (single-wall, double-wall, flexible, or rigid) must be rated for use with a high efficiency, positive pressure vent system.
Corrosion-resistant chimney liner systems are typically made from a high grade stainless steel such as AL29-4C. The liner must be properly sized and fully sealed throughout the entire length. Both the top and bottom of the masonry chimney must be capped and sealed to provide a dead air space around the liner.
WARNING
NOTICE
Do not vent this unit into a masonry chimney without a sealed stainless steel liner system. Any breaks, leaks, or damage to the masonry flue/tile will allow the positive-pressure flue products to leak from the chimney and into occupied living spaces. This could cause serious injury or death due to carbon monoxide poisoning and other harmful flue products.
Check with local code officials to determine code requirements or the advisability of using a masonry chimney with a sealed corrosion-resistant liner system.
Horizontal DV venting termination
Horizontal venting uses the unit’s internal combustion air blower to force the flue products out of the horizontally-terminated flue.
You must purchase a horizontal direct vent kit from the appliance manufacturer to ensure proper operation. When installing the vent cap, the wall opening must provide an air space clearance of 2 inches (5.1cm) around the flue pipe. The diameter of the opening for installation of the sidewall cap will be 4 inches (10.2cm) larger (minimum) than the nominal diameter of the installed vent pipe to the horizontal vent cap.
Install the horizontal vent cap from the outside. Mount the vent cap to the wall using four screws or wall anchors. Seal under the screw heads with caulking. Install the Category IV vent pipe from the unit to the vent cap. See detailed instructions packed with the horizontal direct vent kit.
Horizontal Vent Termination Clearances and Location
Follow all sidewall venting termination information for clearances and location under Sidewall Vent Termination Clearances and Location, page 22.
TABLE - 2E
DIRECT VENT KITS
MODEL
402 DVK3004 VDK3026 992 DVK3000 VDK3023 502 DVK3004 VDK3026 1262 DVK3001 VDK3024
652 DVK3005 VDK3027 1442 DVK3001 VDK3024 752 DVK3005 VDK3027 1802 DVK30000 VDK3024
-- -- -- 2072 DVK30000 VDK3024
*These kits include a DV box adapter, air inlet cap, and a sidewall vent termination. The VDK kits include a DV box adapter and an air inlet cap.
HORIZONTAL
KIT*
VERTICAL
KIT*
MODEL
HORIZONTAL
KIT*
VERTICAL
KIT*
Combustion air inlet piping
The Direct Vent system requires the installation of a pipe to supply combustion air from the outdoors directly to the unit. Make sure the combustion air inlet is in the same pressure zone as the vent terminal.
In cold climates, use a Type-B double-wall vent pipe or an insulated single wall pipe for combustion air. This will help prevent moisture in the cool incoming air from condensing and leaking from the inlet pipe.
CAUTION
Units that are shut down or will not operate may experience freezing due to convective airflow in the air inlet pipe.
27
Page 28
Installation & Operation Manual
2 Venting
Length of air inlet pipe
The installed length of air inlet pipe from the unit to the outside air inlet cap must not exceed 50 equivalent feet (15.2m). Subtract 5 feet (1.5m) of equivalent length for each 90° elbow. Subtract 2.5 feet (0.7m) of equivalent length for each 45° elbow. Do not exceed the limits for the combustion air inlet piping lengths.
Connecting the air inlet pipe to the unit
Connect the air inlet piping directly to the unit by attaching it to the DV box adapter. The DV box adapter is included in the direct vent kits. The combustion air inlet area of the unit is located at the right rear corner of the unit. This unit uses a simple air filter to ensure clean air is used for the combustion process. Attach the DV box adapter over the air filter (see FIG. 2-11). Align screw holes on the DV box adapter with the screw holes surrounding the air filter hanger. Insert sheet metal screws and tighten firmly.
For venting versatility, you can move the air filter assembly and DV box adapter to the right side of the unit. Remove the metal panel on the unit’s right side (see FIG. 2-12). Remove the filter/bracket assembly from the rear of the unit. Attach the filter/bracket assembly and DV box adapter to the right side opening using the pre-drilled screw holes. Make sure you attach the metal panel to the rear combustion air opening of the unit.
The DV box adapter has an air inlet pipe mounting ring. Connect combustion air inlet piping to the direct vent box mounting ring.
VERTICAL DV BOX ADAPTER
HORIZONTAL DV BOX ADAPTER
Figure 2-11_Attaching DV Box Adapter to Unit
Figure 2-12_Moving Air Filter Assembly & DV Box Adapter
Air inlet piping materials
The air inlet pipe(s) must be sealed. Select air inlet pipe material from the following specified materials.
PVC, CPVC, or ABS*
Dryer vent or sealed flexible duct (not recommended for rooftop air inlet)
Galvanized steel vent pipe with joints and seams sealed as specified below
Type-B double-wall vent with joints and seams sealed as specified below. * Plastic pipe may require an adapter (not provided) to transition between the air inlet connection on the unit and the plastic air
inlet pipe.
WARNING
Sealing Type-B double-wall vent pipe or galvanized vent pipe
Follow the steps below to properly seal Type-B double-wall vent pipe or galvanized vent pipe.
1. Seal all joints and seams of the air inlet pipe using either aluminum foil duct tape meeting UL Standard 723 or 181 A-P or a high quality UL Listed silicon sealant such as those manufactured by Dow Corning or General Electric.
2. On horizontal runs, do not install vent pipe with seams pointing down. Position vent pipe so that the seams are on the top side of the vent pipe.
3. Secure all joints with a minimum of three sheet metal screws or pop rivets. Apply aluminum foil duct tape or silicone sealant to all screws or rivets installed in the vent pipe.
4. Ensure that the air inlet pipes are properly supported.
Use only vent or air intake materials specified in this manual. Follow vent pipe manufacturer’s instructions. Failure to do so can result in property damage, personal injury, or death. Mixing of venting materials will void the warranty and certification of this unit.
Sealing PVC, CPVC, ABS, dryer vent, and flex duct vent pipe
1. Clean the PVC, CPVC, or ABS air inlet pipe using the pipe manufacturer’s recommended solvents. Seal the pipe joints using standard commercial pipe cement.
28
Page 29
Installation & Operation Manual
2 Venting (continued)
2. For PVC, CPVC, ABS, dryer vent, or flex duct air inlet piping, use a silicone sealant to ensure a proper seal at the unit inlet and the air inlet cap.
3. For Dryer vent or flex duct, also use a screw-type clamp to attach the inlet vent material to the unit inlet and the air inlet cap.
Properly sealing the air inlet pipe ensures that combustion air will be free of contaminates and supplied in proper volume.
4. Ensure that the air inlet pipes are properly supported.
WARNING
Properly seal all joints and seams in the inlet vent piping system. Failure to do so may result in flue gas recirculation, spillage of flue products, and carbon monoxide emissions. Carbon monoxide poisoning can cause severe personal injury or death.
Vertical and sidewall combustion air inlet
NOTICE
WARNING
You must locate the combustion air cap and the flue gas outlet on the same rooftop surface (vertical direct vent system) or sidewall surface (horizontal direct vent system) and in the same pressure zone as the vent termination. Follow all clearance requirements listed on this page.
Purchase and assemble the combustion air inlet cap to protect the air inlet from wind and weather.
Alternatively, assemble the combustion air inlet cap for vertical rooftop air inlet from items purchased locally. The air inlet cap consists of two 90° elbows installed to the air inlet pipe (see FIG. 2-13). Install the first 90° elbow on the rooftop at the highest vertical point of the air inlet pipe. Install the second 90° elbow on the horizontal outlet of the first elbow. The outlet of the second 90° elbow will be pointing down. You may use a 90° elbow and a 90° straight elbow to make this assembly. If you use a straight piece of pipe between the two 90° elbows, it should not exceed 6" (51mm) in length.
Figure 2-13_Vertical Rooftop Air Inlet
Horizontal combustion air inlet clearances
You must locate the horizontal air inlet termination point at least 12" (30cm) above grade and above normal snow levels.
If the air inlet cap is within a 10-foot (3.05m) radius of the flue outlet, the point of termination for the combustion air inlet cap must be at least 3 feet (0.91m) below the point of flue gas termination (vent cap). Do not install the horizontal combustion air inlet cap above the flue outlet.
Do not install the combustion air inlet cap closer than 10 feet (3.05m) from an inside corner of an L-shaped structure.
Multiple sidewall direct vent installations
You must locate the horizontal air inlet termination points at least 12" (30cm) above grade and above normal snow levels. The combustion air inlet caps for multiple appliance installations must maintain the same minimum clearance from the closest flue vent cap as specified in single appliance installations. You may install multiple flue outlet caps side-by-side and multiple combustion air inlet caps side-by-side, but the air inlet must always be at least 3 feet (0.91m) horizontally and 3 feet (0.91m) below the closest flue outlet. Do not install combustion air inlet caps above the flue outlets.
Maintain all clearances and installation requirements for multiple appliance installations.
To prevent recirculation of flue products into the combustion air inlet, follow all instructions in this section.
Locate and install the combustion air inlet termination correctly. Failure to do so can allow the discharge of flue products to be drawn into the combustion process. This can result in incomplete combustion and potentially hazardous levels of carbon monoxide in the flue products. This will cause operational problems and the spillage of flue products. Spillage of flue products can cause personal injury or death due to carbon monoxide poisoning.
6" MAX
For horizontal direct vent termination of combustion air, you must use the termination cap from the appliance manufacturer. The sidewall air inlet cap is available as part of a direct vent kit. See Table 2E, page 27 for Horizontal Direct Vent Kits.
Vertical Combustion Air Inlet Clearances
You must locate the air inlet termination elbow at least 12" (30cm) above the roof or above normal snow levels.
If the air inlet cap is within a 10-foot (3.05m) radius of the flue outlet, the point of termination for the combustion air inlet cap must be at least 3 feet (0.91m) below the point of flue gas termination (vent cap).
Do not install the combustion air inlet cap closer than 10 feet (3.05m) from an inside corner of an L-shaped structure.
29
Page 30
2 Venting
3'
MIN
3'
MIN
3'
MIN
3'
MIN
Outdoor installation - see page 14.
F
Installation & Operation Manual
NOTICE
Before installing a venting system, follow all requirements found in the General Venting section.
Units are self-venting and can be used outdoors when installed with the optional outdoor cap. This cap mounts directly to the top of the unit and covers the flue outlet and combustion air inlet openings. No additional vent piping is required.
WARNING
Only install outdoor models outdoors and only use the vent cap supplied by the appliance manufacturer. Personal injury or product damage may result if any other cap is used or if an outdoor model is used indoors. Properly install all covers, doors and jacket panels to ensure proper operation and prevent a hazardous condition.
Combustion air supply must be free of contaminants (see Combustion and Ventilation Air, page 10). To prevent recirculation of the flue products into the combustion air inlet, follow all instructions in this section.
Outdoor vent/air inlet location
Keep venting areas free of obstructions. Keep area clean and free of combustible and flammable materials. Maintain a minimum clearance of 3" (76mm) to combustible surfaces and a minimum of 36" (915mm) clearance to the air inlet. To avoid a blocked air inlet or blocked flue condition, keep the outdoor cap air inlet, flue outlet and drain slot clear of snow, ice, leaves, debris, etc.
Do not install outdoor models directly on the ground. You must install the outdoor unit on a concrete, brick, block, or other non­combustible pad.
Do not locate unit so that high winds can deflect off of adjacent walls, buildings or shrubbery causing recirculation. Recirculation of flue products may cause operational problems, bad combustion or damage to controls. Locate unit at least 3 feet (0.91m) from any wall or vertical surface to prevent wind conditions from affecting performance.
Multiple unit outdoor installations require 48" (1.22m) clearance between each vent cap. Locate outdoor cap at least 48" (1.22m) below and 48" (1.22m) horizontally from any window, door, walkway or gravity air intake.
Locate unit at least 10 feet (3.05m) away from any forced air inlet.
Locate unit at least 3 feet (0.91m) outside any overhang.
Clearances around outdoor installations can change with time. Do not allow the growth of trees, shrubs or other plants to obstruct the proper operation of the outdoor vent system.
Do not install in locations where rain from building runoff drains will spill onto the unit.
Flue gas condensate can freeze on exterior walls or on the vent cap. Frozen condensate on the vent cap can result in a blocked flue condition. Some discoloration to exterior building or unit surfaces can be expected. Adjacent brick or masonry surfaces should be protected with a rust resistant sheet metal plate.
The outdoor vent cap kit
The optional outdoor vent cap kit is available from the appliance manufacturer. The outdoor cap part numbers are listed by model number. See Table 2F for kit numbers.
Install the outdoor vent cap on the rear of the unit. Complete installation instructions are included with the outdoor vent cap kit.
MODEL
402 ODK3748 ODK3052 992 ODK3036 ODK3049 502 ODK3748 ODK3052 1262 ODK3064 ODK3065
652 ODK3749 ODK3053 1442 ODK3037 ODK3050 752 ODK3749 ODK3053 1802 ODK30002 ODK30001
-- -- -- 2072 ODK30002 ODK30001
30
*These kits include an outdoor vent cap and gasket.
KIT* WITHOUT
PUMP COVER
Figure 2-14_Outdoor vent cap installed
TABLE - 2F
OUTDOOR VENT CAP KITS
KIT* WITH
PUMP COVER
MODEL
KIT* WITHOUT
3'
3'
PUMP COVER
3'
3'
KIT* WITH
PUMP COVER
Page 31
3 Gas connections
Installation & Operation Manual
Connecting to gas supply
Verify that the appliance is supplied with the type of gas specified on the rating plate. This appliance is configured for operation up to 4,500 feet altitude. Consult factory for installations above 4,500 feet elevation.
Inlet gas pressure: Measured at the inlet pressure tap on the
appliance gas manifold. The pressure tap is located upstream of the combination gas valve(s) (FIG. 3-3 on page 33).
See Table 3A for maximum and minimum inlet pressures. Do not exceed the maximum. Minimum inlet pressure is for the purpose of input adjustment.
TABLE 3A
INLET GAS PRESSURE
NATURAL LP
MODEL
402 - 2072 14.0 4.5 14.0 8.0
Manifold pressure: The gas regulator on the unit’s
combination gas valve is adjustable to supply proper manifold pressure for normal operation. See the Copper-fin II Service Manual for net manifold pressure settings.
If you must adjust regulator pressure, follow the instructions under Gas Manifold Pressure Adjustment in the Copper-fin II Service Manual. Do not increase regulator pressure beyond specified pressure setting.
Max.
w.c.
Min.
w.c.
Max.
w.c.
Min.
w.c.
Gas pressure test
1. The appliance must be disconnected from the gas supply piping system during any pressure testing of that system at a test pressure in excess of 1/2 PSIG (3.5 kPa).
Install a manual main gas shutoff valve, outside of the unit gas connection within six feet of the unit in accordance with the requirements of the National Fuel Gas Code, ANSI Z223.1.
You must provide a sediment trap (drip leg) in the inlet of the gas connection to the unit.
NOTICE
CAUTION
It is the installer’s responsibility to supply the sediment trap (drip leg).
Do not block access to the electrical cover plate when installing the sediment trap. The sediment trap must be a minimum of 12 inches from the appliance.
The combination gas valves have an integral vent limiting device and do not require venting to atmosphere, outside the building. The unit will not operate properly if the reference hose is removed or a vent to atmosphere is installed.
Optional gas controls may require routing of bleeds and vents to the atmosphere, outside the building when required by local codes.
Gas connection
All gas connections must be made with pipe joint compound resistant to the action of liquefied petroleum (L.P.) and natural gases. All piping must comply with local codes and ordinances. Piping installations must comply with approved standards and practices.
1. Make sure gas line is a separate line direct from the meter unless the existing gas line is of sufficient capacity. Verify pipe size with your gas supplier.
USE WRENCH TO HOLD SUPPLY PIPE
UNION
COUPLING
12"
MIN
2. The appliance must be isolated from the gas supply piping system by closing a manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.5 kPa).
3. The appliance and its gas connection must be leak tested before placing it in operation.
Gas piping
To safely operate this unit, you must properly size the gas supply piping. See Tables 3B through 3D for piping and fitting requirements. Gas pipe size may be larger than heater connection.
For ease of service, install a union.
MANUAL MAIN SHUT OFF VALVE
NIPPLE
CAP
Figure 3-1_Gas Line Connection
NOTICE
If an inline high gas pressure regulator is used, it MUST BE of the lockup type and be located a minimum of 10 feet from the appliance. Failure to do so may result in insufficient gas volume supplied to the appliance.
31
Page 32
3 Gas connections
Installation & Operation Manual
2. Use new, properly threaded black iron pipe free from chips. If you use tubing, make sure the ends are cut square, deburred and clean. Make all tubing bends smooth and without deformation. Avoid flexible gas connections. Internal diameter of flexible lines may not provide unit with proper volume of gas.
3. Install a manual main gas shutoff valve at the unit’s gas inlet, outside of the unit.
4. Run pipe or tubing to the unit’s gas inlet. If you use tubing, obtain a tube to pipe coupling to connect the tubing to the unit’s gas inlet.
5. Install a sediment trap in the supply line to the unit’s gas inlet (see FIG. 3-1).
6. Apply a moderate amount of good quality pipe compound (do not use Teflon tape) to pipe only, leaving two end threads bare.
7. Remove seal over gas inlet to unit.
8. Connect gas pipe to inlet of unit. Use wrench to support gas manifold on the unit.
9. For L.P. gas, consult your L.P. gas supplier for expert installation.
10. Ensure that all air is completely bled from the gas line before starting the ignition sequence. Start up without properly bleeding air from the gas line may require multiple reset functions of the ignition control module to achieve proper ignition.
Do not have any open flame in proximity to
WARNING
the gas line when bleeding air from the gas line. Gas may be present.
Gas train and controls
NOTICE
COMBINATION VALVE
The gas train and controls assembly provided on this unit have been tested under the applicable American National Standard to meet minimum safety and performance criteria such as safe lighting, combustion and safety shutdown operation.
402 MODEL
TABLE 3B
SUGGESTED GAS PIPE SIZE FOR
SINGLE UNIT INSTALLATIONS
MODEL
Distance from Meter (in feet)
0 - 50 51 - 100 101 - 200 201 - 300 301 - 500
402 1 1/4" 1 1/4" 1 1/2" 2" 2" 502 1 1/4" 1 1/2" 2" 2" 2 1/2"
652 1 1/2" 2" 2" 2 1/2" 2 1/2" 752 1 1/2" 2" 2" 2 1/2" 3"
992 2" 2" 2 1/2" 2 1/2" 3" 1262 2" 2 1/2" 2 1/2" 3" 3" 1442 2 1/2" 2 1/2" 3" 3" 3 1/2" 1802 2 1/2" 3" 3" 3 1/2" 3 1/2"
2072 2 1/2" 3" 3" 3 1/2" 4"
For each elbow or tee, add equivalent straight pipe to total length from Table 3C.
TABLE - 3C
FITTINGS TO EQUIVALENT STRAIGHT PIPE
Diameter
Pipe
3/4 1 1 1/4 1 1/2 2 3 4 5
(inches)
Equivalent
length of
Straight Pipe
22345101420
(feet)
Water heater models do not have downstream test valves, but the rest of the gas train is represented by FIG. 3-2.
Combination gas valves
These units fire in multiple stages of burner input. Each stage of burner operation has a combination gas valve(s) to cycle the gas supply on and off and regulate gas to the burners. Each combination valve consists of a gas regulator and two valve seats to meet the requirements for redundant gas valves. The valve has a gas control knob that must remain in the open position at all times when the unit is in service. The gas control valve has pressure taps located on the inlet and discharge sides of the valve. Manifold pressure is adjusted using the regulator located on the valve. A manifold gas pressure tap for each burner stick is located on the discharge side of the valve.
2072 MODEL
TO BURNERS
DOWNSTREAM TEST VALVE
TO BURNERS
COMBINATION VALVE
DOWNSTREAM TEST VALVE
Figure 3-2_Typical Boiler Gas Train Drawing
32
The manifold pressure is preset at the factory and adjustment is not usually required. If you must adjust regulator pressure, follow the instructions in the Copper-fin II Service Manual.
Venting of combination gas valves
The combination gas valve/regulator used on all units is equipped with an integral vent limiting orifice per ANSI Z21.78. The vent limiter ensures that the volume of gas emitted from the valve in the event of a failed gas diaphragm does not exceed the maximum safe leakage rate allowed by agency requirements.
Page 33
3 Gas connections (continued)
Combination gas valve/regulators equipped with integral vent limiters are not required to have vent or relief lines piped to the outdoors. The termination of the vent limited opening on the combination gas valve/regulator complies with the safety code requirements of CSD-1, CF-190(a) as shipped from the appliance manufacturer without the installation of additional vent lines.
Checking gas supply pressure
Use the following procedure to check gas supply pressure.
1. Turn the main power switch to the “OFF” position.
2. Turn gas valve knobs to the “OFF” position.
3. Shut off gas supply at the field-installed manual gas cock in the gas piping to the unit. If fuel supply is L.P. gas, shut off gas supply at the tank.
4. Remove the 1/8" hex plug, located on the “inlet” side of the gas valve. You may also use a tapping on the field-installed main manual gas cock or gas piping. Install a fitting in the inlet pressure tapping suitable to connect to a manometer or magnehelic gauge. Range of scale should be 14" w.c. or greater to check inlet pressure.
5. Turn on gas supply at the manual gas cock, turn on L.P. gas at the tank if required.
6. Turn the power switch to the “ON” position.
7. Turn the gas valve knobs to the “ON” position. Set the electronic temperature control or thermostat to call for heat.
8. Observe the gas supply pressure as all burners are firing. Ensure that inlet pressure is within the specified range. See Connecting To Gas Supply, page 31 for minimum and maximum gas supply pressures.
9. If gas pressure is out of range, contact gas utility, gas supplier, qualified installer or service agency to determine necessary steps to provide proper gas pressure to the control.
10. If gas supply pressure is within normal range, turn the power switch to the “OFF” position.
11. Turn gas valve knobs to the “OFF” position.
12. Shut off gas supply at the manual gas cock in the gas piping to the unit. If fuel supply is L.P. gas, shut off gas supply at the tank.
Installation & Operation Manual
13. Remove the manometer and related fitting from the “inlet” side of the gas valve, replace 1/8" hex plug in gas valve and tighten.
14. Turn on gas supply at the manual valve, turn on L.P. gas at the tank if required.
15. Turn the power switch to the “ON” position.
16. Turn the gas valve knob to the “ON” position.
17. Set the electronic temperature control or thermostat to call for heat.
WARNING
Check burner performance by cycling the system while you observe burner response. Burners should ignite promptly. Flame pattern should be stable, see Burner Flames in the Copper-fin II Service Manual. Turn system off and allow burners to cool, then cycle burners again to ensure proper ignition and flame characteristics.
Figure 3-3_Measuring Gas Supply Pressure at Combination Gas Valve
After completing any testing on the gas system, leak test all gas connections. Apply a soap/water solution to all gas connections while main burners are operating. Bubbles forming indicate a leak. Repair all leaks at once. Do not operate this unit with a leak in the gas train, valves or related piping.
MANOMETER
SUPPLY INLET PRESSURE TAP
GAS VALVE CONTROL KNOB
INLET
OUTLET
TABLE - 3D
GAS PIPING SIZE CHART
Nominal
Iron Pipe
Size
Inches
3/4 369 256 205 174 155 141 128 121 113 106 95 86 79 74
1 697 477 384 328 292 267 246 256 210 200 179 164 149 138
1 1/4 1,400 974 789 677 595 543 502 472 441 410 369 333 308 287
1 1/2 2,150 1,500 1,210 1,020 923 830 769 707 666 636 564 513 472 441
2 4,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974 871 820
2 1/2 6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 1,300
3 11,200 7,900 6,400 5,400 4,870 4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340
4 23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720
10 20 30 40 50 60 70 80 90 100 125 150 175 200
Length of Pipe in Straight Feet
Maximum Capacity of Pipe in Thousands of
Btu/hr per hour
for gas pressures
of 14 Inches
Water Column
(0.5 PSIG) or less
and a pressure
drop of 0.5 Inch
Water Column
(Based on NAT
GAS, 1025 Btu/hr
per Cubic Foot
of Gas and 0.60
Specific Gravity)
33
Page 34
4 Water connections
Installation & Service Manual
Inlet and outlet connections
For ease of service, install unions on the water inlet and water outlet of the unit. The connection to the unit marked “Inlet” on the header should be used for return from the system. The connection on the header marked “Outlet” is to be connected to the supply side of the system.
2" NPT WATER INLET
2" NPT WATER OUTLET
INSPECTION PLUGS
Figure 4-1_Water Connections - Models 402 - 752
2-1/2" NPT WATER INLET
2-1/2" NPT WATER OUTLET
Initial set-up of maximum water flow
On initial start-up of the Copper-fin II, the maximum water flow to the heat exchanger must be checked and manually limited with a valve or bypass before normal operation begins.
CAUTION
An appliance allowed to operate at return temperatures below the specified minimum setting may experience problems with the operating controls, safety switches, obstruction of the flue gas passages on the heat exchanger, incomplete combustion and possible flue gas spillage. Sustained operation at lower than specified water temperatures (140°F) may cause hazardous conditions that may result in personal injury or non-warrantable damage to the appliance.
Water flow switch
A water flow switch is factory installed in the outlet on all heating boilers and water heaters. The flow switch must prove water flow before a trial for ignition can begin. The flow switch requires a minimum flow of 15 - 18 GPM on Models 402 - 752 and 26 GPM on Models 992 - 2072 to make the flow switch and start burner operation. A water flow switch meets most code requirements for a low water cutoff device on boilers requiring forced circulation for operation. A fault message, Flow Sw/ LWCO will be indicated in the Operator Interface on a low water flow condition as sensed by the flow switch.
Low water cutoff (if equipped)
INSPECTION PLUGS
Figure 4-2_Water Connections - Models 992 - 2072
Heat exchanger
This appliance uses a finned copper tube heat exchanger to maximize the heat transfer process. The heat exchanger is mounted in the inner jacket of the appliance. A series of “V” shaped baffles are installed between the individual tubes to control the movement of the flue products over the finned copper surface and increase heat transfer. Water enters the heat exchanger and makes two passes over the area exposed to direct heat from the burner. A circulating pump MUST be installed to ensure proper water flow over the heat transfer surfaces during burner operation. Water temperatures in the heat exchanger are determined by water flow.
If this boiler is installed above radiation level, a low water cutoff device must be installed at the time of boiler installation. An electronic low water cutoff is available as a factory supplied option on all models. The low water cutoff should be inspected every 6 months. A fault message, Flow Sw/LWCO will be indicated in the Operator Interface on a low water condition as sensed by the low water cutoff.
34
Page 35
4 Water connections (continued)
Installation & Operation Manual
Relief valve
This unit is supplied with a relief valve(s) sized in accordance with ASME Boiler and Pressure Vessel Code, Section IV (“Heating Boilers”). The relief valve(s) is installed in the vertical position and mounted in the hot water outlet. No valve is to be placed between the relief valve and the unit. To prevent water damage, the discharge from the relief valve shall be piped to a suitable floor drain for disposal when relief occurs. No reducing couplings or other restrictions shall be installed in the discharge line. The discharge line shall allow complete drainage of the valve and line. Relief valves should be manually operated at least once a year.
CAUTION
Avoid contact with hot discharge water.
Heating boiler installations
Piping of the boiler system
The drawings in this section show typical boiler piping installations, see FIG.’s 4-3 through 4-6. Before beginning the installation, consult local codes for specific plumbing requirements. The installation should provide unions and valves at the inlet and outlet of the boiler so it can be isolated for service. An air separation device must be supplied in the installation piping to eliminate trapped air in the system. Locate a system air vent at the highest point in the system. The system must also have a properly sized expansion tank installed. Typically, an air charged diaphragm-type expansion tank is used. The expansion tank must be installed close to the boiler and on the suction side of the system pump to ensure proper operation.
CAUTION
Hot water piping must be supported by suitable hangers or floor stands, NOT by the boiler. Copper pipe systems will be subject to considerable expansion and contraction. Rigid pipe hangers could allow the pipe to slide in the hanger resulting in noise transmitted into the system. Padding is recommended on rigid hangers installed with a copper system. The boiler pressure relief valve must be piped to a suitable floor drain. See the Relief Valve section on this page.
CAUTION
Water connections (heating boilers only)
Models 402 - 752 have 2" NPT inlet and outlet connections and Models 992 - 2072 have 2 1/2" NPT inlet and outlet connections.
CAUTION
The boiler system should not be operated at less than 12 PSIG.
A leak in a boiler “system” will cause the “system” to intake fresh water constantly, which will cause the tubes to accumulate a lime/scale build up. This will cause a non­warrantable failure.
Field installed reducing bushings must not be used.
Any reduction in pipe size may decrease flow resulting in high water temperatures, boiler noise, flashing to steam, and non­warrantable heat exchanger damage.
The boiler may be installed with a primary/secondary piping system provided to the boiler. It is important to guarantee that adequate flow is provided to properly dissipate heat from the boiler and also ensure that flow through the boiler does not exceed the maximum recommended flow rate of 55 GPM for Models 402 - 752 and 90 GPM for Models 992 - 2072 for a boiler equipped with a copper heat exchanger.
Boiler circulator requirements
This is a low mass, high efficiency hot water boiler which must have adequate flow for quiet, efficient operation. Pump selection is critical to achieve proper operation. A pump should be selected to achieve proper system design water temperature rise. Pipe diameter and length are critical to ensure proper flow through the boiler. A System Temperature Rise Chart (Table 4C on page 38) is provided to assist in proper pump selection. This table provides GPM and boiler head-loss at various temperature rises for each model based on Btu/hr input. Temperature rise is the difference in boiler inlet temperature and boiler outlet temperature while the boiler is firing at full rate.
Example: The boiler inlet temperature is 160°F (71.1°C) and the boiler outlet temperature is 180°F (82.2°C). This means that there is a 20°F (11.1°C) temperature rise across the boiler. The boiler temperature rise is visible in the Operator Interface on the boiler’s front control panel.
Circulator pump specifications
1. Maximum operating pressure for the pump must exceed system operating pressure.
2. Maximum water temperature should not exceed the nameplate rating.
3. Cast iron circulators may be used for closed loop systems.
4. A properly sized expansion tank must be installed near the boiler and on the suction side of the pump.
Circulator pump operation (heating boilers only)
The boiler pump must run when the boiler is firing. Separate supply circuits can be provided or the two circuits (pump and controls) can be combined for connection to one circuit, properly sized for both.
Pump delay operation
A pump delay operation feature is provided. The boiler’s circulating pump will cycle on at each call for heat, before the burner fires. The pump will continue to operate while the burner is firing. The pump will run for a 30 second period after the temperature set point is satisfied. This timing is selectable from the Operator Interface. This timing will remove any of the residual heat from the combustion chamber before turning the pump off. See the wiring diagram in Section 9 of this manual.
35
Page 36
4 Water connections
Installation & Service Manual
Pump Maintenance: Inspect the pump every six (6) months
and oil as necessary. Use SAE 30 non-detergent oil or lubricant specified by the pump manufacturer.
The boiler is recommended for installation in a primary/ secondary piping system. This type of system uses a separate
boiler circulating pump to supply flow to and from the boiler only. The secondary pump is sized based on the head loss of the boiler and related pipe and fittings in the secondary loop only.
A properly sized primary system pump provides adequate flow to carry the heated boiler water to radiation, air over coils, etc. The fittings that connect the boiler to the primary system should be installed a maximum of 12 inches (0.30m) (or 4 pipe diameters) apart to ensure connection at a point of zero pressure drop in the primary system. There should be a minimum of 10 pipe diameters of straight pipe before and after the boiler secondary loop connections to prevent turbulent flow at the secondary loop connections. The secondary loop piping to and from the boiler must have a fully ported ball valve installed in both the supply and return side piping. The ball valves must be fully ported having the same inside diameter as the installed piping. The ball valve in the piping supplying water to the boiler will only be used as a service valve. The ball valve installed in the discharge from the boiler back to the primary system will be used to adjust boiler flow and temperature rise to ensure proper performance.
The boiler primary piping system must have a circulator installed in the main system loop to carry the heated boiler water to the point of use in the main system.
Multiple boilers may also be installed with a primary/secondary manifold system. Multiple boilers should be connected to the common manifold in reverse return to assist in balancing flow to multiple boilers.
The installer must ensure that the boiler has adequate flow without excessive temperature rise. Low system flow can result in overheating of the boiler water which can cause short burner cycles, system noise, relief valve discharge and in extreme cases, a knocking flash to steam. These conditions indicate the need to increase boiler flow to and from the boiler. This is generally accomplished by either increasing the size of the boiler pump or by increasing the diameter of the piping that connects the boiler to the primary system. A larger diameter pipe reduces head loss and increases flow.
CAUTION
At no time should the system pressure be less than 12 PSIG.
Minimum boiler water temperatures
Inlet water temperatures below the specified minimum of 140°F (60°C) can excessively cool the products of combustion resulting in condensation on the heat exchanger. Condensation on the heat exchanger can cause operational problems, bad combustion, sooting, flue gas spillage and reduced service life of the related components. See the Low Temperature Bypass Requirements section for boiler system applications below the minimum specified temperature.
Low Temperature Return Water Systems
Any non-condensing boiler will develop operational problems when exposed to inlet water temperatures below 140°F. Lochinvar offers a low temperature protection valve (LTV) that is factory preset to maintain 140°F inlet water to the boiler regardless of the system return water temperature. See Table 4A for available valve kits.
TABLE 4A
LTV VALVE KITS
MODEL LTV VALVE KIT
402 - 752 VAL3048
992 - 2072 VAL3047
Low temperature bypass requirements
To prevent condensation problems, a boiler MUST NOT be operated (other than for brief periods during initial system startup) with an inlet water temperature of less than 140°F (60°C). If normal system return temperatures are less than the required 140°F (60°C) boiler inlet requirement, a method of low return water temperature protection MUST BE provided to protect the boiler.
For Example: Night Setback of the system loop water temperature, Night Shutdown and Weekend Shutdown of the entire boiler / heating system, and Indoor / Outdoor Air Reset of the system loop water temperature. If any of these control functions are being utilized, some type of low return water protection MUST BE provided.
If the boiler heating system will be used on a Water Source Heat Pump System, Radiant Floor Heating System, Snow Melting Heating System, etc., some type of low return water protection must be provided.
Condensation can cause operational problems, bad combustion, sooting, flue gas spillage and reduced service life of the vent system and related components.
To prevent system return water temperature below 140°F (60°C) from entering the boiler inlet, an electrically actuated 3-way mixing valve is available, consult manufacturer for kit availability (see FIG. 4-5 on page 41). By using this valve, the SMART SYSTEM control will bypass outlet water back into the inlet of the boiler to maintain the inlet temperature above 140°F (60°C).
A fast acting, self contained mixing valve, set to 140°F (60°C), may also be used. The installation of this valve must be done as shown in FIG. 4-5. This arrangement will maintain the required flow through the boiler.
36
Page 37
4 Water connections (continued)
Installation & Operation Manual
When a mixing valve is used, an optional system return sensor should be installed into the system return piping. This will allow the display of the actual system return temperature, and will also allow control of the system return temperature when the SMART SYSTEM control is programmed for inlet temperature control. As always, installation of the system supply sensor is strongly recommended as well. This will reduce the potential for short cycling of the boiler, and provide more responsive temperature regulation, even when the SMART SYSTEM control is programmed for inlet temperature control.
CAUTION
A boiler allowed to operate at set point temperatures below the specified minimum settings may experience operational problems with the operating controls and safety switches, obstruction of the flue gas passages on the heat exchanger, incomplete combustion and possible flue gas spillage. Operation at lower than specified water temperatures may cause hazardous conditions that result in non-warrantable damage to the appliance.
Three way valves in system
The installation of a three way valve on this boiler is not generally recommended because most piping methods allow
the three way valve to vary flow to the boiler. This boiler is a low mass, high efficiency appliance which requires a constant water flow rate for proper operation. Low flow rates can result in overheating of the boiler water which can cause short burner cycles, system noise, relief valve discharge and in extreme cases, a knocking flash to steam. These conditions can cause operational problems and non-warrantable failures of the boiler.
Radiant floor and snow melt heating systems
This type of heating boiler application operates in a low temperature range which requires a boiler bypass as described under the Low Temperature Bypass Requirements section. A non-metallic rubber or plastic tubing installed in a radiant (in floor) system must have an oxygen barrier to prevent oxygen from entering the system through the walls of the installed tubing. Excessive oxygen absorption into the system will result in an accelerated rate of corrosion causing a sludge buildup. This excessive corrosion will also damage the boiler and system components. Sludge formed as the result of excessive oxygen in the system can restrict water flow resulting in a premature boiler failure. Any boiler damage due to excessive oxygenation is non-warrantable.
TABLE - 4B
MAXIMUM FLOW FOR HEATING BOILER
The maximum flow rate through the boiler with a copper
heat exchanger must not exceed the following:
Model Maximum Flow
402, 502, 652, and 752 55 GPM
992, 1262, 1442, 1802, and 2072 90 GPM
If higher flow rates are required through the boiler, an optional Cupro-Nickel heat exchanger is available. Consult the factory for specific application requirements.
Low system water volume
System run time is very important to the overall operating efficiency of the boiler. Short cycling of the boiler creates problems with condensation in the vent stack, condensation on the heat exchanger, system temperature spikes, and mechanical component failures. To prevent short cycling of the boiler, it is important to limit the boiler cycles to six or fewer per hour.
A buffer tank is an effective way to enhance a small system load and increase heating system efficiency (see FIG. 4-6 on page 42 of this manual). Buffer tanks add water volume to the system and act as a flywheel to absorb the additional Btu’s provided by the boiler when only a single zone of a large system is calling for heat.
To calculate the proper buffer tank size for a multiple zone system:
(Run Cycle) (Output - Minimum System Load)
(Temp. Rise) (8.33) (60 Min.)
CFN2072
Min. Load = 100,000 Btu/Hr
Min. Boiler Output = 850,000 Btu/Hr
Cycle Time = 10 Min
Temp. Rise = 38
(10)(850,000 – 100,000) / (38)(8.33)(60) = 395 Gallons
37
Page 38
Installation & Service Manual
4 Water connections
TABLE - 4C
SYSTEM TEMPERATURE RISE CHART
Temperature Rise and Head Loss Based on Boiler Output in Btu/hr
Btu/hr 30°F T 35°F T 40°F T 45°F T 50°F T 55°F T 60°F T
Input Output GPM Ft/hd GPM Ft/hd GPM Ft/hd GPM Ft/hd GPM Ft/hd GPM Ft/hd GPM Ft/hd
399,999 339,999 23 1.1 19 0.7 -- -- -- -- -- -- -- -- -- --
500,000 425,000 28 1.6 24 1.2 21 0.7 19 0.7 -- -- -- -- -- --
650,000 552,500 37 3.0 31 2.2 28 1.6 24 1.2 22 0.9 20 0.7 18 0.6
750,000 637,500 42 4.1 36 2.8 32 2.3 28 1.6 25 1.3 23 1.1 21 0.7
990,000 841,500 55 2.6 48 2.3 42 1.5 37 1.4 33 1.0 30 0.9 28 0.9
1,260,000 1,071,000 71 4.4 61 3.6 53 2.7 48 2.3 42 1.7 39 1.5 35 1.2
1,440,000 1,224,000 81 6.3 70 5.0 61 3.8 54 2.7 48 2.3 44 2.0 40 1.8
1,800,000 1,530,000 102* 11.8 87 9.0 76 6.6 68 5.6 61 4.4 55 2.6 50 3.0
2,070,000 1,759,500 -- -- 100* 10.1 87 9.0 78 7.6 70 6.2 64 5.4 58 4.6
*Cupro-Nickel Heat Exchanger Required at Flows Above 55 GPM on Models 402 - 752 and above 90 GPM on Models 992 - 2072.
TABLE - 4D
BOILER TEMPERATURE RISE AT MAXIMUM FLOW
Temperature Rise at Full Rate Fire, 55 and 90 GPM
Maximum Flow
Model Temperature Rise °F
402 12 @ 55 GPM 502 15 @ 55 GPM
652 20 @ 55 GPM
752 23 @ 55 GPM
992 19 @ 90 GPM
1262 24 @ 90 GPM
1442 27 @ 90 GPM
1802 34 @ 90 GPM
2072 39 @ 90 GPM
Boiler bypass requirements
The installer must ensure that the boiler is supplied with adequate flow without excessive temperature rise. It is recommended that this boiler be installed with a bypass in the piping if the maximum recommended flow rate is exceeded. The bypass will help to ensure that the boiler can be supplied with adequate water flow. Flow rates exceeding the maximum recommended flow will result in erosion of the boiler tubes. A typical bypass with a valve as shown in FIG. 4-5 will allow control of boiler flow.
Temperature / pressure gauge
This boiler is equipped with a dial type temperature / pressure gauge. This gauge is factory installed in the outlet side of the boiler piping. The gauge has one scale to read system pressure and a separate scale to read water temperature in degrees Fahrenheit. The temperature / pressure gauge is provided to meet code requirements. Water temperatures can be more accurately monitored from the data provided in the digital display in the Operator Interface.
38
Typical heating boiler installations
General plumbing rules:
1. Check all local codes.
2. For serviceability of boiler, always install unions.
3. Always pipe pressure relief valve to an open drain.
4. Locate system air vents at highest point of system.
5. Expansion tank must be installed near the boiler and on the suction side of the system pump.
6. Support all water piping.
Installation with a chilled water system
Pipe refrigeration systems in parallel. Install duct coil downstream at cooling coil. Where the hot water heating boiler is connected to a heating coil located in the air handling units which may be exposed to refrigeration air circulation, the boiler piping system must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
The coil must be vented at the high point and hot water from the boiler must enter the coil at this point. Due to the fast heating capacity of the boiler, it is not necessary to provide a ductstat to delay circulator operation. Also, omit thermostat flow checks as the boiler is cold when heating thermostat is satisfied. This provides greater economy over maintaining standby heat.
DHW installation
Boilers may be utilized with a Hot Water Generator tank for domestic hot water. When used for DHW, either a tank thermostat or sensor must be installed in a bulbwell within the tank and connected back to the unit in order for the controller to regulate water temperature and a pump for DHW. Pumps used for DHW purposes should be sized to provide adequate flow to the boiler when in DHW Mode. Reference FIG. 4-3 shown with a Hot Water Generator for DHW on page 39 for a typical DHW piping scheme.
Page 39
4 Water connections (continued)
Figure 4-3_Primary/Secondary Piping of a Single Boiler w/DHW
Installation & Operation Manual
COMMON MANIFOLD SIZE (Min.)
Models: 402, 502, 652, & 752
Number of Units GPM
1552
Diameter
(in.)
TO FLOOR DRAIN
COMMON MANIFOLD SIZE (Min.)
Models: 992, 1262, 1442, 1802 & 2072
Number of Units GPM
1 90 2 1/2
TO EXPANSION TANK AND MAKEUP WATER SYSTEM
Diameter
(in.)
HEATING RETURN LOOP
NOTICE
12" MAX
HEATING
HOT WATER GENERATOR
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
SUPPLY LOOP
39
Page 40
4 Water connections
Figure 4-4_Primary/Secondary Piping of Multiple Boilers
Installation & Service Manual
COMMON MANIFOLD SIZE (Min.)
Models: 402, 502, 652, & 752
Number of Units GPM
2 110 3
3 165 3 1/2
4 220 4
5 275 5
6 330 5
7 385 6
8 440 6
MAKE-UP WATER
Diameter
PRESSURE
RELIEF
VALVE
(in.)
COMMON MANIFOLD SIZE (Min.)
Models: 992, 1262, 1442, 1802 & 2072
Number of Units GPM
2 180 4
3 270 5
4 360 6
5 450 6
6 540 6
7 630 8
8 720 8
EXPANSION TANK
LOW WATER CUT-OFF (OPTIONAL)
TO SYSTEM
Diameter
(in.)
AIR
SEPARATOR
FROM SYSTEM
12" OR 4X
PIPE DIAMETERS
SECONDARY
BOILER
PUMP
SYSTEM PUMP
NOTICE
40
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
Page 41
Installation & Operation Manual
4 Water connections (continued)
Figure 4-5_Boiler with Low Temperature Bypass Piping - Using a Low Temperature Valve Required for Systems Operating at less than 140°F (60°C) Return Water Temperatures from the Heating Return Loop
COMMON MANIFOLD SIZE (Min.)
Models: 402, 502, 652, & 752
Number of Units GPM
Diameter
(in.)
1552
COMMON MANIFOLD SIZE (Min.)
Models: 992, 1262, 1442, 1802 & 2072
Number of Units GPM
TO EXPANSION TANK AND MAKEUP WATER SYSTEM
MIXING VALVE
Diameter
(in.)
1 90 2 1/2
HEATING RETURN LOOP
HEATING SUPPLY LOOP
NOTICE
TO FLOOR DRAIN
12" MAX
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
41
Page 42
4 Water connections
Figure 4-6_Primary/Secondary Piping with Buffer Tank
Installation & Operation Manual
COMMON MANIFOLD SIZE (Min.)
Models: 402, 502, 652, & 752
Number of Units GPM
2 110 3
3 165 3 1/2
4 220 4
5 275 5
6 330 5
7 385 6
8 440 6
1" TEMPERATURE
AND PRESSURE
GAUGE
AUTOMATIC AIR
ELIMINATOR/VENT
Diameter
(in.)
COMMON MANIFOLD SIZE (Min.)
Models: 992, 1262, 1442, 1802 & 2072
Number of Units GPM
2 180 4
3 270 5
4 360 6
5 450 6
6 540 6
7 630 7
8 720 7
Diameter
(in.)
PUMP
SYSTEM
OUTLET
SYSTEM
SENSOR
LOCATION
SYSTEM
INLET
NOTICE
NOTICE
42
COMMOM MANIFOLD MUST BE SIZED TO ACCOMODATE COMBINED FLOW RATE FOR ALL BOILERS
BUFFER
TANK
The Inlet/Outlet System tappings are shown in the optional location on the side of the tank for pictorial purposes. The standard location for the system tappings is 180° from the recirculation tappings.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
DRAIN
Page 43
5 Electrical connections
Installation & Operation Manual
Boiler operating control module
The operating control for the appliance is the SMART SYSTEM control module. It is located on the inside of the control panel, behind the front access door. Access to adjust the temperature set point and other user adjustable points is made through the Operator Interface located on the front access door. The outlet sensor is installed in the outlet side of the heat exchanger top header. The inlet sensor is located on the inlet side of the heat exchanger top header.
The operating sensor, inlet or outlet, is selectable from the screen in the Operator Interface.
The exact temperature set point is based on the system’s requirements. Set the control set point(s) to the desired operating water temperature.
The maximum temperature set point that can be programmed into the control module from the Operator Interface on a heating boiler is 220°F (104.4°C). The manual reset high limit control for a heating boiler is adjustable up to a fixed maximum setting of 230°F (110°C).
The maximum temperature set point for a water heater is 190°F (88°C). The auto reset high limit is fixed at 200°F (93°C), and the adjustable manual reset high limit has a maximum setting of 230°F (110°C).
A 120 VAC, 15 Amp, 1 ph, 60 Hz circuit is required for operation of the appliance controls.
The appliance, when installed, must be electrically grounded in accordance with the requirements of the authority having jurisdiction or in the absence of such requirements, with the latest edition of the National Electrical Code ANSI/ NFPA No. 70. When the unit is installed in Canada, it must conform to the CAE C22.1, Canadian Electrical Code, Part I and/or local Electrical Codes. Multiple units connected in a Cascade must be grounded to the same ground connection.
TABLE - 5A
AMP DRAW DATA
Model Controls Blower
402 3.6 2.7 5.8 12.1
502 3.6 2.7 5.8 12.1
652 5.4 3.4 5.8 14.6
752 5.4 3.4 5.8 14.6
992 7.3 3.2 7.4 17.9
1262 7.3 3.2 7.4 17.9
1442 7.3 6.7 7.4 21.4 1802 7.3 6.7 7.4 21.4 2072 7.3 6.7 7.4 21.4
*Standard Pump Supplied with Water Heaters Only
WARNING
NOTICE
CAUTION
ELECTRICAL SHOCK HAZARD – For your safety, turn off electrical power supply before making any electrical connections to avoid possible electric shock hazard. Failure to do so can cause severe personal injury or death.
Wiring must be N.E.C. Class 1.
If original wiring as supplied with the boiler must be replaced, use only type 105°C wire or equivalent.
Boiler must be electrically grounded as required by National Electrical Code ANSI/ NFPA 70 – latest edition.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Pump
FLA*
Approximate Total
Amps @ 120 VAC
Installation must comply with:
1. All wiring between the appliance and field installed devices shall be made with type T wire [63°F (35°C) rise].
2. All line voltage wire exterior to the appliance must be enclosed in approved conduit or approved metal clad cable.
3. The circulating pump must run continuously when the appliance is being fired.
4. To avoid serious damage, DO NOT energize the appliance until the system is full of water. Ensure that all air is removed from the heat exchanger and piping before beginning initial operation. Serious damage may result if the appliance is operated without proper flow.
5. Provide the appliance with proper overload protection.
1. National Electrical Code and any other national, state, provincial, local codes, or regulations.
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and any local codes.
43
Page 44
5 Electrical connections
Installation & Operation Manual
Line voltage connections
1. Connect 120 VAC power wiring to the line voltage terminal strip in the junction box, as shown in FIG. 5-1.
2. Provide and install a fused disconnect or service switch (15 AMP recommended) as required by the code (see FIG. 5-1).
3. To activate a system pump, wire as shown in FIG. 5-1. If the motor is larger than 1 HP, you must install a contactor.
4. When connecting power to units which are to be cascaded, each unit must be connected to the same ground connection.
BOILER ONLY
SUPPLY
BOILER
PUMP
SYSTEM
PUMP SUPPLY
D I S C O N N E C T
SYSTEM
PUMP
DHW PUMP
SUPPLY
D I S C O N N E C T
DHW PUMP
UNIT PUMP
UNIT
SUPPLY
LNG LNG LNG LNG
D
D I
I
S
S
C
C
O
O
N
N
N
N
E
E
C
C
T
T
EMS or remote thermostat connection
An EMS, remote thermostat or other remote temperature control may be connected to the boiler (see FIG. 5-3). Follow the manufacturer’s instructions supplied with the remote temperature control for proper installation and adjustment. Connection of a set of dry switching contacts or a remote on/off thermostat to the low voltage connection board will allow the unit to be switched on and off by making or breaking a 24 VAC control circuit. Remove the factory jumper between the Staging S1 terminals on the low voltage connection board and connect the remote temperature control in its place, see FIG. 5-4 on page 46.
Ensure that all wiring used to connect the switching contacts of the remote temperature controller to the connection board are a minimum of 18 gauge and have a maximum installed length of 300 feet (91.4m). Set the SMART SYSTEM control to a set point temperature slightly higher than the setting of the remote temperature control. This will ensure that the remote temperature controller functions as the operating control for the heater.
120V
120V
RELAY
LN
120V
SUPPLY
GROUND SPLICE
1 HP MAX
UNIT
PUMP
SYSTEM
RELAY COIL
R
PUMP
RELAY
R
DHW
PUMP
RELAY COIL
CHASSIS GROUND
LBL20175 REV A
Figure 5-1_Line Voltage Field Wiring Connections
Low voltage connections
1. Route all low voltage wires through the knockouts on the left side of the heater, as shown in FIG. 5-2.
2. Connect low voltage wiring to the low voltage connection board as shown in FIG. 5-4 on page 46 of this manual and the heater wiring diagram.
LOW VOLTAGE KNOCKOUTS
REMOTE ON/OFF CONNECTION
Figure 5-3_Remote ON/OFF Wire Connection
DHW (Domestic Hot Water) thermostat
Connect the DHW tank thermostat (FIG. 5-4) to the tank thermostat terminals on the connection board.
LINE VOLTAGE KNOCKOUTS
Figure 5-2_Routing Field Wiring
44
DHW tank sensor
If a tank sensor is used, it must be connected to the tank sensor terminals on the low voltage connection board. The correct Lochinvar sensor (TST20015) MUST BE USED.
Page 45
5 Electrical connections (continued)
Installation & Operation Manual
Louver relay
When the heater is to control combustion air louvers, a field provided 24VAC louver relay must be installed. Connect
the Louver Relay Coil terminals to the louver relay coil.
Louver proving switch
The operation of a louver proving switch needs to be verified before the boiler fires. Remove the jumper wire from these terminals and connect them to the normally open contacts on its proving switch (FIG. 5-4).
System supply sensor (recommended use)
1. By installing the system supply sensor into the supply of the primary loop, the temperature of the primary supply can be controlled. The SMART SYSTEM control automatically detects the presence of this sensor, and controls the boiler firing rate to maintain the system supply temperature to the set point (if the outlet sensor control is currently selected).
2. Connect these terminals to the system supply sensor (FIG. 5-4).
System return sensor (optional use)
1. By installing the system return sensor into the return of the primary loop, the temperature of the primary return can be sensed when a 3-way valve or other device is installed ahead of the heater inlet. The SMART SYSTEM control automatically senses the presence of this sensor. If the inlet sensor is selected as the controlling sensor, the SMART SYSTEM control will adjust the firing rate to hold the system return temperature to the set point. It is strongly recommended that the system supply sensor be installed as well.
2. Connect these terminals to the system return sensor (FIG. 5-4).
Boiler Management System (BMS)
Runtime contacts
The SMART SYSTEM control closes a set of dry contacts whenever the burner is running. This is typically used by Building Management Systems to verify that the boiler is responding to a call for heat.
3-way valve out
An electric 3-way mixing valve may be used when the return temperature to the heater is less than 140°F (60°C). Connect the Open output to the Open terminal on the 3-way valve. Connect the Close output to the Close terminal on the valve and the COM output to the 24VAC terminal on the valve.
0 - 10V rate out
A 0 - 10VDC signal is available to allow a Building Management System (BMS) to monitor the firing rate of the heater. Make sure the (-) terminal is connected to the (-) or common terminal of the external control, and the (+) terminal is connected to the (+) or Vdc terminal of the external control.
0 - 10V system pump in
A 0 - 10VDC input is available so that the boiler can monitor the speed of a variable speed system pump. This allows the boiler to anticipate changes in the heat load as the system flow changes. Connect the (-) terminal to the (-) or common terminal on the system pump VFD drive, and the (+) terminal to the (+) or 0 ­10VDC terminal on the system pump VFD drive. A 0 - 020mA signal may also be used, by adding a 500 ohm resistor between the (+) and (-) terminals.
Sequencer
The individual stages in the heater can be controlled separately with an external sequencer. Connect the Staging S1 terminals to the first stage contacts on the sequencer, the Staging S2 terminals to the second stage contacts, and so forth. Note that the sequencer must enable the stages in order, with Stage 1 first, Stage 2 second and so on.
1. An external control may be connected to control either the firing rate or the set point of the appliance (boiler or water heater). Connect the 0 - 10 VDC terminals to the 0 - 10 VDC output of the external control. The SMART SYSTEM control can be programmed to use the enable output of the Boiler Management System, or use the voltage signal to enable the heater. Connect the Staging S1 or tank thermostat terminals to the enable output of the BMS, when used.
2. Make sure the ground terminal is connected to the ground output terminal of the external control, and the 0 - 10 V BMS IN terminal is connected to the 0 - 10 VDC terminal of the external control.
Alarm contacts
The SMART SYSTEM control closes another set of contacts whenever the heater is locked out or the power is turned off. This can be used to turn on an alarm, or signal a Building Management System that the boiler is down.
45
Page 46
5 Electrical connections
Installation & Operation Manual
Wiring of the cascade
When wiring the heaters for Cascade operation, select one heater as the Leader. The remaining heaters will be designated as Members. See page 50 Configuration of the Cascade for a detailed explanation of this procedure.
On boilers, connect the system supply sensor and outdoor air sensor (if used) to the Leader boiler. The location of the system supply sensor should be downstream of the boiler connections in the main system loop (FIG.’s 4-3 and 4-6). The system supply sensor should be wired to the low voltage connection board at the terminals marked for the system supply sensor (see FIG. 5-4). The Leader control will use the water temperature at the system supply sensor to control the operation of the Cascade.
If outdoor air reset is desired, the outdoor air sensor should be wired to the low voltage connection board at the terminals marked for the outdoor air sensor (FIG. 5-4). If the outdoor air sensor is connected, the Leader control will calculate the water temperature set point based on the programmed reset curve parameters. If the outdoor air sensor is not connected, the Leader control will maintain the space heating (SH) set point that is programmed into the control.
If a Thermostat, Zone Control enable output, or Building Management System enable output are available, it should be wired to the low voltage connection board on the Leader boiler at the Staging S1 terminals. If the boilers are to run continuously, leave the jumper wire between these terminals. This will initiate a call for heat on the Cascade. Also, leave the jumpers on the Staging S1 terminals of all the Member heaters. This will allow them to run independently should the Leader heater fail.
Figure 5-4_Low Voltage Field Wiring Connections
1
TO MONITORING DEVICE
TO MONITORING DEVICE
THREE WAY
VALVE
LOUVER PROVING SWITCH
LINE TO LOUVER
DHW TANK THERMOSTAT
10K-TANK SENSOR
FROM PREVIOUS HEATER
TO NEXT HEATER
EXTERNAL SEQUENCER/ BUILDING AUTOMATIC CONTROL
A
B
A
B
EXTERNAL
STAGING
SEQUENCER
S1
S2
S3
S4
ALARM
CONTACTS
2
RUN-TIME
3
CONTACTS
4
OPEN
5
CLOSE
6
COM
7
S1
8
S1
9
S2
10
S2
11
S3
12
S3
13
S4
14
S4
15
LOUVER
16
PROVING SW
17
LOUVER
18
RELAY COIL
19
TANK
20
AQUASTAT
21
CN3
TANK
22
SENSOR
23
SHIELD
24
A
25
B
26
SHIELD
27
+ 0-10V
28
29
- BMS IN
+ 0-10V
30
- RATE OUT
31
SHIELD
32
A
33
B
34
SHIELD
35
CN2
Y
E
A
V L
W
A
­3
V
G N
I G A T S
E D A C S A C
S U B D O M
On water heaters, connect the tank thermostat or BMS enable output to the low voltage connection board on the Leader heater, at the terminals marked for the tank Aquastat. If a tank sensor is used, connect this sensor to the low voltage connection board on the Leader heater, at the terminals marked for the tank sensor.
Communication between the Leader heater and the Member heaters is accomplished by using shielded, 2-wire twisted pair communication cable. Connect one of the twisted pair wires to terminal A on each of the low voltage connection boards, and the other wire of the twisted pair to terminal B on each of the low voltage connection boards. Connect the shield wire to the shield ground terminal on all of the heaters. If more than two heaters are on the Cascade, daisy chain the wiring from the Cascade terminals on the second heater to the Cascade terminals on the third heater, then from the third to the forth, and so on. The connections can be made in any order, regardless of the addresses of the heaters. Try to keep each cable as short as possible.
OUTDOOR AIR SENSOR
SYSTEM SUPPLY SENSOR
SYSTEM RETURN SENSOR
PUMP SPEED INPUT
0-10VDC
COMMON
(BOILER ONLY)
OUTDOOR
SENSOR
SYS SUPPLY
SENSOR
SYS RETURN
SENSOR
+ 0-10V SYS
- PUMP IN
CN2
46
Page 47
6 Start-up
Installation & Operation Manual
Check/control water chemistry
CAUTION
Hardness less than 7 grains
1. Consult local water treatment companies for hard
water areas (above 7 grains hardness).
Chlorine concentration less than 200 ppm
1. Do not fill boiler or operate with water containing
chlorine in excess of 200 ppm.
2. Filling with chlorinated fresh water should be acceptable
since drinking water chlorine levels are much lower.
3. Do not use the boiler to directly heat swimming pool or
spa water.
Test/replace freeze protection fluid
1. For systems using freeze protection fluids, follow fluid
manufacturer’s instructions.
2. Freeze protection fluid must be replaced periodically
due to degradation of inhibitors over time. Follow all fluid manufacturer’s instructions.
Do not use petroleum-based cleaning or sealing compounds in the boiler system. Damage to elastomer seals and gaskets in the system could occur, resulting in substantial property damage.
Freeze protection (when used)
1. Determine freeze protection fluid quantity using system water content, following fluid manufacturer’s instructions. Appliance water content is listed on page
8. Remember to include expansion tank water content.
2. Local codes may require a backflow preventer or actual disconnect from city water supply.
3. When using freeze protection fluid with automatic fill, install a water meter to monitor water makeup. Freeze protection fluid may leak before the water begins to leak, causing concentration to drop, reducing the freeze protection level.
Fill and test water system
1. Fill system only after ensuring the water meets the
requirements of this manual.
2. Close manual and automatic air vents and boiler drain
valve.
3. Fill to correct system pressure. Correct pressure will
vary with each application.
a. The minimum cold water fill pressure should be
12 PSI.
b. Pressure will rise when boiler is turned on and
system water temperature increases.
4. At initial fill and during boiler startup and testing,
check system thoroughly for any leaks. Repair all leaks before proceeding further.
WARNING
Eliminate all system leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in the heat exchanger, reducing heat transfer, overheating the heat exchanger, and causing heat exchanger failure.
Purge air from water system
1. Purge air from system: a. Connect a hose to the purge valve (see purge/drain
valves, in the piping diagrams on pages 39 - 42). Route the hose to an area where water can drain and be seen.
b. Close the boiler or system isolation valve between
the purge valve and fill connection to the system. c. Close zone isolation valves. d. Open quick-fill valve on cold water makeup line. e. Open purge valve. f. One zone at a time, open the isolation valves. Allow
water to run through the zone, pushing out the air.
Run until no noticeable air flow is present. Close the
zone isolation valves and proceed with the next zone.
Follow this procedure until all zones are purged. g. Close the quick-fill water valve and purge valve and
remove the hose. Open all isolation valves. Watch
that system pressure rises to correct cold-fill
pressure. h. After the system has operated for a while, eliminate
any residual air by using the manual air vents located
throughout the system. i. If purge valves are not installed in the system, open
the manual air vents in the system one at a time,
beginning with the lowest floor. Close the vent when
water squirts out. Repeat with remaining vents.
2. Open automatic air vent (diaphragm-type or bladder-type
expansion tank systems only) one turn.
3. Open other vents: a. Starting on the lowest floor, open air vents one at a
time until water squirts out. b. Repeat with remaining vents.
4. Refill to correct pressure.
Check for gas leaks
WARNING
WARNING
Before starting the boiler, and during initial operation, smell near the floor and around the boiler for gas odorant or any unusual odor. Remove the front access panel and smell the interior of the boiler enclosure. Do not proceed with startup if there is any indication of a gas leak. Use an approved leak detection solution. Repair any leaks at once.
Propane boilers only – Your propane supplier mixes an odorant with the propane to make its presence detectable. In some instances, the odorant can fade, and the gas may no longer have an odor. Before startup (and periodically thereafter), have the propane supplier verify the correct odorant level in the gas.
47
Page 48
6 Start-up
Installation & Operation Manual
Check thermostat circuit(s)
1. Disconnect the two external wires connected to the enable terminals on the connection board.
2. Connect a voltmeter across these two incoming wires. Close each thermostat, zone valve, and relay in the external circuit one at a time and check the voltmeter reading across the incoming wires.
3. There should NEVER be a voltage reading.
4. If a voltage does occur under any condition, check and correct the external wiring. (This is a common problem when using 3-wire zone valves.)
5. Once the external thermostat circuit wiring is checked and corrected if necessary, reconnect the external thermostat circuit wires to the connection board. Allow the boiler to cycle.
Check vent and air piping
Inspect vent piping and air piping for signs of deterioration from corrosion, physical damage or sagging. Verify air piping and vent piping are intact and correctly installed per this manual.
Placing the boiler in operation
Boiler operational checks
1. Turn the boiler main power switch to the “ON”
position.
2. Verify operation of the SMART SYSTEM control
module and Operator Interface.
3. Program the adjustable points from the Operator
Interface.
4. Push the reset for the low water cutoff (if equipped).
5. Ensure that maximum flow to the boiler does not exceed
55 GPM on Models 402 - 752 and 90 GPM on Models 992 - 2072. Verify by checking temperature rise while burner is firing at 100% of rated input.
6. Install a manometer on the gas supply to the boiler and
verify minimum gas supply pressure as the burner fires at 100% of rated input.
7. Verify operation of safeties as necessary (low water
cutoff, high limit, gas pressure, etc.,).
8. Verify that all adjustable points in the Operator
Interface are set as required.
9. Once the boiler analysis is complete, test the safety shutoff
device by turning the manual shutoff valve to the OFF position and ensuring that the boiler shuts down and registers an alarm. Open the manual shutoff valve and reset the control.
10. Place the boiler back into normal operation.
Boiler operation
11. Boiler should begin the start-up process for the
sequence of operation.
12. The boiler will ignite at the proper ignition speed and
will stage to meet the system demand.
13. Ensure that inlet water temperature does not fall below
the specified minimum for the boiler.
14. Based on system demand, boilers may run for an
extended period of time at a reduced rate of input to maximize efficiency.
48
15. As system demand is satisfied, the burner will cycle off and the combustion air blower will run for a post purge operation before the boiler shuts down.
Start the boiler
Read and follow the Lighting Instructions in FIG. 6-1, on page
49.
If boiler does not start correctly
1. Check for loose connections, blown fuse or service switch off?
2. Is external limit control (if used) open? Is boiler water temperature above 200°F (93.3°C)?
3. Is thermostat set below room temperature?
4. Is gas turned on at meter or boiler?
5. Is incoming gas pressure less than 4.5" water column?
If none of the above corrects the problem, refer to the Troubleshooting Section of the Copper-fin II Service Manual.
WARNING
The venting system must be installed so that it will prevent flue gas spillage and carbon monoxide emissions, which will result in severe personal injury or death.
Set space heating operation (boiler only)
Determine controlling sensor
For space heating systems, the temperature control can be based on one of four sensors; the inlet, outlet, system supply sensor, or system return sensor. The SMART SYSTEM control is programmed at the factory to control the temperature of the outlet sensor. The control will automatically switch to the system supply sensor once it is connected. If it is desired to base the temperature control on the inlet sensor, the appropriate parameter must be changed in the control. See the Copper-fin II Service Manual for a detailed explanation of this procedure. The control will automatically switch to the system return sensor once it is connected. It is recommended that a system supply sensor be installed even when using the inlet sensor as the controlling sensor.
Verify space heat circulator mode
The Space Heating Mode controls both the system (primary) pump (if connected), and the boiler (secondary) pump. When the SMART SYSTEM control receives a space heating call for heat, it turns on the system pump. If the boiler is not heating an indirect DHW (Domestic Hot Water) tank, it also turns on the boiler pump. After the space heating call for heat ends, the system pump continues to run for a short period of time. If the boiler pump was running, it continues to run for a short period of time as well. These pump delays are factory set to 30 seconds. If different delays are desired, the appropriate parameters in the control must be changed. See the Copper-fin II Service Manual for a detailed explanation of this procedure.
Set space heating set point temperature
The UP and DOWN keys may be used during normal operation to adjust the space heating set point temperature (see FIG. 7-1 on page 56 of this manual). Once the desired temperature is displayed, press the ENTER/RESET key to save the new setting. If the ENTER/RESET key is not pressed, the new setting will be used for the current heating cycle only. The old setting will become active after the current heating cycle ends.
Page 49
6 Start-up (continued)
Figure 6-1_Lighting Instructions
FOR YOUR SAFETY READ BEFORE OPERATING
Installation & Operation Manual
WARNING:
If you do not follow these instructions
exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device which automatically lights the burner. Do not
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
1. STOP! Read the safety information above on
2. Turn off all electric power to the appliance.
3. Open control access panel.
4. This appliance is equipped with an ignition
try to light the burner by hand.
"WHAT TO DO IF YOU SMELL GAS"
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
FOR YOUR SAFETY
OPERATING INSTRUCTIONS
this label.
device which automatically lights the burner.
Do not
try to light the burner by hand.
PSI
IN
SHOWN IN THE "ON" POSITION
ON
OFF
GAS CONTROL KNOB
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to turn the gas
control knob. Never use tools. If the knob will not turn by hand, don't try to repair it, call a qualified service tech­nician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part
has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas con­trol which has been under water.
5. Push in gas control knob slightly and turn clockwise to "OFF."
NOTE: On the 36C valve, knob cannot be turned to "OFF" unless knob is pushed in slightly. Do not force.
6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If
you smell gas, STOP! Follow "B" in the safety
information above on th
smell gas, go to the next step".
7. Turn gas control knob counterclockwise
8. Replace control access panel.
9. Turn on all electric power to the appliance.
10. If the appliance will not operate, follow the instructions "To Turn Off Gas To
Appliance" and call your service tech-
nician or gas supplier.
OFF
to "ON."
ON
OFF
ON
is label. If you don't
TO TURN OFF GAS TO APPLIANCE
1. Turn off all electric power to the appliance if service is to be performed.
2. Open control access panel.
3. Push in gas control knob slightly and turn clockwise to "OFF". Do not force.
4. Replace control access panel.
OFF
ON
LBL2084 REV D
49
Page 50
6 Start-up
Installation & Operation Manual
Set DHW operation
Verify DHW circulator mode (boiler only)
The DHW Mode is programmed to heat an indirect domestic hot water tank. When the tank thermostat or tank sensor calls for heat, the SMART SYSTEM control will turn on the DHW pump and turn off the boiler pump (if running). If the system pump is running, it will remain on. When the DHW call for heat ends, and there is no space heating call for heat, the DHW pump will continue to run for a period of time. This pump delay is set at the factory to 30 seconds. If a shorter or longer delay is desired, the appropriate parameter in the control must be changed. See the Copper-fin II Service Manual for a detailed explanation of this procedure. If there is an active space heating call for heat, then the boiler pump will be turned on and the DHW pump will be turned off.
Set outlet target temperature (boiler only)
When in the DHW Mode, the control will modulate to maintain the outlet temperature to a set point. This set point is set at the factory to 180°F (82.2°C). If a different set point is desired, the appropriate parameter in the control must be changed. See the Copper-fin II Service Manual for a detailed explanation of this procedure.
Set tank target temperature
If a tank sensor is used, the tank set point can be adjusted by pressing either the UP or DOWN key. A menu will appear on the LCD display. Press the DOWN key to select the tank set point, and press ENTER. Use the UP and DOWN keys to adjust the set point. Press the ENTER key again to save the new set point and return to the normal display.
Set clock
The SMART SYSTEM control has a built-in clock that it uses for its night setback feature and for logging events. This clock must be set when the appliance is installed, and anytime the appliance has been powered off for more than one month. Use the following procedure to set the clock:
1. Press and hold the MENU key (FIG. 7-1) for at least 5 seconds.
2. The display changes to ready “ENTER MENU CODE”, with four (4) zeros below it.
3. Change the zeros to match the user code (factory set at “0704”). Use the UP and DOWN keys to increment or decrement the flashing digit, and the NEXT and PREVIOUS keys to select which digit flashes.
4. Press the ENTER key.
5. The display changes to read USER CODE for a few seconds, then displays a menu.
6. Press the ENTER key.
7. Press the UP key twice to display “A3 DATE AND TIME”.
8. Press the ENTER key once.
9. The date and time are displayed as “YY:MM:DD W hh:mm”, where: mm: minutes hh: hour (24 hour time; e.g., 2:00 PM = 14:00) W: day of the week (1 = Sunday, 2 = Monday, 3 = Tuesday, etc.,) YY: year MM: month DD: date
NOTICE
Use the UP and DOWN keys to increment or decrement the flashing number, and the NEXT and PREVIOUS keys to select which number flashes.
10. Press the ENTER key to save the setting.
11. Press the MENU key twice to exit the Programming Mode.
Configuration of the cascade
When installed in a Cascade system, the individual controls must be programmed for cascade operation. This is accomplished by accessing the control parameters.
Input the Installer code as described in the Copper-fin II Service Manual. Once the control parameters have been accessed, use the DOWN arrow key to select the H Control Mode parameters. Press the ENTER key to access these parameters. Use the UP arrow key to access parameter H4 Cascade. Press the ENTER key to access this parameter. Use the DOWN arrow key to select Enable. Press the ENTER key to program this into the control. Press the EXIT key, then press the DOWN key until I Cascade is selected.
Press the ENTER key to select the parameter I1 BLR Address. Press the ENTER key to access this parameter. Each unit in the Cascade system must be programmed with its own address. The unit designated as the Leader will have an address of 0. The remaining units in the Cascade will be Members and have addresses from 1 - 7. Use the UP and DOWN arrow keys to select the appropriate address. Press the ENTER key to program this into the control.
Press the MENU key twice to exit the control parameters. Repeat this procedure for all appliances in the Cascade, designating the Leader control and the Member controls.
The internal clock does not adjust for Daylight Savings Time and therefore, will require a manual adjustment.
50
Page 51
7 Operating information (continued)
Installation & Operation Manual
General
How the appliance operates
The Copper-fin II uses a copper finned tube heat exchanger to transfer heat from the flue products to the water. An electronic control module monitors various inputs to initiate a call for heat. The blower provides both primary and secondary air to the burner and forces the flue products out of the combustion chamber and into the vent system. The control module regulates the blower speed and firing stages, based upon the heat demand. Gas valves regulate the amount of gas supplied for the firing stages, which is then mixed with the combustion air supplied to the burner.
NOTICE
NOTICE
How the control module operates
The SMART SYSTEM control module receives input from appliance sensors and external devices. The control module activates and controls the blower and gas valves to regulate heat input and switches the boiler, Domestic Hot Water (DHW), and system pumps on and off as needed. The user programs the module to meet system needs by adjusting control parameters. These parameters set operating temperatures and appliance operating modes. Boiler operation can be based on boiler outlet water temperature, boiler inlet water temperature, system supply temperature, or system return temperature, depending on the parameter setting. Water heater operation can be based on a tank sensor or a tank thermostat.
If an inline high gas pressure regulator is used, it MUST BE of the lockup type and be located a minimum of 10 feet from the appliance. Failure to do so may result in insufficient gas volume supplied to the appliance.
If a pressure drop of more than 2" water column occurs between Standby (static) Mode and Operating (dynamic) Mode, a gas volume problem exists. Contact the gas utility, gas supplier, qualified installer, or service agency to determine the necessary steps to provide the proper gas volume to the appliance.
0 - 10V input (set point or power)
The Copper-fin II can be controlled by a Building Management System (BMS) using a 0 - 10 VDC signal. The control can be configured by the installer to use this signal to either control set point or firing rate.
DHW priority (boiler only)
The SMART SYSTEM control module allows connection of a DHW thermostat or tank sensor to the low voltage connection board. When the DHW thermostat or tank sensor calls for heat, the module activates the DHW pump, shuts down the boiler pump, and immediately sets the target outlet water temperature to 180°F (82.2°C). This provides automatic priority heat allocation to the indirect water heater for maximum response and recovery. The DHW pump continues for 30 seconds after the heating cycle to deliver the most possible heat.
DHW / SH (space heating) cycling (boiler only)
If an indirect DHW call for heat is received while a space heating call is in progress, the control will start the DHW pump and shut the boiler pump off. The system pump will remain on. If the space heating call is still active while the DHW call is in operation, the control will wait for 30 minutes (time adjustable by installer) then it will switch back to the space heating demand. The control will switch back and forth until one of the heat demands end.
Programmable controlling sensor (boiler only)
The control module is programmed to use the outlet sensor as the control sensor by default. If a system supply sensor is connected, the control automatically uses it as the control sensor. The control sensor can be changed by the installer to the inlet sensor. In this case, if a system return sensor is installed, the control automatically uses it as the control sensor. If the inlet sensor is chosen as the controlling sensor, it is recommended that the system supply sensor be installed for the best system performance.
Anti-cycling (boiler only)
After the set point has been satisfied, the control will delay the next burner cycle for a set time period (time is adjustable by the installer). The time delay will be bypassed if the system return temperature drops too far during the delay.
Control inputs and outputs
Staging S1 - S4
The S1 input tells the boiler to provide water for space heating. The S2 - S4 inputs are used when a sequencer controls the boiler.
Tank Aquastat
This input tells the boiler to provide water for heating a domestic hot water tank.
Boiler, system, and DHW pump control
When a space heating call for heat starts and no DHW call is on, the system and boiler pumps are turned on. As long as the space heating call for heat is on, the system pump will remain on. If a DHW call for heat is on, the boiler pump will wait to turn on until just before the DHW pump turns off. After the space heating call for heat ends, both pumps will run for an additional period of time.
When a DHW call for heat starts, the DHW pump is turned on. If a space heating call for heat was on, the boiler pump will turn off a few seconds after the DHW pump turns on.
51
Page 52
7 Operating information
Installation & Operation Manual
Temperature control
Firing rate
Depending upon the model, the Copper-fin II is capable of staging its firing rate from a minimum of 25% to a maximum of 100%. The firing rate is dictated by the call for heat (i.e., space heating or domestic hot water), the heating load, ramp delay (if enabled), and various other temperature limitations.
Ramp delay (boiler only)
For systems with lower flow, the SMART SYSTEM can limit the firing rate (when enabled) when a space heating call for heat starts, or when switching from a DHW call for heat to a space heating call for heat. There are six (6) limits that can be programmed, as well as six (6) time intervals corresponding to each limit. The sixth limit will also limit the firing rate for the rest of the call for heat.
Gradient limiting
If during operation of the heater the outlet water temperature is rising too quickly, the control will reduce the firing rate to its lowest setting.
Outdoor air reset (boiler only)
Protection features
Outlet temperature, and temperature rise limiting
The outlet temperature is monitored by the boiler outlet temperature sensor. When the outlet temperature exceeds 230°F (110°C) (boilers) or 190°F (88°C) (water heaters), the unit will reduce the firing rate. If the outlet water temperature exceeds 235°F (113°C) (boilers) or 200° (93°C) (water heaters) the control will shut the unit down until it cools off.
The control monitors the temperature difference between the inlet and the outlet sensor. If this difference exceeds the first limit the control will turn off stages. If the temperature difference exceeds a second limit the control will shut the unit down. The unit will restart automatically once the temperature difference has dropped 10°F (6°C) and the minimum off time has expired.
Freeze protection
DO NOT install the appliance in a room likely to freeze.
The following integral feature of the SMART SYSTEM control module provides some protection for the appliance only -- not for the system.
With the outdoor air sensor connected, the control module will calculate the set point based on the programmed reset curve. The installer can change the slope of the reset curve by several adjustable parameters. The user can limit the maximum set point for the system using the space heating set point.
Boost function (boiler only)
If outdoor air reset is active, and a space heating demand has been active continuously for a set period of time (time adjustable by installer) and there has been no DHW demands, the control may be programmed to increase the set point by a fixed number of degrees (adjustable by installer). This process will repeat until the space heating demand ends, the set point reaches the programmed set point or a maximum of 20 increases has occurred. Once the system heat demand is satisfied, the set point will revert to the value determined by the reset curve.
Night setback
The controller may be programmed to reduce the space heating (boilers) and tank set points during a certain time each day. A start and stop time can be programmed for each day of the week.
• The SMART SYSTEM control module provides freeze-up protection as follows when the appliance water temperature drops below 45°F (7.2°C):
Below 45°F (7.2°C), the appliance and system pumps operate constantly.
Below 37°F (2.7°C), the appliance turns on.
• Appliance and pumps turn off if appliance water temperature rises above 45°F (7.2°C).
CAUTION
High limit operations
When outlet temperature exceeds 240°F (116°C) (boilers) or 210°F (99°C) (water heaters), high limit action occurs. The appliance shuts down until the outlet water cools down and the RESET button on the Operator Interface is pressed.
This feature of the SMART SYSTEM control module does not eliminate the possibility of freezing. The installer must still use recognized design, installation and maintenance practice to prevent freeze potential for the appliance and system.
52
Page 53
7 Operating information (continued)
Installation & Operation Manual
Low water cutoff protection
1. The SMART SYSTEM control module uses temperature sensing of both inlet and outlet areas of the heat exchanger. If the flow rate is too low or the outlet temperature too high, the control module modulates and shuts the appliance down. This along with the flow switch, ensures appliance shutdown in the event of low water or low flow conditions.
2. Some codes and jurisdiction may accept these integral features of the control in lieu of requiring an additional limit control or low water cutoff. Consult local jurisdiction to determine. Contact manufacturer for low water cutoff kit availability.
Monitor external limits
Connections are provided on the connection board for external limits such as a louver proving switch. The SMART SYSTEM will shut off the burner and inhibit relighting whenever any of these external limits open.
Run-time and alarm outputs
The appliance provides dry contacts for indicating when the appliance is running, and when it is unable to operate.
Run-time and cycle counting
The control uses two timers to monitor the total hours of burner operation. One timer monitors the time the appliance is firing under 50% of rate. The other timer monitors the time the appliance is firing over 50% rate.
Boiler temperature regulation
Operating temperature (target)
The SMART SYSTEM control module senses water temperature and regulates appliance firing and firing rate to achieve a target temperature. The target temperature can be set between 70°F (21°C) and 220°F (104°C) (boilers) or between 60°F (16°C) and 190°F (88°C) (water heaters).
• Target temperature is fixed when the outdoor sensor is not installed (boilers).
• Target temperature is calculated as described under “Outdoor Air Reset Operation” and “Boost Function” when the outdoor sensor is connected (boilers).
Outdoor reset operation, if used (boilers
only)
Target temperature with outdoor reset
This feature improves the system’s efficiency as the outdoor temperature warms up.
See the Copper-fin II Service Manual to change the settings.
Reset curve
The reset curve looks at outdoor air temperature and adjusts the set point.
The control uses four (4) ignition counters to monitor the amount of appliance cycles. The first counter counts all ignitions of the control. The second counter counts only ignition attempts that have failed. The third and fourth counters are the same as the first and second respectively, but can be reset by the installer.
Service reminder
The control can be programmed for service reminder notification. This notification will become active when either a set time frame has expired, or a set amount of running hours or cycles has expired (all adjustable by the installer). The display will alternate the standard text on the display screen with Service Due every 5 seconds. The service reminder notification can be reset by the installer.
Error logging
The control will hold in memory the last 10 error codes as well as the last 10 turn-off functions. The date and time of the occurrence will be recorded as well. Only the 10 most current occurrences will be held in memory.
Cascade
When multiple appliances are installed, they can be wired together in a cascade sequence. A maximum of eight appliances can be controlled from a single control. In this application one appliance would be designated as the Leader control and all others would be designated as Member controls. The set point or firing rate can be controlled by the 0 - 10V input as well.
Once the Leader appliance receives a call for heat from a BMS, tank sensor, or external thermostat, the control will determine what the set point will be. A fixed temperature set point can be programmed into the control. See Copper-fin II Service Manual to program the set point.
On boilers, if the water temperature at the system sensor is less than the set point + the turn-off offset - the off-on differential, then the control will initiate a call for heat on the Cascade (see the Copper-fin II Service Manual for an explanation of the offset and differential). The Leader will energize the lead appliance on the Cascade. For a new startup this will be the Leader appliance.
On water heaters, if the water temperature at the tank sensor is less than the tank set point - the off differential, then the control will initiate a call for heat on the Cascade.
53
Page 54
7 Operating information
Installation & Operation Manual
The appliance will fire at its ignition speed and will then stage its firing rate to maintain the set point. If the first appliance reaches 100% of its firing rate, the Leader will calculate at what point the second appliance could fire at its minimum firing rate. At this point, the Leader will fire the second appliance on the Cascade. For a new startup, this would be the first Member appliance. The appliance will fire at its ignition speed and will then staging its firing rate to maintain the set point.
If the set point still cannot be met, the Leader will continue firing more Members until either the heat demand is met or all appliances on the Cascade are firing. As the heat demand decreases, the last appliance on will stage down to its minimum firing rate. Once the demand for that appliance is 0% it will shut down. As the heat demand decreases further, the second to last appliance will stage down and shut off. This will continue until the demand is satisfied and all appliances are shut off.
Sequence of the cascade
To equalize the run time of all appliances on the Cascade, the firing sequence will automatically be changed at set intervals.
For the first 24 hours after initializing the Cascade, the sequence will be changed every hour. After that the sequence will be changed once every 24 hours. The switching on/off sequence will be as follows:
DHW, Night Setback, and Ramp Delay operation with cascade
For indirect DHW operation any boiler(s) in the Cascade can be selected to provide heat for a DHW call. Select a boiler to be designated as the DHW boiler. Connect the tank thermostat or tank sensor to the corresponding terminals on the low voltage connection board. When the boiler receives a DHW call, the Leader control will take that boiler out of the Cascade sequence. If another boiler is available, the Leader will start it up to take its place.
The DHW boiler will adjust its set point to the programmed outlet set point and will adjust its firing rate to maintain this. Once the DHW call has been satisfied, the Leader control will place that boiler back into the Cascade sequence.
Switching of the boiler between DHW operation and SH operation when there is a call for both does not occur. The boiler will provide heat for the DHW demand until it is satisfied.
Night Setback operation of the boilers or water heaters within the Cascade is available. Programming of the Space Heating (SH) Night Setback will be done through the Leader boiler. Refer to the Copper-fin II Service Manual for information regarding Night Setback.
Ramp Delay operation of the boilers as described in the Copper-fin II Service Manual is available when the boilers are part of a Cascade system.
DAY SWITCHING ON SEQUENCE
Start L-M1-M2-M3-M4-M5-M6-M7
+ 1 hour M1-M2-M3-M4-M5-M6-M7-L
+ 2 hour M2-M3-M4-M5-M6-M7-L-M1
54
Page 55
7 Operating information (continued)
Sequence of operation
OPERATION DISPLAY
Installation & Operation Manual
1. The manual reset high limit must be closed before any action will take place.
2. Upon a call for heat the control turns on the appropriate pumps (system and boiler pumps for space heating; DHW pump for DHW call). The flow switch and low water cutoff (if equipped) must close.
3. • If the unit is equipped with a proof of closure valve, the proof of closure switch must be closed. The proof of closure valve is then energized. The gas pressure switch(es) (if equipped) must close.
• If the contact for the louvers is closed, the louver proving, and auto reset high limit (water heater only) inputs must close.
• If the air pressure switch is open, the prepurge cycle then begins by starting the combustion blower. Once started, the air pressure switch must close.
4. After the 15 second prepurge, the blower slows down and the hot surface igniter (HSI) is energized. The HSI is heated for at least 20 seconds.
5. Once the HSI is hot, the trial for ignition begins with the opening of the gas valve.
6. If the SMART SYSTEM control does not sense flame, then it will lock out.
HTR: Standby OUT: 123.8F(129)
HTR: Standby OUT: 123.8F(129)
HTR: Standby OUT: 123.8F(129)
HTR: PREPURGE OUT: 123.9F(129)
HTR: IGNITION OUT: 123.9F(129)
HTR: POSTPURGE, LOCKOUT OUT: 123.9F(129)
7. If the SMART SYSTEM control senses flame, it will fire the burner to maintain the set point. The firing rate will stage as required to hold the actual temperature at the set point. If the boiler lights due to a space heating call for heat, and the ramp delay function is active (default is disabled), the staging will be held to a series of increasing limits after the burner has lit.
8. If the space heating call for heat is active, and a DHW call for heat becomes active, the control will turn on the DHW pump, wait 2 seconds, and then turn off the boiler pump. This will divert the hot water away from the heating zone(s) and send it to the DHW tank instead. The control will then modulate to maintain the outlet temperature to the DHW boiler set point.
9. If the DHW call for heat remains active for more than 30 minutes, and the space heating call for heat is also on, then the control will turn on the boiler pump, turn off the DHW pump after 2 seconds, and resume firing based on the space heating set point. As long as both the space heating and DHW calls for heat remain active, the control will switch back and forth between the two modes until one of them is satisfied.
10. Once both calls for heat are satisfied, the control will turn off the burner. The blower will remain on for the 30 second postpurge cycle. Any pumps that are running will continue to run for their respective pump delay times, then turn off.
11. Boiler pump off, system pump continues its delay if longer.
HTR: RUN STG: 1 OUT: 124.8F(129)
HTR: DHW STG 123 OUT: 177.8(180)
HTR: RUN STG 12 OUT: 123.0F(129)
HTR: POSTPURGE OUT: 127.4F(129)
HTR: Standby OUT: 124.7F(129)
12. System pump off.
HTR: Standby OUT: 122.9F(129)
55
Page 56
Installation & Operation Manual
7 Operating information
Copper-fin II control module
Use the control panel (FIG. 7-1) to set temperatures, operating conditions, and monitor appliance operation.
Figure 7-1_Control Panel - Operator Interface
• Hold 5 seconds to enter code Input Mode (Menu Mode)
• Press to move up one level in Menu Mode or to exit Menu Mode
MENU/EXIT
DISPLAY SCREEN
• Press to turn heater off or back on
• Press to select a menu item
• Press after parameter programming to store parameter data
• Press to exit Service Mode
ENTER/RESET
56
• Press to change boiler water temperature and/or tank water temperature set point during normal operation
• Press to change displayed data values in Menu Mode
• Press to navigate through menu listing in Menu Mode
TXENSUOIVERPNWODPU
• Press to toggle display during normal operation to show outlet and return temperatures, fan speed, flame signal, etc.
• Press to toggle between digits when entering access code or between hour, minutes, etc., when entering date and time
• Press and hold both to enter Service Mode
Page 57
Installation & Operation Manual
7 Operating information (continued)
Access modes
User
The user can adjust the space heating target temperature and the tank target temperature (if a tank sensor is used) by using the UP and DOWN buttons (FIG. 7-1) at any time during normal operation. By entering the USER code (0704), the user can also change temperature units, time and date, and night setback settings. In User Mode, the following parameters can be viewed but not changed:
• Boiler outlet water target temperature in DHW Mode
• Appliance model number
• Software version
• Total operating hours
• Total cycles
Installer
Most parameters are available only to the installer, accessible only by entering the installer access code, see the Copper-fin II Service Manual.
Saving parameters (reference the Parameter Table in the Copper-fin II Service
Manual)
To save parameters and exit programming:
Press the ENTER/RESET button, then the MENU/EXIT button 3 times.
To keep parameter settings only for a current operating cycle:
Press the MENU/EXIT button 3 times after making all desired parameter changes.
To enter a parameter and continue programming:
Press the MENU/EXIT button 1 time to return to the parameter listings; press again to return to the menu listings. Remember to press the ENTER/RESET button when finished programming in order to save the changes made.
See the Copper-fin II Service Manual for a detailed description of parameters and access modes.
57
Page 58
Installation & Operation Manual
7 Operating information
Status display screens
Status Display Screens
By using the Previous/Next (, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the 11 display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:
Screen # Display Shows Description
Screen #1
Line 1
HTR: OFF
HTR: STAND-BY
HTR: SETPOINT MET
HTR: PRE-PURGE The unit has initiated the 10 second air purge upon a call for heat.
HTR: IGNITER * ON
HTR: RUN STG **** Or HTR: DHW STG ****
HTR: POST-PURGE
The unit has been turned OFF by the Enter/Reset button on the SMART SYSTEM display panel.
The unit has not received a call for heat from a remote thermostat nor has it received a call for heat from a DHW thermostat.
The unit has met the water temperature set point, but is still receiving a call for heat from either a remote thermostat, a DHW thermostat, or a BMS.
The unit has begun the 30 second heatup time prior to the trial for ignition. Display will show IGNITER A or IGNITER B depending on which stage has priority.
The unit has fired and is running at the displayed number of stages (1,2,3,4)
The call for heat has been satisfied and the unit runs the fan for an additional 10 seconds to clear the combustion chamber and vent system of residual flue products.
Screen #1
Line 2
HTR: SERVICE MODE
OUT: ***F (***)
OUT: ***F
OUT: OPEN The control does not detect the outlet sensor.
OUT: SHORTED The outlet sensor wires or the sensor itself has become shorted.
Press the Next arrow key on the SMART SYSTEM display to access Screen #2.
The unit has been placed in a temporary mode that will allow the unit to fire for the purpose of combustion analysis.
When the outlet sensor has been selected as the control sensor (default), the control will display the outlet temperature as well as the set point in parenthesis.
If the outlet sensor has not been selected as the control sensor or a system supply sensor is connected, only the outlet temperature will be displayed.
58
Page 59
Installation & Operation Manual
7 Operating information (continued)
Status Display Screens (cont’d)
By using the Previous/Next (, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the 11 display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:
Screen # Display shows: Description
When the inlet sensor has been selected as the control sensor, the
INLET: ***F (***)
control will display the inlet temperature as well as the set point in parenthesis.
Screen #2
Line 1
Screen #2
Line 2
Screen #3
Line 1
INLET: ***F
INLET: OPEN The control does not detect the inlet sensor.
INLET: SHORTED The inlet sensor wires or the sensor itself has become shorted.
RISE: ***F
Press the Next arrow key on the SMART SYSTEM display to access Screen #3.
SYSSUP: ***F (***)
SYSSUP: ***F
SYSSUP: OPEN The control does not detect the system supply sensor.
SYSSUP: SHORTED The system supply sensor wires or the sensor itself has become shorted.
SYSRTN: ***F (***)
If the inlet sensor has not been selected as the control sensor or a system return sensor is connected, only the inlet temperature will be displayed.
The difference between the inlet temperature and the outlet temperature is displayed.
When the system supply sensor has been selected as the control sensor, the control will display the system supply temperature as well as the set point in parenthesis.
If the system supply sensor has not been selected as the control sensor, only the system supply temperature will be displayed.
When the system return sensor has been selected as the control sensor, the control will display the system return temperature as well as the set point in parenthesis.
Screen #3
Line 2
Screen #4
Line 1
Screen #4
Line 2
SYSRTN: ***F
SYSRTN: OPEN The control does not detect the system return sensor.
SYSRTN: SHORTED
Press the Next arrow key on the SMART SYSTEM display to access Screen #4.
OUTDOOR: ***F
OUTDOOR: OPEN The control does not detect the outdoor air sensor.
OUTDOOR: SHORTED The outdoor air sensor wires or the sensor itself has become shorted.
TANK: ***F
TANK: OPEN The control does not detect the tank sensor.
TANK: SHORTED The tank sensor wires or the sensor itself has become shorted.
If the system return sensor has not been selected as the control sensor, only the system return temperature will be displayed.
The system return sensor wires or the sensor itself has become shorted.
The control will display the outdoor air temperature as sensed by the outdoor air sensor.
The control will display the tank temperature as sensed by the tank sensor.
59
Page 60
Installation & Operation Manual
7 Operating information
Status Display Screens (cont’d)
By using the Previous/Next (, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the 11 display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:
Screen Display shows: Description
Press the Next arrow key on the SMART SYSTEM display to access Screen #5.
Screen #5
Line 1
Screen #5
Line 2
Screen #6
Line 1
Screen #6
Line 2
Screen #7
Line 1
Screen #7
Line 2
0 – 10V BMS: **.*V The control displays the BMS voltage input from 0 to 10 volts.
STG DEMAND: **** The control displays the number of stages being called by the control.
Press the Next arrow key on the SMART SYSTEM display to access Screen #6.
FAN SPEED: ***
0 – 10V RATE: **.*V
Press the Next arrow key on the SMART SYSTEM display to access Screen #7.
SH CFH: ***
WHR CFH: ***
Press the Next arrow key on the SMART SYSTEM display to access Screen #8.
The control will display either OFF, LOW, or HIGH depending upon fan speed requirements of number of stages firing.
The control will display 0 to 10 volts based upon the number of stages firing.
The control will display either ON or OFF based upon a demand (call for heat) for space heating.
The control will display either ON or OFF based upon a demand (call for heat) for DHW (domestic hot water).
Screen #8
Line 1
Screen #8
Line 2
Screen #9
Line 1
Screen #9
Line 2
60
SYS PUMP: ***
SYSPUMPSPD: **.*V
Press the Next arrow key on the SMART SYSTEM display to access Screen #9.
UNIT PUMP: ***
UNIT PUMP: DELAY
DHW PUMP: ***
DHW PUMP: DELAY
The control will display either ON or OFF based upon system pump requirements upon demand for space heating.
The control will display the 0 – 10V input voltage from the system pump based upon system pump speed.
The control will display either ON or OFF based upon unit pump requirements upon demand for space heating.
The control will display delay in unit pump operation after the space heating requirements have been satisfied.
The control will display either ON or OFF based upon unit pump requirements upon demand for DHW.
The control will display delay in unit pump operation after the DHW requirements have been satisfied.
Page 61
Installation & Operation Manual
7 Operating information (continued)
Status Display Screens (cont’d)
Operation of the cascade
The boiler designated as the Leader will have two additional display screens that can be viewed. These screens will provide information regarding the operation of the Cascade. Each screen will contain two viewable items. The following is a description of the individual items and what they can display:
Screen Display shows: Description
Press the Next arrow key on the SMART SYSTEM display to access Screen #10.
Screen #10
Line 1
Screen #10
Line 2
Screen #11
Line 1
Screen #11
Line 2
FLM SIG – A: **.* µA The control displays the igniter flame signal of igniter A in microamps.
FLM SIG – B: **.* µA The control displays the igniter flame signal of igniter B in microamps.
Press the Next arrow key on the SMART SYSTEM display to access Screen #11.
IGN * AMPS: *.* A The control displays the current of either igniter A or B.
MIX VAL POS: ** % The control displays the mixing valve percentage open to the system.
61
Page 62
8 Domestic water heaters
Installation & Operation Manual
This section applies only to those appliances used to supply domestic hot water, installed with a storage tank(s). A circulating pump MUST be installed in the piping assembly to the storage tank and valves used to control water velocity through the appliance. Proper water velocity is important for correct operation of your water heater.
This section contains specific instructions for those appliances used to supply domestic hot water. All warnings, cautions, notes and instructions in the general installation and operation sections apply to these instructions. Water heaters are designed for installation with a storage tank. The operation of the circulating pump, proper sizing of the piping between the tank and heater and the control of water velocity, as explained in this section, are important for correct operation of your water heater.
NOTICE
To ensure proper velocity through the heat exchanger, it is necessary to regulate the temperature rise across the heat exchanger from inlet to outlet. This must be done on initial installation and periodically rechecked. With the correct temperature rise across the heat exchanger when the water heater is firing at 100% of rated input, you may be assured of the proper velocity in the tubes. This will yield long life and economical operation from your water heater.
Excessive lime/scale build-up in the heat exchanger tubes is a result of restricted flow and too little velocity in the tubes. Excessive pitting or erosion in the tube is caused by high water flow and too much velocity through the tubes. Care should be taken to measure temperature rise and maintain velocity as follows:
Initial set-up of maximum water flow
On initial start-up of the Copper-fin II the maximum water flow through the heat exchanger must be manually set before normal operation begins.
TABLE - 8A
MAXIMUM WATER FLOW
CAUTION: The maximum flow rate through a Copper-fin II water heater with a copper heat exchanger must be set to provide and not exceed the following flow:
Model Maximum Flow
402, 502, 652, and 752 55 GPM
992, 1262, 1442, 1802, and 2072 90 GPM
If higher flow rates are required through the water heater, an optional Cupro Nickel heat exchanger is available. Consult the factory for specific application requirements.
The heat exchanger is capable of operating within the design flow rates required for the water heater, storage tank(s), and connecting piping. Erosion of the finned copper tubes may occur if the flow rate exceeds the maximum allowable flow rate through the water heater. The maximum flow rate through the water heater must be adjusted. Maximum flow on Models 402
- 752 is 55 GPM and 90 GPM on Models 992 - 2072. Flow rate can be determined by measuring the temperature rise through the water heater when it is firing at full rate input.
TABLE - 8B
TEMPERATURE RISE AT FULL RATE FIRE
55 AND 90 GPM FLOW
Model Temperature Rise °F
402 12 502 15
652 20
752 23
992 19
1262 24
1442 27
1802 34
2072 39
1. The pump must run continuously when the burner is firing.
2. With the pump running and the burner in the water heater in the off cycle, the inlet water temperature and outlet water temperature readings on the Operator Interface should read approximately the same temperatures. Water Temperature Rise on the Operator Interface should read near zero.
3. Turn the water heater on and allow time for the temperature to stabilize. The Service Mode can be used to force the water heater to run at full fire. See the Copper-fin II Service Manual for a detailed explanation of the Service Mode. Check the water temperature rise in the Operator Interface when the burner is firing at 100% of rated input.
4. Compare the water temperature rise in the Operator Interface with the required temperature rise. Should adjustment be needed, proceed as follows.
62
Page 63
8 Domestic water heaters (continued)
Installation & Operation Manual
If the temperature rise is too high, the water velocity is too low, adjust as follows:
1. Check for restrictions in the outlet of the water heater.
2. Be sure all valves are open between the water heater and the storage tank. Ensure that all ball valves are fully ported.
3. Check the pump to be sure it is running properly and that the pump motor is running in the proper direction.
4. Check diameter and length of the piping between the storage tank and water heater against the head capacity of the circulating pump.
5. Be sure the pipes between the water heater and storage tank are not less than 2 or 2 1/2 inch (63.5mm) diameter (depending on model). To increase flow and decrease temperature rise, increase the piping to 3 inch (76.2mm) diameter (depending on model) to decrease head loss in the piping to the storage tank.
6. Common manifold piping for multiple unit installations will require larger minimum pipe sizes and tank circulating tappings to ensure proper flow.
Water chemistry
NOTICE
The required temperature rise and the standard circulating pump are sized based on the heating of potable water with a hardness of 5 to 25 grains per gallon and a total dissolved solids not exceeding 350 ppm. Consult the manufacturer when heating potable water exceeding these specifications. Heating of high hardness and/or high total dissolved solids water may require a larger circulating pump, an optional Cupro Nickel heat exchanger and a revised temperature rise specification based on the water chemistry of the water to be heated. Water with a hardness of less than 5 grains per gallon will usually have a pH which can be aggressive and corrosive causing non­warrantable damage to the heater, pump, and associated piping. Corrosion due to water chemistry generally shows up first in the hot water system because heated water increases the rate of corrosive chemical reactions.
Water temperature rise and maximum flow data is based on heating potable water with a hardness of 5 to 25 grains per gallon and total dissolved solids not exceeding 350 ppm.
If the temperature rise is too low, the water velocity is too high, adjust as follows:
1. Temperature rise can be increased by slowly closing the field-installed ball valve in the outlet piping from the water heater to the storage tank to achieve the proper temperature rise.
2. Sustained high water velocity and low temperature rise may result in pitting or erosion of the copper tubes in the heat exchanger. This is a non-warrantable failure. Temperature rise must be properly adjusted to achieve the specified flow rate.
3. Once temperature rise has been properly set, return to normal operation.
CAUTION
Temperature rise cannot be adjusted when the burner is firing at less than 100% of rated input.
63
Page 64
8 Domestic water heaters
Figure 8-1_Typical Water Heater Piping with Storage Tank
Installation & Operation Manual
COMMON MANIFOLD SIZE (Min.)
Models: 402, 502, 652, & 752
Number of Units GPM
Diameter
1552
BUILDING
HOT WATER
SUPPLY
(in.)
MIXING VALVE
COLD WATER SUPPLY
COMMON MANIFOLD SIZE (Min.)
Models: 992, 1262, 1442, 1802 & 2072
Number of Units GPM
1 90 2 1/2
RELIEF
VALVE
INLET
Diameter
(in.)
RELIEF
VALVE
LOCK-TEMP
STORAGE
NOTICE
OUTLET
BUILDING RETURN
DRAIN
TANK
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
64
Page 65
8 Domestic water heaters (continued)
Figure 8-2_Single Water Heater Piping with Two Storage Tanks
Installation & Operation Manual
COMMON MANIFOLD SIZE (Min.)
Models: 402, 502, 652, & 752
Number of Units GPM
Diameter
1552
BUILDING
HOT WATER
SUPPLY
RELIEF
VALVE
(in.)
MIXING VALVE
OUTLET
COMMON MANIFOLD SIZE (Min.)
Models: 992, 1262, 1442, 1802 & 2072
Number of Units GPM
1 90 2 1/2
INLET
Diameter
(in.)
COLD WATER SUPPLY
LOCK-TEMP
STORAGE
TANK
DRAIN
NOTICE
BUILDING RETURN
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
65
Page 66
8 Domestic water heaters
Figure 8-3_Multiple Water Heater Piping with a Single Storage Tank
Installation & Operation Manual
COMMON MANIFOLD SIZE (Min.)
Models: 402, 502, 652, & 752
Number of Units GPM
Diameter
2 110 3
3 165 3 1/2
4 220 4
5 275 5
6 330 5
7 385 6
8 440 6
BUILDING
HOT
WATER
SUPPLY
(in.)
MIXING VALVE
COLD WATER SUPPLY
COMMON MANIFOLD SIZE (Min.)
Models: 992, 1262, 1442, 1802 & 2072
Number of Units GPM
Diameter
(in.)
2 180 4
3 270 5
4 360 6
5 450 6
6 540 6
7 630 7
8 720 7
RELIEF
VALVE
LOCK-TEMP
STORAGE
NOTICE
MIN 4" COMMON
TANK
DRAIN
MANIFOLD SIZE
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
BUILDING RETURN
66
Page 67
8 Domestic water heaters (continued)
Figure 8-4_Multiple Water Heater Piping with Multiple Storage Tanks
Installation & Operation Manual
COMMON MANIFOLD SIZE (Min.)
Models: 402, 502, 652, & 752
Number of Units GPM
2 110 3
3 165 3 1/2
4 220 4
5 275 5
6 330 5
7 385 6
8 440 6
Diameter
(in.)
MIXING VALVE
COMMON MANIFOLD SIZE (Min.)
Models: 992, 1262, 1442, 1802 & 2072
Number of Units GPM
2 180 4
3 270 5
4 360 6
5 450 6
6 540 6
7 630 7
8 720 7
COLD WATER SUPPLY
Diameter
(in.)
BUILDING
HOT
WATER
SUPPLY
RELIEF
VALVE
LOCK-TEMP
STORAGE
TANK
NOTICE
MIN 4" COMMON MANIFOLD SIZE
DRAIN
BUILDING RETURN
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
67
Page 68
8 Domestic water heaters
TABLE 8C
COMMON WATER MANIFOLD SIZE FOR
MULTIPLE WATER HEATER INSTALLATIONS
Pipe sizing chart provides minimum pipe size for common manifold piping to ensure adequate flow.
Common Manifold Size (Min.)
Number of Water Heaters
402 - 752 992 - 2072
1 2" 2 1/2"
23"4"
3 3 1/2" 5"
44"6"
55"6"
65"6"
7 8
Pump operation
1. The water heater must have a properly sized circulating pump. This pump is sized to circulate water between the heater and the storage tank only.
2. The pump is sized to the heater input and water chemistry specifications noted in the Water Chemistry section on page 63.
3. The diameter and length of the piping installed between the storage tank(s) and water heater must be properly sized based on the capacity of the circulating pump.
4. The pump must run continuously when the water heater is energized. This is the standard operating system for a water heater.
A pump delay control function with an all bronze pump is installed as standard equipment on all water heater systems. The pump will operate only while there is a “Call for Heat” and for a timed period after the water temperature set point is satisfied to remove any residual heat from the combustion chamber.
5. Lubricate pump to manufacturer’s recommendations. Pump damage due to inadequate lubrication is non-warrantable.
The tank sensor must be installed in the tapping provided in the lower 25% of the storage tank to achieve proper operation. As shipped from the factory, the tank sensor is in the literature package shipped with the unit. Placing the sensor in the tapping provided on the storage tank will improve temperature response and prevent short cycles of operation.
68
Models
6" 7"
6" 7"
Installation & Operation Manual
The standard circulating pump on this water heater is sized based on installation of a single storage tank and heater in close proximity. If the number of fittings and straight pipe exceeds the specified maximum equivalent number of straight feet for a specified diameter of pipe, non-warrantable operational problems may be experienced.
402 - 752 Models
1/4 HP, 120 VAC, 5.8 Amps
992 - 2072 Models
1/2 HP, 120 VAC, 7.4 Amps The standard pump selection is based on the following pipe and fittings from the water heater to the storage tank: 6 - 90° elbows 2 - ball valves 2 - unions 1 - cold water tee Not more than 45 feet of straight pipe. For every elbow and tee in excess of those shown above, DEDUCT 6.5 FEET from the maximum allowable straight pipe in the heater to tank circulating loop.
TABLE D
MINIMUM PUMP PERFORMANCE
Based on heating potable water with a hardness of 5 to 25 grains per gallon and total dissolved solids not exceeding 350 ppm. See Water Chemistry section on page 63.
Model GPM Ft. Hd.
402 - 502 - 652 - 752 55 10
992 - 1262 - 1442 - 1802 - 2072 90 15
When installing multiple water heaters and/or multiple storage tanks, the diameter of the inter-connecting pipe and all fittings must be increased. An increase in pipe diameter will decrease head loss in the system piping and ensure proper flow. Proper pipe size between the heater and storage tank MUST be maintained to ensure that the standard pump supplied on the water heater will maintain desired flow.
When DHW Night Setback is enabled, the system pump output can be used to control a building circulation pump. The pump output will be on during the time Night Setback is not active and will be off when Night Setback is active. A field installed contactor must be used when controlling a circulation pump larger than 1/6 HP.
Heat exchanger
This is a highly sophisticated heat exchanger designed to carry water in such a way that it generates a scouring action which keeps all interior surfaces free from build-up of impurities. The straight-line, two pass design of the copper finned tubes send water into the headers at a properly rated velocity. The configuration of the headers, in turn, creates a high degree of turbulence which is sufficient to keep all contaminants in suspension. This “scouring action” provides greater cost savings for owners. Tubes are always able to transfer heat at peak efficiency. Every surface within this water containing section is of a non-ferrous material, providing clear, clean, rust­free hot water. Straight copper tubes-finned on the outside for maximum heat transfer and glass lined, cast iron, one piece, cored headers make up an entirely rust-proof unit. On all models, header inspection plugs in the heat exchanger can be removed for field inspection and cleaning of copper tubes. The heat exchanger may be removed from the unit.
Page 69
8 Domestic water heaters (continued)
Installation & Operation Manual
Thermostat adjustment procedure
1. Press the UP or DOWN key to view the set point setting.
2. Press either the UP or DOWN key to increase or decrease the displayed set point value.
3. Press the ENTER key to permanently store the new set point into the control module’s memory.
Failure to press the ENTER key after changing the display value will result in the set point reverting back to its previous value after the current heat demand ends.
The control may be adjusted any time regardless of call for heat status. When pressing the UP or DOWN key to enter any new set points, the control module will immediately begin controlling based on the new set point.
Minimum water temperatures (domestic hot water use)
Domestic water temperatures:
This high efficiency water heater should be operated at a temperature setting high enough to prevent condensing of the products of combustion on the unit’s heat exchanger or in the attached venting system. Use extreme caution when storing water at elevated temperatures. A water temperature setting maintained above the dew point of the products of gas combustion should prevent condensate formation and ensure proper performance of the venting system. The manufacturer recommends the use of a properly sized thermostatic mixing valve to supply domestic hot water at temperatures less than 140°F (60°C). Storing the water at a higher temperature and thermostatically mixing the water will increase the available quantity of mixed hot water, greatly reducing the possibility of condensate formation on the heat exchanger or in the venting system and help prevent the growth of water borne bacteria.
NOTICE
Adequate care MUST be taken to prevent a potential scald injury when storing water at elevated temperatures for domestic use.
Inlet water temperatures below the specified minimum recommendations can excessively cool the products of combustion resulting in condensation on the heat exchanger. Condensation on the heat exchanger can cause operational problems, bad combustion, sooting, flue gas spillage and reduced service life of the related components.
CAUTION
The maximum temperature set point that can be programmed into the control module from the Operator Interface for water heater operation is 190°F (88°C). The control is factory pre-set at approximately 120°F (49°C). Facilities with small children or invalids may require 120°F (49°C) or a lower temperature setting to reduce risk of scald injury. Some states may require a lower temperature setting. Check with your gas supplier for local requirements governing the temperature setting. Remember, no water heating system will provide exact temperature at all times. Allow a few days of operation at this setting to determine the correct temperature setting consistent with your needs.
NOTICE
CAUTION
An appliance allowed to operate at return temperatures below the specified minimum setting may experience problems with the operating controls, safety switches, obstruction of the flue gas passages on the heat exchanger, incomplete combustion, and possible flue gas spillage. Sustained operation at lower than specified water temperatures may cause hazardous conditions that may result in personal injury or non-warrantable damage to the appliance.
1. This water heater, when set at the lower temperature setting, is not capable of producing hot water of sufficient temperature for sanitizing purposes.
2. Higher stored water temperature increases the ability of the water heater to supply desired quantities of hot water, however remember --
Hotter water increases the risk of scald injury.
69
Page 70
8 Domestic water heaters
Figure 8-5_Danger Warning
Location of Cold Water Supply Piping Connections
Incorrect piping of the cold water supply to the system may result in excessive low temperature operation causing condensate formation on the primary heat exchanger and operational problems. The cold water supply piping must be installed in the discharge piping from the heater to the storage tank. This allows the cold water to be tempered in the storage tank before entering the heater. See typical installation drawings provided in this manual for correct piping (FIG.’s 8-1 thru 8-4). Higher water temperatures reduce the volume of condensate formed.
CAUTION
Setting the temperature selector to higher settings provides hotter water, which increases the risk of scald injury.
Installation & Operation Manual
A high limit control is located on the inside of the left front panel, as shown in FIG. 8-6. The setting of this control knob limits maximum discharge water temperature. The water heater temperature limit control is adjustable up to a maximum setting of 210°F (99°C). This water heater also includes a fixed high water temperature limit control set to 200° (93.3°C). The RESET key on the display must be pushed whenever water temperature has exceeded the set point of the limit. The temperature of the water in the heat exchanger must drop a minimum of 15°F (8.3°C) below the setting of the high limit control before the reset function can be activated. A high limit message will be shown in the Operator Interface when water temperature exceeds the high water temperature limit control set point.
NOTICE
Optional relief valve
This water heater is normally supplied with a temperature and pressure relief valve sized in accordance with applicable codes. Units may be supplied with an optional pressure only relief valve. When a water heater is equipped with this optional relief valve and is piped to a separate storage vessel, the storage vessel must have a properly installed temperature and pressure relief valve which complies with local codes.
Thermal expansion
The high limit control will not reset until the water temperature has dropped below the set point of the high limit.
WARNING
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
Optional adjustable auxiliary high water temperature limit control
ADJUSTABLE AUXILIARY HIGH WATER TEMPERATURE LIMIT CONTROL (OPTION)
A relief valve that discharges periodically may be due to thermal expansion in a closed system. A water heater installed in a closed system, such as one with a backflow preventer or check valve installed in the cold water supply, shall be provided with means to control expansion. Contact the water supplier or local plumbing inspector on how to correct this situation. Never plug or cap the relief valve discharge.
Cathodic protection
Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend the hot water faucet be open for several minutes at the kitchen sink before you use any electrical appliance which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipe as the hot water begins to flow. There should be no smoking or open flames near the faucet at the time it is open.
Figure 8-6_Adjustable Auxiliary High Water Temperature Limit Control
70
Page 71
9 Maintenance
Maintenance and annual startup
Table 9A_Service and Maintenance Schedules
Installation & Operation Manual
Service technician
(see the following pages for instructions)
General:
• Address reported problems
• Inspect interior; clean and vacuum if necessary;
• Check for leaks (water, gas, flue, condensate)
• Examine venting system
Check system water pressure/system piping/expansion tank
• Check control settings
Check igniter
• Check wiring and connections
• Check flue gas passageways
• Flame inspection (stable, uniform)
ANNUAL START-UP
Inspect and clean the burner
• Check manifold gas pressure
Owner maintenance
(see the Copper-fin II User’s Information Manual for
instructions)
• Check appliance area
Check pressure/temperature
Daily
Monthly
Periodically
gauge
• Check vent piping
• Check air piping
• Check relief valve
• Replace combustion air filter Note: More frequent replacement may be necessary in dirty environments.
• Test low water cutoff (if used)
Perform start-up checkout and performance verification per Section 6 in the Copper-fin II Installation and Operation Manual.
If combustion or performance indicate need:
• Clean heat exchanger with a stiff bristle brush
Remove and clean burners using water. Dry before re-assembling.
• Clean the blower wheel with a brush and vacuum. Do not let dirt from cleaning get pulled into the blower.
Every
6 months
End
of season
months
• Reset button (low water cutoff)
Check appliance piping (gas and
water) for leaks
• Operate relief valve
Shut appliance down (unless
boiler used for domestic hot water)
71
Page 72
9 Maintenance
Installation & Operation Manual
WARNING
WARNING
WARNING
Follow the service and maintenance procedures given throughout this manual and in component literature shipped with the appliance. Failure to perform the service and maintenance could result in damage to the appliance or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death, or substantial property damage.
The appliance should be inspected annually only by a qualified service technician. In addition, the maintenance and care of the appliance designated in Table 9A and explained on the following pages must be performed to assure maximum appliance efficiency and reliability. Failure to service and maintain the appliance and system could result in equipment failure.
Electrical shock hazard – Turn off power to the appliance before any service operation on the appliance except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.
Address reported problems
1. Inspect any problems reported by the owner and correct before proceeding.
Inspect appliance area
1. Verify that appliance area is free of any combustible materials, gasoline and other flammable vapors and liquids.
Inspect appliance interior
1. Remove the outer access panels and inspect the interior of the appliance.
2. Vacuum any sediment from inside the appliance and components. Remove any obstructions.
Check all piping for leaks
Check water system
1. Verify all system components are correctly installed and operational.
2. Check the cold fill pressure for the system. Verify it is correct (must be a minimum of 12 PSI).
3. Watch the system pressure as the boiler heats up (during testing) to ensure pressure does not rise too high. Excessive pressure rise indicates expansion tank sizing or performance problem.
4. Inspect automatic air vents and air separators. Remove air vent caps and briefly press push valve to flush vent. Replace caps. Make sure vents do not leak. Replace any leaking vents.
WARNING
1. Inspect all water and gas piping and verify to be leak free.
2. Look for signs of leaking lines and correct any problems found.
3. Check gas line using the procedure found in Section 3 - Gas Connections of the Copper-fin II Installation and Operation Manual.
Eliminate all system or appliance leaks. Continual fresh makeup water will reduce appliance life. Minerals can build up in sections, reducing heat transfer, overheating heat exchanger, and causing heat exchanger failure. Leaking water may also cause severe property damage.
Flue vent system and air piping
1. Check for gastight seal at every connection, seam of air piping, and vent piping periodically inspected by a qualified service agency.
WARNING
Venting system must be sealed gastight to prevent flue gas spillage and carbon monoxide emissions, which will result in severe personal injury or death.
Check expansion tank
1. Expansion tanks provide space for water to move in and out as the heating system water expands due to temperature increase or contracts as the water cools. Tanks may be open, closed, diaphragm or bladder type. See Section 4 - Water Connections of the Copper-fin II Installation and Operation Manual for suggested best location of expansion tanks and air eliminators.
72
Page 73
9 Maintenance (continued)
Installation & Operation Manual
Check relief valve
1. Inspect the relief valve and lift the lever to verify flow. Before operating any relief valve, ensure that it is piped with its discharge in a safe area to avoid severe scald potential. Read Section 4 - Water Connections of the Copper-fin II Installation and Operation Manual before proceeding further.
WARNING
WARNING
Safety relief valves should be re-inspected AT LEAST ONCE EVERY THREE YEARS, by a licensed plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency – not by the owner. Failure to re-inspect the boiler relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage.
Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal. Otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down the appliance until a new relief valve has been installed.
Inspect/replace hot surface igniter
This unit uses a proven SMART SYSTEM control module and a hot surface igniter. The SMART SYSTEM control module is not repairable. Any modification or repairs will invalidate the warranty.
WARNING
A faulty hot surface igniter or control module must be replaced with an identical part. A specification igniter and control module for this specific unit is available from your local distributor. Do not use general purpose field replacement
control modules or igniters.
Do not attempt to repair a faulty hot surface igniter or control module. Any modification or repairs may create hazardous conditions that result in property damage, personal injury, fire, explosion and/or toxic gases.
Ignition system checkout
1. Turn off gas supply to unit.
2. Turn electric power on.
3. Adjust the set point on the temperature control to a setting above water temperature or to the highest safe setting.
4. The igniter will cycle on trial for ignition.
5. The control module will lock out and turn the alarm light on.
6. Adjust the Set Point Differential and High-Fire Offset to the desired settings.
7. Turn on gas supply.
8. Press the RESET button at the electronic display panel to reset the control module.
9. If ignition system fails to operate properly, repair work must be performed by a qualified service person or installer.
Check all wiring
1. Inspect all wiring, making sure wires are in good condition and securely attached.
Check control settings
2. After following the above warning directions, if the relief valve weeps or will not seat properly, replace the relief valve. Ensure that the reason for relief valve weeping is the valve and not over-pressurization of the system due to expansion tank waterlogging or undersizing.
1. Set the SMART SYSTEM control module display to Parameter Mode and check all settings. See Section 1 of this manual. Adjust settings if necessary. See Section 1 of this manual for adjustment procedures.
2. Check settings of external limit controls (if any) and adjust if necessary.
73
Page 74
9 Maintenance
Installation & Operation Manual
Perform start-up and checks
1. Start appliance and perform checks and tests specified in Section 7 - Start-up of the Copper-fin II Installation and Operation Manual.
2. Verify cold fill pressure is correct and that operating pressure does not go too high.
Check burner flame
Visually check main burner flames at each start-up after long shutdown periods or at least every six months. A burner viewport is located on the burner mounting flange.
WARNING
Figure 9-2_Flame Pattern Illustration
NORMAL
YELLOW FLAME
Normal Flame: A normal flame at 100% of burner input is blue, with slight yellow tips, a well defined flame and no flame lifting.
Yellow Tip: Yellow tipping can be caused by blockage or partial obstruction of air flow to the burner.
Yellow Flames: Yellow flames can be caused by blockage of primary air flow to the burner or excessive gas input. This condition MUST be corrected immediately.
The area around the burner viewport is hot and direct contact could result in burns.
YELLOW TIP
FLAME LIFT
Check flue gas passageways
Any sign of soot around the inner jacket, outer jacket, flue pipe connections, burner or in the areas between the fins on the copper heat exchanger indicates a need for cleaning. The following cleaning procedure must only be performed by a qualified serviceman or installer. Proper service is required to maintain safe operation. Properly installed and adjusted units seldom need flue cleaning.
NOTICE
CAUTION
All gaskets/sealants on disassembled components or jacket panels must be replaced with new gaskets/sealants on reassembly. Gasket and sealant kits are available from your distributor.
When a Category IV vent system is disconnected for any reason, the flue must be reassembled and resealed according to the vent manufacturer’s instructions.
Inspect and clean burner
1. Turn off main power to unit.
2. Turn off main manual gas shutoff to unit.
3. Remove the front outer jacket panels.
4. Disconnect manifold from gas train using union(s) just below each gas valve(s).
5. Remove mounting screws from manifold mounting brackets. Pull the manifold/orifice assembly away from burners. Repeat for each manifold assembly.
6. Remove two mounting screws from burner and slide burner out toward front of unit. Use caution to prevent damage to burners, refractory, hot surface igniter or wiring.
7. Remove soot from burners with a stiff bristle brush.
Dirt may be removed from burner ports by rinsing the burner thoroughly with water. Drain and dry burners before re-installing. Damaged burners must be replaced.
Lifting Flames: Lifting flames can be caused by over firing the burner, excessive primary air or high draft.
If improper flame is observed, examine the venting system, ensure proper gas supply and adequate supply of combustion and ventilation air.
74
When installed in a dusty and dirty location, the burners may require cleaning on a 3 to 6 month schedule or as needed, based on severity of contamination. Contaminants can be drawn in with the combustion air. Non combustible particulate matter such as dust, dirt, concrete dust or dry wall dust can block burner ports and cause non-warrantable failure. The standard inlet air filter will help eliminate dust and dirt from entering the unit. Use extreme care when operating a unit for temporary heat during new construction. The burners could require a thorough cleaning before the unit is placed in service.
Page 75
9 Maintenance (continued)
Inspect and clean the heat exchanger
1. While burners are removed, check the heat exchanger surface for sooting. If present, heat exchanger must be cleaned and problem corrected. Proceed as follows.
2. Remove gas manifold(s)/orifice assemblies as described in steps 1 through 5 in Burner Removal and Cleaning, page 74.
3. Disconnect wiring from the hot surface igniter and hose from the burner pressure tap.
4. Remove inner jacket panel mounting screws and slide door assembly out toward front of the unit. Use caution to prevent damage to the refractory and hot surface igniter.
5. Check “V” baffles and frame runners along front and back edges of heat exchanger. Remove and clean if necessary.
6. Remove soot from heat exchanger with a stiff bristle brush. Use a vacuum to remove loose soot from surfaces and inner chamber.
7. The heat exchanger can be removed by sliding towards the front of the unit. Once the heat exchanger is removed from the unit, a garden hose can be used to wash the tubes to ensure that all soot is removed from the heat exchanger surfaces. Note: Do not wet the unit’s refractory.
8. Ensure that all burner ports are cleaned to remove any soot. See Burner Removal and Cleaning, page 74.
9. Carefully reinstall the heat exchanger, “V” baffles, and frame runners if removed from the unit. Note: Make sure frame runners seal securely where they contact the front and rear compartment refractory.
10. Carefully reinstall inner jacket panels, burners, manifolds, wires and hoses. Use new gasket material to ensure a proper air seal.
11. Reassemble all gas and water piping. Test for gas leaks.
NOTICE
Upon completion of any testing on the gas system, leak test all gas connections with a soap and water solution while main burners are operating. Do not spray soap and water solution on the SMART SYSTEM control module housing. The use of an excessive amount of soap and water solution can damage the control. Immediately repair any leak found in the gas train or related components. Do not operate an appliance with a leak in the gas train, valves, or related piping.
Installation & Operation Manual
HEAT
EXCHANGER
Figure 9-3_Location of the Heat Exchanger Inside Jacket
Review with owner
1. Review the Copper-fin II User’s Information Manual with the owner.
2. Emphasize the need to perform the maintenance schedule specified in the Copper-fin II User’s Information Manual (and in this manual as well).
3. Remind the owner of the need to call a licensed contractor should the appliance or system exhibit any unusual behavior.
4. Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.
Oiled bearing circulators
Inspect the pump every six (6) months and oil as necessary. Use SAE 30 non-detergent oil or lubricant specified by the pump manufacturer.
12. Reassemble outer jacket panels.
13. Cycle unit and check for proper operation.
75
Page 76
10 Connection diagram
R
S
Y
Y
Y
1
3
5
S
Installation & Operation Manual
FIELD WIRING
TO MONITORING DEVICE
TO MONITORING DEVICE
3-W AY
24V
VALVE
STA GE #1
CONNECT
STA GE #2
TO
TERMINAL
STA GE #3
#19
(LO UV ER
STA GE #4
RELAY)
LOUVERS
TANK
M
COM
PROVE
LINE
NEU
AQUASTAT
SENSOR
UNITS
FROM
BMS
BMS
MOD
BUS
BMS
SAFETY SUPPLY
10K/20K
TO
POOL
0-10V DC IN
COMMON 0-10V DC OUT
COMMON
BK
G
R W
POOL/BOIL ER
FROM PUM P
OUT PUT
SAFETY
10K/20 K
OUTLET
SENSOR
INLET
SENSOR
IND-DHW PUMP
RELAY COIL
120V
SYSTEM PUMP
RELAY COIL
120V
1HP
UNIT
PUMP
MAX
120V/60Hz
NEUTRAL
SUPPLY
GROUND
OPEN
CLOSE
COMMON
R
OUT
DOOR
10K
AIR
10K
10K
0-10V DC IN
COMMON
10K
R
R
LINE
+
ALARM
1
CONTACTS
+
2
+
RUNTIME
3
+
CONTACTS
4
+
OPEN
5
+
CLOSE
6
COM
+
7
+
S1
8
S1
+
9
+
S2
10
S2
+
11
+
S3
12
S3
+
13
+
S4
14
+
S4
15
+
LOUVER PROVING
16
SWITCH
+
17
+
LOUVER RELAY
18
COIL
+
19
+
TANK
20
AQUASTAT
+
21
CN3
+
TANK
22
+
SENSOR
23
+
SHIELD
24
+
A
25
B
+
26
SHIELD
+
27
+
+0-10V
28
-BMS IN
+
29
+
+0-10V
30
-RATE OUT
+
31
+
SHIELD
32
+
A
33
B
+
34
SHIELD
+
35
CN2
OUT DOOR
+
1
SENSO R
+
2
SYS SU PPLY
+
3
SENSO R
+
4
+
SYS R ETUR N
5
SENSO R
+
6
+
0-10V SYS
7
-PUMP IN
+
8
CN2
BOILER/POOL HEATER
G
W
W
P
W
PR
BR
BR
W
BK
G
OPT. ALARM HARNESS
CN4
3-W AY
VAL VE
STAGI NG
CN5
FIELD
SUPP LIED
WIRING
CN6
CA S CA D EMO DBUS
4
3
10K
10K
10K
2
1
CN1
20K
10K
BK
R
CN1
SENSOR
POO L SU P
MODBUS MODULE
CONNECTIONS
BR
BR
MAIN POWER HARNESS
OPT. MODBUS HARNESS
BK
1
2G
3
W
CHASSIS GROUND
BK
BK
PR
BL
Y
BR
1
R/O
3
T/W
4
Y
5
BL
6
Y
BR/W
BL
PR
Y
P
W/BK
1
3
ON/OFF SWITCH
1
PR
4
2
5
3
6
BR/W
7
R
8
9
R/BK
R/W
10
GY
11
W/BK
12
12
1
6
R/W
BR
7
3
Y/G
8
4
BL/BK
9
5
O/R
10
1
Y
2
1
5
2
6
7
8
4
2
3
1
W
CONTROLLER
12 0V
BK
60VA
W
BR/
W
W
P
P
R
3
T
BK
W/R
R/BK
BK/R
Y
Y
XFMR
24V
Y
BL
CKT. BREAKER
BR BR
120V
PUMP RELAY
120VAC COIL
G
GY
BK/W
BK
P
BR/W
3
AC
12
10
8
6
4
2
GY/ W
GY/ W
GROU ND
2
BK
4
3
2
1
G
7
GY
3
W
1
PR
4
2
1
PR
PR
P
P
24V COM
24V
LOW VOLT HARNE
DIGITA L HARN ES
F2
F4
X1
F5
X2
F6
X3
X10
X12
CONT
X9
DISPLAY
Y
Y
Y
2
3
BL
G
2
4
GY/W
GY/W
6
W
2
BK/W
4
S1/S2
1
3
5
1
3
5
GY
GY
G
BK/R
BK
S3/S4
BL
1
4
R/O
2
5
R/W
3
BL
R
R/BK
6
1
4
Y
2
5
Y
3
6
Y
GY
GY
G
IGNITER
G
MAIN UNIT
76
Page 77
10 Connection diagram (continued)
Installation & Operation Manual
VOLT HARNESS
ITAL HARNESS
F2
F4
CONTROLLER
X9
PLAY
BL
1
4
R/O
2
5
R/W
3
6
1
BL
2
R
3
R/BK
GY
GY
ITER
MAIN UNIT
G
Notes:
1. All wiring must be installed in accordance with : local, state , provincial and national code requirements per either N.E.C. in USA or C.S.A. in Canada.
2. If any original equipment wire as supplied with the appliance must be replaced , it must be replaced with wire
R/B K
1
Y
1
X13
X8
X7
X6 X5
X11
X4
20
W
2
19
BL
3
18
17
BL
5
16
R/B K
6
BL/BK
12
15
BR
7
14
W/BK
8
13
12
12
R
10
11
O/R
4
8
BL
1
10
R
2
11
O/B K
3
12
R
4
13
O/R
5
14
R/O
6
15
12
BR
7
16
IDENTIFICATION PLUG
MODEL SPECIFIC
CONSULT FACTORY
NOTE: NUMBER OF GA S VA LVES VARIES BY MODEL
R
R
R Y
O/
O
BK
Y
Y
LOW GAS
Y
SWITCH
3
21
S1
1
STAGE #1 ST AGE #2
R/BKY R/BK
Y R
21
1
3
2
S2
S1
3
2
STAGE #1 STAGE #3 STAGE #4
BURNER
GROU NDHSI
#1
1
G
2
3
4
GY/ W
5
GY/ W
6
BK
1
G
3
BK/R
5
GY
GY
G
MAIN UNIT HARNESS
2
W
BK/W
4
!
THIS HEATER MAY BE CONNECTED T O MORE THAN ONE BRANCH
DANGER
TO PREVENT ELECTRI CAL SHOCK
CIRCUI T. MORE THAN ONE DISCONNECT SWITCH MAY BE
REQUIRED TO DE-ENERGIZE THE EQUIPMENT FOR SERVICING
having same wire gauge (A WG) and rated for a minimum of 105°C
3. Actual connector block locations may vary from proper connector block locations when using diagrams to trouble shoot unit .
T
GY
Y/G
BR/W
BK/R
BK
W/R
R/W
W
PR
Y
W/BK
T
GY
T/W
R/W
BR/W
O
4
P
BL
2
O/R
1
BL
BL R
R
C21 C NONC
AUXILLIARY
BL
1
Y
2
FLOW SW ITCH
1 2OO/B K
T
NO
COM
BL
LWCO
1 2
NC
COM
AIR PROVE
SWTICH
1
BL
Y
O
O/B K
BLOCK
FLUE
SWITCH
O/B K
2 1
O
O/B K
2
1
3
2
4
FLOW
SWITCH
O
BL
O/BK
O
CHASSIS GROU ND
2 1
2 1
HI-LIMIT
LOW VOLT HARNESS
1 2
O/B K
O
1
3
GY/W
GY/W
R/O Y R/O
21
S3
4
3
R/O Y R/O
1
2
S3
5
STAGE #3
HSI#2
R/W Y R/ W
3
BURNER GROU ND
G
S4
6
213
BK
BK/
W
BK
2
R
3
W
4
G
W
W
HI
LO
NEU GND
BK
120V
BLOWER RELAY
120VAC COIL
NEU GND
BK/
W
BREAKER
BK
W
LO
120V
BK
HI
R
W
G
BK
HI/LO SPEED RELAY
CIRCUIT
50VA 60VA 75VA
100VA
.
GAS VALVE XF MR
those shown on diagrams . Refer to actual components for
OPT . ALARM
LOW VOLTAGE HARNESS
3
6
120V
ALARM RELAY
120VAC COIL
GROUNDING
OPTI ON
++
JUMPER
CONNECTION
3
BOARD
GBK
1
BK
TO
XFM R
3
W
FIELD
OPTIONS
T= TA N Y=YEL LOW BR=BROWN
G=GR EEN GY=GR AY R= RE D
BLY
2
3 1
R
TO
O/B K
BL
G
CONNECTION
BOARD
O/BK
2
O
1
O12
O/BK
DIGITAL
HARNESS
2-SPD BLOWER
1
2
3
4
BK/
W
R
LO
HI
120V
120VAC COIL
24V
LWCO 24VAC
LO - GAS
120V
BK/
R
BL
Y
3
2
6
5
HI-GAS
W
1
4
T
3
2
1
BL
BL
SILENC ING
SWITCH
1
GY
3
BL
Y
T
TEST
LWCO
PROBE
~~~~
~~~~
~~~~
RESET
PR
PR
P
6
P
5 4
PR
1
PR
ALARM
BELL
Y
BL
R
O
2
G
1
2
1
TO
2
PWR
3
W
MODBUS ADAPTER
FACTORY
OPTIONS
WIRE COLOR REFERENCE
W = WHITE BK = BLACK PR=PURPL E
BL=BLUE P=PIN K O=OR ANGE
Y/G = YELLOW WITH GREEN STR IPE
LBL20082 R EV A
BL
1
45
R
BL
G
2
77
Page 78
11 Ladder diagram
Installation & Operation Manual
WHERE POSSIBLE, SWITCHES ARE SHOWN WITHOUT UTILITIE
S (GAS,
WATER OR ELECTRICITY) CONNECTED TO THE UNIT. AS SUCH, ACTUAL
SWITCH STATES MAY VARY FROM THOSE SHOWN ON DIAGRAMS
DEPENDING UPON W HETHER UTILITIES ARE CONNECTED OR A FAULT
CONDITION IS PRESENT. SEE WIRING DIAGRAM FOR ADDIT
BOX DEPICTS
OPTIONAL ITEMS
LOW VOLTAGE
120 VAC
RELAY
UNIT PUMP
GL
N
N
BLOWER
BLOWER RELAY
HIGH
STRIP
TERMINAL
LOW
SPEED
SPEED
X1-8X1-8X1-8
UNIT PUMP RELAY
HI/LO SPEED RELAY
X2-4
X1-2
STRIP
TERMINAL
RECIRC
SYSTEM /
PUMP RELAY
STRIP
TERMINAL
X1-1
DHW PUMP
X1-4
X1-3
RELAY
(BOILER)
X1-10
STAGE 1 HSI
X1-7
X2-2
STAGE 3 HSI
X2-1
IONAL NOTES.
X1-2
X1-12
CHASSIS
X1-3
TRANSFORMER
X10-4
X10-5
STAGE 1 GAS VALVE
X10-2
X10-1
INTERGRATED CONTROL BOARD
TRANSFORMER
X12-4
X10-6
X12-5
X12-6
STAGE 2 GAS VALVE
STAGE 3 GAS VALVE
STAGE 4 GAS VALVE
X10-3
X12-2
X12-3
X6-4
X12-1
78
HI/LO SPEED
BLOWER
RELAY
RELAY
RELAY
HI/LO SPEED
ON/OFF
SWITCH
BOARD
CONTROL
INTERGRATED
F2
-6
X1
F4
3.15A
5A
F5
F6
5A
5A
MODBUS INTERFACE BOARD
CIRCUIT BREAKER
X1-1
CIRCUIT BREAKER OR FUSE
HIGH LIMIT
MANUAL RESET
Page 79
11 Ladder diagram (continued)
ALARM
CONTACT S
1
2
BOARD 1
CONNECTIO N
CN4-1
CN4-4
ALARM
SUPPLY
2ND POOL
LOUVER RELAY
RUNTIME
CONNECTIO N BOARD 1
SILENCE
ALARM RELAY
CONTACT S
CN4-5X3-1
CN4-6X3-2
CN5-11X6-1 X6-13 CN5-5
OUTDOOR
CONNECTION BOARD 2
SENSOR S5
SENSOR S8
CN1-2
Installation & Operation Manual
MODBUS
RTU
A
SHIELD
-1
CN1
10K
20K
SUPPLY
RETURN
SENSOR S6
SYSTEM / POOL
SENSOR S7
SYSTEM / POOL
CN1-5X8-14
CN1-6X8-13
INLET SENSOR S2
OUTLET SENSOR S1
2ND OUTLET SENSOR S9
-1
CN6
SHIELD
CASCADE
TANK
SENSOR S4
CONNECTION BOARD 1
CN1-1
X6-3
X4-3
B
CN1-3X6-1
CN1-2
X6-2
BOARD
MODBUS
INTERFACE
X4-1X8-10
X4-2
X3-3
X3-4
X6-3
(
(
(
(
(
TEST
J3-3
J2-3
PROBE
LOW WATER
CUTOFF
-2
J2
RESET
-1
J2
FLOW SWITCH
J3-2
J3-4
J3-6
J3-5
X6-5
X6-12
CONNECTIO N BOARD 1
HIGH GAS
BLOCKED FLUE
AIR PRESSURE
PRESS SWITCH
LOW GAS PRESS
X6-10
X6-7CN5-1
3 WAY VALVE
24V
X6-2CN5-8
X6-16CN5-7
OPEN
CLOSE
STAGE 1 / ENABLE
24V COM
CN5-6
X8-19
POOL
X8-11
BOILER
X6-6CN5-3
X13-1CN5-9
X6-15CN5-10
STAGE 2
STAGE 3
STAGE 4
X6-11CN5-12
TANK TSTAT
X8-5CN6-4
X6-14CN5-4
+
0-10V
LOUVER PROVING
X8-3
X8-2
X8-8
X8-1
X7-8CN6-5
X7-4CN6-10
X8-15CN6-9
-
BMS
INPUT
X8-7CN6-7
-
+
A
0-10V
RATE
OUTPUT
X8-6CN1-7
X8-17CN6-3
+
B
CONNECTION BOARD 2
CASCADE
X8-12 CN6-6
X8-16CN1-8
-
SPEED INPUT
SYSTEM PUMP
X8-18 CN6-8
DISPLAY BOARD
X8-20
X4
X11
COMPUTER
LBL20083 REV B
79
Page 80
Revision Notes: Revision A (ECO #C08226) initial release.
CFX-CHX-I-O Rev A
6/11