Littelfuse SIO-RTD User Manual

Protection Relays, Monitors & Systems
Temperature Monitoring
SIO-RTD SERIES
Temperature Input Monitor
Simplified Circuit Diagram
Description
Features & Benefits
FEATURES BENEFITS
8 Inputs
CSA Class 1 Zone 2 Hazardous-location Certified
Individually-selectable Input Type
Conformal Coating
Remote Monitoring
Single module can collect multiple data points
Can be mounted in hazardous areas
Flexible ; can be used with Pt100, Ni100, Ni120, Cu10 RTD or 4 -20 mA inputs
Protects circuit boards against corrosion and moisture
Up to 1.2 km away from network master
SUPPLEMENTAL MONITORING
M
RTD x 8
SIO-RTD
(Temperature Input Monitor)
RS-485 Modbus RTU
Ordering Information
CATALOG/ SYSTEM NUMBER CONTROL POWER, OUTPUT
SIO-RTD-02-00 24 Vdc, Modbus RTU
Notch Filter
Rejects noise from motor monitoring applications
For detailed wiring diagram, see page 86.
Specifications
Input Voltage 18 to 32 Vdc, 2W Dimensions H 87 mm (3.43”); W 112.5 mm (4.43”) ;
D 56 mm (2.2”) RT D Type s Pt100 (default), Ni100, Ni120, Cu10 RTD Range -40 to 200˚ C with open and short detection Analog Range 4-20 mA Accuracy (Pt100, Ni100, Ni120) 1˚ C (Cu10) 3˚ C (4-20 mA) 0.1 m A Lead Compensation Up to 20 Ω Communications Modbus RTU Conformally Coated Standard feature Warranty 5 years Mounting DIN, Surface
®
©2011 Littelfuse Startco Product Catalogue
37
www.startco.ca/products/sio-rtd