Littelfuse SE-701 User Manual

Protection Relays & Controls
Ground-Fault Protection–Grounded Systems
SE-701 SERIES (PGR-5701)
Ground-Fault Monitor
Simplified Circuit Diagram
A
CT
A
SUPPLY
B
C
Description
The SE-701 is a microprocessor-based ground-fault relay for resistance­and solidly-grounded systems. In addition to common systems, it is uniquely suited for use on systems with significant harmonic content. The SE-701 can provide main-plant protection, feeder-level protection, or individual-load protection. Proper current transformer selection provides the desired pickup range. The output contacts can be connected for use in protective tripping circuits or in alarm indication circuits. The analog output can be used with a PLC or a meter.
Features & Benefits
FEATURES BENEFITS
Adjustable pickup (1-99%)
Adjustable time delay (50 ms - 2.5 s)
Output contacts
Analog output (0 - 5 V)
CT-Loop monitoring Alarms when CT is not connected Selectable DFT or peak
detection filtering Harmonic filtering Eliminates nuisance tripping Non-volatile trip
memory Microprocessor based No calibration required, saves on maintenance cost
Universal power supply
Trip setting based on input CT primary, allows use with any CT. Minimum 50 mA with EFCT Series.
Adjustable trip delay allows quick protection and system coordination
Form A and Form B ground-fault output contacts for operation of separate annunciation and trip circuits
Allows for connecting an optional meter (PGA-0500) or a control system
Compatible with variable-speed drives
Retains trip state while de-energized to simplify troubleshooting
Allows operation in application where one side of PT is faulted, provides flexibility for numerous applications
SE-701 SERIES
L1
L2
(Ground-Fault Monitor)
Ordering Information
ORDERING NUMBER CONTROL POWER
SE-701-OU 120/240 Vac/ Vdc
SE-701-OD 12/24 Vdc
SE-701-OT 48 Vdc
SE-701-O3 24 Vac
ACCESSORIES REQUIREMENT
Current Transformer Required
PGA-0500 Optional
PMA-55, PMA-60 Optional
SE-EFVC Voltage Clamp Optional
Note: For o ptional conformal coati ng pleas e consult factory.
Accessories
A
B
Ground-Fault Current Transformer
Required current transformer model depends on application. We offer a variety of sensitive CTs with 5- and 30-A primaries.
PGA-0500 Analog % Current Meter
Optional panel-mounted analog meter displays ground-fault current as a percentage of the CT primary rating.
Specifications
IEEE Device Numbers Ground fault (50G/N, 51G/N) Input Voltage See ordering information Dimensions Trip Level Settings 1-99% CT-Primary Rating Trip Time Settings 0.05 -2.5 s Contact Operating Mode Selectable fail-safe or non-fail-safe Harmonic Filtering Standard feature Test Button Standard feature Reset Button Standard feature CT-Loop Monitoring Standard feature Output Contacts Isolated Form A and Form B Approvals
CE (European Union), C-Tick (Australian)
Analog Output 0-5 V Conformally coated Consult factory Warranty 5 years Mounting DIN, Surface (standard)
Panel (with PMA-55 or PMA-60 adapter)
H 75 mm (3.0"); W 55 mm (2.2"); D 115 mm (4.5")
CSA certified
, UL Listed (E340889),
© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/se-701
Based on Manual Rev 10-A-041213
Rev: 4-A-050213