Littelfuse SE-601 User Manual

Protection Relays & Controls
Ungrounded DC System
SE-601 SERIES (PGR-2601)
DC Ground-Fault Monitor
Simplified Circuit Diagram
+
A
UNGROUNDED
SUPPLY
SE-GRM SERIES
GROUND-REFERENCE MODULE
Description
The SE-601 is a microprocessor-based ground-fault relay for ungrounded dc systems. It provides sensitive ground-fault protection without the problems associated with nuisance tripping. Ground-fault current is sensed using an SE-GRM Series Ground-Reference Module—a resistor network that limits ground-fault current to 25 mA. The SE-601 is used on ungrounded dc systems ranging from industrial 24-Vdc control circuits to 1000-Vdc solar and transportation systems.
Features & Benefits
FEATURES BENEFITS
Adjustable pickup (1 - 20 mA)
Adjustable time delay (50 ms - 2.5 s)
Output contacts
Analog output (0 - 5 V)
Non-volatile trip Memory
Selectable contact operating mode
Microprocessor based No calibration required saves on maintenance cost
Ten settings provide a wide range of low-level protection
Adjustable trip delay allows quick protection or delayed response
Form A and Form B output contacts for operation of separate annunciation and trip circuits
Provides means for connecting to a meter (PGA-0500) or a control system
Retains trip state when de-energized to simplify troubleshooting
Selectable fail-safe or non-fail-safe operating modes allow connection to shunt or undervoltage breaker coil
-
SE-601
L1
L2
Ordering Information
ORDERING NUMBER CONTROL POWER
SE-601-OU 120/240 Vac/Vdc
SE-601-OD 12/24 Vdc
SE-601-OT 48 Vdc
ACCESSORIES REQUIREMENT
SE-GRM SERIES Required
PGA-0500 Optional
PMA-55 Optional
PMA-60 Optional
Note: For o ptiona l conformal coating p lease consult factory.
(DC Ground-Fault Monitor)
Accessories
A
SE-GRM Series Ground-Reference Module Required accessory, used to connect the SE-601 DC Ground-Fault Monitor to the DC bus.
PGA-0500 Analog % Current Meter
Optional panel-mounted analog meter displays ground-fault current as a percentage of 22 mA.
Specifications
IEEE Device Numbers DC Overcurrent Relay (76G) Input Voltage See ordering information Dimensions Trip Level Settings 1-20 mA Trip Time Settings 0.05 -2 .5 s Output Contacts Isolated Form A and Form B Contact Operating Mode Selectable fail-safe or non-fail-safe Test Button Local Reset Button Local and remote Analog Output 0-5 V Conformally Coated Consult factory Approvals
CE (European Union), C-Tick (Australian)
Warranty 5 years Mounting DIN, Surface (standard)
Panel (with PMA-55 or PMA-60 adapter)
H 75 mm (3.0”); W 55 mm (2.2”); D 115 mm (4.5”)
CSA certified
, UL Listed (E340889),
© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/se-601