Littelfuse SE-330HV User Manual

Protection Relays & Controls
NGR
L2
CT
L1
SE-330 SERIES
ER SERIES
(Sensing Resistor)
(NGR Monitor)
Neutral-Grounding-Resistor Monitoring
SE-330, SE-330HV SERIES (PGR-5330)
Neutral-Grounding-Resistor Monitor
Simplified Circuit Diagram
Description
The SE-330 is an advanced ground-fault and neutral-grounding­resistor monitoring relay. It measures neutral current, neutral-to­ground voltage, and neutral-to-ground resistance. It provides continuous monitoring of the neutral-to-ground path to verify that the neutral-grounding resistor (NGR) is intact. This is of utmost importance—an open NGR renders current-sensing ground-fault protection inoperative and could result in a false belief that the system is functioning properly. The SE-330 can be used with low- and medium-voltage transformers and generators with low- or high-resistance grounding used in processing, manufacturing, chemical, pulp and paper, petroleum, and water-treatment facilities. For high-voltage applications, use the SE-330HV. For applications that require conformance to Australian standard AS/NZS 2081.3:2002, see the SE-330AU.
Resistor Monitoring
The SE-330 combines the measured values of resistance, current, and voltage to continuously determine that the NGR is intact. It is able to detect a resistor failure with or without a ground fault present. Sensing resistors are matched to the system voltage and are used to monitor NGRs on systems up to 72 kV.
Ground-Fault Monitoring
The SE-330 uses an application-appropriate current transformer to reliably detect ground-fault currents as small as 100 mA. DFT
B
filtering ensures that false trips due to harmonic noise from adjustable-speed drives do not occur. Should the resistor open and a ground fault subsequently occur, the SE-330 will detect the fault through voltage measurement, while other current-only
A
sensing relays would be ineffective.
Pulsing Ground-Fault Location
For detailed wiring diagram, see adjacent page.
Ordering Information
ORDERING NUMBER
POWER SUPPLY
COMM CERTIFICATION
SE-330 - X X - X
0=RS-232
SE-330 for all apps. 35 kV or less
SE-330HV for 72 kV apps.
NOTE: For Australian applications, see the SE-330AU on pg. 38.
ACCESSORIES REQUIREMENT
0=120/240 Vac/Vdc
2=48 Vdc
1=RS-232 & DeviceNet
2=RS-232 & Profibus
3=RS-232 &
& Modbus
®
EtherNet/IP™
TCP
0=CSA,
UL, C-Tick
1=CSA, UL, CE, C-Tick
®
ER Series Sensing Resistor Required Current Transformer Required SE-IP65CVR-G Optional SE-MRE-600 Optional RK-332 Optional NGRM-ENC Optional
Littelfu se res erves the right to m ake product c hanges, without notice. Material in this docum ent is as accurate as known a t the time of publication. Visit Lit telfuse.c om for the mos t up-to-date inf ormation.
© 2013 Littelfuse Protection Relays & Controls
© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/se-330
K4 UNIT HEALTHY CONTACT
X
0=Normally Open
1=Normally Closed
The SE-330 is capable of controlling a pulsing contactor, which is used to switch the NGR resistance in a pulsing-compatible NGR package. The resulting ground-fault current is distinguishable from charging currents and noise and will only appear upstream of the ground fault, making fault location fast and easy, even without isolating feeders or interrupting loads.
Accessories
A
B
ER Series Sensing Resistor
Required interface between the power system and the SE-330/SE-330HV. Eliminates hazardous voltage levels at the relay.
EFCT Series Ground-Fault Current Transformer
Sensitive ground-fault current detection (5 A primary).
SE-CS30 Series Ground-Fault Current Transformer
Sensitive ground-fault current detection (30 A primary).
Other Current Transformer
For low-resistance NGRs choose a CT primary approximately equal to the NGR rating.
Rev: 4-B-050213
Based on Manual Rev 9
Protection Relays & Controls
Neutral-Grounding-Resistor Monitoring
SE-330, SE-330HV SERIES (PGR-5330)
Neutral-Grounding-Resistor Monitor
Features & Benefits
FEATURES IEEE # BENEFITS
Continuous NGR monitoring
Ground-fault detection
Adjustable pickup (2-100%)
Adjustable time delay (0.1 - 10 s)
Universal CT compatibility
Output contacts
Analog output (4 - 20 mA)
Pulsing output
Data logging
Harmonic filtering (DFT)
Local communications
Network communications
Software Selectable contact
operating mode Selectable reset mode Calibrate push button Unit-healthy output Conformal coating
3
50G/N, 51G/N,
59N
Detects resistor failure within seconds, reduces transient-overvoltage risk, removes risk of ground-fault-detection failure
Main or backup protection to detect a ground fault anywhere on the monitored system
Select greatest sensitivit y without false operation
Adjustable trip delay allows quick protection and system coordination
Allows the use of a CT that gives required ground-fault settings
Two Form C (Ground Fault and Resistor Fault), Two Form A (Trip/Pulse, Healthy)
Allows for connecting an optional PGA-0500 meter or control system
Control the operation of a pulsing ground-fault-location circuit
On-board 10-event recorder helps with system diagnostics
Eliminate false trips due to harmonic noise from ASDs
RS-232 port to view measured values, log to a PC and check event records
Remotely view measured values and event records, reset trips, and cause a remote trip
PC-interface software (SE-MON330) is included Selectable fail-safe or non-fail-safe operating modes allows connection to shunt or undervoltage breaker coil
or alarm circuit Selectable latching or auto-reset operation Ensures resistor-failure sensitivity is correct Verifies SE-330 is operating correctly Internal circuits are conformally coated to protect against corrosion and moisture
Typical Values
SYSTEM
VOLTAGE
(VOLTS)
480 5 55 ER-600VC 20 k
600 5 69 ER-600VC 20 k 2,400 5 277 ER-5KV 20 k 4,160 5 480 ER-5KV 20 k 7,200 10 416 ER-15KV 100 k
14,400 15 554 ER-15KV 100 k
DISCLAIMER: The above table is for illustrative purposes only. Actual values may differ based on a variety of individual system considerations, such as capacitive charging current and coordination study results.
Wiring Diagram
POWER SYSTEM NEUTRAL (X0)
SENSING RESISTOR
ER SERIES
N
CURRENT TRANSFORMER
EFCT FAMILY
NEUTRAL-GROUNDING RESISTOR SENSING RESISTOR
(required)
(required)
CONTROL POWER
G
CURRENT
(AMPERES)
1
2
3
R
6
7
A
8
9
10
B
11
NEUTRAL-GROUNDING­RESISTOR MONITOR
SE-330 SERIES
R
G
EFCT
1 A
5 A
COMMON
RESISTANCE
(OHMS)
UNIT
HEALTHY
ANALOG OUTPUT
4-20 mA
TRIP OR
PULSING
GROUND
FAU LT
RESISTOR
FAU LT
+24 Vdc
0 V
+
12
13
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
MODEL
RESET
PULSE ENABLE
RESISTANCE
(SWITCH S5 SETTING)
Ω Ω Ω Ω
Ω Ω
Specifications
IEEE Device Numbers Ground Fault (50G/N, 51G/N, 59N), Checking Relay (3), Lockout Relay (86)
Input Voltage See ordering information Dimensions H 213 mm (8.4"); W 98 mm (3.9"); D 132 mm (5.2") GF Trip-Level Settings 2-100% of CT-Primary Rating GF Trip-Time Settings 0.1-10 s Vn Trip-Level Settings 20-2,000 Vac (≤5 kV systems)
100-10,000 Vac (>5 kV systems)
Contact Operating Mode Selectable fail-safe or non-fail-safe (K1) Harmonic Filtering Standard feature Reset Button Standard feature Output Contacts Two Form A and two Form C Pulsing Circuit 1.0-3.0 s in 0.2 s increments Approvals
CE (European Union) optional, C-Tick (Australian) Communications RS-232; (standard) DeviceNet Ethernet (optional)
Analog Output 4-20 mA, self or loop powered Conformally Coated Standard feature Warranty 5 years Mounting Panel and Surface
Littelfu se res erves the right to m ake product c hanges, without notice. Material in this docum ent is as accurate as known a t the time of publication. Visit Lit telfuse.c om for the mos t up-to-date inf ormation.
© 2013 Littelfuse Protection Relays & Controls
© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/se-330
GROUND-FAULT
PICKUP LEVEL
(AMPERES)
2.5 170
2.5 200
2.5 800 3 1,700 2 170 x 5 = 850 3 340 x 5 = 1,700
CSA certified
, UL Listed (E340889),
V
PICKUP LEVEL
N
(VOLTS)
, Profibus®,
Rev: 4-B-050213
Based on Manual Rev 9