Littelfuse RLN series, RLS series Catalog Page

POWR-GARD® Fuse Datasheet
UL Class H
RLN/RLS SERIES RENEWABLE FUSES AND LKN/LKS SERIES LINKS
250/600 VAC • Renewable • 1-600 Amperes
Ordering Information
AMPER E RATINGS
1 6 20 45 90 175 350 2 8* 25 50 100 200 400 3 10 30 60 110 225
4 12 * 35 70 12 5 250 5 15 40 80 150 300
*RL S only. †These ampere ratings require two links per fuse.
TYPE VOLTA GE CATA LOG NUMBER SYS TE M NUMBER
FUSE 600 RLS020 0RLS020.T FUSE 250 RLN020 0RLN020.T
LINK 600 LKS025 0LKS025.S LINK 250 LKN030 0LKN030.S
† †
450 500
600
† †
Littelfuse RLN and RLS series renewable fuses are a quality product that have traditionally been used to provide low cost protection of general purpose feeder and branch circuits where available short-circuit currents do not exceed 10,000 amperes. However, generally increased levels of available fault current and the distinct possibility that renewable fuses may be improperly renewed, have rendered them unsafe. The use of these fuses in new applications is prohibited by law.
Applications
• General purpose residential and commercial circuits with little or no motor load.
• Replacement only
Features/Benefits
• Replaceable fuse links
• 10 kA Interrupting Rating
Specifications
Voltage Ratings: AC: 250 V (RLN); 600 V (RLS) Interrupting Ratings: AC: 10 kA rms symmetrical Ampere Range: 1 – 600 A Approvals: Standard 248-6, Class H
UL Listed (File No. E81895) CSA Certified (File No. LR29862)
Fuse Links: To order, specify LKN (250V) or LKS (600V) plus
ampere rating.
Web Resources
TC Curves, downloadable CAD drawings and other technical information:
www.littelfuse.com/rln www.littelfuse.com/rls
Recommended Fuseholders
LFH60 Series LFH25 Series
Still using Class H fuses?
Littelfuse offers several fuse and fuseblock combinations that can greatly improve electrical safety.
LLNRK/LLSRK FLNR/FLSR fuses LFR fuseholders
Renewable Fuse Guide for Proper Usage
• Renewable fuses should only be used where short-circuit currents are known to be less than 10,000 amperes, and where correct replacement of open links is assured.
• Renewable fuses and links are not recommended for new applications.
1
© JUNE 2011 Littelfuse POWR-GARD Productswww.littelfuse.com
POWR-GARD® Fuse Datasheet
A
A
E
UL Class H
RLN/RLS SERIES RENEWABLE FUSES AND LKN/LKS SERIES LINKS
Dimensions in inches (mm)
AMPERES
REF ER T O
FIG. NO.
1 – 30 1
35 – 60 1
70 – 100 2
110 – 200 2
225 – 400 2
450 – 600 2
B
FIG. 1
C
SERIES
RLN 2 (50.8)
RLS 5 (127.0)
RLN 3 (76.2)
1
RLS 5
RLN 5
RLS 7
RLN 7
RLS 9
RLN 8
RLS 11
RLN 10
RLS 13
⁄2 (139.7) 1 (25.4)
7
⁄8 (149.2) 1 (25.4) 1 (25.4) 11⁄16 (27.0)
7
⁄8 (200.0) 11⁄4 (31.8 ) 1 (25.4) 15⁄16 (33.3)
1
⁄8 (181.0 ) 11⁄2 (38 .1) 13⁄8 (34.9) 19⁄16 (39.7)
5
⁄8 (244.5) 13⁄4 (44.5) 13⁄8 (34.9) 127⁄32 (46.8)
5
⁄8 (219 .1) 2 (50.8) 17⁄8 (47. 6 ) 23⁄32 (53.2)
5
⁄8 (295.3) 21⁄2 (63.5) 17⁄8 (47. 6 ) 219⁄32 (65.9)
3
⁄8 (263.5) 21⁄2 (63.5) 21⁄4 (57.2) 219⁄32 (65.9)
3
⁄8 (339.7) 3 (76.2) 21⁄4 (57.2) 33⁄32 (78.6)
D
B
C
FD
G
FIG. 2
DIMENSIONS IN INC HES ( mm IN PARENTHESES)
A B C D E F G
1
⁄2 (12.7 )
3
⁄4 (19 .1)
3
⁄4 (19 .1)
1
⁄2 (12.7 )
5
⁄8 (15.9)
5
⁄8 (15.9)
5
⁄8 (15.9) 11⁄16 (27.0)
9
⁄16 (14.3)
13
⁄16 (20.6)
13
⁄16 (20.6)
1
⁄8 (3.2)
1
⁄8 (3.2)
3
⁄16 (4.8) 11⁄8 (28.6) 17⁄8 (47. 6 )
3
⁄16 (4.8) 11⁄8 (28.6) 23⁄32 (53.2)
1
⁄4 (6.4) 15⁄8 (41. 3) 213⁄32 (61.1 )
1
⁄4 (6.4) 15⁄8 (41. 3) 27⁄8 (73.0)
1
⁄4 (6.4) 2 ( 50.8) 27⁄8 (73.0)
1
⁄4 (6.4) 2 ( 50.8) 37⁄16 (8 7.3 )
3
⁄4 (19 .1) 15⁄16 (33.3)
3
⁄4 (19 .1) 19⁄16 (39.7)
2
© JUNE 2011 Littelfuse POWR-GARD Productswww.littelfuse.com
Loading...