7
KLPC Series POWR-PRO®Class L Fuses
600 V A C■Time-Delay■200 – 6000 Amperes
SPECIFICATIONS
Voltage Ratings: AC: 600 V olts
DC: 480 Volts
Interrupting Ratings: AC: 200,000 amperes rms symmetrical
300,000 amperes rms symmetrical
(Littelfuse self-certified).
DC:20,000 amperes
Ampere Range: 200 – 6000 amperes
Approvals: AC: Standard 248-10, Class L
UL Listed 601 – 6000 amps
(File No: E81895)
UL Recognized 200 – 600 amps
(File No: E71611)
CSA Certified 200 – 6000 amps
(File No: LR29862)
QPL Federal Specifications WF-1814
700 – 6000 amps
DC:Littelfuse self-certified
AMPERE RATINGS
200 500 800 1350 2000 3500
250 600 900 1400 2100 4000
300 601 1000 1500 2200 4500
350 650 1100 1600 2300 5000
400 700 1200 1800 2500 6000
450 750 1300 1900 3000
Example part number (series & amperage): KLPC 1000
KLPC series POWR-PRO
®
fuses provide ideal overcurrent
protection for circuits from 200 through 6000 amperes.KLPC
series POWR-PRO
®
fuses specification-grade construction
and performance meet or exceed the most stringent project
specifications: 99.9% pure silver links, silver-plated copper
end bells, glass-reinforced melamine bodies, O-ring seals
between body and end bells, and granular quartz fillers.
KLPC series POWR-PRO®fuses are the only UL listed Class
L fuses that provide a minimum of ten seconds time delay at
500% rated current and are also as current limiting as the
fastest Class L fuse on the market.On average, the peak letthrough currents of KLPC series fuses are 10% less than any
other “time-delay”Class L fuse.
APPLICATIONS
Service switches
Switchboard mains and feeders
Bolted pressure contact switches
Motor control center mains
Large motor branch circuits
UL Listed series-rated protection for molded case circuit
breaker panelboards and loadcenters.(See panelboard
manufacturers’literature for recommended fuse rating.)
Primary and secondary protection for transformers
Protection of power circuit breakers
FEATURES AND BENEFITS
■
Eliminate unnecessary downtime — KLPC POWR-
PRO
®
series fuses’ time delay withstands system surges
and keeps your circuits in service.
■
Best protection for system components — Maximum
current limitation means less equipment and system
damage when short circuits occur. Reduced damage
means that electrical service can be restored quickly,
reducing costly downtime, and often permitting equipment
repair rather than replacement.
■
Coordinates with other system components — KLPC
series fuses provide maximum coordination with fuses and
circuit breakers both on the line and load side of the fuses.
See the Fuseology section of this catalog for additional
information.
■
Eliminate need to oversize fuses — This may permit the
use of smaller less expensive switches, and, since the
lower rated fuses are more current limiting, equipment
receives even better protection.
■
300kA Interrupting Rating — Littelfuse self-certified to
300,000 amperes as standard. Meets future trend towards
higher available short circuit currents.