POWR-GARD® Fuse Datasheet
1.880
(47.8)
.850
(21.6)
1.50
(38.1)
.50
(12.7)
.41
(10.3)
.25
(6.4)
.125
(3.2)
35-60 A
0-30 A
CLASS CC KLKR SERIES FUSES
600 VAC • 300 VDC • Fast-Acting • 1/10-30 A
Description
KLKR Series Class CC fuses are fast-acting fuses intended
for general purpose branch circuit protection. Their compact
size, fast-acting overload response, and highly currentlimiting design make them ideal for use in OEM equipment
and control panels.
Features/Benefits
• Meets UL and CSA standards
• Class CC fuses are the smallest 600 V, 200,000 A.I.R.
fuses approved for branch circuit protection
• Rejection feature prevents use of fuses with lower
interrupting ratings or voltage ratings when used with
corresponding fuse holders
• Extremely current limiting reduces damage caused by
heating and magnetic effects of short-circuit currents
Specifications
Voltage Rating AC: 600 V
DC: 300 V
Amperage Rating
1
/10 – 30 A
Interrupting Rating AC: 200 kA rms symmetrical
DC: 20 kA
Material Body: Melamine
Caps: Nickel-plated Bronze
Fuse Weight
1
1
/10 – 1 A: .030 lb (13.61g)
1
/2 – 30 A: .034 lb (15.42g)
Approvals AC: Standard 248-4, Class CC
UL Listed
CSA Certified
1
/10-30 A (File: E81895)
1
/10-30 A (File: LR29862)
DC: Littelfuse self-certified
Environmental RoHS Compliant
Country of Origin Mexico
Ordering Information
AMPERAGE RATINGS
1
10
/
1
8
/
2
10
/
1
4
/
3
10
/
1
1 1/
2
/
3
4
/
1
2
2
2 1/
6 12
3 7 15
2
3 1/
8 20
4 9 25
2 5 10 30
Applications
• General purpose protections for equipment requiring
fast overload protection
Dimensions Inches (mm)

POWR-GARD® Fuse Datasheet
CLASS CC KLKR SERIES FUSES
Electrical Specifications
ORDERING
NUMBER
AMPERAGE
RATING
VOLTAGE
RATING
INTERRUPTING
RATING
WATTS LOSS AT 100%
RATED CURRENT (W)
WATTS LOSS AT 80%
RATED CURRENT (W)
TOTAL CLEARING I2T
(A2 SEC) 200 kA
AGENCY
APPROVALS
AC DC AC DC UL VDE
KLKR001.T 1 600 300 200 k A 20 kA 0.20 0.38 80 • • •
KLKR006.T 6 600 300 200 kA 20 kA 0.7 7 1. 36 210 • • •
KLKR012.T 12 600 300 200 kA 20 kA 0.83 1. 58 6520 • • •
KLKR030.T 30 600 300 200 kA 20 kA 2.10 3.75 1720 • • •
Peak Let-Thru Curve
1000000
100000
10000
30 A
25 A
20 A
PEAK LET-THRU IN AMPERES
1000
15 A
12 A
RoHS
100
100
1000
AVAILABLE FAULT CURRENT
SYMMETRICAL R. M. S. AMPERES
10000
100000
200000