POWR-GARD® Fuse Datasheet
CLASSCCKLKRSERIESFUSES
600 VAC • 300 VDC • Fast-Acting • 1/10-30 A
Description
KLKR Series Class CC fuses are fast-acting fuses intended for general purpose branch circuit protection. Their compact size, fast-acting overload response, and highly currentlimiting design make them ideal for use in OEM equipment and control panels.
Features/Benefits
•Meets UL and CSA standards
•Class CC fuses are the smallest 600 V, 200,000 A.I.R. fuses approved for branch circuit protection
•Rejection feature prevents use of fuses with lower interrupting ratings or voltage ratings when used with corresponding fuse holders
•Extremely current limiting reduces damage caused by heating and magnetic effects of short-circuit currents
Applications
•General purpose protections for equipment requiring fast overload protection
Specifications
Voltage Rating |
|
AC: 600 V |
|
|
|
|||
|
|
|
DC: 300 V |
|
|
|
||
Amperage Rating |
|
1/10 – 30 A |
|
|
|
|||
Interrupting Rating |
AC: 200 kA rms symmetrical |
|
||||||
|
|
|
DC: 20 kA |
|
|
|
||
Material |
|
Body: Melamine |
|
|
|
|||
|
|
|
Caps: Nickel-plated Bronze |
|
||||
Fuse Weight |
|
1/10 – 1 A: .030 lb (13.61g) |
|
|||||
|
|
|
11/2 – 30 A: .034 lb (15.42g) |
|
||||
Approvals |
|
AC: Standard 248-4, Class CC |
|
|||||
|
|
|
|
UL Listed 1/10-30 A (File: E81895) |
|
|||
|
|
|
|
CSA Certified 1/10-30 A (File: LR29862) |
||||
|
|
|
DC: Littelfuse self-certified |
|
||||
Environmental |
|
RoHS Compliant |
|
|
|
|||
Country of Origin |
|
Mexico |
|
|
|
|||
Ordering Information |
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
AMPERAGE RATINGS |
|
|
|
||
1/10 |
|
1/2 |
|
2 1/2 |
|
6 |
|
12 |
1/8 |
|
3/4 |
|
3 |
|
7 |
|
15 |
2/10 |
|
1 |
|
3 1/2 |
|
8 |
|
20 |
1/4 |
|
1 1/2 |
|
4 |
|
9 |
|
25 |
3/10 |
|
2 |
|
5 |
|
10 |
|
30 |
Dimensions Inches (mm)
1.50 |
.25 |
(6.4) |
|
(38.1) |
|
0-30 A |
.41 |
(10.3) |
|
.50 |
.125 |
(3.2) |
|
(12.7) |
|
POWR-GARD® Fuse Datasheet
CLASSCCKLKRSERIESFUSES
Electrical Specifications
ORDERING |
AMPERAGE |
VOLTAGE |
INTERRUPTING |
WATTS LOSS AT 100% |
WATTS LOSS AT 80% |
TOTAL CLEARING I2T |
AGENCY |
|
RATING |
RATING |
APPROVALS RoHS |
||||||
NUMBER |
RATING |
RATED CURRENT (W) |
RATED CURRENT (W) |
2 |
||||
|
|
(A SEC) 200 kA |
|
|
|
AC |
DC |
AC |
DC |
|
|
|
|
UL |
VDE |
|
KLKR001.T |
1 |
600 |
300 |
200 kA |
20 kA |
|
0.20 |
0.38 |
80 |
• |
• |
• |
KLKR006.T |
6 |
600 |
300 |
200 kA |
20 kA |
|
0.77 |
1.36 |
210 |
• |
• |
• |
KLKR012.T |
12 |
600 |
300 |
200 kA |
20 kA |
|
0.83 |
1.58 |
6520 |
• |
• |
• |
KLKR030.T |
30 |
600 |
300 |
200 kA |
20 kA |
|
2.10 |
3.75 |
1720 |
• |
• |
• |
Peak Let-Thru Curve |
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
1000000 |
|
|
|
|
|
|
|
|
|
|
|
|
100000 |
|
|
|
|
|
|
|
|
|
|
|
<![if ! IE]> <![endif]>AMPERES |
10000 |
|
|
|
|
|
|
|
|
|
|
|
<![if ! IE]> <![endif]>THRU IN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
30 A |
|
|
|
|
|
|
|
<![if ! IE]> <![endif]>LET- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
25 A |
|
|
|
|
|
|
|
<![if ! IE]> <![endif]>PEAK |
|
|
|
|
|
20 A |
|
|
|
|
|
|
|
|
|
|
|
15 A |
|
|
|
|
|
|
|
|
|
|
|
|
|
12 A |
|
|
|
|
|
|
|
1000 |
|
|
|
|
|
|
|
|
|
|
|
|
100 |
|
|
|
|
|
|
|
|
|
|
|
|
<![if ! IE]> <![endif]>100 |
|
<![if ! IE]> <![endif]>1000 |
<![if ! IE]> <![endif]>10000 |
<![if ! IE]> <![endif]>100000 |
<![if ! IE]> <![endif]>200000 |
|
|
|
|
|
|
|
|
|
AVAILABLE FAULT CURRENT |
|
|
|
|
|
|
|
|
|
|
|
|
SYMMETRICAL R. M. S. AMPERES |
|
|
|
|
|