“dangerous voltage” that poses risk of electric shock.
Read Instructions - All safety and
operating instructions should be read
before installing or operating the VMC1
Video Intercom system.
Retain Instructions - The safety and
operating instructions should be retained
for future reference.
Heed Warnings - All warnings on the
appliance and in the operating instructions
should be adhered to.
Follow Instructions - All operating and
use instructions should be followed.
Water and Moisture - The appliance
should not be used near water - for
example: near bathtub, washbowl, kitchen
sink, laundry tub, in a wet basement, or
near a swimming pool, and the like. Doing
so can create fire or shock hazards and
impair the warranty.
Attachments - Do not use attachments not
recommended by the product manufacturer
as they may cause hazards.
Ventilation - The appliance should be
situated so that its location or position does
not interfere with its proper ventilation.
For example, the appliance should not be
situated on a bed, sofa, rug, or similar surface
that may block the ventilation openings: or,
placed in a built in installation, such as a
bookcase or cabinet that may impede the
flow of air to the ventilation openings.
Heat - The appliance should be situated
away from heat sources such as radiators,
heat registers, stoves, or other appliances
(including amplifiers) that produce heat.
Power Sources - The appliance should be
connected to a power supply only of the
type described in the operating instructions
or as marked on the appliance.
Grounding or Polarization - Precautions
should be taken so that the grounding or
polarization means of an appliance is not
defeated.
operating, maintenance, and servicing instructions for
Power Lines - Locate outdoor antennas
away from power lines.
Outdoor Antenna Grounding - If an
outside antenna is connected to the
receiver, be sure the antenna system is
grounded so as to provide some protection
against voltage surges and built up static
charges. Section 810 of the National
Electrical Code, ANSI/NFPA No. 70 1984,
provides information with respect to proper
grounding of the mast and supporting
structure, grounding of the lead in wire
to an antenna discharge unit, size of
grounding conductors, location of antenna
discharge unit, connection to grounding
electrodes, and requirements for the
grounding electrode (see fi gure).
Object and Liquid Entry - Never push
objects of any kind into this product through
openings as they may touch dangerous
voltage points or short out parts that could
result in a fi re or electric shock. Never spill
liquid of any kind on the product.
CAUTION!
This sign warns user about important
this product.
Servicing - The user should not
attempt to service the appliance
beyond that described in the operating
instructions. All other servicing should be
referred to qualifi ed service personnel.
Damage Requiring Service - The
appliance should be serviced by qualifi ed
service personnel when:
• The power supply cord or the plug
has been damaged; or Objects have
fallen, or liquid has been spilled into
the appliance; or
• The appliance has been exposed to
rain; or
• The appliance does not appear to
operate normally or exhibits a marked
change in performance; or
• The appliance has been dropped, or
the enclosure damaged.
When the product exhibits a distinct
change in performance - this indicates a
need for service.
Replacement Parts - When replacement
parts are required, be sure the service
technician has used replacement parts
specifi ed by the manufacturer or have the
same characteristics as the original part.
Unauthorized substitutions may result in
fi re, electric shock, or other hazards.
Safety Check - Upon completion of any
service or repairs to this product, ask
the service technician to perform safety
checks to determine that the product is in
proper operating condition.
Wall or Ceiling Mounting - The product
should be mounted to a wall or ceiling only
as recommended by the manufacturer.
Keep this manual in a safe place for future reference.
To replace this manual, download available from Linear Web site:www.linearcorp.com
IMPORTANT DO’S & DON’TS
✔ DO ensure that all instructions have been followed before
power is applied to system. The installation shall be carried
out in accordance with all applicable installation rules.
✔ DO use only Cat-5 & RG-6 and specifi ed wires called out in
these instructions. The cable is designed and constructed
with electrical specifi cations necessary for proper audio
performance.
✔ DO use only a damp cloth to clean the exterior plastics on
the VMC1 Master Station and Room Stations.
✔ DO NOT use liquid or aerosols.✔ DO make gradual bends of the cable where necessary -- no
sharper than 1” radius.
✔ DO dress the cables neatly with cable ties or Velcro™
wraps. Use loose or moderate pressure.
✔ DO use cable-pulling lubricant only for cable runs that may
otherwise require great force to install. When cable lubricant
is used, read the instructions to be sure it is compatible with
the cable jacket material (PVC or FEP).
✔ DO avoid stressing cable conductors, limit pulling tension to
25 pounds or less as specifi ed by EIA/TIA-568A standard.
Pull cables gradually and with constant tension, taking care
not to crush or pinch bundles.
✔ DO use grommets to protect the cable where passing
through metal studs or anything that can possibly damage
them.
✔ DO test every installed cable run with a cable tester. “Toning”
alone is not acceptable.
✔ DO label every termination point. Use a unique identifi er
for each cable run. It will make moves, adds, changes, and
troubleshooting easier.
✔ DO support horizontal cable bundles using board supports,
J-hooks, or cable trays.
✔ DO have signal cables cross at right angles to power cables
to minimize induced interference.
✔ DO always obey all local and national fi re and building
codes. Be sure to “fi re-stop” all cables that penetrate a fi rewall. Use plenum-rated cable where mandated.
✔ DO have a licensed electrician to run a 120 VAC line from A
DEDICATED 15-AMP BREAKER to the VMC1 power supply.
✔ DO Use Cat-5 wire for all VMC1 wire runs. ✔ DO label all wire runs. Connecting the wires to the VMC1
master, room station, or door station incorrectly may result
in system damage.
✔ DO NOT STAPLE CABLES. Staples cause shorts.
✔ DO NOT SPLICE CABLES. Splices are unreliable and
defeat the signal isolation properties of the cable.
✔ DO keep cables at least 18 inches from fl uorescent light
fi xtures, Dimmer controls, and all other wiring. This includes
AC wiring, security cable, and other control wires. These can
cause a “hum” or “buzzing” sound.
✔ DO keep cables away from objects such as heating and air
conditioning ducts, metal construction plates, and anything
else with sharp edges that can damage the cables.
✔ DO follow the grounding and bonding requirements
established by Electrical Code TIA standard 607, and
equipment manufacturer’s specifi cations.
✔ DO NOT locate the VMC1 Master Station or Room Stations
on an exterior wall.
✔ DO NOT locate the VMC1 Master Station or Room Stations
in any wall cavity with any other electrical wiring in the
cavity.
✔ DO NOT attach non line-level audio devices or non M&S
authorized equipment to the system.
✔ DO NOT power up Master Station until all stations are
connected.
✔ DO NOT splice or repair cables damaged during wire
pulling, install a new cable.
✔ DO NOT coil or bundle the cables. This can cause electronic
feedback.
✔ DO NOT over-tighten the screws for the stations or the
intercom Master Station to prevent cracking.
✔ DO NOT install any station or speaker cables inside the 120
VAC transformer enclosure.
✔ DO NOT tie cables to electrical conduits or lay cables on
electrical fi xtures.
✔ DO NOT allow the cable to be sharply bent or kinked at any
time.
✔ DO NOT install cables “taut” anywhere. Good installation
should have cables loose, but never sagging.
✔ DO NOT run signal and power cables parallel without
adequate separation to minimize interference.
✔ DO NOT exert more than 25 pounds of tension on 4-pair
cables.
✔ DO NOT step on Cat-5 cable during installation.✔ DO NOT overtighten the cable ties, apply cable ties loosely,
with random spacing.
✔ DO NOT untwist the wire pairs in Cat-5 cable more than 1/2”
to avoid crosstalk.
Keep this manual in a safe place for future reference.
To replace this manual, download available from Linear Web site:www.linearcorp.com
The VMC1H installation rough-in prepares the home to
accommodate the video intercom system. A VMC1MB
mounting bracket is necessary for the Master Station. Room
stations and the Alloy Color Video Door Station (VMC1VDS)
can be mounted directly onto fi nished walls. All other door
stations require a rough-in enclosure (VMC1HR). The VMC1HR
is also recommended for installing room stations in new
construction or installations where the drywall has not yet
been installed.
Rough-in Kit
The VMC1H Rough-in Kit includes:
1 - (VMC1MB) Master Station mounting bracket
1 - (TE6D) Power Supply
1 - (101093) FM dipole antenna (#3)
1 - (226804) 300 ohm to 75 ohm F female Balum
1 - (250106-2) AM Antenna wire, Orange, 25 feet
1 - (233103) H628 Data Hub (#4)
VMC1MB
233103
TE6D
101093
226804250106-2
4
Tools
Most are required for purposes of this installation, but may
vary according to installer preferences.
WIRE STRIPPERS/CUTTER
110 PUNCH-DOWN TOOL
Materials Required
POWER DRILL WITH 1” AUGER
PHILLIPS SCREWDRIVER
TAPE MEASURE
COAX CABLE
MOUNTING SCREWS
(VARIOUS SIZES)
HAMMER
CAT-5 CABLE
DRYWALL SAW
14/18 GAUGE WIRE
LEVEL
0-M
10
0.5
50
50
250
200
500
+-
600
10
50
250
VOLTMETER
5
Overview
The VMC1 System
Designed for installation in new homes, the VMC1 is a Whole
House Color Video Security Intercom system that provides
room to room communication, multiple camera support,
basic home automation controls, and video security for mid to
large residential applications. VMC1 provide years of service
and security for the homeowner as many people move into
‘smart home’ environment. New housing takes advantage of
state of the art electronics, internet, and security applications
such as video surveillance and monitoring. VMC1 provides up
to 20 remote intercom stations, three video camera stations,
and offers music and communication for the whole house.
With multiple 12 volt Control Outputs, VMC1 can trigger
lights, monitors, voice and text message alerts, and e-mail
door chime alerts delivered to a smart phone. VMC1 offers a
wide range of capacities with expanded options, accessories,
and recommended parts. (See Appendix A).
It is important that each step of the installation be
carefully completed by the installer. In the event you need
troubleshooting assistance, please call our technical support
staff at1-800-421-1587.
General Information
The following general procedures must be observed in
relation to the location and installation of VMC1 components:
Where stations are to be installed outdoors, appropriate
measures to provide protection from the weather are to be
taken.
The power supply should be located in an area with suffi cient
space for heat dissipation.
Guidelines for maximum cable lengths as set out in this
manual are to be observed to avoid the possibility of operating
problems due to excessive cable voltage drop.
Interference
The circuitry of the intercom is designed to minimize the
effects of Radio Frequency Interference (RFI); and there will
be minimal and occasional radio frequency interference as
power outages, lightning storms, and any electrical apparatus
can affect the system. To reduce instances of interference,
reduce any unwanted audible buzz in audio appliances
such as microphone amplifi er, speaker amplifi er, car radio,
telephones etc, you add on-board EMI fi lters or special layout
techniques to help bypass EMI or improving RF immunity.
Most circuits have integrated RF fi lters or special design that
prevents demodulation of high-frequency carriers. The use of
microwaves, cell phones, cable television, bug zappers, even
heating pads in close proximity, can create interference.
Master Station
The Master Station should be positioned at a suggested
height of 4-1/2’ to 5-1/2’ from the fl oor to the center of the
unit. As all wiring from other stations is generally terminated
at the rear of the Master Station, the wall should be no less
than 3 inches in depth. Use the VMC1MB to provide adequate
support for the unit.
Room Stations
To avoid audio feedback, Room Stations should be kept at least
10 feet away from other stations. Never have more than one
station in any one room and avoid mounting stations in the
same wall cavity (i.e. directly below and above one another in
a two-story house). A suitable height is generally 4.5 feet from
the fl oor to the center of the unit. For Room Stations mounted
on wood frame walls, place near a stud to allow for adequate
support. For tiled surfaces, install a wall box before lining or
tiling the walls. Cut the tiles to the inside dimensions of the
wall box. Where Room Stations are mounted outside and are
exposed to the weather, the fi tting of weatherproof covers is
recommended (p/n DSWS). Stations must not be installed in
saunas.
Door Stations
Door Stations are best located adjacent to the front door
or at the front gate at a suggested height of 4’-6” and may
require a wall box depending upon the surface to which they
are to be affi xed. Door Stations are weather resistant, but
should not be exposed directly to rain or extreme weather.
Any station exposed to the weather requires a weather shield.
When equipped with the appropriate weather shield the Door
Station is designed to meet ANSI/IEC 60529 IP31 weather
proof standards.
Gates and Entrances
Where stations are to be installed in brick or concrete columns
at a front gate, the cable should be run in conduit from the
station to below ground level and back to the house.
Cameras
For Door Stations fi tted with cameras, consideration must be
given to the viewing area of the camera taking factors such as
lighting and sun exposure into account.
Power Supply
The Power Supply should be attached to the VMC1MB as
directed. Improper installation of the Power Supply can lead
to unit malfunction and void the warranty. The Power Supply
needs suffi cient space to dissipate heat effectively.
AM & FM Antennas
The antenna arrangement is critical to the installation for quality
radio reception. Place AM and FM antennas at the highest
point of the roof and at least 6 feet away from any electrical
or intercom wiring. Both AM and FM antennas are directional,
and correct positioning requires some experimentation to
achieve the best possible result. Antenna wires should also
be positioned at the highest and most accessible point in
the roof. Allow additional cable at the mounting bracket for
termination, at least 3 feet for the Master Station.
6
Cables and Wiring
Excellent locations to run cables include:
• Roof space
• False ceilings/ bulkhead area
• Through and/or around external walls
• Under fl oors (subject to access being available)
• Underground in conduit
✓ NOTE: Keep Intercom cables far from any AC wiring. Avoid running
intercom cable in parallel to AC or any other type of wiring. Avoid placing
joins or splices in cables. Locate cables where there is access for future
servicing.
Maximum Length for Cable Runs
The system can be “home-run wired” from a central point or
“daisy chained” from station to station. However, the number
of stations on a daisy chain run governs the overall length
of the run. The tables below show the relationship between
the length on a cable run and the number of room stations
permitted and the maximum cable run to a Door Station.
✓ NOTE: The tables are based on the use of Cat-5 or Cat-6 cable. Where
required, the wire lengths maximum distances can be doubled by
running 12 AWG speaker wire in parallel with the POS & NEG wires. It
is important that the POS and NEG wires are balanced in terms of the
type of wire and the number of wires being used - i.e. if a Cat-5 wire and
12 AWG speaker wire are being used for the positive connection, a Cat-5
wire and a 12 AWG speaker wire should also be used for the negative
connection.
Wiring Information
Cable Type and Confi guration
The general intercom functions for VMC1 can be cabled using
Cat-5 or Cat-6 cables. If required, 6-conductor telephone
cables can be used provided the system is confi gured for
6-wire operation.
Be sure to clearly tag all cables to identify any damaged cables
or other system faults. See the table below for Cat-5 wire color
recommendations.
ROOM STATIONS SHOULD
BE AT LEAST TEN FEET
APART FROM ONE
ANOTHER
MAXIMUM CABLE LENGTH TO ROOM STATIONS NUMBER OF STATIONS ALLOWED
100 yards1 Room Station
50 yards2 Room Stations
33 yards3 Room Stations
25 yards4 Room Stations
MAXIMUM CABLE LENGTH TO DOOR STATIONSNUMBER OF STATIONS ALLOWED
80 yards1 Door Station
MASTER STATION CONNECTIONVIDEO DOOR STATIONNON-VIDEO DOOR STATIONROOM STATIONWIRING
POS
NEGGreenGreenGreen
TCOrange WhiteOrange WhiteOrange White
VLCOrange
VLCxOrangeOrange
COM1Blue WhiteBlue WhiteBlue White
COM2BlueBlueBlue
MUS1Brown White
MUS2Brown
VIDxSignal
GNDGround
AUXYellowOptional
Green WhiteGreen WhiteGreen White
Cat-5/6
Optional Video SignalBrown White
Optional Video GroundBrown
Cat-5/6
7
Master Station Rough-In
VMC1MB Master Station Mounting Bracket
The VMC1MB mounts fl ush with the wall stud and holds the
Master Station and Power Supply (See Figure 1). Position the
VMC1MB at a suggested height of 4-1/2 to 5-1/2 feet from the
fl oor to center of the unit. As all wiring from other stations
is generally terminated at the rear of the Master Station, the
wall should be no less than 3 inches deep. If required, install
additional wood shims or metal rough-in enclosures to allow
for adequate support of the Master Station.
✓ IMPORTANT: Install the Master Station in a cavity wall to allow for the
wiring behind it. Do not install in a brick wall. For wall tiling around the
Master Station, ensure that it is mounted either completely within or
clear of tile to avoid an uneven surface. Be sure to allow at least 10” of
space below Master Station Bracket and fi rebreaks for Power Supply.
This is also necessary for clearance when installing the Master Station
Mounting Bracket into pre-cut drywall opening.
The VMC1MB has a correct orientation, so review Figures 1
and 2 to be sure it is right side up.
WALL STUD
VMC1MB Installation - Unfi nished Wall
Install the VMC1MB fl ush with the front of the wall stud and
fasten in place with screws as shown. After drywall has been
installed, cut out an opening to the inside dimensions of the
VMC1MB (7-1/4” x 11.”).
MOUNT
BRACKET
FLUSH WITH
FRONT OF
WALL STUD
BRACKET
FLANGE
FRONT VIEW
VMC1MB
MASTER STATION
BRACKET
POWER SUPPLY (TE6D)
MOUNTS TO FLANGE ON
MASTER STATION BRACKET
MOUNT BRACKET AT LEAST
10” FROM ANY FIREBREAK
TRACE THIS AREA
AS A TEMPLATE
FOR MASTER
STATION OPENING
ON DRYWALL
(7-1/4” x 11”)
WALL STUDS
VMC1MB
MASTER
STATION BRACKET
FIREBREAK
4’-5” to 5’-5”
MOUNTING HEIGHT
FROM FLOOR TO
CENTER LINE OF
BRACKET
Figure 1. Installing Bracket - Unfi nished Wall
8
VMC1MB Installation - Finished Wall
Cut out an opening in the drywall (Height 7-1/4” x Width 11”)
but do not cut right up against the wall stud. Allow 5/8”
clearance between drywall opening and stud. This ensures that
drywall will overlap bracket (See Figure 2). Slide the VMC1MB
vertically, then turn clockwise 90˚. Mount in place onto stud
using fasteners as shown. Hang Power Supply on VMC1MB
in the lower right corner as shown. It may be necessary to
lightly tap Power Supply in place onto VMC1MB fl ange with
a hammer.
Master Station Rough-In
TRACE THIS AREA
AS A TEMPLATE
FOR MASTER
STATION OPENING
ON DRYWALL
(7-1/4” x 11”)
CUT OPENING
5/8” FROM STUD
DRYWALL OPENING
IS 5/8” FROM STUD
FRONT VIEW
DRYWALL
SLIDE VMC1MB BRACKET
VERTICALLY INTO DRYWALL
OPENING
VMC1MB
STUD
STUD BEHIND
DRYWALL
11”
CUT DRYWALL
OPENING
7-1/4”
FRONT VIEW
DRYWALL
THEN TURN BRACKET 90°
CLOCKWISE AND MOUNT
TO STUD
FRONT VIEW
DRYWALL
OVERLAPS
BRACKET
DRYWALL
HANG POWER
SUPPLY ON VMC1MB
BRACKET AS SHOWN.
USE HAMMER TO LIGHTLY
TAP INTO PLACE ON MASTER
STATION BRACKET FLANGE
Figure 2. Installing Bracket - Finished Wall
DRYWALL
9
Room Station Rough-In
Room Station Mounting
The Room Stations are normally mounted at a height from the
fl oor of: 4-1/2’ to 5’. The Room Stations are not designed to be
installed outdoors.
Room Station Installation - Unfi nished Wall
For an unfi nished wall it is recommended that the VMC1HR
rough-in enclosure be used. Identify the location where the
Room Station is to be installed.
Attach the Rough-In Enclosure to the stud using the two inner
pre-punched holes (see Figure 3). The outside holes on the
wings of the box are to be used to mount the room station
and not to attach the Rough-in Enclosure to the stud.
Pull the Cat-5 wires through the hole in the back of the Roughin Enclosure and make a knot so they do not fall back into the
wall once the drywall is installed.
After drywall is installed, cut out an opening to the inside
dimensions of the VMC1HR utilizing the inside of the box as a
guide (see Figure 3 ).
Room Station Installation - Finished Wall
Identify the location where the Room Station is to be installed.
Cut a 3-1/2” x 7-3/4” rectangular hole in the drywall. When
possible, one short edge should be situated against a wall stud
to provide added support when installing the Room Station.
Pull the wire through the hole and attach to the drywall so it
will not fall back into the wall cavity.
Room Station Auxiliary Activation
When operating in single digit mode, each Room Station
can activate the Auxiliary Control Output (CO) triggers at the
Master Station.
Pull a yellow 18 gauge wire from the VMC1MB to the Room
Station location. Following this color convention will assist in
the fi nal installation of the VMC1 system.
Pull the yellow wire through the hole in the back of the
Rough-In Enclosure and loop it through so it does not fall back
into the wall once the drywall is installed.
USE INNER HOLES FOR
MOUNTING ROUGH-IN
ENCLOSURE TO STUD
VMC1RS-WH
ROOM STATION
MOUNTING PLATE
ELECTRONICS
PANEL
GRILLE
PRE-DRYWALL ROOM STATION
INSTALLATION
-
VOLUME
1
+
2
3
5
4
6
PRIV
MON
7
MUS
CLEAR
HOUSE
DOOR
AUX
BEZEL
VMC1RS-WH
ROOM STATION ROUGH-IN
ENCLOSURE (SEE DRAWING A)
7-3/4”
CAT5 CABLE LOOPED
WITH EXCESS AMOUNT
4’-6” to 5’-0”
MOUNTING HEIGHT
FROM FLOOR LINE
DRYWALL
ANCHORS
3-1/2”
VMC1HR
DRYWALL
DRAWING A
STUDS
ROOM STATION ROUGH-IN
ENCLOSURE
VMC1HR
10
-
VOLUME
1
+
2
3
5
4
6
PRIV
MON
7
MUS
CLEAR
HOUSE
DOOR
AUX
POST-DRYWALL ROOM STATION
INSTALLATION
Figure 3. Pre-Drywall and Post-Drywall Room Station Installation
VMC1VDS Door Station Rough-in
The VMC1VDS is a metal door station with a 90 degree
horizontal viewing area. It is normally mounted at a height
from the fl oor of: 55” – 60”. When installing the VMC1VDS be
aware of the camera location and the direction of sunlight and
other ambient light. Direct sun or lighting into the lens of the
VMC1VDS camera may impact the video quality. Additionally,
exposure to extreme weather conditions is not recommended.
For added protection against weather, the VMC1VDS should
be equipped with a VDSWS-T weather shield. The installation
of the VDSWS-T is shown in Figure 4.
✓ NOTE: When removing allen screw from Video Door Station front bezel, a
small metal tab will drop out of the chassis. Be sure to re-install tab into
camera chassis slot before re-assembly.
Door Station Rough-In
1. Identify the location where the VMC1VDS is to be
installed.
2. Pull Cat-5 wire from the VMC1MB to this location.
3. Label and tie off the wires so they do not fall back into the
wall and are accessible when the VMC1VDS is installed.
4. If the door strike or Chime activated Control Output is
to be utilized, see “Door Release Rough-in” and “Chime
Activated CO Rough-in”.
CAMERA
CHASSIS
PLEXIGLASS
WEATHER
SHIELD (OPTIONAL)
VDSWS-T
BEZEL
VMC1VDS
ANCHORS
NOTE: METAL TAB
DROPS OUT WHEN
REMOVING ALLEN
SCREW HOLDING
FRONT BEZEL
TO CAMERA CHASSIS
DRYWALL
4-1/2’ to 5’-0”
MOUNTING
HEIGHT
FROM FLOOR
LINE
ALLEN
SCREW
Figure 4. VMC1VDS Door Station Rough-In
11
Door Station Rough-In
VMC1VDS-S/BZ Door Station Rough-in
The VMC1VDS-S and VMC1VDS-BZ incorporate a wide angle
120 degree horizontal viewing camera into a Door Station. It
is normally mounted at a height from the fl oor of: 55” – 60”.
Installation of this unit on an exterior wall requires 4 screws
and anchors (See Figure 6). When installing these units, be
aware of the camera location and the direction of sunlight and
other ambient light. Direct sun or light pointed into the lens of
the VMC1VDS camera may impact video quality. Additionally,
exposure to extreme weather conditions is not recommended.
For added protection against weather, the VMC1VDS-S and
VMC1VDS-BZ should be equipped with a DSWS weather
shield. The installation of the DSWS is provided in the VMC1
Finish Out Guide.
VMC1HR Rough-in Enclosure
1. Attach the VMC1HR fl ush to the exterior wall using the
two inner pre-punched holes in the VMC1HR. The outside
holes on the wings of the box are to be used to mount the
VMC1VDS-S/BZ and not to be used to attach the VMC1HR
to the exterior wall.
2. Pull the Cat-5 wires through the hole in the back of the
VMC1HR and loop it through so they do not fall back into
the wall.
3. If the door strike or Chime activated Control Output is
to be utilized, see “Door Release Rough-in and “Chime
Activated CO Rough-in
PRE-DRYWALL COLOR VIDEO DOOR
STATION
USE INNER HOLES FOR
MOUNTING ROUGH-IN
ENCLOSURE TO STUD
VMC1VDS-BZ
VMC1VDS-S
BEZEL
ELECTRONICS
PANEL
VMC1VDS-BZ
VMC1VDS-S
7-3/4”
3-1/2”
CAT5 CABLE LOOPED
WITH EXCESS AMOUNT
COLOR VIDEO DOOR
STATION WALL
MOUNTING PLATE
VMC1HR
DRYWALL
ANCHORS
12
GRILLE
POST-DRYWALL COLOR
VIDEO DOOR
STATION
Figure 5. VMC1VDS-S/BZ Door Station Rough-In
TE6D Power Supply
The Power Supply unit is pre-wired and self contained, and
the wires are tucked inside. To access connection wires, open
the Power Supply unit by removing four screws as shown
in Figure 6. In the unlikely case that the TE6D electrical
connectors become unplugged, the 3-pin and 6-pin connector
blocks can be re-installed in their respective locations on the
power supply board. Plug connectors in as shown.
WARNING
ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE TE6D
POWER SUPPLY MUST BE MADE BY A LICENSED ELECTRICIAN
AND MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL
CODES
Power Supply Rough-In
Power Supply Connections
The 6-pin connector is the low voltage (13.8 VDC, 3.8 amp)
output from the TE6D Power Supply unit:
• Position 3 is the Black Negative connection for the Master
Station
• Position 5 is the Red Positive connection for the Master
Station
The 3-pin connector is for the 110/120 High Voltage input:
• Black wire is position 1
• White wire is position 3
PRE-WIRED SELF CONTAINED TE6D POWER SUPPLY
REMOVE 4 SCREWS
TO ACCESS POWER
SUPPLY WIRES
STRAIN RELIEF
BOTTOM HOUSING
TOP HOUSING
3-PIN
3
WHT
2
CONNECTOR
BLK
1
BOTTOM HOUSING
6-PIN CONNECTOR
6
5
RED
4
BLACK
3
2
1
TOP HOUSING
STRAIN RELIEF
Figure 6. Opening TE6D Power Supply
13
Power Supply Rough-In
Power Supply Wiring
1. Run a 14 AWG 120 VAC power cable (including ground)
from a dedicated 15-amp circuit breaker to the Master
Station Mounting Bracket location. The VMC1 requires a
dedicated power source so there’s no interference from
other equipment.
2. Route incoming power cable into the Power Supply
enclosure through the hole on the SIDE of the Power
Supply.
3. Use wire nuts to connect the incoming power cable
to the TE6D Power Supply BLACK (HOT) and WHITE
(NEUTRAL) input wires.
4. Connect the GREEN (GROUND) wire to the ground
conductor.
PRE-WIRED SELF CONTAINED TE6D POWER SUPPLY
HOT WIRE
GROUND WIRE
(GREEN)
(BLACK)
5. Secure all power cables entering the Power Supply
enclosure with cable strain reliefs.
6. Tuck cables into the Power Supply enclosure.
7. Pull the Red and Black low voltage wires out of the top
of the TE6D for later connection to the Master Station.
Re-assemble the TE6D housing with the provided screws
(See Figure 7).
8. Hook the power supply onto the fl ange of the VMC1MB
and attach the it with screw provided (See Figure 7).
✓ NOTE: Be sure all power cables entering the power supply enclosure are
secured with cable strain reliefs.
BOTTOM HOUSING
NEUTRAL WIRE
(WHITE)
WIRE NUTS
INSERT
WIRE FROM
BREAKER INTO
STRAIN RELIEF
STRAIN RELIEF
FEED WIRES THROUGH
STRAIN RELIEFS ON TOP
HOUSING AS SHOWN. CONNECT
WIRES USING WIRE NUTS, THEN
RE-INSTALL TOP HOUSING
WITH 4 SCREWS
PLUS 13V WIRE (RED)
NEGATIVE WIRE (BLACK)
TOP HOUSING
STRAIN RELIEF
POWER IDENTIFICATION
AT MASTER STATION
PLUS 13V
WIRE (RED)
NEGATIVE
WIRE (BLACK))
110/120V HIGH
VOLTAGE INPUT
(BLACK)
14
RE-ASSEMBLED TE6D POWER SUPPLY
WITH WIRES PROTRUDING
Figure 7 - TE6D Power Supply Wiring
SCREW
(PROVIDED)
NEUTRAL
(WHITE)
TE6D POWER SUPPLY
GROUND
(GREEN)
H628 Data Hub
The H628 Data Hub is used to connect each station to the
Master Station.
Pull Wires
Pull all the Door and Room Station cables to the location of
the Master Station Mounting Bracket (VMC1MB).
If the installation consists of more than 5 room stations, Linear
recommends using the optional Linear DMD-16 (16 stations)
Data Distribution module and the Model H275 Universal
Bracket (Optional, see Appendix A).
1. Determine a mounting location for the H628 Data Hub. It
is recommended to use a Model H275 Universal Bracket
(Optional, see Appendix A).
2. Terminate Cat-5 cables from stations with RJ-45 modular
plugs wired to TIA-568A wiring standard (See Table at
right).
3. Cut a length of Cat-5 cable to run from the H628 Data Hub
to the Master Station location.
4. Strip back about 8” of cable insulation and use a 110
Punch-down tool to bridge all of the punch-down
connectors with the Cat-5 cable as shown in Figure 8.
5. Plug all of the station’s modular plugs into the RJ-45
sockets on the H628 Data Hub.
6. Route the bridged Cat-5 cable to the Master Station
location and secure it so it won’t fall back into the wall.
TIA-568A WIRING STANDARD
DATA HUB RJ-45
MODULAR PLUG
Pin 1White/Green
Pin 2 Green
Pin 3 White/Orange
Pin 4 Blue
Pin 5 White/Blue
Pin 6 Orange
Pin 7 White/Brown
Pin 8Brown
Data Hub Wiring
Cat-5 WIRE COLOR
CAREFULLY PUNCH
WIRES INTO TERMINAL
BLOCK USING A
110 PUNCH-DOWN TOOL
110 PUNCH-DOWN TOOL
CAT-5 CABLE
TO MASTER STATION
Figure 8. H628 Data Hub Wiring
FROM
DOOR
STATION
FROM
ROOM
STATION
STATION
110 PUNCHDOWN CONNECTORS
8” OF CAT-5 CABLE INSULATION STRIPPED
FROM
ROOM
FROM
ROOM
STATION
FROM
NIGHTSTAND
STATION
RJ-45 PLUG SOCKETS
1 BROWN
2 WHITE/BROWN
3 GREEN
4 WHITE/GREEN
5 ORANGE
6 WHITE/ORANGE
7 BLUE
8 WHITE/BLUE
15
Antenna Installation
Radio Antennas
VMC1 requires two antennas, one for AM and one for FM
reception. The AM antenna is a 25-foot wire the FM antenna is
a 25-foot length of coax with a “T” shaped wire dipole at one
end that attaches between rafters in the attic.
Antenna arrangement is crucial to quality radio reception. AM
and FM antennas should be placed at the highest point of the
roof and at least six feet away from any electrical or intercom
wiring.
✓ IMPORTANT! Isolate the antenna leads from the intercom station cables
by running them through a separate hole in the ceiling plate. If grouped
together, the intercom station cables can shield the antenna leads
resulting in poor radio reception. Also keep the antenna leads away
from metal duct work and aluminum backed insulation, which reduces
reception.
AM Antenna
1. Unroll the 25-foot AM antenna wire.
2. Route the antenna wire to the best location, ideally in an
attic.
3. Route the antenna wire down through the hole in the
ceiling plate, down the stud bay to where the VMC1MB
was installed (see Figure 9).
✓ NOTE: the overall length of the antenna wire may be extended by splicing
on to the ‘open’ end of antenna with insulated wire. The gauge end of the
wire should be strong enough to support it without breaking.
✓ NOTE: Some customers may want to use an external tuned loop antenna
or vertical amplifi ed broadband antenna. Refer to those manufacturer’s
installation instructions for further information.
ORIENTATE FM ANTENNA
FOR STRONGEST RECEPTION
FM ANTENNA
WIRING
MASTER STATION
ALARMDOWN UP
POWER BANDMEM
+
5
34
5ME-UP
12
TUNER
AUX MUSIC
RADIO FILTER
GATE STATUS
AUX OUTPUT 1
AUX OUTPUT 2
75 OHM TO 300 OHM
ADAPTER
AM ANTENNA
WIRING
+
-
VOLUME
4
3
2
1
AUX 2
INPUT FILTER
AUX 1
6 7
5
VID 3
VID 1
LOCK
VID 2
MUS
PRIV MON
AUX
DOOR
CLEAR
HOUSE
ATTIC
FM Antenna
1. Unroll and examine the FM antenna. The antenna is
formed by spreading the red and black wires at the end
of the COAX. The terminal lug at the end of each wire is
for screw mounting the wires outstretched. The antenna
is provided with an F type connector allowing for easy
connection of additional cable.
2. Use screws to attach the red and black antenna leads to
the structure outstretched (See Figure 9).
3. Route the connector end of the antenna COAX down
through the hole in the ceiling plate, down the stud bay,
and on the right side of where the VMC1 Master Unit will
be installed.
4. Connect the included 75 Ohm to 300 Ohm adapter to the
end of the cable.
Figure 9. Antenna Location
16
Door Release Rough-in
The Door Release Trigger can be activated from the VMC1
Master or any remote room station by pressing the Lock
button. The Trigger will deactivate after 4 seconds and can be
activated multiple times while the intercom is active.
To connect the optional Linear Model DRW Door Release
Mechanism, refer to Figure 10 For controlling other door
release devices, refer to the hook-up instructions supplied
with the device.
1. Route a blue and a white 18 gauge wire from the Door
Station location or VMC1MB to the optional 12V Model
284 relay. (See Appendix A). Following this color
convention will assist in the fi nal installation of the Door
Station.
2. Connect the blue wire to the red coil wire on the 284
relay.
3. Connect the white wire to the white coil wire on the 284
relay.
4. Connect a red 18 gauge wire to the green Normally Open
wire on the 284 relay.
5. Connect a red 18 gauge wire to the blue Common wire
on the 284 relay.
6. Connect the other end of the red wire from the relay to
the Yellow wire on the RT35 or either of the wires on the
RT11.
7. Connect the other end of the red wire from the relay to
one of the wires from the DRW.
8. Connect the remaining wire on the DRW to the Yellow/
Red wire on the RT35 or the remaining wire on the RT11.
9. Install the optional DRW into the door frame following
the included instructions.
Auxiliary Output Rough-In
Chime Activated Control Output Rough-In
The Chime Activated Control Output allows for any number of
security related automation functions including 10 available
door chimes. To connect an auxiliary Chime refer to Figure 10.
Refer to the hook-up instructions supplied with the chime.
1. Route a blue and a black 18 gauge wire from the Door
Station location or VMC1VDS to the optional 12V
Model 284 relay. (See Appendix). Following this color
convention will assist in the fi nal installation of the Door
Station.
2. Connect the blue wire to the red coil wire on the 284
relay.
3. Connect the black wire to the white coil wire on the 284
relay.
4. Connect a red 18 gauge wire to the green Normally Open
wire on the 284 relay.
5. Connect a red 18 gauge wire to the blue Common wire
on the 284 relay.
6. Connect the other end of the red wire from the relay to
the Yellow wire on the RT35 or either of the wires on the
RT11.
7. Connect the other end of the red wire from the relay to
one of the wires from the Chime.
8. Connect the remaining wire on the Chime to the Yellow/
Red wire on the RT35 or the remaining wire on the RT11.
9. Install the optional Auxiliary Chime following its
instructions.
VMC1VDS
DOOR
STATION
BLUE
WHITE
BLACK
USE WHITE WIRE FOR DOOR RELEASE
USE BLACK WIRE FOR AUXILIARY CONTROL OUTPUT
RED
WHITE
MODEL 284
12V 5 AMP RELAY
Figure 10. Electric Door Strike Wiring
GRAY
N/C NORMALLY CLOSED
COMMON
GREEN
NORMALLY OPEN
110VAC
24VAC
MODEL RT11 OR RT35
PLUG-IN TRANSFORMER
DRW
MODEL DRW
ELECTRONIC DOOR STRIKE
OR CHIME
BLUE
17
Appendix A – Available Components
Point-to-Point, Point-to-Group and All Call
with 10 different door chimes, 90º horizontal
and 50º degree vertical viewing angle. Standard
System Master Station
with 5.6” TFT LED color screen
supporting up to 20 remote stations.
intercom with hands free response.
UL 60950 certifi ed
VMC1 (White pictured)
VMC1-BK (Black)
VMC1-BZ (Bronze)
Color Video Door Station
weather resistance (IP30) Metal Alloy
(VMC1VDS)
Color video door station with 10 door chimes, a
120º horizontal and 80º vertical viewing angle.
Standard weather resistance IP30
Bronze (pictured)(VMC1VDS-BZ)
Silver (VMC1VDS-S)
5 pack of alternative color room station
faceplates
VMC1RST-WH-5 White
VMC1RST-AL-5 Almond (pictured)
VMC1RST-BK-5 Black
VMC1RST-BZ-5 Bronze
Room station for all non-video intercom, home
security and automation functions
White (pictured)
(VMC1RS-WH)
18
Appendix A – Available Components
Starter Kit for VMC1 Security Intercom System
one (1) Master, one (1) Alloy Door Station and
four (4) room stations
White(VMC1PACK)
Non-video door station. Basic doorbell intercom
station where video is not required. Standard
weather resistance IP30
(VMC1DS-BZ Bronze)
(VMC1DS-S Silver) pictured
Nightstand station.
Provides all of the function of the intercom for
use on a nightstand or desk
Black (VMC1TTS)
Plexiglas weather shield increases the weather
resistance of VMC1VDS to IP31 Smoke Color
(VDSWS-T)
Plexiglas weather shield increases the weather
resistance of VMC1VDS-BZ/S to IP31
Clear (DSWS)
19
Appendix A – Available Components
Mounting bracket for VMC1 Master
Steel (VMC1MB)
Rough in kit for the VMC1 Master.
Includes mounting frame,
TE6D power supply,
FM Dipole antenna,
AM antenna wire and
installation hardware
(VMC1H)
Metal mounting box for room and video stations
except VMC1VDS
(VMC1HR Steel)
Model H275 Universal Bracket for
Data Hub Installation
20
Indoor Box Color Camera
(left) & Color Video Cameras w/nite vision (right)
(MLTL2DN49IR)
Appendix A – Available Components
Electronic Door Release
w/power supplies
Remote Door Lock
(DRW)
12V Control Output switched 110V outlets for
lights and other “notifi cation” devices
Remote Turn On for Lights
AC1 (1 outlet) AC3 (2 outlets)
MFG: Xantec/Niles
2-Channel Receiver (DXR-702)
Miniature door / window transmitter
(DXS-32)
Wire Relay
The 284 Leaded Accessory Relay is a 5 amp
Form C relay with wire leads pre-attached.
(0-200284)
Video Modulator and distribution hub to transmit
door camera image to TV or get Video on TV
Single channel video modulator
(5415)
For more parts and accessories, please go to
www.linearcorp.com
21
2 - Year Limited Warranty
Linear LLC warrants these products to be free of defects for
2 years. The warranty period begins on either (a) the date of
purchase or installation date of this product or (b) the date
of closing on a new residence in which this product was
originally installed. The warranty extends to the original user
of the product and to each subsequent owner of the product
during the term of the warranty. Linear LLC will repair or
replace, at its option, parts and materials at no charge. Parts
supplied under this warranty may be new or rebuilt at the
option of Linear LLC.
If during the warranty period the product appears to have a
defect, please call our toll free service number (800-421-1587)
prior to dismantling. Dismantling the product prior to
calling our service number may void the warranty. Before
returning any product to Linear LLC, contact your local dealer
or distributor. Linear LLC will return the repaired product
freight prepaid within the continental United States. There
are no obligations or liabilities on the part of Linear LLC for
consequential damages arising out of or in connection with
use or performance of this product or other indirect damages
with respect to loss of property, revenue, or profi t, or cost of
removal, installation, or reinstallation.
ANY PRODUCT RETURNED TO LINEAR LLC WITHOUT A
RPA NUMBER WILL BE REFUSED. This limited warranty is in
lieu of any other warranties, express or implied, including
any implied warranty of merchantability or fi tness for a
particular purpose or otherwise, and of any other obligations
or liability on the seller’s part. This limited warranty does
not cover damage caused by improper installation, acts
of God, criminal acts, the violation of applicable building
or electrical codes or the use of non-recommended
wire, cable (excluding Cat-5 and RG-6) or wall housings.
Under no circumstances shall Linear LLC be liable for
consequential, incidental or special damages arising in
connection with use, or inability to use this product. In no
event shall Linear LLC liability hereunder exceed the cost of the
product covered hereby. No person is authorized to assume
for us or obligate us for any other liability in connection
with the sale of this product. Some states do not allow the
exclusion or limitation of consequential, incidental or special
damages, so the above limitation or exclusion may not apply
to you. This limited warranty gives you specifi c legal rights,
and you may also have other rights, which vary from state to
state. This Linear LLC Warranty is in lieu of all other warranties
express or implied.