Linear VMC-1 User Manual

VMC1
Video Security Intercom System for the Home
BAND MEM
POWER
12
34
+
5
5
ME-UP
TUNER
AUX MUSIC
RADIO FILTER
GATE STATUS
AUX OUTPUT 1
AUX OUTPUT 2
Rough - In Instructions
-
1
AUX 1
5
VID 1
PRIV MON
CLEAR
VOLUME
2
AUX 2
INPUT FILTER
67
VID 3
VID 2
MUS
DOOR
HOUSE
+
4
3
LOCK
AUX
USA & Canada (800) 421-1587 & (800) 392-0123
(760) 438-7000 - Toll Free FAX (800) 468-1340
www.linearcorp.com
IMPORTANT SAFETY INSTRUCTIONS
SHOCK HAZARD
This sign alerts user about un-insulated
“dangerous voltage” that poses risk of electric shock.
Read Instructions - All safety and operating instructions should be read before installing or operating the VMC1
Video Intercom system. Retain Instructions - The safety and
operating instructions should be retained for future reference. Heed Warnings - All warnings on the appliance and in the operating instructions should be adhered to. Follow Instructions - All operating and use instructions should be followed. Water and Moisture - The appliance should not be used near water - for example: near bathtub, washbowl, kitchen sink, laundry tub, in a wet basement, or near a swimming pool, and the like. Doing so can create fire or shock hazards and impair the warranty. Attachments - Do not use attachments not recommended by the product manufacturer as they may cause hazards. Ventilation - The appliance should be situated so that its location or position does not interfere with its proper ventilation. For example, the appliance should not be situated on a bed, sofa, rug, or similar surface that may block the ventilation openings: or, placed in a built in installation, such as a bookcase or cabinet that may impede the flow of air to the ventilation openings. Heat - The appliance should be situated away from heat sources such as radiators, heat registers, stoves, or other appliances (including amplifiers) that produce heat. Power Sources - The appliance should be connected to a power supply only of the type described in the operating instructions or as marked on the appliance. Grounding or Polarization - Precautions should be taken so that the grounding or polarization means of an appliance is not defeated.
operating, maintenance, and servicing instructions for
Power Lines - Locate outdoor antennas away from power lines. Outdoor Antenna Grounding - If an outside antenna is connected to the receiver, be sure the antenna system is grounded so as to provide some protection against voltage surges and built up static charges. Section 810 of the National Electrical Code, ANSI/NFPA No. 70 1984, provides information with respect to proper grounding of the mast and supporting structure, grounding of the lead in wire to an antenna discharge unit, size of grounding conductors, location of antenna discharge unit, connection to grounding electrodes, and requirements for the grounding electrode (see fi gure).
Object and Liquid Entry - Never push objects of any kind into this product through openings as they may touch dangerous voltage points or short out parts that could result in a fi re or electric shock. Never spill liquid of any kind on the product.
CAUTION!
This sign warns user about important
this product.
Servicing - The user should not attempt to service the appliance beyond that described in the operating instructions. All other servicing should be referred to qualifi ed service personnel. Damage Requiring Service - The appliance should be serviced by qualifi ed service personnel when:
• The power supply cord or the plug has been damaged; or Objects have fallen, or liquid has been spilled into the appliance; or
• The appliance has been exposed to rain; or
• The appliance does not appear to operate normally or exhibits a marked change in performance; or
The appliance has been dropped, or the enclosure damaged.
When the product exhibits a distinct change in performance - this indicates a
need for service.
Replacement Parts - When replacement
parts are required, be sure the service technician has used replacement parts specifi ed by the manufacturer or have the same characteristics as the original part. Unauthorized substitutions may result in fi re, electric shock, or other hazards.
Safety Check - Upon completion of any service or repairs to this product, ask the service technician to perform safety checks to determine that the product is in proper operating condition.
Wall or Ceiling Mounting - The product should be mounted to a wall or ceiling only as recommended by the manufacturer.
Keep this manual in a safe place for future reference.
To replace this manual, download available from Linear Web site:www.linearcorp.com
IMPORTANT DO’S & DON’TS
DO ensure that all instructions have been followed before
power is applied to system. The installation shall be carried out in accordance with all applicable installation rules.
DO use only Cat-5 & RG-6 and specifi ed wires called out in
these instructions. The cable is designed and constructed with electrical specifi cations necessary for proper audio performance.
DO use only a damp cloth to clean the exterior plastics on
the VMC1 Master Station and Room Stations.
DO NOT use liquid or aerosols. DO make gradual bends of the cable where necessary -- no
sharper than 1” radius.
DO dress the cables neatly with cable ties or Velcro™
wraps. Use loose or moderate pressure.
DO use cable-pulling lubricant only for cable runs that may
otherwise require great force to install. When cable lubricant is used, read the instructions to be sure it is compatible with the cable jacket material (PVC or FEP).
DO avoid stressing cable conductors, limit pulling tension to
25 pounds or less as specifi ed by EIA/TIA-568A standard. Pull cables gradually and with constant tension, taking care not to crush or pinch bundles.
DO use grommets to protect the cable where passing
through metal studs or anything that can possibly damage them.
DO test every installed cable run with a cable tester. “Toning”
alone is not acceptable.
DO label every termination point. Use a unique identifi er
for each cable run. It will make moves, adds, changes, and troubleshooting easier.
DO support horizontal cable bundles using board supports,
J-hooks, or cable trays.
DO have signal cables cross at right angles to power cables
to minimize induced interference.
DO always obey all local and national fi re and building
codes. Be sure to “fi re-stop” all cables that penetrate a fi re­wall. Use plenum-rated cable where mandated.
DO have a licensed electrician to run a 120 VAC line from A
DEDICATED 15-AMP BREAKER to the VMC1 power supply.
DO Use Cat-5 wire for all VMC1 wire runs. DO label all wire runs. Connecting the wires to the VMC1
master, room station, or door station incorrectly may result in system damage.
DO NOT STAPLE CABLES. Staples cause shorts.
DO NOT SPLICE CABLES. Splices are unreliable and
defeat the signal isolation properties of the cable.
DO keep cables at least 18 inches from fl uorescent light
fi xtures, Dimmer controls, and all other wiring. This includes AC wiring, security cable, and other control wires. These can cause a “hum” or “buzzing” sound.
DO keep cables away from objects such as heating and air
conditioning ducts, metal construction plates, and anything else with sharp edges that can damage the cables.
DO follow the grounding and bonding requirements
established by Electrical Code TIA standard 607, and equipment manufacturer’s specifi cations.
DO NOT locate the VMC1 Master Station or Room Stations
on an exterior wall.
DO NOT locate the VMC1 Master Station or Room Stations
in any wall cavity with any other electrical wiring in the cavity.
DO NOT attach non line-level audio devices or non M&S
authorized equipment to the system.
DO NOT power up Master Station until all stations are
connected.
DO NOT splice or repair cables damaged during wire
pulling, install a new cable.
DO NOT coil or bundle the cables. This can cause electronic
feedback.
DO NOT over-tighten the screws for the stations or the
intercom Master Station to prevent cracking.
DO NOT install any station or speaker cables inside the 120
VAC transformer enclosure.
DO NOT tie cables to electrical conduits or lay cables on
electrical fi xtures.
DO NOT allow the cable to be sharply bent or kinked at any
time.
DO NOT install cables “taut” anywhere. Good installation
should have cables loose, but never sagging.
DO NOT run signal and power cables parallel without
adequate separation to minimize interference.
DO NOT exert more than 25 pounds of tension on 4-pair
cables.
DO NOT step on Cat-5 cable during installation. DO NOT overtighten the cable ties, apply cable ties loosely,
with random spacing.
DO NOT untwist the wire pairs in Cat-5 cable more than 1/2”
to avoid crosstalk.
Keep this manual in a safe place for future reference.
To replace this manual, download available from Linear Web site:www.linearcorp.com
1
Table of Contents
Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Rough-in Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Materials Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
The VMC1 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Interference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Master Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Room Stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Door Stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Gates and Entrances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Cameras. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
AM & FM Antennas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Cables and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Maximum Length for Cable Runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Cable Type and Confi guration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Master Station Rough-In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
VMC1MB Master Station Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . 8
VMC1MB Installation - Unfi nished Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
VMC1MB Installation - Finished Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Room Station Rough-In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Room Station Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Room Station Installation - Unfi nished Wall . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Room Station Installation - Finished Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Room Station Auxiliary Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Door Station Rough-In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
VMC1VDS Door Station Rough-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Door Station Rough-In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
VMC1VDS-S/BZ Door Station Rough-in . . . . . . . . . . . . . . . . . . . . . . . . . . .12
VMC1HR Rough-in Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Power Supply Rough-In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
TE6D Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Power Supply Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Data Hub Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
H628 Data Hub . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Pull Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Antenna Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Radio Antennas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
AM Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
FM Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Auxiliary Output Rough-In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Door Release Rough-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Chime Activated Control Output Rough-In . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Appendix A – Available Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2 - Year Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
2
DOOR STATION
AM ANTENNA
FM ANTENNA
POWER BAND MEM
12
Block Diagram
ROOM STATION
+
-
VOLUME
4
23
1
6
7
5
MON
MUS
PRIV
AUX
DOOR
HOUSE
CLEAR
ROOM STATION
+
-
VOLUME
4
23
1
6
7
5
MON
MUS
PRIV
AUX
DOOR
HOUSE
ALARM DOWN UP
+
5
34
5
ME-UP
TUNER
AUX MUSIC
RADIO FILTER
GATE STATUS
AUX OUTPUT 1
AUX OUTPUT 2
+
-
VOLUME
4
3
2
1
AUX 2
INPUT FILTER
AUX 1
67
5
VID 3
VID 1
LOCK
VID 2
MUS
PRIV MON
AUX
DOOR
CLEAR
HOUSE
ROOM STATION
CLEAR
DOOR LOCK
VIDEO DOOR STATION
MASTER STATION
H628 DATA HUB
TE6D POWER SUPPLY
-
1
5
PRIV
CLEAR
ROOM STATION
-
1
5
PRIV
CLEAR
ROOM STATION
-
1
5
PRIV
CLEAR
VOLUME
23
6
MON
HOUSE
23
6
MON
HOUSE
23
6
MON
HOUSE
+
4
7
MUS
AUX
DOOR
+
VOLUME
4
7
MUS
AUX
DOOR
+
VOLUME
4
7
MUS
AUX
DOOR
DEDICATED POWER
3
Introduction
The VMC1H installation rough-in prepares the home to accommodate the video intercom system. A VMC1MB mounting bracket is necessary for the Master Station. Room stations and the Alloy Color Video Door Station (VMC1VDS) can be mounted directly onto fi nished walls. All other door stations require a rough-in enclosure (VMC1HR). The VMC1HR is also recommended for installing room stations in new construction or installations where the drywall has not yet been installed.
Rough-in Kit
The VMC1H Rough-in Kit includes:
1 - (VMC1MB) Master Station mounting bracket
1 - (TE6D) Power Supply
1 - (101093) FM dipole antenna (#3)
1 - (226804) 300 ohm to 75 ohm F female Balum
1 - (250106-2) AM Antenna wire, Orange, 25 feet
1 - (233103) H628 Data Hub (#4)
VMC1MB
233103
TE6D
101093
226804250106-2
4
Tools
Most are required for purposes of this installation, but may vary according to installer preferences.
WIRE STRIPPERS/CUTTER
110 PUNCH-DOWN TOOL
Materials Required
POWER DRILL WITH 1” AUGER
PHILLIPS SCREWDRIVER
TAPE MEASURE
COAX CABLE
MOUNTING SCREWS (VARIOUS SIZES)
HAMMER
CAT-5 CABLE
DRYWALL SAW
14/18 GAUGE WIRE
LEVEL
0-M
10
0.5
50
50
250
200
500
+-
600
10
50
250
VOLTMETER
5
Overview
The VMC1 System
Designed for installation in new homes, the VMC1 is a Whole House Color Video Security Intercom system that provides room to room communication, multiple camera support, basic home automation controls, and video security for mid to large residential applications. VMC1 provide years of service and security for the homeowner as many people move into ‘smart home’ environment. New housing takes advantage of state of the art electronics, internet, and security applications such as video surveillance and monitoring. VMC1 provides up to 20 remote intercom stations, three video camera stations, and offers music and communication for the whole house. With multiple 12 volt Control Outputs, VMC1 can trigger lights, monitors, voice and text message alerts, and e-mail door chime alerts delivered to a smart phone. VMC1 offers a wide range of capacities with expanded options, accessories, and recommended parts. (See Appendix A).
It is important that each step of the installation be carefully completed by the installer. In the event you need troubleshooting assistance, please call our technical support staff at 1-800-421-1587.
General Information
The following general procedures must be observed in relation to the location and installation of VMC1 components:
Where stations are to be installed outdoors, appropriate measures to provide protection from the weather are to be taken.
The power supply should be located in an area with suffi cient space for heat dissipation.
Guidelines for maximum cable lengths as set out in this manual are to be observed to avoid the possibility of operating problems due to excessive cable voltage drop.
Interference
The circuitry of the intercom is designed to minimize the effects of Radio Frequency Interference (RFI); and there will be minimal and occasional radio frequency interference as power outages, lightning storms, and any electrical apparatus can affect the system. To reduce instances of interference, reduce any unwanted audible buzz in audio appliances such as microphone amplifi er, speaker amplifi er, car radio, telephones etc, you add on-board EMI fi lters or special layout techniques to help bypass EMI or improving RF immunity. Most circuits have integrated RF fi lters or special design that prevents demodulation of high-frequency carriers. The use of microwaves, cell phones, cable television, bug zappers, even heating pads in close proximity, can create interference.
Master Station
The Master Station should be positioned at a suggested height of 4-1/2’ to 5-1/2’ from the fl oor to the center of the unit. As all wiring from other stations is generally terminated at the rear of the Master Station, the wall should be no less than 3 inches in depth. Use the VMC1MB to provide adequate support for the unit.
Room Stations
To avoid audio feedback, Room Stations should be kept at least 10 feet away from other stations. Never have more than one station in any one room and avoid mounting stations in the same wall cavity (i.e. directly below and above one another in a two-story house). A suitable height is generally 4.5 feet from the fl oor to the center of the unit. For Room Stations mounted on wood frame walls, place near a stud to allow for adequate support. For tiled surfaces, install a wall box before lining or tiling the walls. Cut the tiles to the inside dimensions of the wall box. Where Room Stations are mounted outside and are exposed to the weather, the fi tting of weatherproof covers is recommended (p/n DSWS). Stations must not be installed in saunas.
Door Stations
Door Stations are best located adjacent to the front door or at the front gate at a suggested height of 4’-6” and may require a wall box depending upon the surface to which they are to be affi xed. Door Stations are weather resistant, but should not be exposed directly to rain or extreme weather. Any station exposed to the weather requires a weather shield. When equipped with the appropriate weather shield the Door Station is designed to meet ANSI/IEC 60529 IP31 weather proof standards.
Gates and Entrances
Where stations are to be installed in brick or concrete columns at a front gate, the cable should be run in conduit from the station to below ground level and back to the house.
Cameras
For Door Stations fi tted with cameras, consideration must be given to the viewing area of the camera taking factors such as lighting and sun exposure into account.
Power Supply
The Power Supply should be attached to the VMC1MB as directed. Improper installation of the Power Supply can lead to unit malfunction and void the warranty. The Power Supply needs suffi cient space to dissipate heat effectively.
AM & FM Antennas
The antenna arrangement is critical to the installation for quality radio reception. Place AM and FM antennas at the highest point of the roof and at least 6 feet away from any electrical or intercom wiring. Both AM and FM antennas are directional, and correct positioning requires some experimentation to achieve the best possible result. Antenna wires should also be positioned at the highest and most accessible point in the roof. Allow additional cable at the mounting bracket for termination, at least 3 feet for the Master Station.
6
Cables and Wiring
Excellent locations to run cables include:
• Roof space
• False ceilings/ bulkhead area
• Through and/or around external walls
• Under fl oors (subject to access being available)
• Underground in conduit
✓ NOTE: Keep Intercom cables far from any AC wiring. Avoid running
intercom cable in parallel to AC or any other type of wiring. Avoid placing joins or splices in cables. Locate cables where there is access for future servicing.
Maximum Length for Cable Runs
The system can be “home-run wired” from a central point or “daisy chained” from station to station. However, the number of stations on a daisy chain run governs the overall length of the run. The tables below show the relationship between the length on a cable run and the number of room stations permitted and the maximum cable run to a Door Station.
✓ NOTE: The tables are based on the use of Cat-5 or Cat-6 cable. Where
required, the wire lengths maximum distances can be doubled by running 12 AWG speaker wire in parallel with the POS & NEG wires. It is important that the POS and NEG wires are balanced in terms of the type of wire and the number of wires being used - i.e. if a Cat-5 wire and 12 AWG speaker wire are being used for the positive connection, a Cat-5 wire and a 12 AWG speaker wire should also be used for the negative connection.
Wiring Information
Cable Type and Confi guration
The general intercom functions for VMC1 can be cabled using Cat-5 or Cat-6 cables. If required, 6-conductor telephone cables can be used provided the system is confi gured for 6-wire operation.
Be sure to clearly tag all cables to identify any damaged cables or other system faults. See the table below for Cat-5 wire color recommendations.
ROOM STATIONS SHOULD BE AT LEAST TEN FEET APART FROM ONE ANOTHER
MAXIMUM CABLE LENGTH TO ROOM STATIONS NUMBER OF STATIONS ALLOWED
100 yards 1 Room Station
50 yards 2 Room Stations
33 yards 3 Room Stations
25 yards 4 Room Stations
MAXIMUM CABLE LENGTH TO DOOR STATIONS NUMBER OF STATIONS ALLOWED
80 yards 1 Door Station
MASTER STATION CONNECTION VIDEO DOOR STATION NON-VIDEO DOOR STATION ROOM STATION WIRING
POS
NEG Green Green Green
TC Orange White Orange White Orange White
VLC Orange
VLCx Orange Orange
COM1 Blue White Blue White Blue White
COM2 Blue Blue Blue
MUS1 Brown White
MUS2 Brown
VIDx Signal
GND Ground
AUX Yellow Optional
Green White Green White Green White
Cat-5/6
Optional Video Signal Brown White
Optional Video Ground Brown
Cat-5/6
7
Master Station Rough-In
VMC1MB Master Station Mounting Bracket
The VMC1MB mounts fl ush with the wall stud and holds the Master Station and Power Supply (See Figure 1). Position the VMC1MB at a suggested height of 4-1/2 to 5-1/2 feet from the fl oor to center of the unit. As all wiring from other stations is generally terminated at the rear of the Master Station, the wall should be no less than 3 inches deep. If required, install additional wood shims or metal rough-in enclosures to allow for adequate support of the Master Station.
✓ IMPORTANT: Install the Master Station in a cavity wall to allow for the
wiring behind it. Do not install in a brick wall. For wall tiling around the Master Station, ensure that it is mounted either completely within or clear of tile to avoid an uneven surface. Be sure to allow at least 10” of space below Master Station Bracket and fi rebreaks for Power Supply. This is also necessary for clearance when installing the Master Station Mounting Bracket into pre-cut drywall opening.
The VMC1MB has a correct orientation, so review Figures 1 and 2 to be sure it is right side up.
WALL STUD
VMC1MB Installation - Unfi nished Wall
Install the VMC1MB fl ush with the front of the wall stud and fasten in place with screws as shown. After drywall has been installed, cut out an opening to the inside dimensions of the VMC1MB (7-1/4” x 11.”).
MOUNT BRACKET FLUSH WITH FRONT OF WALL STUD
BRACKET FLANGE
FRONT VIEW
VMC1MB
MASTER STATION BRACKET
POWER SUPPLY (TE6D) MOUNTS TO FLANGE ON MASTER STATION BRACKET
MOUNT BRACKET AT LEAST 10” FROM ANY FIREBREAK
TRACE THIS AREA AS A TEMPLATE FOR MASTER STATION OPENING ON DRYWALL (7-1/4” x 11”)
WALL STUDS
VMC1MB
MASTER STATION BRACKET
FIREBREAK
4’-5” to 5’-5”
MOUNTING HEIGHT FROM FLOOR TO CENTER LINE OF BRACKET
Figure 1. Installing Bracket - Unfi nished Wall
8
VMC1MB Installation - Finished Wall
Cut out an opening in the drywall (Height 7-1/4” x Width 11”) but do not cut right up against the wall stud. Allow 5/8” clearance between drywall opening and stud. This ensures that drywall will overlap bracket (See Figure 2). Slide the VMC1MB vertically, then turn clockwise 90˚. Mount in place onto stud using fasteners as shown. Hang Power Supply on VMC1MB in the lower right corner as shown. It may be necessary to lightly tap Power Supply in place onto VMC1MB fl ange with a hammer.
Master Station Rough-In
TRACE THIS AREA AS A TEMPLATE FOR MASTER STATION OPENING ON DRYWALL (7-1/4” x 11”)
CUT OPENING 5/8” FROM STUD
DRYWALL OPENING IS 5/8” FROM STUD
FRONT VIEW
DRYWALL
SLIDE VMC1MB BRACKET VERTICALLY INTO DRYWALL OPENING
VMC1MB
STUD
STUD BEHIND DRYWALL
11”
CUT DRYWALL OPENING
7-1/4”
FRONT VIEW
DRYWALL
THEN TURN BRACKET 90° CLOCKWISE AND MOUNT TO STUD
FRONT VIEW
DRYWALL OVERLAPS BRACKET
DRYWALL
HANG POWER SUPPLY ON VMC1MB BRACKET AS SHOWN. USE HAMMER TO LIGHTLY TAP INTO PLACE ON MASTER STATION BRACKET FLANGE
Figure 2. Installing Bracket - Finished Wall
DRYWALL
9
Room Station Rough-In
Room Station Mounting
The Room Stations are normally mounted at a height from the fl oor of: 4-1/2’ to 5’. The Room Stations are not designed to be installed outdoors.
Room Station Installation - Unfi nished Wall
For an unfi nished wall it is recommended that the VMC1HR rough-in enclosure be used. Identify the location where the Room Station is to be installed.
Attach the Rough-In Enclosure to the stud using the two inner pre-punched holes (see Figure 3). The outside holes on the wings of the box are to be used to mount the room station and not to attach the Rough-in Enclosure to the stud.
Pull the Cat-5 wires through the hole in the back of the Rough­in Enclosure and make a knot so they do not fall back into the wall once the drywall is installed.
After drywall is installed, cut out an opening to the inside dimensions of the VMC1HR utilizing the inside of the box as a guide (see Figure 3 ).
Room Station Installation - Finished Wall
Identify the location where the Room Station is to be installed.
Cut a 3-1/2” x 7-3/4” rectangular hole in the drywall. When possible, one short edge should be situated against a wall stud to provide added support when installing the Room Station.
Pull the wire through the hole and attach to the drywall so it will not fall back into the wall cavity.
Room Station Auxiliary Activation
When operating in single digit mode, each Room Station can activate the Auxiliary Control Output (CO) triggers at the Master Station.
Pull a yellow 18 gauge wire from the VMC1MB to the Room Station location. Following this color convention will assist in the fi nal installation of the VMC1 system.
Pull the yellow wire through the hole in the back of the Rough-In Enclosure and loop it through so it does not fall back into the wall once the drywall is installed.
USE INNER HOLES FOR MOUNTING ROUGH-IN ENCLOSURE TO STUD
VMC1RS-WH
ROOM STATION MOUNTING PLATE
ELECTRONICS PANEL
GRILLE
PRE-DRYWALL ROOM STATION INSTALLATION
-
VOLUME
1
+
2
3
5
4
6
PRIV
MON
7
MUS
CLEAR
HOUSE
DOOR
AUX
BEZEL
VMC1RS-WH
ROOM STATION ROUGH-IN ENCLOSURE (SEE DRAWING A)
7-3/4”
CAT5 CABLE LOOPED WITH EXCESS AMOUNT
4’-6” to 5’-0” MOUNTING HEIGHT FROM FLOOR LINE
DRYWALL
ANCHORS
3-1/2”
VMC1HR
DRYWALL
DRAWING A
STUDS
ROOM STATION ROUGH-IN ENCLOSURE
VMC1HR
10
-
VOLUME
1
+
2
3
5
4
6
PRIV
MON
7
MUS
CLEAR
HOUSE
DOOR
AUX
POST-DRYWALL ROOM STATION INSTALLATION
Figure 3. Pre-Drywall and Post-Drywall Room Station Installation
VMC1VDS Door Station Rough-in
The VMC1VDS is a metal door station with a 90 degree horizontal viewing area. It is normally mounted at a height from the fl oor of: 55” – 60”. When installing the VMC1VDS be aware of the camera location and the direction of sunlight and other ambient light. Direct sun or lighting into the lens of the VMC1VDS camera may impact the video quality. Additionally, exposure to extreme weather conditions is not recommended. For added protection against weather, the VMC1VDS should be equipped with a VDSWS-T weather shield. The installation of the VDSWS-T is shown in Figure 4.
✓ NOTE: When removing allen screw from Video Door Station front bezel, a
small metal tab will drop out of the chassis. Be sure to re-install tab into camera chassis slot before re-assembly.
Door Station Rough-In
1. Identify the location where the VMC1VDS is to be installed.
2. Pull Cat-5 wire from the VMC1MB to this location.
3. Label and tie off the wires so they do not fall back into the
wall and are accessible when the VMC1VDS is installed.
4. If the door strike or Chime activated Control Output is to be utilized, see “Door Release Rough-in” and “Chime Activated CO Rough-in”.
CAMERA CHASSIS
PLEXIGLASS WEATHER SHIELD (OPTIONAL)
VDSWS-T
BEZEL
VMC1VDS
ANCHORS
NOTE: METAL TAB DROPS OUT WHEN REMOVING ALLEN SCREW HOLDING FRONT BEZEL TO CAMERA CHASSIS
DRYWALL
4-1/2’ to 5’-0”
MOUNTING HEIGHT FROM FLOOR LINE
ALLEN SCREW
Figure 4. VMC1VDS Door Station Rough-In
11
Door Station Rough-In
VMC1VDS-S/BZ Door Station Rough-in
The VMC1VDS-S and VMC1VDS-BZ incorporate a wide angle 120 degree horizontal viewing camera into a Door Station. It is normally mounted at a height from the fl oor of: 55” – 60”. Installation of this unit on an exterior wall requires 4 screws and anchors (See Figure 6). When installing these units, be aware of the camera location and the direction of sunlight and other ambient light. Direct sun or light pointed into the lens of the VMC1VDS camera may impact video quality. Additionally, exposure to extreme weather conditions is not recommended. For added protection against weather, the VMC1VDS-S and VMC1VDS-BZ should be equipped with a DSWS weather shield. The installation of the DSWS is provided in the VMC1 Finish Out Guide.
VMC1HR Rough-in Enclosure
1. Attach the VMC1HR fl ush to the exterior wall using the two inner pre-punched holes in the VMC1HR. The outside holes on the wings of the box are to be used to mount the VMC1VDS-S/BZ and not to be used to attach the VMC1HR to the exterior wall.
2. Pull the Cat-5 wires through the hole in the back of the VMC1HR and loop it through so they do not fall back into the wall.
3. If the door strike or Chime activated Control Output is to be utilized, see “Door Release Rough-in and “Chime Activated CO Rough-in
PRE-DRYWALL COLOR VIDEO DOOR STATION
USE INNER HOLES FOR MOUNTING ROUGH-IN ENCLOSURE TO STUD
VMC1VDS-BZ VMC1VDS-S
BEZEL
ELECTRONICS PANEL
VMC1VDS-BZ VMC1VDS-S
7-3/4”
3-1/2”
CAT5 CABLE LOOPED WITH EXCESS AMOUNT
COLOR VIDEO DOOR STATION WALL MOUNTING PLATE
VMC1HR
DRYWALL
ANCHORS
12
GRILLE
POST-DRYWALL COLOR VIDEO DOOR STATION
Figure 5. VMC1VDS-S/BZ Door Station Rough-In
TE6D Power Supply
The Power Supply unit is pre-wired and self contained, and the wires are tucked inside. To access connection wires, open the Power Supply unit by removing four screws as shown in Figure 6. In the unlikely case that the TE6D electrical connectors become unplugged, the 3-pin and 6-pin connector blocks can be re-installed in their respective locations on the power supply board. Plug connectors in as shown.
WARNING
ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE TE6D POWER SUPPLY MUST BE MADE BY A LICENSED ELECTRICIAN AND MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL CODES
Power Supply Rough-In
Power Supply Connections
The 6-pin connector is the low voltage (13.8 VDC, 3.8 amp) output from the TE6D Power Supply unit:
• Position 3 is the Black Negative connection for the Master Station
• Position 5 is the Red Positive connection for the Master Station
The 3-pin connector is for the 110/120 High Voltage input:
• Black wire is position 1
• White wire is position 3
PRE-WIRED SELF CONTAINED TE6D POWER SUPPLY
REMOVE 4 SCREWS TO ACCESS POWER SUPPLY WIRES
STRAIN RELIEF
BOTTOM HOUSING
TOP HOUSING
3-PIN
3
WHT
2
CONNECTOR
BLK
1
BOTTOM HOUSING
6-PIN CONNECTOR
6 5
RED
4
BLACK
3 2
1
TOP HOUSING
STRAIN RELIEF
Figure 6. Opening TE6D Power Supply
13
Power Supply Rough-In
Power Supply Wiring
1. Run a 14 AWG 120 VAC power cable (including ground) from a dedicated 15-amp circuit breaker to the Master Station Mounting Bracket location. The VMC1 requires a dedicated power source so there’s no interference from other equipment.
2. Route incoming power cable into the Power Supply enclosure through the hole on the SIDE of the Power Supply.
3. Use wire nuts to connect the incoming power cable to the TE6D Power Supply BLACK (HOT) and WHITE (NEUTRAL) input wires.
4. Connect the GREEN (GROUND) wire to the ground conductor.
PRE-WIRED SELF CONTAINED TE6D POWER SUPPLY
HOT WIRE
GROUND WIRE (GREEN)
(BLACK)
5. Secure all power cables entering the Power Supply enclosure with cable strain reliefs.
6. Tuck cables into the Power Supply enclosure.
7. Pull the Red and Black low voltage wires out of the top
of the TE6D for later connection to the Master Station. Re-assemble the TE6D housing with the provided screws (See Figure 7).
8. Hook the power supply onto the fl ange of the VMC1MB and attach the it with screw provided (See Figure 7).
✓ NOTE: Be sure all power cables entering the power supply enclosure are
secured with cable strain reliefs.
BOTTOM HOUSING
NEUTRAL WIRE (WHITE)
WIRE NUTS
INSERT WIRE FROM BREAKER INTO STRAIN RELIEF
STRAIN RELIEF
FEED WIRES THROUGH STRAIN RELIEFS ON TOP HOUSING AS SHOWN. CONNECT WIRES USING WIRE NUTS, THEN RE-INSTALL TOP HOUSING WITH 4 SCREWS
PLUS 13V WIRE (RED)
NEGATIVE WIRE (BLACK)
TOP HOUSING
STRAIN RELIEF
POWER IDENTIFICATION AT MASTER STATION
PLUS 13V WIRE (RED)
NEGATIVE WIRE (BLACK))
110/120V HIGH VOLTAGE INPUT (BLACK)
14
RE-ASSEMBLED TE6D POWER SUPPLY WITH WIRES PROTRUDING
Figure 7 - TE6D Power Supply Wiring
SCREW (PROVIDED)
NEUTRAL (WHITE)
TE6D POWER SUPPLY
GROUND (GREEN)
H628 Data Hub
The H628 Data Hub is used to connect each station to the Master Station.
Pull Wires
Pull all the Door and Room Station cables to the location of the Master Station Mounting Bracket (VMC1MB).
If the installation consists of more than 5 room stations, Linear recommends using the optional Linear DMD-16 (16 stations) Data Distribution module and the Model H275 Universal Bracket (Optional, see Appendix A).
1. Determine a mounting location for the H628 Data Hub. It is recommended to use a Model H275 Universal Bracket (Optional, see Appendix A).
2. Terminate Cat-5 cables from stations with RJ-45 modular plugs wired to TIA-568A wiring standard (See Table at right).
3. Cut a length of Cat-5 cable to run from the H628 Data Hub to the Master Station location.
4. Strip back about 8” of cable insulation and use a 110 Punch-down tool to bridge all of the punch-down connectors with the Cat-5 cable as shown in Figure 8.
5. Plug all of the station’s modular plugs into the RJ-45 sockets on the H628 Data Hub.
6. Route the bridged Cat-5 cable to the Master Station location and secure it so it won’t fall back into the wall.
TIA-568A WIRING STANDARD
DATA HUB RJ-45
MODULAR PLUG
Pin 1 White/Green
Pin 2 Green
Pin 3 White/Orange
Pin 4 Blue
Pin 5 White/Blue
Pin 6 Orange
Pin 7 White/Brown
Pin 8 Brown
Data Hub Wiring
Cat-5 WIRE COLOR
CAREFULLY PUNCH
WIRES INTO TERMINAL
BLOCK USING A
110 PUNCH-DOWN TOOL
110 PUNCH-DOWN TOOL
CAT-5 CABLE
TO MASTER STATION
Figure 8. H628 Data Hub Wiring
FROM
DOOR
STATION
FROM ROOM
STATION
STATION
110 PUNCHDOWN CONNECTORS
8” OF CAT-5 CABLE INSULATION STRIPPED
FROM ROOM
FROM ROOM
STATION
FROM
NIGHTSTAND
STATION
RJ-45 PLUG SOCKETS
1 BROWN 2 WHITE/BROWN 3 GREEN 4 WHITE/GREEN
5 ORANGE
6 WHITE/ORANGE
7 BLUE 8 WHITE/BLUE
15
Antenna Installation
Radio Antennas
VMC1 requires two antennas, one for AM and one for FM reception. The AM antenna is a 25-foot wire the FM antenna is a 25-foot length of coax with a “T” shaped wire dipole at one end that attaches between rafters in the attic.
Antenna arrangement is crucial to quality radio reception. AM and FM antennas should be placed at the highest point of the roof and at least six feet away from any electrical or intercom wiring.
✓ IMPORTANT! Isolate the antenna leads from the intercom station cables
by running them through a separate hole in the ceiling plate. If grouped together, the intercom station cables can shield the antenna leads resulting in poor radio reception. Also keep the antenna leads away from metal duct work and aluminum backed insulation, which reduces reception.
AM Antenna
1. Unroll the 25-foot AM antenna wire.
2. Route the antenna wire to the best location, ideally in an
attic.
3. Route the antenna wire down through the hole in the ceiling plate, down the stud bay to where the VMC1MB was installed (see Figure 9).
✓ NOTE: the overall length of the antenna wire may be extended by splicing
on to the ‘open’ end of antenna with insulated wire. The gauge end of the wire should be strong enough to support it without breaking.
✓ NOTE: Some customers may want to use an external tuned loop antenna
or vertical amplifi ed broadband antenna. Refer to those manufacturer’s installation instructions for further information.
ORIENTATE FM ANTENNA FOR STRONGEST RECEPTION
FM ANTENNA WIRING
MASTER STATION
ALARMDOWN UP
POWER BANDMEM
+
5
34
5ME-UP
12
TUNER
AUX MUSIC
RADIO FILTER
GATE STATUS
AUX OUTPUT 1
AUX OUTPUT 2
75 OHM TO 300 OHM ADAPTER
AM ANTENNA WIRING
+
-
VOLUME
4
3
2
1
AUX 2
INPUT FILTER
AUX 1
6 7
5
VID 3
VID 1
LOCK
VID 2
MUS
PRIV MON
AUX
DOOR
CLEAR
HOUSE
ATTIC
FM Antenna
1. Unroll and examine the FM antenna. The antenna is formed by spreading the red and black wires at the end of the COAX. The terminal lug at the end of each wire is for screw mounting the wires outstretched. The antenna is provided with an F type connector allowing for easy connection of additional cable.
2. Use screws to attach the red and black antenna leads to the structure outstretched (See Figure 9).
3. Route the connector end of the antenna COAX down through the hole in the ceiling plate, down the stud bay, and on the right side of where the VMC1 Master Unit will be installed.
4. Connect the included 75 Ohm to 300 Ohm adapter to the end of the cable.
Figure 9. Antenna Location
16
Door Release Rough-in
The Door Release Trigger can be activated from the VMC1 Master or any remote room station by pressing the Lock button. The Trigger will deactivate after 4 seconds and can be activated multiple times while the intercom is active.
To connect the optional Linear Model DRW Door Release Mechanism, refer to Figure 10 For controlling other door release devices, refer to the hook-up instructions supplied with the device.
1. Route a blue and a white 18 gauge wire from the Door Station location or VMC1MB to the optional 12V Model 284 relay. (See Appendix A). Following this color convention will assist in the fi nal installation of the Door Station.
2. Connect the blue wire to the red coil wire on the 284 relay.
3. Connect the white wire to the white coil wire on the 284 relay.
4. Connect a red 18 gauge wire to the green Normally Open wire on the 284 relay.
5. Connect a red 18 gauge wire to the blue Common wire on the 284 relay.
6. Connect the other end of the red wire from the relay to the Yellow wire on the RT35 or either of the wires on the RT11.
7. Connect the other end of the red wire from the relay to one of the wires from the DRW.
8. Connect the remaining wire on the DRW to the Yellow/ Red wire on the RT35 or the remaining wire on the RT11.
9. Install the optional DRW into the door frame following the included instructions.
Auxiliary Output Rough-In
Chime Activated Control Output Rough-In
The Chime Activated Control Output allows for any number of security related automation functions including 10 available door chimes. To connect an auxiliary Chime refer to Figure 10. Refer to the hook-up instructions supplied with the chime.
1. Route a blue and a black 18 gauge wire from the Door Station location or VMC1VDS to the optional 12V Model 284 relay. (See Appendix). Following this color convention will assist in the fi nal installation of the Door Station.
2. Connect the blue wire to the red coil wire on the 284 relay.
3. Connect the black wire to the white coil wire on the 284 relay.
4. Connect a red 18 gauge wire to the green Normally Open wire on the 284 relay.
5. Connect a red 18 gauge wire to the blue Common wire on the 284 relay.
6. Connect the other end of the red wire from the relay to the Yellow wire on the RT35 or either of the wires on the RT11.
7. Connect the other end of the red wire from the relay to one of the wires from the Chime.
8. Connect the remaining wire on the Chime to the Yellow/ Red wire on the RT35 or the remaining wire on the RT11.
9. Install the optional Auxiliary Chime following its instructions.
VMC1VDS
DOOR
STATION
BLUE
WHITE
BLACK
USE WHITE WIRE FOR DOOR RELEASE USE BLACK WIRE FOR AUXILIARY CONTROL OUTPUT
RED
WHITE
MODEL 284
12V 5 AMP RELAY
Figure 10. Electric Door Strike Wiring
GRAY
N/C NORMALLY CLOSED
COMMON
GREEN
NORMALLY OPEN
110VAC
24VAC
MODEL RT11 OR RT35
PLUG-IN TRANSFORMER
DRW
MODEL DRW
ELECTRONIC DOOR STRIKE
OR CHIME
BLUE
17
Appendix A – Available Components
Point-to-Point, Point-to-Group and All Call
with 10 different door chimes, 90º horizontal
and 50º degree vertical viewing angle. Standard
System Master Station
with 5.6” TFT LED color screen
supporting up to 20 remote stations.
intercom with hands free response.
UL 60950 certifi ed
VMC1 (White pictured)
VMC1-BK (Black)
VMC1-BZ (Bronze)
Color Video Door Station
weather resistance (IP30) Metal Alloy
(VMC1VDS)
Color video door station with 10 door chimes, a
120º horizontal and 80º vertical viewing angle.
Standard weather resistance IP30
Bronze (pictured)(VMC1VDS-BZ)
Silver (VMC1VDS-S)
5 pack of alternative color room station
faceplates
VMC1RST-WH-5 White
VMC1RST-AL-5 Almond (pictured)
VMC1RST-BK-5 Black
VMC1RST-BZ-5 Bronze
Room station for all non-video intercom, home
security and automation functions
White (pictured)
(VMC1RS-WH)
18
Appendix A – Available Components
Starter Kit for VMC1 Security Intercom System
one (1) Master, one (1) Alloy Door Station and
four (4) room stations
White(VMC1PACK)
Non-video door station. Basic doorbell intercom
station where video is not required. Standard
weather resistance IP30
(VMC1DS-BZ Bronze)
(VMC1DS-S Silver) pictured
Nightstand station.
Provides all of the function of the intercom for
use on a nightstand or desk
Black (VMC1TTS)
Plexiglas weather shield increases the weather
resistance of VMC1VDS to IP31 Smoke Color
(VDSWS-T)
Plexiglas weather shield increases the weather
resistance of VMC1VDS-BZ/S to IP31
Clear (DSWS)
19
Appendix A – Available Components
Mounting bracket for VMC1 Master
Steel (VMC1MB)
Rough in kit for the VMC1 Master.
Includes mounting frame,
TE6D power supply,
FM Dipole antenna,
AM antenna wire and
installation hardware
(VMC1H)
Metal mounting box for room and video stations
except VMC1VDS
(VMC1HR Steel)
Model H275 Universal Bracket for
Data Hub Installation
20
Indoor Box Color Camera
(left) & Color Video Cameras w/nite vision (right)
(MLTL2DN49IR)
Appendix A – Available Components
Electronic Door Release
w/power supplies
Remote Door Lock
(DRW)
12V Control Output switched 110V outlets for
lights and other “notifi cation” devices
Remote Turn On for Lights
AC1 (1 outlet) AC3 (2 outlets)
MFG: Xantec/Niles
2-Channel Receiver (DXR-702)
Miniature door / window transmitter
(DXS-32)
Wire Relay
The 284 Leaded Accessory Relay is a 5 amp
Form C relay with wire leads pre-attached.
(0-200284)
Video Modulator and distribution hub to transmit
door camera image to TV or get Video on TV
Single channel video modulator
(5415)
For more parts and accessories, please go to
www.linearcorp.com
21
2 - Year Limited Warranty
Linear LLC warrants these products to be free of defects for 2 years. The warranty period begins on either (a) the date of purchase or installation date of this product or (b) the date of closing on a new residence in which this product was originally installed. The warranty extends to the original user of the product and to each subsequent owner of the product during the term of the warranty. Linear LLC will repair or replace, at its option, parts and materials at no charge. Parts supplied under this warranty may be new or rebuilt at the option of Linear LLC.
If during the warranty period the product appears to have a defect, please call our toll free service number (800-421-1587) prior to dismantling. Dismantling the product prior to calling our service number may void the warranty. Before returning any product to Linear LLC, contact your local dealer or distributor. Linear LLC will return the repaired product freight prepaid within the continental United States. There are no obligations or liabilities on the part of Linear LLC for consequential damages arising out of or in connection with use or performance of this product or other indirect damages with respect to loss of property, revenue, or profi t, or cost of removal, installation, or reinstallation.
ANY PRODUCT RETURNED TO LINEAR LLC WITHOUT A RPA NUMBER WILL BE REFUSED. This limited warranty is in lieu of any other warranties, express or implied, including any implied warranty of merchantability or fi tness for a particular purpose or otherwise, and of any other obligations or liability on the seller’s part. This limited warranty does not cover damage caused by improper installation, acts of God, criminal acts, the violation of applicable building or electrical codes or the use of non-recommended wire, cable (excluding Cat-5 and RG-6) or wall housings. Under no circumstances shall Linear LLC be liable for consequential, incidental or special damages arising in connection with use, or inability to use this product. In no event shall Linear LLC liability hereunder exceed the cost of the product covered hereby. No person is authorized to assume for us or obligate us for any other liability in connection with the sale of this product. Some states do not allow the exclusion or limitation of consequential, incidental or special damages, so the above limitation or exclusion may not apply to you. This limited warranty gives you specifi c legal rights, and you may also have other rights, which vary from state to state. This Linear LLC Warranty is in lieu of all other warranties express or implied.
USA & Canada (800) 421-1587 & (800) 392-0123
(760) 438-7000 - Toll Free FAX (800) 468-1340
www.linearcorp.com
Copyright © 2012 Linear LLC 233254 AX3
Loading...