Linear SWR, SWC, SWD User Manual

SWR - SWC - SWD
Swing Gate Operator
Installation Guide
R
T
E
E
T
K
N
I
CM
C
L
I
Operator models contained in this manual
conform to UL325 standard for use in
Class I, II, III, and IV applications
U
D
S
E
T
USA & Canada (800) 421-1587 & (800) 392-0123
(760) 438-7000 - Toll Free FAX (800) 468-1340
www.linearcorp.com
Table of Contents
Pre-installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Before You Begin... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Always Check the Gate’s Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Gate Operator Classifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Approved Obstruction Detection Devices . . . . . . . . . . . . . . . . . . . . . 1
Safety Information and Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Regulatory Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Wiring Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
AC Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
DC Control and Accessory Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Mounting Pad Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mounting Pad Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Operator Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Vent Plug Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Gate Arm Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Setting Left or Right Hand Confi guration . . . . . . . . . . . . . . . . . . . . . .4
Gate Plate Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Choosing Good Harmonics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Installing the Gate Arm on the Operator . . . . . . . . . . . . . . . . . . . . . . 5
Setting the Arm Lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Operator Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Controller Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
AC Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Earth Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Limit Cam Rough Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Torque Limiter Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Limit Cam Fine Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Indicator Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Terminal Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Operator Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Basic Controller Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Programming Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Entering Programming Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Exiting Programming Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Programming Keystrokes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Left or Right Hand Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Dual Gate Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Auto Close Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Run Alarm and Pre-start Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Maximum Open Direction Current Setting . . . . . . . . . . . . . . . . . . . . 13
Maximum Close Direction Current Setting . . . . . . . . . . . . . . . . . . .13
Advanced Controller Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Entering Advanced Programming Mode . . . . . . . . . . . . . . . . . . . . .14
Maximum Run Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Single Button Input Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Stagger Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Stagger Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Auxiliary Relay Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Reverse Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Low Power Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Power Failure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Soft Start/Stop Duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Reset Cycle Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Maintenance Alert Trigger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Mid-travel Stop Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Motor Type Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Radio Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Antenna Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Radio Transmitter Learn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Radio Transmitter Delete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
MGT Obstacle Transmitter Learn . . . . . . . . . . . . . . . . . . . . . . . . . .17
MGT Obstacle Transmitter Delete . . . . . . . . . . . . . . . . . . . . . . . . . .17
Reset Controller to Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . .17
Loop Layout Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Safety Edge Layout Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Photoeye Installation Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Dual Gate Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Gate Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Open Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Close Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Stop Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Single Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Fire Department Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Open Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Open Obstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Close Obstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Reverse Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Open Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Reverse Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Shadow/Reset Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Operation Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Power-up Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Idle Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Last Gate Position/Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Pre-start Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Reverse Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Run Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Error Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Entrapment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
COMM LINK Connection Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
MGT Obstacle Transmitter Trouble . . . . . . . . . . . . . . . . . . . . . . . . .22
Maximum Run Time Exceeded . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Contacting Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Operator fails to start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Motor operates, but gate does not move . . . . . . . . . . . . . . . . . . . . .23
Motor sounds like it is working harder than normal . . . . . . . . . . . . .23
Limit switch getting out of time . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Gate stopping part way open or closed (but no visible obstruction) 23
Gate staying open with automatic system . . . . . . . . . . . . . . . . . . . . 23
How to Order Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . .23
Model SWR Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Model SWC Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Model SWD Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
SWR, SWC, SWD Gate Arm Assembly Exploded View. . . . . . . . . . . .27
Model SWD Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Battery Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
DC Motor Brush Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6-Month Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . . . .29
FCC Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Gate Operator Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . .30
WARNING
ONLY QUALIFIED TECHNICIANS
SHOULD WORK ON
LINEAR SWING GATE
OPERATORS
WARNING
CONTROLS INTENDED FOR USER ACTIVATION MUST BE LOCATED AT LEAST SIX FEET (6') AWAY FROM ANY MOVING PART OF THE GATE AND WHERE THE USER IS PREVENTED FROM REACHING OVER, UNDER, AROUND OR THROUGH THE GATE TO OPERATE THE CONTROLS. OUTDOOR OR EASILY ACCESSIBLE CONTROLS SHALL HAVE A SECURITY FEATURE TO PREVENT UNAUTHORIZED USE.
SWR SWC SWD Swing Gate Operator Installation Guide 227965 Revision X13 3-28-2008
Pre-installation Information
Before You Begin...
Before unpacking, inspect the carton for exterior damage. If you fi nd damage, advise the delivery carrier of a potential claim. Inspect your package carefully. You can check your accessory box parts with the enclosed packing slip for your convenience. Claims for shortages will be honored for only 30 days from the date of shipment.
Before installing the operator, read this manual completely to ensure all requirements for proper installation are present. Verify that the voltage to be used matches the voltage of the operator.
If you have any questions about the requirements for proper installation of this gate operator contact technical support at 800-421-1587
Always Check the Gate’s Action
It’s very important before installing the gate operator to make sure the gate’s swing is free and level throughout the entire swing path. If the gate does not seem to operate properly, it may affect the operator performance or greatly shorten the life of the unit. The gate should also be designed so that airfl ow is ample to prevent wind resistance and drag.
Gate Operator Classifi cations
All gate operators can be divided into one of four different classifi cations, depending on their design and usage. Install this gate operator only when the operator is appropriate for the construction and usage class as defi ned below:
Class I Residential Vehicular Gate Operator
A vehicular gate operator intended for use in a home or for one to four single family dwellings with a common garage or parking area associated with these dwellings.
Class II Commercial / General Access Vehicular Gate Operator
A vehicular gate operator intended for use in a commercial location or building such as a multi-family housing unit of fi ve or more single family units, hotel, retail store or other building servicing the general public.
Class III Industrial / Limited Access Vehicular Gate Operator
A vehicular gate operator intended for use in an industrial location or building such as a factory or loading dock area or other location not intended to service the general public.
Class IV Restricted Access Vehicular Gate Operator
A vehicular gate operator intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.
Approved Obstruction Detection Devices
The following contact or non-contact obstruction detection devices have been approved for use with this swing gate operator as part of a UL325 compliant installation:
Contact Edges
Miller Edge Models MGO20, MGR20, MGS20, ME120
Photoeyes
MMTC Model IR-55 (165’ range - P/N 2520-441) MMTC Model E3K (28’ range - P/N 2520-031)
SWR SWC SWD Swing Gate Operator Installation Guide - 1 - 227965 Revision X13 3-28-2008
Safety Information and Warnings
THE FOLLOWING FORMATS ARE USED FOR SAFETY NOTES
IN THESE INSTRUCTIONS.
CAUTION
This type of warning note is used to indicate the possibility of damage to the gate or gate operator.
WARNING
This type of warning note is used to indicate possible mechanical hazards that may cause serious injuries or death.
WARNING
This type of warning note is used to indicate possible electrical shock hazards that may cause serious injuries or death.
Regulatory Warnings
Read the following before beginning to install this swing gate operator:
IMPORTANT INSTALLATION SAFETY INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF SEVERE INJURY OR DEATH TO PERSONS, REVIEW THESE INSTALLATION SAFETY
STEPS BEFORE PROCEEDING
1. READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS.
2. Read the yellow “Safety Instructions” brochure enclosed with the
packet of information. If any pages are missing or are unreadable,
or you do not have the safety instructions, please call Linear at
1-800-421-1587 to request additional copies.
3. ALL ELECTRICAL CONNECTIONS TO THE POWER SUPPLY MUST
BE MADE BY A LICENSED ELECTRICIAN AND MUST OBSERVE ALL
NATIONAL AND LOCAL ELECTRICAL CODES.
4. A separate power-disconnect switch should be located near the
operator so that primary power can be turned off when necessary.
5. Install the enclosed warning signs on both sides of the gate. A
minimum of two (2) WARNING SIGNS shall be installed, one on each
side of the gate where easily visible.
6. Never reach between, through or around the fence to operate the
gate.
7. Never connect a button station within reach of the gate or on the
side of the gate operator.
8. Do not adjust the operator controller’s current sensing feature too
high. It should be adjusted high enough to keep the gate from falsely
triggering the sensing, but no higher than necessary for the gate to
operate. DO NOT DEFEAT THE PURPOSE OF THIS FUNCTION!
9. You must install all required safety equipment.
10. UL325 Compliance requires the use of contact edges or photoelectric
controls on all automatic or remotely-controlled gate operators.
11. The operator is intended for installation only on gates used for
vehicles. Pedestrians must be supplied with a separate access
opening. The pedestrian access opening shall be designed to
promote pedestrian usage. Locate the gate such that persons will
not come into contact with the vehicular gate during the entire path
of travel of the vehicular gate.
Wiring Specifi cations
Refer to the following steps for details on power and accessory wiring for the operator.
WARNING
ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE AND THE OPERATOR MUST BE MADE BY A LICENSED ELECTRICIAN AND MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL CODES.
USE COPPER WIRE ONLY!
AC Power Wiring
1. Find the listing on this page corresponding to the model, voltage and horsepower rating of your operator.
2. The distance shown in the table is measured in feet from the operator to the power source. DO NOT EXCEED THE MAXIMUM DISTANCE. These calculations have been based on standard 115 V and 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and you should not run wire too near the maximum distance for the gauge of wire you are using.
3. When large-gauge wire is used, a separate junction box (not supplied) may be needed for the operator power connection.
4. Wire length calculations are based on the National Electrical Code, Article 430 and have been carefully determined based on motor inrush, brake solenoids, and operator requirements.
5. Connect power in accordance with local codes. The green ground
wire must be properly connected.
6. Wire insulation must be suitable to the application.
7. Electrical outlets are supplied in all 115 VAC models for convenience with occasional use or low power consumption devices only. If you choose to run dedicated equipment from these devices, it will decrease the distance for maximum length and the charts will no longer be accurate.
DC Control and Accessory Wiring
1. All control devices are now 24 VDC, which can be run up to 2000 feet with 14 AWG wire.
2. Control wiring must be run in a separate conduit from power wiring. Running them together may cause interference and faulty signals in some accessories.
3. A three-wire shielded conductor cable is required to connect two operators together for dual operation. You must use Belden 8760 Twisted Pair Shielded Cable (or equivalent) only – P/N 2500-1982, per foot). See Page 21 for details of this connection. Note: The shield
wire should be connected in both the operators.
VOLTS & HP
115 VOLTS 1/2-HP
230 VOLTS 1/2-HP
VOLTS & HP
115 VOLTS 1/2-HP
115 VOLTS 3/4-HP
115 VOLTS 1-HP
208 VOLTS 1/2-HP
208 VOLTS 3/4-HP
208 VOLTS 1-HP
230 VOLTS 1/2-HP
230 VOLTS 3/4-HP
230 VOLTS 1-HP
MODEL SWR POWER WIRING
MAXIMUM DISTANCE (FEET)
SINGLE DUAL
316 158 12 502 251 10 800 400 8 1272 636 6 2022 1011 4 764 382 12 1218 609 10 1936 968 8 3076 1538 6 4896 2448 4
MODEL SWC POWER WIRING
MAXIMUM DISTANCE (FEET)
SINGLE DUAL
222 111 12 354 177 10 566 283 8 900 450 6 1430 715 4 178 89 12 282 141 10 450 255 8 716 358 6 1140 570 4 160 80 12 254 127 10 406 203 8 646 323 6 1026 513 4 760 380 12 1200 600 10 1924 962 8 3060 1830 6 4864 2432 4 604 302 12 958 478 10 1526 763 8 2424 1212 6 3856 1928 4 544 272 12 864 432 10 1374 686 8 2184 1092 6 3476 1738 4 894 447 12 1422 711 10 2264 1132 8 3600 1800 6 5724 2862 4 710 355 12 1128 564 10 1796 898 8 2852 1426 6 4538 2269 4 640 320 12 1016 508 10 1616 808 8 2570 1285 6 4090 2045 4
WIRE GAUGE
WIRE GAUGE
MODEL SWD POWER WIRING
VOLTS & HP
115 VOLTS 1/2-HP
SWR SWC SWD Swing Gate Operator Installation Guide - 2 - 227965 Revision X13 3-28-2008
MAXIMUM DISTANCE (FEET)
SINGLE DUAL
970 485 12 1542 771 10 2452 1226 8 3898 1949 6 6200 3100 4
WIRE GAUGE
Mounting Pad Installation
The gate operator mounts bolted to a custom poured concrete mounting pad. The pad supports the operator and prevents it from twisting during operation.
An optional post mount kit is also available (P/N 2120-483) which allows installation without a concrete mounting pad.
Mounting Pad Specifi cations
Recommended pad size is 24” x 20” x 18” deep minimum. Pad depth should be set according to local codes and at least as deep as frost line.
If soil conditions may cause the operator and pad to shift or twist during operation, anti-rotation legs may be required. Use two 6” diameter, 10” deep legs to counteract this problem as shown.
5/8” J-bolts may be set into the concrete before it sets following the dimensions shown, or drilled after the concrete sets.
WARNING
The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come into contact with the vehicular gate during the entire path of travel of the vehicular gate.
WARNING
The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures when opening and closing to reduce the risk of entrapment. Swing gates shall not open into public areas.
NOTE: Maximum gate opening angle is approximately 95 degrees,
depending on gate width. If larger opening angle is required, non-standard positioning of the operator and modifi ed articulating arms may be required. Contact the factory for technical information, pricing, and availability.
GATE LINE ON THIS SIDE
20"
14-1/2"
CONDUIT
ENTRY ZONE
24"
14"
2-3/4"
6-3/4"
1/2" FLEX CONDUIT
8-1/2"
5"
10-1/2"
5"
INSTALLER TIP:
MAKE A WOOD JIG TO ALIGN AND HOLD J-BOLTS AND CONDUITS UNTIL THE CONCRETE SETS
5/8" x 8"
J-BOLTS (4)
"W" DIMENSION IS 33" FOR STANDARD APPLICATIONS (GATE ARM ACCOMODATES TO 40" "W" IF EXTRA SPACE IS REQUIRED)
2-3/4"
GATE PLATE ARM HOLE 2-3/4" BEHIND CENTERLINE OF GATE
BACKSPACE REQUIREMENT
FOR ARM SWING IS 25" STANDARD OR
UP TO 30" WITH FULL ARM EXTENSION
INSIDE VIEW OF GATE
TOP OF GATE PLATE 24-7/8" ABOVE THE
TOP OF THE PAD
GATE TOP VIEW
W
(TYP. 33")
OPERATOR ACCESS DOOR FACES AWAY FROM GATE LINE
GATE HINGE
17"
7"
GATE POST
W
MINUS
12"
25" - 30"
GATE ARM
OPERATOR
W
18"
EARTH
24-7/8"
GROUND STAKE
CONCRETE OPERATOR PAD 3D VIEW
IN SOFT SOIL, POUR TWO 6" DIAMETER 10" DEEP "LEGS" TO PREVENT ROTATION
"RIGHT-HAND" INSTALLATION
Figure 1. Mounting Pad Specifi cations
SWR SWC SWD Swing Gate Operator Installation Guide - 3 - 227965 Revision X13 3-28-2008
Operator Preparation
Vent Plug Installation
In order to keep gear oil from spilling out during shipping, gear reducers used in gate operators have either a solid plug, or a sealed vent plug, installed at the factory.
For operators with a solid plug, replace the solid plug with the vent plug provided (see Figure 2).
With the vent plug installed, remove the vent plug’s breather pin to allow the gear box to vent (see Figure 2).
Gate Arm Installation
The gate arm connects the operator to the gate. The arm supplied can be used in left-hand or right-hand installations. After the proper length of the crank extension and link section of the arm has been determined, the arm is welded to complete the assembly.
Setting Left or Right Hand Confi guration
The welded style gate arm has been pre-assembled at the factory in right-hand confi guration (the back of the overtravel stop faces toward the drive when the gate is fully closed and the arm is installed). For a left-hand operator, rotate the upper portion of the arm as shown in Figure 3 to convert the arm into a left-hand orientation.
Gate Plate Installation
The gate plate mounts on the gate at the recommended height (24-7/8” above the top of the operator pad). The gate plate supplied with the arm assembly can be welded to the gate as shown in Figure 4. Holes have been provided for securing the gate plate to an aluminum gate.
GEAR
REDUCER
REMOVE THE SOLID PLUG
WITH AN ALLEN WRENCH
INSTALL THE VENT PLUG (IF NOT ALREADY INSTALLED)
REMOVE THE BREATHER PIN
Figure 2. Vent Plug Installation
LINK ARM
LEFT-HAND
CONFIGURATION
RIGHT-HAND
CONFIGURATION
(AS SHIPPED)
LINK ARM
OVERTRAVEL
STOP ON
THIS SIDE
OVERTRAVEL
STOP ON
THIS SIDE
CRANK
ARM
VIEWED FROM INSIDE, THE OPERATOR IS ON THE RIGHT SIDE OF GATE
TO CHANGE THE GATE ARM, ROTATE THE LINK END AND OVERTRAVEL STOP ALL THE WAY AROUND
OPEN
VIEWED FROM INSIDE, THE OPERATOR IS ON THE LEFT SIDE OF GATE
Figure 3. Left or Right Hand Gate Arm Setup
CRANK
ARM
OPEN
WELD THE GATE PLATE TO THE GATE (AN EXTRA
SUPPORT WELDED TO THE GATE MAY BE REQUIRED)
GATE PLATE LINK ASSEMBLY
Figure 4. Gate Plate Installation
SWR SWC SWD Swing Gate Operator Installation Guide - 4 - 227965 Revision X13 3-28-2008
Gate Arm Installation (Cont.)
Choosing Good Harmonics
Good harmonics are necessary to minimize wear and tear on the operator. The gate will have smoother starts and stops when the arm is installed with good harmonics. Figure 5 shows an example of good and bad arm harmonics.
Installing the Gate Arm on the Operator
The hex cap screws (see Figure 6) in the side of the crank assembly are shipped loose for placement on the operator drive shaft. Once in place, tighten these cap screws in place by applying 75 ft-lbs of torque. If it becomes necessary to remove the crank, you can do so by loosening these bolts. The arm can also be disconnected for manual operation of the gate by removing the disconnect pin.
Setting the Arm Lengths
Most installations will use the standard dimensions specifi ed. The dimensions shown in Figure 7 can be used to adjust and set the arm. If non-standard mounting is required, contact the factory for information.
Once the arm lengths have been determined, use clamps to temporarily attach the solid bars to their sections of rectangular tubing. If clamps are unavailable, you may also tack weld the parts in place. It is recommended that you
check the arm for proper action and full gate travel before fully welding the parts together. REMOVE THE GATE ARM BEFORE WELDING! Apply Krylon® metallic
gold spray paint or equivalent to touch up welds when fi nished.
GATES SHOWN OPEN
GOOD
HARMONICS
GATE ARM FOLDS OVER ITSELF
GATE WILL HAVE SOFT STARTS AND STOPS
Figure 5. Gate Arm Harmonics
ALIGN CRANK ARM ON OPERATOR THEN TIGHTEN THESE TWO BOLTS
CRANK END OF
GATE ARM
BAD
HARMONICS!
CRANK END OF GATE ARM PARALLEL TO OPEN GATE
GATE ARM JERKS AT START
AND WILL TRANSMIT FORCE INTO GATE AND HARDWARE
RAIN CAP
SHOLDER BOLT
DISCONNECT
PIN
CAUTION
DO NOT WELD THE GATE ARM WHILE IT IS ATTACHED TO THE OPERATOR! Connecting the welder’s ground to the operator’s frame will cause the arc welding current to pass through the operator parts, severely damaging or destroying the operator.
PULL
PIN
Figure 6. Installing Gate Arm on Operator
A
SET LENGTH AND WELD
CAUTION!
CLAMP OR TACK WELD,
THEN TEST ARM ACTION
BEFORE FULLY WELDING
LINK ARM
36-1/2"
TYPICAL
SET LENGTH AND WELD
C
CRANK
ARM
22"
TYPICAL
B
Figure 7. Setting Gate Arm Lengths
SWR SWC SWD Swing Gate Operator Installation Guide - 5 - 227965 Revision X13 3-28-2008
Operator Setup
Controller Access
The Controller in models SWR, SWC and SWD is hinged for access and can be removed without taking off the operator’s cover. It swings down for installation, programming, and troubleshooting access (see Figure 8). Under most circumstances you will not need to remove the Controller.
To access the Controller, lift the metal tab below the AC power switch and swing the Controller down. The Controller is protected by a plastic dust cover. To remove the dust cover, loosen the cover’s wing-screw and lift the cover off.
To remove the Controller from the operator, slide the assembly to the right until the hinges release. Once freed, you can turn the Controller slightly and remove it from the operator. Be careful not to pull on the cables too hard.
LIFT UP ON TAB
CONTROLLER SWINGS DOWN
UNSCREW KNOB TO REMOVE CONTROLLER COVER
AC Power Connection
WARNING
ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE AND THE OPERATOR MUST BE MADE BY A LICENSED ELECTRICIAN AND MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL CODES
All Linear gate operators are supplied with a power disconnect switch to turn on and off the power available to the operator (see Figure 9). Following wiring specifi cations on Page 2, incoming power should be brought into the operator and connected to the labeled pigtails from the disconnect box. A wiring connections print can be found on the label inside the cover of the operator.
Proper thermal protection is supplied with the operator. The motor contains a thermal overload protector to guard from overheating the motor due to overload or high-frequency operation. This overload protector will reset automatically after the motor cools down.
Earth Ground
Install a ground rod and connect it to the operator’s frame in every gate operator installation. A good earth ground is necessary to allow the Controller’s built-in surge and lightning protection circuitry to work effectively. The physical bolting
of the operator to the mounting pad is not suffi cient for a good earth ground.
NOTE: Do not splice the ground wire. Use a single piece of solid
copper 12 AWG wire between the ground rod and the operator.
1. Install an 8-foot long copper ground rod next to the operator mounting pad within three feet of the operator.
2. Use a clamp to connect a solid copper 12 AWG ground wire to the ground rod.
3. Route the ground wire to the operator.
4. Connect the ground wire to the operator’s frame.
Figure 8. Controller Access
115 VAC WIRING
GREEN - GROUND
BLACK - HOT
WHITE - NEUTRAL
CONNECT AC POWER PIGTAIL LEADS TO THE AC SOURCE
230 VAC WIRING
GREEN - GROUND
BLACK - LINE 1 BLACK - LINE 2
Figure 9. Power Disconnect Box Wiring
SWR SWC SWD Swing Gate Operator Installation Guide - 6 - 227965 Revision X13 3-28-2008
Operator Setup (Continued)
Limit Cam Rough Adjustment
The limit cams are not preset at the factory and must be adjusted for each installation. The limit switches are activated by two rotating limit cams attached to the drive shaft (see Figure 10). The Controller is factory set for right hand installations. The top cam is for OPEN and the bottom cam is for CLOSE. The cams fl ip their defi nition in left hand installations (see left-right hand programming on Page 12).
1. With the gate connected to the gate operator in a mid-travel position, the power disconnect switch turned OFF, and the torque limiter set loose enough to slip freely, manually move the gate by hand to its fully open position.
2. Once the gate is in the fully open position, set the OPEN limit cam so that it has just triggered its switch (see Figure 10).
3. Manually move the gate to its fully closed position, set the CLOSE limit cam so that it has just triggered its switch (see Figure 10).
Torque Limiter Adjustment
NOTE: The open and close current sensing may need to be adjusted
before performing the following two steps. See Page 13.
This operator may be supplied with an optional torque limiter. Before adjusting the torque limiter, make sure the gate is in good working condition. With the gate disconnected from the gate arm, one person should be able to move the gate by hand. Be certain the gate moves freely and without binding throughout its travel.
Torque limiters are set light at the factory. They must be adjusted during installation, preferably after limit cams have been manually set. With the gate arm and gate attached, adjust the torque limiter tight enough to keep it from slipping during normal operation. The inherent entrapment protection (current sensing) feature must activate prior to any slipping of the torque limiter. See pages 13-14 for current sense setting.
To adjust the torque limiter in models SWR and SWD:
1. Loosen the set screw on the torque limiter adjustment nut.
2. Cycle the gate open and closed while observing the torque limiter action. TURN THE OPERATOR POWER DISCONNECT SWITCH OFF BEFORE MAKING ANY ADJUSTMENTS.
To increase the torque, turn the adjustment nut clockwise one fl at, or
1/6 turn, at a time until desired output is obtained.
To reduce the torque, turn the adjustment nut counterclockwise one
fl at, or 1/6 turn, at a time until desired output is obtained.
3. When fi nished, tighten the set screw on the torque limiter adjustment nut.
Limit Cam Fine Adjustment
After fi nishing the rough limit cam adjustments and torque limiter adjustment (if optional torque limiter is installed), reposition the gate to approximately the center of travel.
1. Turn the power disconnect switch ON.
2. Stand clear of any moving parts and press the OPEN button.
3. After the gate opens, press the CLOSE button.
4. Observe the gate in both directions as it runs through each complete cycle. Adjust the open or close limit cams again if necessary. If the gate stops during travel, you may need to adjust the Open or Close Current Setting or the Maximum Run Timer (see Pages 13-14).
SWR SWC SWD Swing Gate Operator Installation Guide - 7 - 227965 Revision X13 3-28-2008
LIMIT
SWITCHES (2)
LIMIT
CAMS (2)
RIGHT-HAND INSTALLATION TOP CAM - OPEN LIMIT BOTTOM
LEFT-HAND INSTALLATION TOP BOTTOM
CAM -
CAM -
CAM -
CLOSE
CLOSE
LIMIT
OPEN
LIMIT
LIMIT
Figure 10. Setting Limit Cams
LOOSEN THE SET SCREW ON THE ADJUSTMENT NUT
TO INCREASE TORQUE TURN ADJUSTMENT NUT CLOCKWISE ONE FLAT THEN RE-TEST
MORELESS
TO DECREASE TORQUE TURN ADJUSTMENT NUT COUNTERCLOCKWISE ONE FLAT THEN RE-TEST
TIGHTEN SET SCREW WHEN FINISHED
ADJUSTMENT
NUT
Figure 11. Adjusting the Torque Limiter
CAUTION
If the operator is installed in a left-hand installation. Set the Controller to left-hand operation BEFORE running the operator for the fi ne setting of the limit cams. Failure to do so will result in over-shooting the limit switches, and may cause damage to the operator and/or gate. Refer to programming on Page 12.
Controller Features
WHIP
ANTENNA
ANTENNA
CONNECTOR
DISPLAY
PROGRAMMING
INPUT
POWER
TERMINALS
ACCESSORY
TERMINALS
RESET
BUTTON
TERMINALS
PRIMARY/
SECONDARY
COMM LINK TERMINALS
SINGLE
INPUT
TERMINALS
BUTTONS
POWER
POWER
INDICATORS
OPERATION
BUTTONS
OPERATION AND
PROGRAMMING
INDICATORS
SOLAR PANEL
TERMINALS
MOTOR
BOARD COVER
BATTERY
TERMINALS
PLUG-IN
LOOP
DETECTOR
CONNECTORS
FIRE DEPT
INPUT
TERMINALS
OPEN INPUT
TERMINALS
3-BUTTON
STATION
TERMINALS
OPEN AND CLOSE
OBSTRUCTION
INPUT TERMINALS
REVERSE
INPUT
TERMINALS
REVERSE LOOP
INPUT TERMINALS
OPEN LOOP
INPUT TERMINALS
SHADOW/RESET
INPUT TERMINALS
SHADOW/RESET LOOP
INPUT TERMINALS
LIMIT SWITCH
AUXILIARY
RELAY
TERMINALS
ALARM
OUTPUT
TERMINALS
AC MOTOR
OUTPUT
TERMINALS
Figure 12. Controller Features
SWR SWC SWD Swing Gate Operator Installation Guide - 8 - 227965 Revision X13 3-28-2008
Indicator Descriptions
INDICATOR DEFINITION
OPERATION PROGRAMMING
24 VOLT INPUT POWER
24 VOLT DC ACCY POWER
LOW VOLTAGE AC POWER IS PRESENT
LOW VOLTAGE DC POWER IS PRESENT
INDICATION WHEN LIT
DURING NORMAL OPERATION
INDICATION WHEN LIT
DURING PROGRAMMING
OPEN SIGNAL PRESENT FROM THE INTERNAL
OPEN
RECEIVER OR AN EXTERNAL DEVICE CONNECTED TO THE OPEN INPUT TERMINAL
CLOSE
STOP
CLOSE SIGNAL IS PRESENT FROM A DEVICE CONNECTED TO THE CLOSE INPUT TERMINAL
STOP INPUT TERMINAL IS OPEN AND NOT CONNECTED TO COMMON
PROGRAM CONTROLLER IS IN PROGRAMMING MODE
REVERSE DELAY SET SIGNAL FROM REVERSING DEVICE IS PRESENT SET REVERSE DELAY TIME
LOCKOUT ALARM SET
RADIO LEARN
OPEN CURRENT SET
CONTROLS AND OPERATOR ARE LOCKED OUT BECAUSE OF EXISTING TROUBLE CONDITION
BUILT-IN RECEIVER IS DETECTING A RADIO SIGNAL FROM A REMOTE CONTROL
MOTOR CURRENT HAS EXCEEDED THE OPEN CURRENT SETTING WHILE OPENING
SET RUN ALARM AND PRE-START ALARM
TRANSMITTERS CAN BE ENTERED INTO MEMORY (UP TO 40 TRANSMITTERS)
SET MAXIMUM OPEN CURRENT
OPEN OBSTRUCTION TERMINAL CONNECTED
OPEN OBSTR MGT 2 SET
TO COMMON BY BEAM OR SAFETY EDGE, OR
SET MGT #2 FUNCTION
SIGNAL FROM MGT OBSTACLE TRANSMITTER
OPEN RELAY LH/RH SET OPEN RELAY IS ACTIVATED SET LEFT-HAND RIGHT-HAND OPERATION
OPEN LIMIT BRAKE DELAY OPEN LIMIT SWITCH IS ACTIVATED
CLOSE CURRENT SET
MOTOR CURRENT HAS EXCEEDED THE CLOSE CURRENT SETTING WHILE CLOSING
SET MAXIMUM CLOSE CURRENT
CLOSE OBSTRUCTION TERMINAL CONNECTED
CLOSE OBSTR MGT 1 SET
TO COMMON BY BEAM OR SAFETY EDGE, OR
SET MGT #1 FUNCTION
SIGNAL FROM MGT OBSTACLE TRANSMITTER
CLOSE RELAY AUTO CLOSE SET CLOSE RELAY IS ACTIVATED SET AUTO-CLOSE TIME
CLOSE LIMIT AC DC SET CLOSE LIMIT SWITCH IS ACTIVATED SET MOTOR TYPE
SINGLE SET
SINGLE TERMINAL CONNECTED TO COMMON BY AN EXTERNAL PUSHBUTTON OR RADIO
SET SINGLE BUTTON INPUT FUNCTION
MAX RUN SET MAXIMUM RUN TIMER HAS BEEN EXCEEDED SET MAXIMUM RUN TIME
COMM LINK SET
DUAL OPERATOR CONNECTION DETECTED, BLINKS IF CONNECTION HAS FAILED
MAINT ALERT SET MAINTENANCE IS REQUIRED ON OPERATOR SET MAINTENANCE ALERT CYCLE COUNT
"RL"
"PM"
"AC"
"RP"
"OC"
"CC"
"AD"
LEFT OR RIGHT HAND OPERATION
SINGLE OR DUAL GATE
AUTO CLOSE TIMER
RUN ALARM PRE-START ALARM
MAXIMUM OPEN CURRENT
MAXIMUM CLOSE CURRENT
ADVANCED PROGRAMMING
APEX FUNCTION DISPLAY INDICATIONS
"RT"
"SB"
"SM"
"ST"
"AR"
"RD"
MAXIMUM
RUN TIMER
SINGLE BUTTON INPUT SETUP
STAGGER
MODE
STAGGER TIME
AUXILIARY
RELAY MODE
REVERSE
DELAY TIME
"LP"
"FS"
"SS"
"CT"
"MA"
"MT"
LOW POWER MODE
POWER FAILURE MODE
SOFT START/STOP DURATION
RESET CYCLE COUNT
MAINTENANCE ALERT TRIGGER
MID-TRAVEL STOP POSITION
"MO"
"RA"
"TL"
"TD"
"ML"
"MD"
"CL"
MOTOR TYPE SELECTION
RADIO
ENABLE
LEARN TRANSMITTERS
DELETE TRANSMITTERS
LEARN MGT TRANSMITTERS
ERASE MGT TRANSMITTERS
RESET TO FACTORY DEFAULTS
SWR SWC SWD Swing Gate Operator Installation Guide - 9 - 227965 Revision X13 3-28-2008
Terminal Descriptions
TERMINAL GROUP FUNCTION
AC N
AC
DC -
DC +
RESET
COMMON
C
A
COMMON
SINGLE
COMMON
FIRE DEPT
COMMON
OPEN
OPEN
CLOSE
COMMON
STOP
COM
O-OBS
C-OBS
COM
COM
REV
OPEN LOOP
OPEN LOOP
REVERSE LOOP
REVERSE LOOP
SHADOW/RESET LOOP
SHADOW/RESET LOOP
-
+
N.O.
COM
N.C.
+
-
+
-
24 VOLT INPUT
ACCESSORY POWER PROVIDES 24 VOLT DC POWER FOR ACCESSORIES.
RESET BUTTON FACTORY CONNECTED TO THE CONTROLLER’S RESET BUTTON.
COMM LINK FOR 3-WIRE NETWORK CONNECTION TO SECOND OPERATOR IN DUAL GATE INSTALLATIONS.B
SINGLE BUTTON INPUT
FIRE BOX INPUT CONNECT TO NORMALLY OPEN SWITCH IN FIRE BOX FOR FIRE DEPARTMENT ACCESS.
OPEN INPUT
3-BUTTON STATION INPUT
OBSTRUCTION INPUTS
REVERSE
OPEN LOOP
REVERSE LOOP
SHADOW/RESET LOOP
ALARM FACTORY CONNECTED TO THE ALARM BEEPER.
AUX RELAY
24 VOLT SOLAR PANEL FOR CONNECTION TO 24 VOLT SOLAR PANEL FOR BATTERY CHARGING.
24 VOLT BATTERY FACTORY CONNECTED TO BATTERIES IN DC MODEL OPERATORS.
FACTORY CONNECTED TO 24 VAC FROM TRANSFORMER OR 24 VDC FROM CONTINUOUS DUTY DC SUPPLY.
CONNECT TO NORMALLY OPEN SWITCH FOR SINGLE BUTTON OPERATION. ALTERNATES BETWEEN OPEN-CLOSE OR OPEN-STOP-CLOSE DEPENDING ON PROGRAMMING.
CONNECT TO NORMALLY OPEN DEVICES (KEYPAD, CARD READER, KEYSWITCH, TELEPHONE ENTRY SYSTEM) TO OPEN THE GATE. A CONSTANT OPEN INPUT WILL OVERRIDE THE MID-TRAVEL STOP AND HALT THE AUTO CLOSE TIMER UNTIL RELEASED.
CONNECT TO 3-BUTTON STATION FOR OPEN-CLOSE-STOP CONTROL. A CONSTANT OPEN INPUT WILL OVERRIDE THE MID-TRAVEL STOP AND HALT THE AUTO CLOSE TIMER UNTIL RELEASED.
CONNECT TO NORMALLY OPEN DEVICES (GATE EDGE, PHOTO BEAM) TO DETECT AN OBSTRUCTION DURING OPENING. WHILE GATE IS IN MOTION, ANY OPEN OBSTRUCTION SIGNAL WILL CAUSE THE GATE TO STOP, REVERSE A SHORT DISTANCE, AND THEN STOP AGAIN. AT THIS TIME THE AUTO CLOSE TIMER IS DISABLED, AND A RENEWED INPUT WILL BE REQUIRED TO START THE GATE AGAIN. SHOULD THE GATE BE RESTARTED AND THE OBSTACLE SIGNAL OCCUR AGAIN PRIOR TO REACHING A LIMIT, THE GATE WILL STOP AGAIN, LOCKOUT, AND SOUND THE EMERGENCY ALARM.
FUNCTIONS THE SAME AS THE OPEN OBSTRUCTION, EXCEPT IN THE CLOSING DIRECTION.
CONNECT TO NORMALLY OPEN DEVICES TO CAUSE A REVERSAL WHEN THE GATE IS TRAVELING CLOSED. THE GATE WILL REVERSE TO THE FULL OPEN POSITION.
CONNECT TO OPEN LOOP/FREE EXIT LOOP. THE GATE WILL OPEN WHEN THE LOOP IS TRIGGERED, AND REMAIN OPEN AS LONG AS THE LOOP IS TRIGGERED
CONNECT TO REVERSE LOOP. TRIGGERING THE LOOP WILL CAUSE A REVERSAL WHEN THE GATE IS TRAVELING CLOSED. THE GATE WILL REVERSE TO THE FULL OPEN POSITION.
CONNECT TO SHADOW/RESET LOOP TO KEEP THE GATE IN ITS FULLY OPEN POSITION AS LONG AS THE SIGNAL IS PRESENT. USED TO KEEP GATE OPEN WHILE VEHICLE IS PASSING THROUGH.
FOR CONNECTION TO AUXILIARY DEVICES (MAGNETIC LOCK, SOLENOID LOCK, STROBE LIGHT) FOR ACTIVATION (OR DEACTIVATION) DURING GATE OPERATION.
SWR SWC SWD Swing Gate Operator Installation Guide - 10 - 227965 Revision X13 3-28-2008
Operator Accessory Connections
3-BUTTON STATION
KEYSWITCH
FIRE ACCESS SWITCH
TELEPHONE ENTRY
KEYPAD
SOLENOID LOCK
EXTERNAL POWER
PHOTOEYE FOR REVERSE
PHOTOEYE FOR CLOSE OBSTRUCTION
PHOTOEYE FOR OPEN OBSTRUCTION
SINGLE-CHANNEL RADIO RECEIVER
TWO-CHANNEL RADIO RECEIVER
CHANNEL #1 OPEN/CLOSE
MAGLOCK
GATE EDGE SENSOR FOR REVERSE
WARNING STROBE OR AUDIBLE SOUNDER
WIRELESS GATE EDGE SENSOR
MGT
TRANSMITTER
Figure 13. Operator Accessory Connections
SWR SWC SWD Swing Gate Operator Installation Guide - 11 - 227965 Revision X13 3-28-2008
Basic Controller Programming
Programming Overview
The Controller can be programmed with various options for the operator. The programming fi elds are defi ned as “functions” that have “options”. To make setup easier for the installer, the Controller’s programming is divided into two groups: basic and advanced. The basic programming group contains the functions commonly used in most swing gate installations. The advanced programming group contains functions less commonly used (i.e. dual gate stagger delay, maximum run timer, etc.).
Entering Programming Mode
Enter programming mode by pressing the UP and DOWN buttons together for one second. While in programming mode the PROGRAM indicator will light.
Exiting Programming Mode
Exit programming mode at any time by pressing the UP and DOWN buttons together. The Controller will automatically exit programming mode after three minutes of inactivity.
Programming Keystrokes
(Typical Programming Method)
While in programming mode, press the UP or DOWN buttons to scroll through the programming functions. When the desired function is displayed press the ENTER button to display the currently set option for the function. When an option is displayed, the decimal points are lit.
To change the option, press and hold the ENTER button for 1 second. To indicate that an option is ready to be changed, the display will fl ash. While the display is fl ashing, press the UP or DOWN button to display the other options available for that function.
When the desired option is displayed, press the ENTER button to store it into memory. To select another function, press ENTER, UP, or DOWN.
Left or Right Hand Operation
The factory default is for right hand operation (operator on right side of the driveway when viewed from the inside of the gate). For left hand installations, program the Controller for left hand operation.
Dual Gate Enable
The factory default is for single gate operation. For dual gate operation, wire the two gate controllers together through the COMM LINK terminals (see Page 21) and enable dual gate operation with this programming step.
NOTE: The Mid-travel Stop feature is disabled when dual gate
operation is enabled for paired units.
Auto Close Timer
The factory default turns off the Auto Close Timer. The timer can be set from 1 to 59 seconds and from 1 to 9 minutes. When the Auto Close Timer is set, after opening, the gate will wait for the length of the Auto Close Timer then close automatically.
DOWN UP
PRESS DOWN AND UP
BUTTONS TOGETHER
FOR ONE SECOND
ENTERING
PROGRAMMING
SELECT
FUNCTION
UP
OR
DOWN
PRESS UP OR DOWN TO SCROLL DISPLAY
THROUGH FUNCTIONS
ENTER
PROGRAMMING
KEYSTROKES
FUNCTION
"RL"
LEFT HAND
RIGHT HAND
FUNCTION
"PM"
SINGLE GATE
DUAL GATE
FUNCTION
"AC"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
PROGRAM
INDICATOR
AND
PROGRAM INDICATOR
WILL LIGHT WHEN SYSTEM
IS IN PROGRAM MODE
CURRENTLY SET OPTION
PRESS ENTER TO
DISPLAY CURRENTLY
OPTION READY
TO CHANGE
ENTER ENTER ENTER
PRESS ENTER FOR
ONE SECOND TO
SELECT OPTION
(THE DISPLAY
WILL FLASH)
SET OPTION
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
TO CHANGE
OPTIONS
PRESS UP OR
OPTIONS
PRESS UP OR
OPTIONS
CHOOSE
OPTION
UP
OR
DOWN
PRESS ENTER
PRESS UP OR DOWN
OPTION
RIGHT HAND INSTALLATION (OPERATOR ON RIGHT OF GATE WHEN VIEWED FROM INSIDE)
LEFT HAND INSTALLATION (OPERATOR ON LEFT OF GATE WHEN VIEWED FROM INSIDE)
SINGLE GATE INSTALLATION
DUAL GATE INSTALLATION
AUTO CLOSE TIMER DISABLED
SET TIMER VALUE 1 TO 59 SECONDS
SET TIMER VALUE 1 TO 9 MINUTES
TO STORE
OPTION
PRESS UP, DOWN
OR ENTER SELECT
NEXT FUNCTION
OPTION STORED
OR
UP
OR
DOWN
SELECT
FUNCTION
AUTO CLOSE
TIMER
SWR SWC SWD Swing Gate Operator Installation Guide - 12 - 227965 Revision X13 3-28-2008
Basic Controller Programming (Cont.)
Run Alarm and Pre-start Alarm
The factory default is Run Alarm on and a 3-second Pre-start Alarm. The operator’s beeper will sound 3 seconds before the operator starts. The options are:
Run Alarm Off and Pre-start Alarm Off• Run Alarm On and Pre-start Alarm Off• Run Alarm On and Pre-start Alarm On for 3-9 Seconds
Maximum Open Direction Current Setting
To detect obstacles or mechanical problems with the gate, the operator monitors its motor current. If the open current load exceeds the programmed maximum load number, the operator will stop, reverse a short distance, then stop again. The Auto Close Timer will be disabled, and another open request will be required to start the operator again. If after restart, the overload or an open obstacle happens again before the open limit is reached, the operator will lockout and sound the alarm.
To measure the motor load used during opening, while this function is being displayed, push and hold the OPEN button to open the gate. The motor current will be displayed as a load number from 0 to 99. Set the programmed load number above the measured load number, so that a minimal force (50-75 lbs.) will activate a reversal should an obstruction occur, but high enough to keep the gate moving under normal conditions without interruption.
Maximum Close Direction Current Setting
To detect obstacles or mechanical problems with the gate, the operator monitors its motor current. If the close current load exceeds the programmed maximum load number, the operator will stop, reverse a short distance, then stop again. Another close request will be required to start the operator again. If after restart, the overload or a close obstacle happens again before the close limit is reached, the operator will lockout and sound the alarm.
To measure the motor load used during closing, while this function is being displayed, push and hold the CLOSE button to close the gate. The motor current will be displayed as a load number from 0 to 99. Set the programmed load number above the measured load number, so that a minimal force (50-75 lbs.) will activate a reversal should an obstruction occur, but high enough to keep the gate moving under normal conditions without interruption.
FUNCTION
"RP"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
RUN ALARM
PRE-START ALARM
FUNCTION
"OC"
MAX OPEN
CURRENT
FUNCTION
"CC"
MAX CLOSE
CURRENT
OPTIONS
RUN ALARM OFF PRE-START ALARM OFF
RUN ALARM ON PRE-START ALARM OFF
RUN ALARM ON PRE-START ALARM ON FOR 3 - 9 SECONDS
OPTIONS
PRESS AND HOLD THE OPEN BUTTON TO CYCLE THE OPERATOR OPEN, THE DISPLAY WILL SHOW THE MEASURED LOAD NUMBER
PRESS ENTER FOR 1 SECOND
ENTER
WHILE DISPLAY IS FLASHING, PRESS UP TO SET A LOAD NUMBER ABOVE THE MEASURED LOAD NUMBER
PRESS ENTER TO STORE THE VALUE
ENTER
OPTIONS
PRESS AND HOLD THE CLOSE BUTTON TO CYCLE THE OPERATOR CLOSED, THE DISPLAY WILL SHOW THE MEASURED LOAD NUMBER
PRESS ENTER FOR 1 SECOND
ENTER
WHILE DISPLAY IS FLASHING, PRESS UP TO SET A LOAD NUMBER ABOVE THE MEASURED LOAD NUMBER
PRESS ENTER TO STORE THE VALUE
ENTER
SWR SWC SWD Swing Gate Operator Installation Guide - 13 - 227965 Revision X13 3-28-2008
Advanced Controller Programming
Entering Advanced Programming Mode
To access and program the Advanced Programming functions, for each programming session, Advanced Programming must be enabled.
After exiting programming, the Advanced Programming functions will be available on the programming display during the next programming session unless the operator has run 50 or more cycles. After that, Advanced Programming must be enabled again.
Maximum Run Time
The factory default for the Maximum Run Time is 99 seconds. When the operator starts, a timer will begin counting. If a open or close limit is not reached or an obstacle or reversing input is not received before the timer expires, the operator will stop, the unit locks out and the alarm sounds. The timer can be set for 10 to 99 seconds.
Single Button Input Setup
This function is used for selecting the operation for single button controls and radio receivers.
The factory default sets the SINGLE input terminal so successive inputs will cycle the operator in OPEN-STOP-CLOSE-STOP order.
Alternately, the SINGLE input can be set to cause the gate to OPEN unless the gate is fully open. If the gate is fully open, the input will cause the gate to CLOSE.
Stagger Mode
This function is used in dual gate installations only. The factory default sets the Stagger Mode to OFF. In dual gate installations the two operators communicate through the 3-wire COMM LINK interface. When using the Stagger Mode, set one operator for delayed opening and the other operator for delayed closing. The Stagger Time programming function (see below) sets the length of the delay.
NOTE: This function will only be displayed if dual gate operation is
selected.
FUNCTION
"AD"
ADVANCED
PROGRAMMING
FUNCTION
"RT"
MAXIMUM RUN
TIMER
FUNCTION
"SB"
SINGLE BUTTON
INPUT SETUP
OPTIONS
ADVANCED PROGRAMMING FUNCTIONS WILL NOT BE DISPLAYED
ADVANCED PROGRAMMING OPTIONS WILL BE DISPLAYED
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
OPTIONS
DISPLAY SHOWS CURRENT MAXIMUM RUN TIME SETTING
PRESS ENTER FOR 1 SECOND
ENTER
WHILE DISPLAY IS FLASHING, PRESS UP OR DOWN TO CHANGE THE MAXIMUM RUN TIME (10-99 SECONDS)
PRESS ENTER TO STORE THE VALUE
ENTER
OPTIONS
SINGLE INPUT WILL CYCLE OPERATOR IN ORDER OF OPEN-STOP-CLOSE-STOP
SINGLE INPUT WILL OPEN OPERATOR, IF OPERATOR IS ALREADY OPEN, SINGLE INPUT WILL CLOSE OPERATOR
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
NOTE: ADVANCED PROGRAMMING WILL STAY ENABLED AFTER EXITING PROGRAMMING UNTIL THE GATE CYCLES 50 TIMES
Stagger Delay Time
This function is used in dual gate installations only. The factory default sets the Stagger Time to 0 seconds (OFF). The Stagger Time
FUNCTION
"SM"
OPTIONS
DISABLES STAGGER FUNCTION
sets the delay for the Stagger Mode. The Stagger Delay Time can be set from 1-99 seconds.
NOTE: This function will only be displayed if dual gate operation is
selected.
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
STAGGER
MODE
FUNCTION
"ST"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
STAGGER
DELAY TIME
SWR SWC SWD Swing Gate Operator Installation Guide - 14 - 227965 Revision X13 3-28-2008
PRESS ENTER TO
SELECT AN OPTION
SETS THIS OPERATOR FOR
DELAYED OPEN
SETS THIS OPERATOR FOR DELAYED CLOSE
OPTIONS
STAGGER TIMER DISABLED
SET STAGGER DELAY VALUE 1 TO 99 SECONDS
DUAL GATES
ONLY
DUAL GATES
ONLY
Advanced Controller Programming (Cont.)
Auxiliary Relay Mode
The Auxiliary Relay has normally open and normally closed contacts. The factory setting disables the Auxiliary Relay. The relay can be set for:
Maglock: The relay will energize during any pending or actual gate motion (open only), to deactivate a magnetic or solenoid gate lock. Ticket Dispenser: The relay will be energized at all times (enabling a ticket dispenser) unless the operator is fully open or in an entrapment condition. Strobe: The relay will energize during any pending or actual gate motion (either open or close), to activate a warning strobe light. Alarm: The relay will energize if the gate is manually forced open from the full closed position.
Reverse Delay Time
The factory default sets the Reverse Delay to 1 second. The operator will wait the length of the delay before reversing direction. This feature will not change the reversal time when the operator is responding to an entrapment condition from an obstruction input or inherent entrapment protection sensor. The Reverse Delay can be set from 1 to 9 seconds. Heaver gates require a longer delay to allow time for the gate to stop.
Low Power Mode
This function is only used with DC swing gate Model SWD. The factory default disables the Low Power Mode. When Low Power Mode is enabled, and AC power fails, the controller will assume Low Power Mode after 60 seconds of gate inactivity. Low power mode turns off all accessory power and indicators. Only inputs from the radio receiver, reverse loop, or restoring AC power will wake the Controller from Low Power Mode. Programming Mode can still be accessed while the Controller is in Low Power Mode.
NOTE: This function will only be displayed in Model SWD operators.
Power Failure Mode
This function is only used with DC swing gate Model SWD. The factory default is set for Fail Safe, alternately the Controller can be set for Fail Secure, Open Immediate, or Close Immediate.
Fail Safe: If the AC power fails and the battery voltage drops below approximately 22 Volts, 5 seconds later the operator will cycle open if not already open. When AC power is restored, or the battery gets charged by solar panels, the operator will resume normal operation and auto-close if programmed to do so. Fail Secure: If the AC power fails and the battery voltage drops below approximately 22 Volts, 5 seconds later the operator will cycle closed if not already closed. When AC power is restored, or the battery gets charged by solar panels, the operator will resume normal operation.
NOTE: Fail Safe and Fail Secure are disabled if Stagger Mode is
enabled.
Open Immediate: If the AC power fails, the operator will cycle open if not already open and cease operation. When AC power is restored, the operator will resume normal operation and auto-close if programmed to do so. Close Immediate: If the AC power fails, the operator will cycle closed if not already closed and cease operation. When AC power is restored, the operator will resume normal operation.
NOTE: This function will only be displayed in Model SWD operators.
FUNCTION
"AR"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
AUXILIARY
RELAY MODE
FUNCTION
"RD"
REVERSE
DELAY TIME
FUNCTION
"LP"
LOW POWER
MODE
FUNCTION
"FS"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
POWER
FAILURE MODE
OPTIONS
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
OPTIONS
AUXILIARY RELAY DISABLED
AUXILIARY RELAY USED FOR MAGLOCK CONTROL
AUXILIARY RELAY USED FOR TICKET DISPENSER CONTROL
AUXILIARY RELAY USED FOR WARNING STROBE LIGHT
AUXILIARY RELAY USED FOR CONNECTION TO ALARM DEVICE
SET TIMER VALUE 1 TO 9 SECONDS
LOW POWER MODE DISABLED
LOW POWER MODE ENABLED
MODEL SWD
SET TO FAIL SAFE MODE
SET TO FAIL SECURE MODE
SET TO OPEN IMMEDIATE MODE
SET TO CLOSE
IMMEDIATE MODE
MODEL SWD
ONLY
ONLY
SWR SWC SWD Swing Gate Operator Installation Guide - 15 - 227965 Revision X13 3-28-2008
Advanced Controller Programming (Cont.)
Soft Start/Stop Duration
This function is only used with DC swing gate Model SWD. This
FUNCTION
"SS"
OPTIONS
SOFT START DISABLED
function causes the operator to start and stop the DC motor slowly reducing gate wear and tear (at the full open or closed positions only). The factory default sets the Soft Start/Stop Duration to 3 seconds. The Soft Start/Stop Duration can be set from 1 to 10 seconds.
NOTE: Changing the Soft Start/Stop Duration will reset the open and
close current setting value to zero. It will be necessary to reprogram maximum open and close current settings.
SOFT START/STOP
DURATION
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
SET SOFT START DURATION TIME FROM 1 TO 10 SECONDS
MODEL SWD
ONLY
NOTE: This function will only be displayed in Model SWD operators
set for DC motor operation with soft start motor selection.
Reset Cycle Count
The Controller counts of the number of times the operator has been
FUNCTION
"CT"
OPTIONS
DISPLAY SHOWS NUMBER OF OPERATION CYCLES (OPEN OR CLOSE) ROUNDED TO THE NEAREST 1000
activated and can display the count rounded off to the nearest 1000. To reset the Cycle Count, press and hold the ENTER button for 2 seconds while the Cycle Count is displayed.
If the Maintenance Alert has been triggered, resetting the Cycle Count
NOTE: PRESS ENTER FOR 2 SECONDS WHILE THE "CT" FUNCTION IS DISPLAYED TO RESET CYCLE TIMER TO ZERO
will also reset the Maintenance Alert indicator.
Maintenance Alert Trigger
RESET CYCLE
COUNT
The Controller has a MAINT ALERT indicator that can be programmed to light when the number of activations exceeds a set number of cycles.
The factory default sets the Maintenance Alert Trigger to 10,000 cycles. The Maintenance Alert Trigger can be programmed for 5, 10, 15, or 25
FUNCTION
"MA"
OPTIONS
DISABLES THE MAINENANCE ALERT FUNCTION
thousand cycles.
The Maintenance Cycle Count can be reset independently from the operator’s absolute Cycle Count.
Mid-travel Stop Position
The Controller can be programmed so the gate will stop at a mid-travel point instead of fully opening. This can be useful in installations where a large gate, that takes a long time to open and close fully, only needs to
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
MAINTENANCE
ALERT TRIGGER
SETS THIS MAINTENANCE ALERT TRIGGER FOR 5, 10, 15, OR 25 THOUSAND CYCLES
RESETS THE MAINTENANCE ALERT INDICATOR AND SETS THE MAINTENANCE ALERT COUNT TO ZERO
be opened partway to allow traffi c to pass.
The factory default sets the Controller for full open operation. Alternately, the Controller can be programmed to open for 1 to 99 seconds then stop,
FUNCTION
"MT"
OPTIONS
MID-TRAVEL STOP DISABLED (GATE RUNS FULL TRAVEL)
before reaching the open limit.
When a Mid-travel Stop Position time has been programmed, the gate will still fully open if the Fire Department input is triggered, if the OPEN button is held down beyond the Mid-travel Stop Position, or a close obstruction or reverse loop input is triggered.
NOTE: The Mid-travel Stop feature is disabled when dual gate
operation is enabled for paired units.
MID-TRAVEL
STOP POSITION
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
SET LENGTH OF OPENING TIME FROM 1 TO 99 SECONDS
Motor Type Selection
The factory sets the default for the Controller to match the type of motor in the operator. If required, change the motor selection option to a different
FUNCTION
"MO"
type of motor used in the operator. The options available are:
AC Motor Only• DC Motor Only with Mechanical Braking
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
DC Motor with Electronic Soft Start/Stop• 3 Phase AC Motor• AC Motor with DC Motor Backup with Mechanical Braking• AC Motor with DC Motor Backup with Electronic Soft Start/Stop
PRESS ENTER TO
SELECT AN OPTION
MOTOR TYPE
SELECTION
SWR SWC SWD Swing Gate Operator Installation Guide - 16 - 227965 Revision X13 3-28-2008
OPTIONS
AC MOTOR ONLY
DC MOTOR ONLY WITH BRAKING
DC MOTOR WITH SOFT START/STOP
NOTE: SELECTION
3 PHASE AC MOTOR
AC MOTOR PRIMARY WITH DC MOTOR BACKUP WITH BRAKING
AC MOTOR PRIMARY WITH DC MOTOR BACKUP WITH SOFT START/STOP
MUST MATCH
MOTOR BOARD!
Advanced Controller Programming (Cont.)
Radio Enable
The Controller contains a built-in MegaCode® radio receiver to allow activation from up to 40 access control transmitters and two Model MGT (gate edge) transmitters. The factory default enables the internal radio receiver. Alternately, the internal receiver can be disabled.
Antenna Installation
The Controller is supplied with a local whip antenna installed. If using a remote antenna, remove the whip antenna and connect coax cable from the antenna to the ANTENNA connector.
Radio Transmitter Learn
The Controller’s built-in MegaCode® radio receiver can store the IDs of up to 40 transmitters. Refer to the fi gure for the steps required to learn transmitters.
NOTE: This function will NOT be displayed if the transmitter memory
is full, or if the radio receiver is disabled.
Radio Transmitter Delete
Transmitters can be deleted from the Controller’s memory either individually, or all at the same time. Refer to the fi gure for the steps required to delete transmitters.
NOTE: This function will NOT be displayed if no transmitters are
stored in memory, or if the radio receiver is disabled.
MGT Obstacle Transmitter Learn
The Controller supports one or two Model MGT Obstacle Transmitters. The transmitters can be programmed to function as Open Obstruction, Close Obstruction, Reverse, or Stop. Refer to the fi gure for the steps required to learn MGT transmitters.
NOTE: This function will NOT be displayed if two MGT transmitters
are already stored in memory, or if the radio receiver is disabled.
MGT Obstacle Transmitter Delete
MGT transmitters can be deleted from the Controller’s memory either individually, or all at the same time. Refer to the fi gure for the steps required to delete MGT transmitters.
NOTE: This function will NOT be displayed if no MGT transmitters are
stored in memory, or if the radio receiver is disabled.
Reset Controller to Factory Defaults
The Controller can be reset with this function. ALL PROGRAMMED DATA WILL BE LOST, and the factory defaults will be loaded. This
function will not erase radio transmitters. Transmitters must be deleted with the two functions above.
FUNCTION
"RA"
RADIO
ENABLE
FUNCTION
"TL"
LEARN
TRANSMITTERS
FUNCTION
"TD"
DELETE
TRANSMITTERS
FUNCTION
"ML"
LEARN MGT
TRANSMITTERS
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
ENTER
ENTER
ENTER
UP DOWN
OR
ENTER
ENTER
OR
UP DOWN
ENTER
INTERNAL RADIO RECEIVER DISABLED
INTERNAL RADIO RECEIVER ENABLED
PRESS ENTER (ONCE FOR EACH TRANSMITTER, UP TO 40 TRANSMITTERS TOTAL)
"TL" WILL BLINK FOR 30 SECONDS WHILE THE CONTROLLER IS READY TO LEARN A TRANSMITTER
ACTIVATE THE TRANSMITTER
DISPLAY WILL SHOW "- -" THEN THE TRANSMITTER ID NUMBER - IF TRANSMITTER IS ALREADY ENTERED, "dU" WILL BE DISPLAYED, IF DECODE IS BAD "ERROR" WILL BE DISPLAYED
PRESS ENTER
"TD" WILL BLINK FOR 30 SECONDS WHILE THE CONTROLLER IS READY TO DELETE ONE OR MORE TRANSMITTERS, (TO EXIT WITHOUT DELETING ANY, PRESS ENTER)
TO DELETE ALL TRANSMITTERS, PRESS ENTER FOR 2 SECONDS, OR TO PICK TRANSMITTERS GO TO NEXT STEP
PRESS UP OR DOWN TO SCROLL THROUGH THE LIST OF TRANSMITTER ID NUMBERS
THE TRANSMITTER ID NUMBER IS DISPLAYED (TO EXIT WITHOUT DELETING, PRESS ENTER) (TO PICK A DIFFERENT TRANSMITTER ID, PRESS UP OR DOWN)
PRESS ENTER FOR 2 SECONDS TO DELETE THE TRANSMITTER DISPLAYED
PRESS ENTER, "ML" WILL BLINK FOR 30 SECONDS WHILE THE CONTROLLER IS READY TO LEARN AN MGT TRANSMITTER
ACTIVATE THE MGT TRANSMITTER, THE DISPLAY WILL FLASH "rE" - IF THE TRANSMITTER IS ALREADY ENTERED, "DU" WILL BE DISPLAYED, IF DECODE IS BAD "ERROR" WILL BE DISPLAYED
PRESS UP OR DOWN TO SELECT THE MGT FUNCTION: "rE" = REVERSE "St" = STOP "OP" = OPEN OBSTRUCTION "CL" = CLOSE OBSTRUCTION
PRESS ENTER TO ACCEPT THE SELECTION
DISPLAY WILL SHOW "--" FOR 5 SECONDS, THEN SHOW THE TRANSMITTER'S ID NUMBER - REPEAT STEPS FOR SECOND MGT TRANSMITTER IF USED
FUNCTION
"CL"
RESET TO
FACTORY DEFAULTS
WHILE "CL" IS DISPLAYED, PRESS ENTER
ENTER
ALL PROGRAMMED DATA WILL BE CLEARED AND THE FACTORY DEFAULTS WILL BE STORED IN MEMORY.
NOTE: THIS FUNCTION WILL NOT ERASE TRANSMITTERS
FUNCTION
"MD"
ERASE MGT
TRANSMITTERS
ENTER
ENTER
PRESS ENTER
"MD" WILL BLINK FOR 30 SECONDS WHILE THE CONTROLLER IS READY TO DELETE ALL MGT TRANSMITTERS
TO DELETE ALL MGT TRANSMITTERS, PRESS ENTER FOR 2 SECONDS, (TO EXIT WITHOUT DELETING ANY, QUICKLY PRESS ENTER)
THE DISPLAY WILL SHOW "DELETE ALL" AND THE CONTROLLER RETURNS TO PROGRAMMING MODE
SWR SWC SWD Swing Gate Operator Installation Guide - 17 - 227965 Revision X13 3-28-2008
Loop Layout Illustration
LOOP
SEALANT
3/8"
2"
WALL PARTIALLY
SHOWN FOR CLARITY
MULTIPLE TURNS
FOR DETAILS
REFER TO LOOP
INSTALLATION NOTES
GATE
OPEN
SHOWN
PARTIALLY
2" MAX.
FOOT
AT LEAST SIX TIMES PER
TWIST WIRE FROM END OF
LOOPS BACK TO OPERATOR
6 FT.
NOTE: POSITION SHADOW LOOP APPROXIMATELY HALF WAY
BETWEEN ENTRY AND EXIT REVERSING LOOPS. THE DISTANCE
BETWEEN THE SHADOW LOOP AND EXIT/REVERSING LOOPS
SHOULD NEVER EXCEED THE LENGTH OF THE SHORTEST
VEHICLE TYPE WHICH IS EXPECTED TO USE THIS GATE.
SEPARATE PEDESTRIAN
GATE REQUIRED
7 FT. MINIMUM DISTANCE
AWAY FROM GATE
AT CORNERS
USE RELIEF CUTS
SWR SWC SWD Swing Gate Operator Installation Guide - 18 - 227965 Revision X13 3-28-2008
Safety Edge Layout Illustration
1
6
4
3
5
2
REVERSING EDGE
ASSEMBLY CLOSE-UP
RECEIVER INSIDE
1 GATE (REFERENCE ONLY)
2 EDGE
ITEM DESCRIPTION
EDGES MOUNTED ACROSS
BOTTOM OF GATE
GATE EDGE
GATE OPERATOR
TRANSMITTER
3 EDGE EXTRUSION
EDGE MOUNTED ON
OF GATE
LEADING OUTSIDE EDGE
6 RETAINING BRACKET
4 SPACERS (3)
5 8-32 X 1" SCREWS (3)
WIRE EDGES SHOWN TO THE CLOSE OBSTRUCTION INPUT ONLY
WARNING
SEPARATE PEDESTRIAN
GATE REQUIRED
7FT. MINIMUM DISTANCE
One or more contact sensors shall be located on the
inside and outside leading edge of a swing gate.
Additionally, if the bottom edge of a swing gate is
greater than six inches (152 mm) above the ground
at any point in its arc of travel, one or more contact
sensors shall be located on the bottom edge.
A hardwired contact sensor shall be located and its
wiring arranged so that the communication between
the sensor and the gate operator is not subjected to
mechanical damage.
A wireless contact sensor such as one that transmits
radio frequency (RF) signals to the gate operator for
entrapment protection functions shall be located where
the transmission of the signals are not obstructed or
impeded by building structures, natural landscaping
or similar obstruction. A wireless contact sensor shall
function under the intended end-use conditions.
SWR SWC SWD Swing Gate Operator Installation Guide - 19 - 227965 Revision X13 3-28-2008
AWAY FROM GATE
Photoeye Installation Illustration
OBSTRUCTION DETECTING APPLICATION
(WIRE TO OPEN OBSTRUCTION)
BEAM PATH
SEPARATE PEDESTRIAN GATE REQUIRED
7 FT. MINIMUM DISTANCE AWAY FROM GATE
PHOTOEYE REVERSE APPLICATION
(WIRE TO REVERSE)
BEAM PATH
REFER TO CONNECTION ILLUSTRATIONS FOR DETAILS
BEAM PATH
OBSTRUCTION DETECTING APPLICATION
(WIRE TO CLOSE OBSTRUCTION)
SWR SWC SWD Swing Gate Operator Installation Guide - 20 - 227965 Revision X13 3-28-2008
TO POSSIBLE LOCATIONS FOR THE INSTALLATION
THIS DRAWING IS INTENDED TO DRAW ATTENTION
MAY EXIST DEPENDING ON EACH SPECIFIC
OF CONTACT OR NON-CONTACT OBSTRUCTION
SENSING DEVICES. OTHER AREAS OF ENTRAPMENT
INSTALLATION.
SO THAT NUISANCE TRIPPING IS MINIMIZED.
CARE MUST BE TAKEN TO POSITION PHOTOEYES
Dual Gate Installations
Two operators can be used in dual gate installations. The operators communicate with each other through the 3-wire COMM LINK terminals.
When one operator activates, the COMM LINK connection signals the other operator to activate. Each operator functions independently, controlling its gate and monitoring its inputs and accessories.
A three-wire shielded conductor cable is required to connect two operators together for dual operation. Use Belden 8760 Twisted Pair Shielded Cable (or equivalent) only – P/N 2500-1982, per foot).
NOTE: The shield wire should be connected COMM LINK terminal
“C” in both operators.
Three of the programming functions available are only used for dual gate installations:
Dual Gate Enable
Dual Gate Enable must be set for all dual gate installations.
Stagger Mode
The Stagger Mode function determines if the operator has a delayed open or a delayed close. In dual swing gate installations, typically one operator is programmed for delayed open, and the other operator is programmed for delayed close.
Stagger Delay Time
The Stagger Time sets the length of the delay for the Stagger Mode.
See Pages 12 & 14 for details on these three dual gate programming functions.
Gate Operation
Open Button
Opens the gate. If the Controller is programmed to stop opening the gate at mid-travel, a constant press of the OPEN button will override the Mid-travel Stop and completely open the gate. If the Auto Close Timer is set, it will be suspended until the OPEN button is released.
Close Button
Closes the gate if the gate is open. Also closes the gate if the gate is in the process of opening.
Stop Button
Stops the gate from opening or closing at any time.
DUAL GATE COMM LINK
WIRING
SHIELD
CONNECT
C - C B - B A - A
CONNECT SHIELD
WIRE AT BOTH ENDS
Figure 14. COMM LINK Wiring
USE BELDEN 8760 TWISTED PAIR
SHIELDED CABLE OR EQUIVALENT
SHIELD
OPERATOR #1
OPERATOR #2
Open Input
Functions the same as the OPEN button.
Open Obstruction
While the gate opening, any open obstruction signal will cause the gate to stop, reverse a short distance, and then stop again. The Auto Close Timer will be disabled, and a renewed input will be required to start the gate again. Should the gate be restarted and the obstacle signal occur again prior to reaching a limit, the gate will stop again, lockout, and sound the emergency alarm.
Close Obstruction
Same as the open obstruction, but in the closing direction.
Reverse Input
If the reverse input is triggered while the gate is closing, the gate will reverse to the full open position. If the Auto Close Timer is set, when the reverse input is cleared, the gate will close when the Auto Close Timer expires.
Single Input
Opens the gate if it’s closed and closes the gate if it’s open (open-close programming option). Activating the input while the gate is moving will reverse the gate.
Can be programmed to stop the gate while the gate is moving (open-stop-close programming option).
Fire Department Input
Fully opens the gate when the input is activated. Overrides the Mid-travel Stop and Auto Close Timer (if either is programmed for the gate). The gate will lockout in the open position without sounding the alarm. Press the STOP button to release the lockout.
SWR SWC SWD Swing Gate Operator Installation Guide - 21 - 227965 Revision X13 3-28-2008
Open Loop
Functions the same as the OPEN button.
Reverse Loop
Functions the same as the reverse input.
Shadow/Reset Loop
Only used with Swing Gates. Holds the gate fully open or fully closed while triggered. If open, the gate closes immediately when cleared.
Operation Indications
During normal operation, the Controller’s displays will indicate current operating conditions and status.
Power-up Display
When the Controller powers up, dashes will show on the display for one second, then the fi rmware version number will be displayed for one second.
Exiting programming restarts the Controller. The power-up display will show upon the restart.
Idle Condition
While the Controller is idling, waiting for a command, the display will show circulating dashes.
Last Gate Position/Condition
When the gate moves or stops, the display will show the status for up to one minute.
Stop is displayed as St Full Close is displayed as FC Full Open is displayed as FO Entrapment is displayed as En
Pre-start Delay
During the pre-start delay, the display will countdown the number of seconds remaining before the operator starts.
Reverse Delay
If the gate travel direction is reversed from a user activation or reversing device, and a reverse delay is set, the display will count down the delay time in seconds before the operator restarts.
Run Timer
While the gate is opening or closing, the number of seconds running time is displayed.
Error Indications
During abnormal operation, the Controller’s displays and beeper will indicate the error condition that has occurred.
Entrapment
If an entrapment condition occurs detected by two repeated open or close obstruction triggers, the Controller will lock the operator out. The beeper will sound constantly and the gate will not operate. To reset the Controller press the STOP button or press the RESET button on the operator’s cover.
WARNING
The Stop and/or Reset button must be located in the line-of­sight of the gate. Activation of the reset control shall not cause the operator to start.
COMM LINK Connection Failure
In dual gate installations, if there is a connection failure between the two operators, the COMM LINK indicator will blink once a second. During this condition the gate will not operate, except if triggered by the FIRE DEPT input, which functions normally.
MGT Obstacle Transmitter Trouble
If any MGT transmitters are used with the operator, their supervision feature will alert the Controller if there is any trouble with the transmitter. MGT transmitters send hourly status reports and will send low battery reports when the transmitter has a low battery. The MGT transmitters also have a tamper detection switch that will trigger when their case is opened.
When the Controller detects a low transmitter battery, a tamper signal, or missing transmitter status reports, the gate will still operate normally, but the beeper will change as follows:
The Pre-start Alarm will beep twice as fast.• The Run Alarm will beep twice as fast and continue for fi ve minutes • after the gate stops. The sounder will “chirp” every fi ve seconds when the gate is idle.
Correct the trouble (close case, replace battery, or replace transmitter) to clear the obstacle transmitter trouble indications.
Maximum Run Time Exceeded
If the Maximum Run Time is exceeded, the Controller stops the operator the same as if a double obstacle has occurred in an entrapment condition. The entrapment alarm sounds constantly, and is cleared by pressing the STOP button or the RESET button on the cover. After the STOP or RESET button is pressed, because the Maximum Run Time has been exceeded, the sounder will beep twice every fi ve seconds. The next operation of the gate will clear the indication.
CONTROLLER ERROR CAUSES AND INDICATIONS
ERROR CAUSE ERROR INDICATION HOW TO CLEAR
TWO SAFETY REVERSALS (ON SINGLE GATE OR ON EITHER DUAL GATE)
MAXIMUM RUN TIMER EXCEEDED ON OPENING
MAXIMUM RUN TIMER EXCEEDED ON CLOSING
COMM LINK FAILURE
GATE FULL OPEN RESULTING FROM FIRE DEPT INPUT
FAIL SAFE OR FAIL SECURE BECAUSE OF AC POWER LOSS
OTHER CONTROLLER IN ENTRAPMENT (DUAL GATE)
LOW AC VOLTAGE AT CONTROLLER
INPUT TRIGGERED DURING ENTRAPMENT LOCKOUT
COMPATIBILITY PROBLEM En 09, GATE DISABLED
EEPROM PROBLEM En 10, GATE DISABLED TRY RESET, CALL TECH. SUPPORT
DC MOTOR MISMATCH En 11, GATE DISABLED
MOTOR FAILURE En 12, GATE DISABLED REPLACE MOTOR
MGT SUPERVISORY CONDITION (TAMPER, LOW BATTERY, MISSING HOURLY STATUS)
En 00, CONTINUOUS ALARM BEEPER, GATE DISABLED
En 01, AND MAX RUN LED, CONTINUOUS ALARM BEEPER, GATE DISABLED
En 02, AND MAX RUN LED, CONTINUOUS ALARM BEEPER, GATE DISABLED
En 03, AND COMM LINK LED, CONTINUOUS ALARM BEEPER FOR 1 MINUTE, GATE DISABLED (EXCEPT FOR FIRE DEPT INPUT)
En 04, GATE DISABLED PRESS STOP BUTTON
En 05, GATE DISABLED
En 06, GATE DISABLED
En 07, GATE DISABLED
En 08, GATE DISABLED PRESS STOP BUTTON
FAST BEEPS DURING PRESTART, FAST BEEP RUN ALARM, CHIRP EVERY 5 SECONDS AT IDLE
PRESS STOP BUTTON
PRESS STOP BUTTON, CLEARS CONTINUOUS ALARM, THEN DOUBLE BEEP EVERY 5 SECONDS UNTIL NEXT OPERATION
PRESS STOP BUTTON, CLEARS CONTINUOUS ALARM, THEN DOUBLE BEEP EVERY 5 SECONDS UNTIL NEXT OPERATION
PRESS STOP BUTTON, CLEARS CONTINUOUS ALARM
BATTERY VOLTAGE MUST RISE ABOVE 24 VDC
CLEAR ENTRAPMENT ON OTHER CONTROLLER (PRESS STOP)
LOW VOLTAGE AC POWER MUST RISE ABOVE 20 VAC
UPDATE FIRMWARE AND RESET BOTH PAIRED CONTROLLERS
REPROGRAM MOTOR TYPE OR CHANGE DC MOTOR BOARD, NEXT GATE MOVEMENT WILL RETRY DC MOTOR CHECK
CLEARS WHEN MGT CONDITION CLEARS
SWR SWC SWD Swing Gate Operator Installation Guide - 22 - 227965 Revision X13 3-28-2008
Troubleshooting
Contacting Technical Support
For technical questions regarding Linear gate operators, contact the Technical Services Department at:
1-800-421-1587
Operator fails to start
A. If the operator has been running a large number
of cycles, the motor may have become too hot and tripped its thermal overload breaker. Allow the motor to cool down and the thermal overload breaker will reset automatically.
B. Make sure you have power at the master distribution
panel and that the power has not been turned off.
Motor operates, but gate does not move
A. In operators with torque limiters and friction pad clutches,
check for signs of slipping. You can mark the sprocket and clutch with a yellow or white grease pen and watch for the lines to move apart if slipping is taking place. Adjust the torque limiter tighter if this is the problem.
B. Check for broken chain or worn belts.
C. Check all setscrews on pulleys and sprockets and tighten
them if necessary, and check for keys which may have fallen loose from keyways.
Motor sounds like it is working harder than normal
A. Make sure the gate is moving freely and without binding
throughout its entire travel.
B. Check the drive chain for obstructions (if the operator
has one).
C. If the operator has an internal brake mechanism, make
sure it is releasing.
from 6:30 AM to 4:30 PM Pacifi c time
Gate stopping part way open or closed (but no visible obstruction)
A. The Controller may have received a false obstruction
input triggered by current sensing set too low. Make sure the gate moves freely through its entire travel before adjusting the current sensing.
B. The Maximum Run Timer may have counted down and
expired. This can be caused by having the timer set too low, if a chain or belt is broken, or if a sprocket or pulley is slipping. When the timer expires, the gate stops and the beeper will sound.
C. An obstruction signal from an accessory wired to the
obstruction input may have triggered falsely. Check the control board for lit indicators for any of the following inputs: safety, shadow/reset, open obstruction, close obstruction, stop, etc. If any are lit when the operator should be running, remove all devices hooked to that function and hook them up one at a time and try to run the operator until the problem device is found. Refer to Page 9 for details on the control board indicators.
Gate staying open with automatic system
A. If there are vehicle detectors used with the operator, one
of the loops or loop detectors may be sending a false signal or needs to be reset. Observe the indicators on the loop detector. Unplug the detector and try running the operator.
B. An opening or reversing device may be stuck or
malfunctioning. Try disconnecting these devices and hook them back up one at a time and try running the operator until the malfunctioning device is found.
C. Make sure the close limit switch isn’t activated. If it is, the
operator will think the gate is already closed.
Limit switch getting out of time
A. Check the setscrews in limit cams for tightness. Replace
if necessary.
How to Order Replacement Parts
Use the part numbers listed on the following pages.
Contact your local Linear dealer or distributor to order parts.
1. Supply the model number and serial number of your operator.
2. Specify the quantity of pieces needed and order by part number and name of part.
3. State whether to ship by freight, truck, parcel post, UPS or air express.
4. State whether transportation charges are to be prepaid or collect.
5. Specify name and address of person or company to whom parts are to be shipped.
6. Specify name and address of person or company to whom invoice is to be sent
SWR SWC SWD Swing Gate Operator Installation Guide - 23 - 227965 Revision X13 3-28-2008
Model SWR Exploded View
13C
13A
15
19
26
22
17
18
20
23
25
4
13B
13
16
2
12
10
14
5
3B
3A
7A
7B
11
7
8
9
3
1
MODEL SWR MECHANICAL PARTS LIST
REF. # PART # DESCRIPTION
2300-925-BEIGE Operator Cover, Tan
1
2300-925-BLACK Operator Cover, Black 2300-926-BEIGE Rain Cap, Tan
2
2300-926-BLACK Rain Cap, Black 2100-2030-BEIGE Access Door, Tan (no lock or reset button)
3
2100-2030-BT Access Door, Black (no lock or reset button) 2510-354 Plunger Reset Assembly
3A
2500-2240 Plunger Reset Button 2500-2241 Plunger Extension Only 2200-790 Lock for Cover, with Keys
3B
2200-824 Extra Keys 4 2110-785 Frame Assembly 5 2400-509 Socket Head Cap Screw, 3/8-16 x 1-1/2”
2510-274 Motor Assembly, 1/2 HP, 115 VAC, with Harness
7
2510-275 Motor Assembly, 1/2 HP, 230 VAC, with Harness
2500-261 Capacitor for 115 VAC
7A
2500-552 Capacitor for 230 VAC
7B 2200-872 Capacitor Clamp
8 2200-132 Pulley, 2”, 5/8” bore 9 2200-208 V-belt, 4L, 26”
10 2200-926 Gear Reducer, 60:1 11 2100-388 Pulley, 5”, 5/8” bore 12 2200-190 Sprocket, 40-B-12, 3/4” bore
13 2100-2020-PLT Drive Shaft 13A 2200-015 Shaft Collar, 1” diameter, 9/16 LTB 13B 2100-519-PLT Sleeve Spacer 13C 2200-016 Moisture Seal
14 2200-274 Pillow Block Bearing, 1” diameter
15 2200-376 Sprocket, 40-B-36, 1” bore
2200-673 #40 Chain, 21 Links
16
2200-006 #40 Master Link 17 2100-1748 Limit Cam 18 2200-015 Shaft Collar, 1” diameter, 9/16 LTB 19 2500-2347 Limit Switch
MOTORS
CAPACITORS
REF. # PART # DESCRIPTION
2510-422 115 VAC Power Box Assembly 2510-430 230 VAC Power Box Assembly 2500-2411 Power Switch Only, 115 VAC and 230 VAC 2500-2413 Power Outlet (only available on 115 VAC Models)
20
2500-212 115 VAC - 24 VAC Power Transformer 2500-791 230 VAC - 24 VAC Power Transformer 2100-2113 Back Plate
2100-2112 Cover Plate 21 2100-2111 Controller Latch 22 2100-2108 Limit Switch Mounting Bracket
2100-2024 Accessory Mounting Shelf 23
2200-874-PLT Hinge, Male for Control Box
2500-2393 APeX Module
2500-2399 APeX DC Motor Module
2100-2104 APeX Mounting Plate 25
2300-1025 Plastic Cover Only
2510-423 Knob Kit
2510-420 Stop/Reset Switch and Bracket Assembly 26 2500-2435 Alarm
2510-427 115 VAC Wiring Harness Assembly (not shown) 27
2510-429 230 VAC Wiring Harness Assembly (not shown)
2120-483 Post Mounting Kit
2220-047
2200-591 Friction Disc pair for 3” Torque Limiter
2200-593 Bushing for 3” Torque Limiter
2200-281 Sprocket, 40-A-36, 1” Bore
2100-2041 Operator Base Plate
OPTIONAL PARTS
3” Torque Limiter with Bushing and 40-A-36 Sprocket
SWR SWC SWD Swing Gate Operator Installation Guide - 24 - 227965 Revision X13 3-28-2008
Model SWC Exploded View
13C
13A
15 12
19
26
22
17
18
20
23
25
4
MODEL SWC MECHANICAL PARTS LIST
REF. # PART # DESCRIPTION
2300-925-BEIGE Operator Cover, Tan
1
2300-925-BLACK Operator Cover, Black 2300-926-BEIGE Rain Cap, Tan
2
2300-926-BLACK Rain Cap, Black 2100-2030-BEIGE Access Door, Tan (no lock or reset button)
3
2100-2030-BT Access Door, Black (no lock or reset button) 2510-354 Plunger Reset Assembly
3A
2500-2240 Plunger Reset Button 2500-2241 Plunger Extension Only 2200-790 Lock for Cover, with Keys
3B
2200-824 Extra Keys 4 2110-785 Frame Assembly 5 2400-509 Socket Head Cap Screw, 3/8-16 x 1-1/2”
2500-2307 1/2 HP, 115 VAC, 1 Phase
2500-2308 1/2 HP, 208/230 VAC,1 Phase
2500-2309 3/4 HP, 115 VAC, 1 Phase
2500-2310 3/4 HP, 208/230 VAC,1 Phase
2500-2311 1 HP, 115 VAC, 1 Phase
2500-2312 1 HP, 208/230 VAC, 1 Phase 7
2500-2336 Cap for 2500-2307 motor
2500-2337 Cap for 2500-2308 motor
2500-1926 Cap #1 for 2500-2309 motor
2500-1930 Cap #2 for 2500-2309 motor
2500-1931 Cap for 2500-2310 motor
2500-2338 Cap for 2500-2311 motor
2500-1932 Cap for 2500-2312 motor
2200-012 Pulley, 2”, 5/8” bore (for 1/2 and 3/4 HP) 8
2200-960 Pulley, 1-5/8”, 5/8” bore (for 1 HP only)
2200-013 V-belt, 31” (for 1/2 and 3/4 HP) 9
2200-931 V-belt, 30” (for 1 HP only)
2200-081 Gear Reducer, 60:1 (for 1/2 and 3/4 HP)
10
2200-957 Gear Reducer, 60:1 (for 1 HP)
2200-885 Pulley, 8”, 3/4” bore (for 1/2 and 3/4 HP)
11
2200-969 Pulley, 8”, 7/8” bore (for 1 HP only)
2200-084 Sprocket, 40-B-13, 1” bore (for 1/2 and 3/4 HP)
12
2200-958 Sprocket, 40-B-14, 1-1/8” bore (for 1 HP)
13 2100-2020-PLT Drive Shaft
MOTORS
CAPACITORS
13B
13
16
14
10
5
11
7
8
3B
3A
9
3
REF. # PART # DESCRIPTION
13C 2200-016 Moisture Seal
14 2200-274 Pillow Block Bearing, 1” diameter
2200-376 Sprocket, 40-B-36, 1” bore (for 1/2 and 3/4 HP)
15
2200-959 Sprocket, 40-B-40, 1” bore (for 1 HP) 2200-972 #40 Chain, 24 Links (for 1/2 and 3/4 HP) 2200-973 #40 Chain, 26 Links (for 1 HP)
16
2200-006 #40 Master Link
2400-145 #40 Half Link 17 2100-1748 Limit Cam 18 2200-015 Shaft Collar, 1” diameter, 9/16 LTB 19 2500-2347 Limit Switch
2510-422 115 VAC Power Box Assembly
2510-430 230 VAC Power Box Assembly
2500-2411 Power Switch Only, 115 VAC and 230 VAC
2500-2413 Power Outlet (only available on 115 VAC Models) 20
2500-212 115 VAC - 24 VAC Power Transformer
2500-791 230 VAC - 24 VAC Power Transformer
2100-2133 Back Plate
2100-2112 Cover Plate 21 2100-2111 Controller Latch 22 2100-2108 Limit Switch Mounting Bracket
2100-2024 Accessory Mounting Shelf 23
2200-874-PLT Hinge, Male for Control Box
2500-2393 APeX Module
2100-2104 APeX Mounting Plate 25
2300-1025 Plastic Cover Only
2510-423 Knob Kit
2510-420 Stop/Reset Switch and Bracket Assembly 26 2500-2435 Alarm
2120-483 Post Mounting Kit
2220-048
2220-049
2300-381 Friction Disc pair for 5” Torque Limiter
2200-782 Bushing for 5” Torque Limiter
2200-583 Sprocket, 40-A-36, 1” Bore
2200-970 Sprocket, 40-A-40, 1” Bore
2100-2041 Operator Base Plate
2
1
OPTIONAL PARTS
5” Torque Limiter with Bushing and 40-A-36 Sprocket (for 1/2 and 3/4 HP) 5” Torque Limiter with Bushing and 40-A-40 Sprocket (for 1 HP)
13A 2200-015 Shaft Collar, 1” diameter, 9/16 LTB 13B 2100-519-PLT Sleeve Spacer
SWR SWC SWD Swing Gate Operator Installation Guide - 25 - 227965 Revision X13 3-28-2008
Model SWD Exploded View
28
20
25
13C
13A
15
19
26
22
17
18
23
2
13B
12
13
14
4
10
3B
3A
16
7B
5
11
7
7A
1
8
3
9
MODEL SWD MECHANICAL PARTS LIST
REF. # PART # DESCRIPTION
2300-925-BEIGE Operator Cover, Tan
1
2300-925-BLACK Operator Cover, Black 2300-926-BEIGE Rain Cap, Tan
2
2300-926-BLACK Rain Cap, Black 2100-2030-BEIGE Access Door, Tan (no lock or reset button)
3
2100-2030-BT Access Door, Black (no lock or reset button) 2510-354 Plunger Reset Assembly
3A
2500-2240 Plunger Reset Button 2500-2241 Plunger Extension Only 2200-790 Lock for Cover, with Keys
3B
2200-824 Extra Keys 4 2110-785 Frame Assembly 5 2400-509 Socket Head Cap Screw, 3/8-16 x 1-1/2” 7 2500-1902 Motor, 24 VDC
7A 2100-2037 Motor Mounting Plate 7B 2510-223 Transformer Assembly
2500-1776 Transformer only, 115 VAC - 24 VAC, 250VA 8 2200-411 Pulley, 1-1/2”, 1/2” bore 9 2200-975 V-belt, 4L, 29”
10 2200-081 Gear Reducer, 60:1 11 2200-079 Pulley, 7”, 3/4” bore 12 2200-084 Sprocket, 40-B-13, 1” bore
13 2100-2020-PLT Drive Shaft 13A 2200-015 Shaft Collar, 1” diameter, 9/16 LTB 13B 2100-519-PLT Sleeve Spacer 13C 2200-016 Moisture Seal
14 2200-274 Pillow Block Bearing, 1” diameter
2220-048
15
2300-381 Friction Disc Pair for 5” Torque Limiter 2200-782 Bushing for 5” Torque Limiter 2200-583 Sprocket, 40-A-36, 1”
5” Torque Limiter with Bushing and 40-A-36 Sprocket
Bore
REF. # PART # DESCRIPTION
2200-673 #40 Chain, 21 Links
16
2200-006 #40 Master Link 17 2100-1748 Limit Cam 18 2200-015 Shaft Collar, 1” diameter, 9/16 LTB 19 2500-2347 Limit Switch
2510-432 Power Box Assembly
2500-2411 Power Switch
2500-2413 Power Outlet
2100-2113 Back Plate 20
2100-2112 Cover Plate
2500-1819 Fuse Holder
2500-1742 Fuse, 6 Amp, Slow-Blow
2500-2473 Relay, 24 VDC
2500-1768 Bridge Rectifi er 21 2100-2111 Controller Latch 22 2100-2108 Limit Switch Mounting Bracket
2100-2024 Accessory Mounting Shelf 23
2200-874-PLT Hinge, Male for Control Box
2510-439 APeX Module and DC Motor Board Assembly
2500-2393 APeX Module
2500-2399 APeX DC Motor Module 25
2100-2104 APeX Mounting Plate
2300-1025 Plastic Cover Only
2510-423 Knob Kit
2510-420 Stop/Reset Switch and Bracket Assembly 26 2500-2435 Alarm
2510-182 Battery Assembly 28
2500-1118 Battery, 12V (2 required)
2300-450 Velcro Tape, per foot 29 2510-433 Wiring Harness Assembly (Not Shown)
2120-483 Post Mounting Kit
2100-2041 Operator Base Plate
OPTIONAL PARTS
SWR SWC SWD Swing Gate Operator Installation Guide - 26 - 227965 Revision X13 3-28-2008
SWR, SWC, SWD Gate Arm Assembly Exploded View
16
17
17
16
13
9
8
10
17
19
17
16
18
16
7
17
5
6
4
11
19
12
16
16
15
13
20
3
19
14
15
2
1
GATE ARM ASSEMBLY MECHANICAL PARTS LIST
REF. # PART # DESCRIPTION
2120-493 Complete Arm Assembly 1 2100-2068-PLT Threaded Crank Block 2 2100-2069-PLT V-Block for Crank Block 3 2100-2067 Crank Extension Solid Bar 4 2110-810 Crank Extension and Spacer Assembly 5 2100-1924-PLT Overtravel Stop 6 2300-969 Plastic Elbow Offset Spacer 7 2100-2072 Gate Arm Link Tube 8 2100-2071 Solid Link Bar 9 2200-964 Gate Plate Tube Spacer
10 2100-2070 Gate Plate 11 2400-511 Disconnect Pin
2400-351 Disconnect Hair Pin
12
2200-034 Disconnect Lock (optional)
13 2400-512 Hex Head Screw, grade 8, 1/2-13 x 2-1/2” 14 2400-505 Hex Head Screw, grade 8, 1/2-13 x 2” 15 2400-513 Lockwasher, grade 8, 1/2” 16 2400-506 Flatwasher, grade 8 17 2300-238 Nylon Washer 18 2400-508 Hex Head Screw, grade 8, 1/2-13 x 3-3/4” 19 2400-507 Nylon Insert Locknut, grade 8, 1/2-13 20 2400-510 Shoulder Bolt for Rain Cap, 1/4-20
SWR SWC SWD Swing Gate Operator Installation Guide - 27 - 227965 Revision X13 3-28-2008
Model SWD Maintenance
Battery Maintenance
The gel-cell batteries in this operator require no routine maintenance. For assured continued performance, they should be replaced every year. If power is to be removed for one week or more, disconnect the negative wire from the batteries as this will prevent deep discharging. Fully charge before use after storage or upon initial installation.
DC Motor Brush Replacement
Brushes should be inspected every 100,000 cycles or yearly, whichever comes fi rst. The motor has two brushes, one on each side.
Original brushes are approximately 3/4” long and should be replaced when they are 1/4” long, or sooner. If brushes are allowed to wear beyond this point, permanent damage to the motor may result.
To inspect the brushes: (1) remove the retaining cap with straight-blade screwdriver; (2) carefully pull assembly straight out; (3) measure the remaining brush material.
To reinstall: (4) place the brush in holder, aligning the brush’s rounded indentation correctly with motor shaft; (5) gently push in the spring and align metal contact with oval slot in the brush holder, then push it in with retaining cap. Hold the cap in place and thread the cap into brush holder. Do not
overtighten or cap will crack!
Repeat for the other brush.
REMOVE BRUSH RETAINING
1
CAP WITH FLATBLADE SCREWDRIVER
REPLACE CAP AND
5
CAREFULLY SCREW INTO HOLDER
DON'T OVERTIGHTEN THE CAP, IT WILL CRACK!
PULL ON CONTACT
2
TO REMOVE BRUSH
INSPECT THE LENGTH
3
OF THE BRUSH
3/4" WHEN NEW,
REPLACE WHEN 1/4"
LONG OR SOONER
PUSH BRUSH INTO
4
THE HOLDER (IT ONLY FITS IN ONE WAY)
Figure 15. Replacing DC Motor Brushes
SWR SWC SWD Swing Gate Operator Installation Guide - 28 - 227965 Revision X13 3-28-2008
REPEAT INSPECTION WITH THE BRUSH ON THE OTHER SIDE OF THE MOTOR
Preventative Maintenance
WARNING
Always disconnect power from operator before servicing. Keep clear of gate during operation.
General
Linear gate operators are designed for many years of trouble-free operation and, under recommended operating conditions, will require only minimal maintenance. To ensure that a unit is ready for operation at all times, and to preclude serious damage or failure, inspect the unit systematically. Proper adjustments and lubrication should be made as recommended.
Lubrication
Bearings — For models which have pillow block style
bearings with grease fi ttings, lubricate at least twice a year with a lithium complex based, petroleum oil NLGI 2 rated grease. Oilite and precision sealed bearings do not require additional lubrication.
Motor — Motors have sealed ball bearings and do not
require further lubrication. If bearing noise develops after several years of operation, bearings should be replaced by a motor repair company, or the motor should be replaced if necessary.
Swing Gate Arm — Check all bolts for proper tension
and tighten if necessary. Make sure the arm folds overextends itself slightly against the overtravel stop to reduce the chance that the gate can be backdriven open. Adjust the close limit slightly if additional travel is required. Lightly lubricate all pivot points with a light machine oil.
6-Month Preventative Maintenance
1. For operators which utilize torque limiting clutches, check for proper tightness. If there appears to be dust from wear on the pads, inspect the pads and replace if necessary. If the clutch cannot be adjusted tightly enough to move the gate without slipping, the pads must be replaced.
2. For operators with V-belts, inspect for wear and replace as necessary. Check for proper tension and adjust if required. Check all pulley setscrews for tightness and tighten if necessary.
3. For operators with internal chain drives, inspect chain and sprockets for wear and replace if necessary. Check for proper tension and alignment, and adjust if required. Check all hub sprocket setscrews and tighten if required.
4. Check limit switches and limit actuators (cams, limit nuts, etc.) for wear and replace as required. In rotary limit switch assemblies, wipe the limit shaft clean and apply a light coating of dry lubricant.
5. Inspect all nuts and bolts for proper tightness and tighten as necessary.
6. Check all reversing devices for proper function. Inspect all contact edges for wear and replace if required. Check photoeyes for proper alignment and function.
7. Check current sensing for proper adjustment when fi nished with inspection and maintenance.
8. Inspect the installation area. Are all the warning signs intact and visible? If they are missing or need replaced, contact Linear. Be sure there are no control stations mounted within reach of the gate. Review safety literature with the customer and advise them to remove any such stations found.
FCC Notice
This device complies with FCC Rules Part 15 and Industry Canada Rules & Regulations. Operation is subject to the following two conditions: (1) This device may not cause harmful interference and (2) this device must accept any interference received, including interference that may cause undesired operation.
For all gate operators, you must inspect the gate for proper operation. The gate should move easily without binding through its entire travel. If the gate does bind, adjust or fi x as required. Failure to keep the gate in good working condition will have adverse effects on the operator.
SWR SWC SWD Swing Gate Operator Installation Guide - 29 - 227965 Revision X13 3-28-2008
Gate Operator Installation Checklist
INSTALLER CUSTOMER
1. The gate has been checked to make sure it is level and moves freely in both directions.
2. Potential pinch areas have been guarded so as to be inaccessible OR have
3. The installer has installed one or more contact or non-contact obstruction sensing
4. If pedestrian traffi c is expected, a separate pedestrian gate has been
5. Warning signs have been installed on each side of the gate in highly visible locations.
6. There are no controls installed on the gate operator, or within seven feet of the gate.
7. The installer has properly adjusted the obstruction sensing feature and has tested
contact and/or non-contact obstruction sensing devices installed.
devices, in compliance with UL325 requirements for this installation.
installed, a minimum of seven feet from the gate. The customer has been informed that all pedestrian traffi c must use the pedestrian gate.
The customer has been informed that these signs must remain at all times.
the gate to make sure that the gate stops and reverses a short distance with minimal resistance applied (40 lbs. on a swing gate at the end of the gate, 75 lbs. on a slide gate)
By signing this installation checklist, I/we hereby certify that each item listed and checked above has been covered by the installer and is clearly understood by the customer.
8. The installer has instructed the customer in the proper use of the gate operator and reviewed
9. The installer has instructed the customer in the proper use of the operator’s
10. The installer has reviewed all safety instructions with the customer, and has left
11. The installer has answered any questions the customer has regarding the
12. The installer has explained to the customer that a regular maintenance
all of the operational functions, obstruction sensing devices, warning beeper and reset, etc.
manual disconnect feature. The manual disconnect must never be used while the gate is in motion. The power switch must be turned off before using the manual disconnect and disengaging the operator.
the safety instructions and owner’s information sheets for their reference.
operation of the gate operator and gate operator safety precautions.
schedule for both the gate and the gate operator is recommended.
Customer’s Signature
Installer’s Signature
SWR SWC SWD Swing Gate Operator Installation Guide - 30 - 227965 Revision X13 3-28-2008
Date
Date
Loading...