LOT Series Uninterruptible Power Supplies LOT
Page 1 of 2 1.5 kVA - 4.2 kVA Single Phase UPS System
Operates incandescent, magnetic and electronic ballast fluorescent, high power factor compact fluorescent, and high intensity discharge (HID) lamp types.
B)
A)
(
Electronics/
Battery
Cabinet
How to Specify:
LOT
SERIES
OT = Single
L
hase
P
Uninterruptible
ower
P
Supplies
(
VA 1.5 - 3.5 4.2
k
Width (A) 36” 36”
epth (B) 24” 24”
D
C)
(
NPUT OUTPUT UNIT BACK-UP NOL OUTPUT # ON 2ND # OF NOL NOL # OF NOL
I
VOLTAGE VOLTAGE SIZE DURATION CKT BRKRS VOLTAGE CKT BRKRS VOLTAGE 2nd VOLTAGE
= 120 V
A
= 120/240V
G
J = 277 V
L = 120/208V
A = 120 V
G = 120/240V
= 277 V
J
L = 120/208V
= 120/277V
Y
Height (C) 72” 80”
.5 = 1.5 kVA
1
2.2 = 2.2 kVA
3.0 = 3.0 kVA
3.5 = 3.5 kVA
4.2 = 4.2 kVA
S = 90 min
X = 10 min
Y = 20 min
= None
0
1 = Yes
T = NOL w/ TDT
0X = Hardwire
0
01X = 1 OCB
02X = 2 OCB
03X = 3 OCB
04X = 4 OCB
:
:
20X = 20 OCB
-----------------01A = 1 OCBA
02A = 2 OCBA
03A = 3 OCBA
:
:
10A = 10 OCBA
Max. Pole
Spaces 20
0 = 2nd
0
Voltage
Hardwire or no
ltage
2nd Vo
01
02
03
:
:
19
A = 1
B = 2
= 3
C
= 4
D
E = 5
= 6
F
G = 7
H = 8
I = 9
J = 10
K = 11
L = 12
M = 13
N = 14
O = 15
P = 16
Q = 17
R = 18
S = 19
T = 20
Z = No NOL
= First
1
2 = Second
3 = Both
0 = No NOL
A = 1
B = 2
= 3
C
= 4
D
E = 5
= 6
F
G = 7
H = 8
I = 9
J = 10
K = 11
L = 12
M = 13
N = 14
O = 15
P = 16
Q = 17
R = 18
S = 19
Z = No NOL
Overall Characteristics
• 87 - 90% throughput efficiency, 85% emergency efficiency
• Operating temperature range 32°F (0°C) to 104°F (40°C)
• Fault current rating 42kAIC
• Audible noise less than 50dB at 3 ft on “A” weighted scale
• Automatic low battery voltage disconnect
Electrical
• Sine Wave Output
• Double conversion, no interruption
• Voltage regulation ±2%
equency r
Fr
•
Output voltage distor
•
egulation - synchr
onized to utility
tion maximum 3% THD with linear load
• Load power factor capability 0.7 lead to 0.7 lag
Overload capacity 125% for 10 seconds
•
• Input power factor correcting to 0.99
• Frequency range 60Hz, ±2.5%
• Input harmonic current distortion <5% THD
• UL 1449, ANSI,IEEE C62, 41 surge suppression
• Completely solid-state Pulse Width Modulation (PWM) inverter
eak maintenance by-pass
nal, make befor
Inter
•
Standard, UL 924 compliant, 90 minute battery backup
•
e br
• UL 924 auxiliary equipment 10 and 20 minute backup available
opr
Micr
•
ray system status panel
ar
LED
•
ocessor contr
ol and diagnostic system
• Fault annunciating audible alarm
• Current limiting start sequence
• Optional output circuit breakers (OCB) and circuit breakers with trip alarm
(OCBA)
f load (NOL) energizes only during power outage,
Optional nor
•
mally of
normally off load with time delay (TDT) also available
, free running 60 Hz, ±0.5%
Housing
Free standing, NEMA 1 enclosure
•
• Seismic anchoring compatible
• Lockable control access panel
Applications
• The solid-state Pulse Width Modulated (PWM) inverter offers enhanced load
compatibility
• Provides conditioned, uninterruptible power for other types of critical loads.
Consult factory for non-lighting load applications.
ob Inf
J
ob Name:
J
Cat. No.:
Lamp(s):
Notes:
Lightolier a Genlyte Company
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
e r
W
© 2006 Genlyte Gr
ormation Type:
ve the right to change details of design, materials and finish.
eser
oup LLC (Lightolier Division) • B0406
www
.lightolier
.com
LOT Series Uninterruptible Power Supplies LOT
Page 2 of 2 1.5 kVA - 4.2 kVA Single Phase UPS System
System Input/Output Ratings
System Rating (kW/kVA) 1.5 2.2 3.0 3.5 4.2
Input Voltage (V) : Input Current (A) 120 : 22.1 120 : 26.7 120 : 39.4 120 : 45.0 120 : 47.0
120/240 : N/A 120/240 : N/A 120/240 : 19.1 120/240 : 21.8 120/240 : 23.5
277 : 9.8 277 : 11.9 277 : 17.1 277 : 19.5 277 : 20.3
120/208 : N/A 120/208 : N/A 120/208 : 22.1 120/208 : 25.2 120/208 : 27.0
Output Voltage : Output Current* 120 : 12.5 120 : 18.3 120 : 25.0 120 : 29.2 120 : 35.0
120/240 : N/A 120/240 : N/A 120/240 : 25.0/12.5 120/240 : 29.2/14.6 120/240 : 35.0/17.5
277 : 5.4 277 : 7.9 277 : 10.8 277 : 12.6 277 : 15.2
120/208 : N/A 120/208 : N/A 120/208 : 25.0/14.4 120/208 : 29.2/16.8 120/208 : 35.0/20.2
120/277 : 12.5/5.4 120/277 : 18.3/7.9 120/277 : 25.0/10/8 120/277 : 29.2/12.6 120/277 : 35.0/15.2
OCB Pole Spaces Available
without trip alarm 20 20 20 20 20
with trip alarm 10 10 10 10 10
Heat Rejection (Btu/hr) 515 750 1025 1195 1870
Weight
Electronics 650 650 640 640 840
90 min battery 445 445 610 610 760
20 min battery 90 195 330 330 350
10 min battery 60 90 195 195 230
Multi-voltage total loads not to exceed system rating
*
Warranty
Standard Warranty
(Requires executiion of factory start-up within 120 days of shipment) Lightolier will provide parts and on-site labor for the first 12 months
following start-up of the product, and parts only for an additional 12 months. If factory start-up is not executed within 120 days of shipment,
Lightolier will provide a parts warranty for 12 months from the date of shipment.
Extended Warranty
Consult factory for extended warranty and service option.