11
2
58
9
6
7
10
1 34
Vertical Adjustment: 5/8" (16 mm 2 7/8" (73 m
2" (50 mm) max. Ceiling Thickness
13-1/4" (337 mm) Dia.
13-3/4"
(349 mm)
12" (305 mm) Dia.
13" (330 mm)
10-3/4"
(273 mm)
16-3/8" (416 mm)
20" (508 mm) to 30" (762 mm)
21-1/4" (540 mm) 175-250W
23-3/4" (603 mm) 320-400W
Top View
11"
(280 mm)
Calculite
®
HID Lensed Downlight C12E28FL-PL
Page 1 of 3 12" Aperture, ED28 (Enclosed), Metal Halide, Prismatic or Fresnel Lens
Ceiling Cutout: 12 9/16” (256 mm) Dia.
Reflector Trim Frame-In Kit Lamp (Enclosed, Coated)
C12E28PLWHW Prismatic Lens, White Step Baffle. C1217MHPU Magnetic, 120V/277V Pulse Start 175W ED28, BT28 PS MH C12E28FLWHW Fresnel Lens, White Step Baffle.
C1225MHPU Magnetic, 120V/277V Pulse Start 250W ED28, BT28 PS MH C1232MHPU Magnetic, 120V/277V Pulse Start 320W ED28, BT28 PS MH C1240MHPU Magnetic, 120V/277V Pulse Start 400W ED28, BT28 PS MH C1217MHU Magnetic, 120V/277V 175W ED28, BT28 MH C1225MHU Magnetic, 120V/277V 250W ED28, BT28 MH C1240MHU Magnetic, 120V/277V 400W ED28, BT28 MH
Features
1. Reflector: Specular anodized aluminum, 16 ga. Removable from inside
2. Lens: Prismatic (C12E28PLWHW) or Fresnel (C12E28FLWHW) lens.
3. Die-Cast Baffle: Painted white, deep conical step baffle for low brightness,
4. Torsiontite Springs:Permit removal of lens assembly without tools.
5. Socket Cup: Heat dissipating die-cast aluminum with medium base pulse
6. Mounting Frame: 0.048" (18-ga.) galvanized steel, includes pre-installed
7. Mounting Ring: 0.048"(18-ga.) galvanized steel. Designed for vertical
8. Vertical Adjustment Mechanism: accommodates mounting to virtually
9. Mounting Bars: 0.048" (18-ga.) pre-installed, telescoping bars extend to 30"
10.Ballast: Dual voltage (120V/277V) magnetic. Assembly is accessible from
11.Junction Box: 0.048" (18ga.) galvanized steel. UL listed for maximum of (8)
12.Thermal Protector: (not shown) Meets NEC and UL requirements. Do not
Electrical
Magnetic Ballast: 120/277V dual voltage, 60 Hz., encased and potted, CWA or
Super CWA (pulse start) circuit type, high power factor, sound rating “B” (175W and 250W PS)/sound rating “C” (others), -20°F minimum starting Temperature, Type 1 Outdoor rating.
fixture for access to splices and ballast.
Regressed 2 1/4" from ceiling line.
supports lens. Small Allen-head set screw provides secure attachment for use where vandal resistant luminaires are required.
rated porcelain socket with nickel plated screw shell. Positive locking attach­ment, without tools, to reflector assures proper optical alignment of lamp.
mounting bars.
adjustment from above or below for ceilings from 0" to 2" thick. Center-line notches allow consistent alignment of multiple fixtures.
any ceiling system using mounting bars (provided, or 1/2" EMT tubing (by others). Single locking feature secures all adjustments. Alignment holes and markings allow fixture to be preset prior to installation.
long; lock securely into position. Built-in locking tabs provide positive attach­ment to common T-bar systems. Self-centering feature simplifies installation in 24" O.C. grid systems. Attaches to steel/wood joists without accessories.
below without tools for inspection and replacement.
No. 12 AWG, 90°C through branch circuit conductors; allows inspection from
below
install insulation above nor within 3" (76mm) of any part of the luminaire.
Electrical (Cont.)
Ballast ANSI Code Voltage Max. Amps Input Watts
175W PS MH M137 120/277 2.20/0.90 205 250W PS MH M138 120/277 2.80/1.20 290 320W PS MH M132 120/277 3.40/1.50 370 400W PS MH M135 120/277 4.10/1.80 465 175W MH M57 120/277 2.00/0.90 205 250W MH M58 120/277 2.60/1.10 290 400W MH M59 120/277 3.90/1.70 460
Options and Accessories
Auxiliary: Add suffix A to Frame-In Kit and Reflector Trim. See Spec.Sheet ”A“. Emergency: Add suffix E to Reflector Trim and Frame-In Kit. See Spec. Sheet “E”. Slope Ceiling Adapters: See Specification Sheet SCA. Fuse (magnetic ballast): Add suffix F1 or F2to Frame in Kit (F1=120V, F2=277V). Chicago Plenum: Consult Factory.
Labels
UL (Suitable for Wet Locations), CSA (magnetic ballast only), I.B.E.W. For 320W/400W, install fixtures with minimum spacing: 4 feet from center-to-center of adjacent luminaries; 3 inch from top of luminaire to over­head building member; 2 feet from luminaire center to side building member.
Job Information Type:
Job Name: Cat. No.:
Lamp(s): Notes:
Lightolier a Genlyte Thomas Company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2004 Genlyte Thomas Group LLC (Lightolier Division) • A0504
Calculite
®
HID Lensed Downlight C12E28FL-PL
Page 2 of 3 12" Aperture, ED28 (Enclosed), Metal Halide Prismatic or Fresnel Lens
FRESNEL LENS/ WHITE BAFFLE - 175W ED28 G.E. METAL HALIDE COATED LAMP. LUMEN RATING = 12900 LMS., ADVANCE BALLAST
1,500
3,000
4,500
6,000
** EFFICIENCY = 48.8% ** CERTIFIED TEST REPORT NO. 2554FR, DATE: MAR 21, 2004 SC = .9 COMPUTED BY LSI PROGRAM **TEST-LITE**
FRESNEL LENS/ WHITE BAFFLE- 250W ED28 PHILIPS METAL HALIDE COATED LAMP. LUMEN RATING = 19475 LMS., UNIVERSAL BALLAST
2,000
4,000
6,000
8,000
** EFFICIENCY = 46.9% ** CERTIFIED TEST REPORT NO. 2557FR, DATE: MAR 21, 2004 SC = .9 COMPUTED BY LSI PROGRAM **TEST-LITE**
ANGLE MEAN CP LUMENS
0 8996 0 5781
5 5575 529 10 5247 15 4882 1372
60°
20 4348 25 3584 1647 30 2713 35 1883 1214 40 1250 45 859 692 50 608 55 448 414 60 341 65 259 263 70 201 75 142 141 80 47 85 14 20
30°
90 0
ANGLE MEAN CP LUMENS
0 7764
5 7645 728 10 7434 15 7120 1986 20 6350
60°
25 5182 2386 30 3901 35 2741 1763 40 1841 45 1276 1026 50 908 55 668 617 60 506 65 385 391 70 299 75 210 209 80 71 85 21 31 90 0
30°
LUMINANCE SUMMARY - CD. / SQ. M.
ANGLE MEAN CD/SQ M
45 601630 55 387161 65 303788 75 271565 85 79179
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 3547 27.5 56.38 0-40 4761 36.91 75.68 0-60 5867 45.49 93.26
0-90 6292 48.78 100 40-90 1530 11.86 24.32 60-90 424 3.29 6.74
90-180 0 0 0
0-180 6292 48.78 100
LUMINANCE SUMMARY - CD. / SQ. M.
ANGLE MEAN CD/SQ M
45 893382 55 576797 65 450887 75 400904 85 120690
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 5099 26.18 55.82
0-40 6861 35.23 75.11
0-60 8504 43.67 93.1
0-90 9135 46.91 100 40-90 2273 11.67 24.89 60-90 630 3.24 6.9
90-180 0 0 0
0-180 9135 46.91 100
CEILING 80% 70% 50% 30%
WALL 70 50 30 10 50 10 50 10 50 10 0
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
RCR
0 .58 .58 .58 .58 .57 .57 .54 .54 .52 .52 .49 1 .55 .54 .52 .51 .53 .50 .50 .49 .49 .47 .45 2 .52 .50 .48 .46 .49 .45 .47 .44 .46 .43 .41 3 .49 .46 .43 .41 .45 .41 .44 .40 .43 .40 .38 4 .47 .43 .40 .38 .42 .38 .41 .37 .40 .37 .36 5 .44 .40 .37 .35 .39 .35 .39 .34 .38 .34 .33 6 .42 .37 .34 .32 .37 .32 .36 .32 .36 .32 .31 7 .40 .35 .32 .30 .35 .30 .34 .29 .33 .29 .28 8 .38 .33 .30 .28 .32 .27 .32 .27 .31 .27 .26 9 .36 .31 .28 .26 .30 .26 .30 .25 .30 .25 .25 10 .34 .29 .26 .24 .29 .24 .28 .24 .28 .24 .23
LUMINAIRE INPUT WATTS = 205
Coefficients of Utilization
CEILING 80% 70% 50% 30%
Coefficients of Utilization
WALL 70 50 30 10 50 10 50 10 50 10 0
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
RCR
0 .56 .56 .56 .56 .55 .55 .52 .52 .50 .50 .47 1 .53 .51 .50 .49 .51 .48 .49 .47 .47 .45 .43 2 .50 .48 .46 .44 .47 .43 .45 .42 .44 .41 .40 3 .47 .44 .42 .40 .43 .39 .42 .39 .41 .38 .37 4 .45 .41 .38 .36 .41 .36 .40 .36 .39 .35 .34 5 .42 .38 .35 .33 .38 .33 .37 .33 .36 .32 .31 6 .40 .36 .33 .31 .35 .31 .35 .30 .34 .30 .29 7 .38 .33 .30 .28 .33 .28 .32 .28 .32 .28 .27 8 .36 .31 .28 .26 .31 .26 .30 .26 .30 .26 .25 9 .34 .29 .26 .24 .29 .24 .29 .24 .28 .24 .23 10 .32 .28 .25 .23 .27 .23 .27 .23 .27 .23 .22
LUMINAIRE INPUT WATTS = 290
FRESNEL LENS/ WHITE BAFFLE - 320W ED28 PHILIPS METAL HALIDE COATED LAMP. LUMEN RATING = 30100 LMS., ADVANCE BALLAST
ANGLE MEAN CP LUMENS
0 10463 5 10298 981
2,750
5,500
8,250
11,000
** EFFICIENCY = 42.6% ** CERTIFIED TEST REPORT NO. 2558FR, DATE: MAR 21, 2004
SC = .9 COMPUTED BY LSI PROGRAM **TEST-LITE**
10 10043 15 9696 2715 20 8873
60°
25 7298 3355 30 5523 35 3882 2497 40 2614 45 1810 1456 50 1287 55 953 878 60 724 65 557 564 70 433 75 307 311 80 128 85 31 52 90 1
30°
LUMINANCE SUMMARY - CD. / SQ. M.
ANGLE MEAN CD/SQ M
45 1267525 55 822644 65 652886 75 588204 85 177806
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 7050 23.42 55.05
0-40 9547 31.72 74.54
0-60 11882 39.47 92.77
0-90 12808 42.55 100 40-90 3260 10.83 25.46 60-90 926 3.08 7.23
90-180 0 0 0
0-180 12808 42.55 100
CEILING 80% 70% 50% 30%
Coefficients of Utilization
WALL 70 50 30 10 50 10 50 10 50 10 0
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
RCR
0 .51 .51 .51 .51 .49 .49 .47 .47 .45 .45 .43 1 .48 .47 .45 .44 .46 .44 .44 .42 .42 .41 .39 2 .45 .43 .41 .40 .42 .39 .41 .38 .40 .37 .36 3 .43 .40 .38 .36 .39 .35 .38 .35 .37 .34 .33 4 .41 .37 .35 .33 .37 .32 .36 .32 .35 .32 .31 5 .38 .35 .32 .30 .34 .30 .33 .30 .33 .29 .28 6 .36 .32 .30 .28 .32 .28 .31 .27 .31 .27 .26 7 .34 .30 .27 .26 .30 .25 .29 .25 .29 .25 .24 8 .33 .28 .25 .24 .28 .24 .27 .23 .27 .23 .23 9 .31 .26 .24 .22 .26 .22 .26 .22 .25 .22 .21 10 .29 .25 .22 .20 .25 .20 .24 .20 .24 .20 .19
LUMINAIRE INPUT WATTS = 370
FRESNEL LENS/ WHITE BAFFLE - 400W ED28 G.E. METAL HALIDE COATED LAMP. LUMEN RATING = 35000 LMS. ADVANCE BALLAST
ANGLE MEAN CP LUMENS
0 15666 5 15225 1443
3,750
7,500
11,250
15,000
** EFFICIENCY = 49.2% ** CERTIFIED TEST REPORT NO. 2561FR, DATE: MAR 22, 2004 SC= .9 COMPUTED BY LSI PROGRAM **TEST-LITE**
10 14335 15 13279 3728 20 11715
60°
25 9625 4433 30 7341 35 5183 3331 40 3500 45 2420 1946 50 1711 55 1256 1160 60 950 65 719 731 70 559 75 396 394 80 138 85 41 60 90 0
30°
LUMINANCE SUMMARY - CD. / SQ. M.
ANGLE MEAN CD/SQ M
45 1695165 55 1084702 65 842680 75 758600 85 235481
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 9603 27.44 55.75
0-40 12933 36.95 75.08
0-60 16040 45.83 93.12
0-90 17225 49.22 100 40-90 4291 12.26 24.92 60-90 1185 3.39 6.88
90-180 0 0 0
0-180 17225 49.22 100
Job Information Type:
Coefficients of Utilization
CEILING 80% 70% 50% 30%
WALL 70 50 30 10 50 10 50 10 50 10 0
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
RCR
0 .59 .59 .59 .59 .57 .57 .55 .55 .52 .52 .49 1 .56 .54 .53 .51 .53 .51 .51 .49 .49 .48 .45 2 .52 .50 .48 .46 .49 .45 .47 .44 .46 .44 .42 3 .50 .46 .44 .42 .46 .41 .44 .41 .43 .40 .39 4 .47 .43 .40 .38 .43 .38 .42 .37 .41 .37 .36 5 .45 .40 .37 .35 .40 .35 .39 .34 .38 .34 .33 6 .42 .38 .35 .32 .37 .32 .36 .32 .36 .32 .31 7 .40 .35 .32 .30 .35 .30 .34 .30 .33 .29 .28 8 .38 .33 .30 .28 .32 .28 .32 .27 .31 .27 .26 9 .36 .31 .28 .26 .31 .26 .30 .25 .30 .25 .25 10 .34 .29 .26 .24 .29 .24 .28 .24 .28 .24 .23
LUMINAIRE INPUT WATTS = 460
Lightolier a Genlyte Thomas Company www.lightolier.com