How to Specify:
C1
SERIES DC VOLTAGE BATTERY # OF LAMP
HEADS HEADS
C1 = Rec esse d
Emergency Lighting
Unit
Blank = 6 volt
2 = 12 volt
6V, Lead C alcium
18L = 18W Unit
25L = 25W Unit
6V, Nickel C admium
14N = 14W Unit
28N = 28W Unit
12V, Lead Calcium
50L = 50W Unit
75L = 75W Unit
(24.1 cm)
Blank = No Heads
1 = One Head
2 = Two Heads
5.8”
(14.7 cm)
Rect angular Wedge Base
S6 = 5.4W Tungsten (6V only)
S7 = 7.2W Tungs ten (6V only)
S9 = 9W Tungsten
S12 = 12W Tungsten (12V only)
S18 = 18W Tungsten (12V only)
Features
1. Illumination: Provided by two adjustable lamp heads. Choose from round
or rectangular thermoplastic heads with Par 36 sealed beam tungsten or
halogen, or wedge base tungsten or halogen lamps.
2. Housing: Faceplate constructed of impact resistant, UL 94 V-0, 5 VA white
thermoplastic. Backbox constructed of 20 gauge galvanized steel with 1/2”
conduit. Fully recessed assembly for ceiling or wall installation. An optional
bar hanger kit is available for mounting in suspended ceilings.
3. Electronics: 120/277 VAC dual voltage input with surge-protected, solidstate circuitry. Charging system is complete with low voltage disconnect, AC
lockout, brownout protection, AC indicator lamp and test switch.
4. Battery: Maintenance-free, sealed, lead calcium bat ter y has an estimated
service life of 5 years, and an operating temperature range of 65°F (19°C)
to 85°F (30°C). Maintenance-free, sealed nickel cadmium battery has an
estimated service life of 10 years, and an operating temperature range of
20°F (-7°C) to 95°F (35°C).
5. Input Power Requirements: 120 VAC/6V: 0.07 amps, 7.3 watts; 277
VAC/6V: 0.03 amps, 7.3 watts; 120 VAC/12V: 0.29 amps, 30 watts; 277
VAC/12V: 0.13 amps, 30 watts
Code Compliance
UL 924 listed.
Options
V = Voltmeter
DL = Damp Location Listing (12V, 50W units only)
C128N can not accom modate a v oltmeter.
Accessories
BHK1 = Bar Hanger Kit
PCS1 = Polycarbonate Vandal Shield
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier is a Philips group brand
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • E0308
C1 Series Emergency Lighting C1
Page 2 of 2 6 Volt 14 to 28 Watts Thermoplastic Housing
Lamp Head Photometrics
S9- 12 Volt, 9 Watt, Tungsten
60
50
40
30
20
10
0
10 5 0 5 10
left
80
60
40
20
0
15
up
.1
.2
.3
.5
1
feet
.1
.2
.3
.5
1
5
0
5
feet
S7- 6 Volt, 7.2 Watt, Tungsten
S12- 12 Volt, 12.5 Watt, Tungsten
50
40
30
20
10
0
right
15
10
down
10
left
80
60
40
20
0
10
up
5
.1
15
.1
.2
.3
.5
1
0
feet
.2
.5
5
10
feet
5
1
0
10
right
5
10
down
S9- 6 Volt, 9 Watt, TungstenS6- 6 Volt, 5.4 Watt, Tungsten
S18- 12 Volt, 18 Watt, Tungsten
60
50
40
30
20
10
0
10
90
60
30
0
5
left
15
10
up
.1
.2
.3
.5
1
0
feet
.1
.3
.5
5
10
5
.2
1
0
feet
15
right
10
5
down
Unit Battery Capacity
DC Suggested Watts to 871⁄2
Voltage Unit Lamp Head of Rated Voltage*
1
1
⁄2 hrs. 2 hrs. 4 hrs. 8 hrs.
6 C118L S9 18 13.5 7 —
C125L S9 25 19 9.5 —
C114N S6 14 10.5 — —
C128N S9 28 21 10.5 5.4
12 C1250L S9 50 37.5 19 10
C1275L S9 75 59.8 33.3 14.4
Lightolier is a Philips group brand
Warranty
Electronics: 3 years
Battery: 1 year full, 4 years pro-rata (lead calcium);
5 year full, 5 years pro-rata (nickel cadmium)
* Per NEC Specifications
Job Information Type:
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • E0308